Control DamperProducts
Manual Balancing Dampers
Commercial Control Dampers
Industrial Control Dampers
Application
Control Dampers are an integral part of every HVAC system. They are positioned manually or automatically to control air volume and temperature throughout the air handling system.
Basic Functions
• Volume Control - Regulates airflow.
• Temperature Control - Maintains desired temperature.
• Pressure Control - Maintains desired pressure. (uncommon)
Control Damper Training
Volume Control
• Branch Dampers Regulates airflow and branches.
• Balancing Dampers Limit flow down the duct or through a device by holding damper blades at a specific position (typically via a manual locking quadrant).
• Fan Inlet/Outlet Dampers Used to control flow rate to or from the fan.
Control Damper Training
Temperature ControlMixing Dampers
• Operate as a pair to maintain temperature.
• Simultaneously regulates two different air streams - each with
different incoming air temperature.
• Able to control air temperature and volume.
Control Damper Training
Basic Mixing Application Basic System Design
Temperature Control
Face & Bypass/Multi-Zone Dampers
• Regulates face air (hot or cold) with bypass/return air to maintain temperature.
• Arranged side-by-side, top-bottom, or at right angles.
Control Damper Training
Typical Side-by-Side Face & Bypass Application
Standard Construction
Control Dampers have different designs and are constructed from a variety of frames, blades, axles, bearings, blade linkage and other parts to suit the particular application for that damper.
Control Damper Training
Frames
Flat
Hat Channel
‘U’ Channel
Flanged
Flat
Hat Channel
‘U’ Channel
Flanged
Blades• Flat, typically for single-blades dampers, low pressure applications.
• Triple-V, economical. Low to medium pressure applications.
• Airfoil, lower pressure drop, medium to high pressure applications.
Control Damper Training
3-V Blade
Airfoil Blade
Blade ActionParallel• All blades rotate together in the same direction.• Typically two-position control.
Opposed• Adjacent blades rotate in opposite directions.• Balancing and modulating control.
Control Damper Training
Parallel Opposed
Axles
Attached to the damper blade and extend through the damper frame to permit the blades to rotate.• Various sizes, lengths, materials depending upon the application.
Control Damper Training
Bearings
Pressed into the damper frame to permit easy rotatingOf the damper blade & shaft.• Various types and materials depending upon the application.
Blade LinkageMechanism that connects the blades together.
• Concealed - hidden within the frame on one side or the other or in rare cases, both sides of the damper.
• Exposed - attached to the blade face.
Control Damper Training
Exposed Linkage
Concealed Linkage
Damper Drive MechanismMechanism that drives (operates) - all the blades together.Typically connected to one blade - Drive Blade.
• Direct Drive - typically a shaft extending from one side of the damper adjacent to the damper frame.
• Jack Shaft - typically a shaft, offset but connected to the drive blade, extending past the side of the damper- used mostly when connecting multiple single-sectioned dampers together.
Control Damper Training
Direct Drive
Jack Shaft
Optional Low Leakage Seals
• Stainless Steel Jamb Seals - positioned between the end of the blades and the inside of the damper frame and blade edge seals attached to the damper blades.
Control Damper Training
Optional Stainless Steel Construction
• Typically standard construction material is galvanized steel. Most models have type 304 stainless steel (only), and a few offer 316.
Design BasicsManual Balancing • Commonly found at duct branches and used to restrict airflow in the branch to the desired level.
Commercial Control • Most common type and widely used for volume and temperature control.
Industrial • Employed when the temperature, pressure, or velocity exceed standard commercial damper limits. Units are typically flange mounted directly to the duct or fan housing.
Control Damper Training
Manual Balancing DampersUsed to control the flow of air to meet a required volume, temperature and/or pressure.
Cable Control • Enables remote damper positioning from within the occupied space. • Available for round and square duct.
Quadrant Control • Quieter than diffuser mounted OBD. • With or without integral sleeve. • Requires access to set quadrant.
Control Damper Training
CD-10R
RCS-10RRCS-10
Concealed Operator
CD-10ISCD-10
Hand Quadrant
Integral Sleeve
Commercial Control DampersBlade Type • 3-V Economical - Galvanized Steel
• Airfoil Lower Pressure Drop Galvanized Steel or Aluminum
• True-Round Blade Action • Parallel - Blades move together in the same direction - 2-position control
• Opposed - Adjacent blades turn in opposite directions - Balancing dampers and modulating control
Control Damper Training
3-V Blade Airfoil Blade
Concealed Linkage
Exposed Linkage
True RoundCD-22R
Multi-Blade
True RoundCD-25R
Single BladeIntegral Sleeve
Integral Sleeve
DriveShaft
Commercial Control DampersMultiple Sections • Jackshaft • Bracing - As required • Face & Bypass Vertical Blades • Actuator/Quadrant Access • Thrust Washers
Control Damper Training
Jackshaft
DriveShaft
Hat Channel Frame
Note H = Blade Length
H
Face & Bypass Dampers
Industrial Control Dampers• Employed when temperature pressure or velocity exceeds commercial damper limitations.• Typically are flanged frame construction and mounted directly to the duct or fan housing. Supplied approx. net I.D.• Are controlled by a manual locking quadrant or by an electric or pneumatic actuator. Actuators are external mount only.• Actuators are normally, but not always larger in size (more powerful - larger torque) than those used for Commercial Control Dampers/
Control Damper Training
Actuators
Electric Pneumatic
CD-81R CD-82
Industrial Control Dampers
Control Damper Training
Blade Type • 3-V • Airfoil (n/a for Pottorff) • True Round Frame Type • Channel
Concealed Linkage
Channel Frame
Continuous Blade Axle
CD-81R
No-Sleeve vs. Sleeve
Control Damper Training
No-Sleeve Dampers • 1/4” under nominal size Side Plate • 12” wide x 16 gaugeSleeved Dampers • 20 gauge sleeve = 1/8” under nominal size, the thicker the sleeve the closer the OD is to nominal size • Optional Transitions: AR (round), AO (oval), AF (Flange) • Labor Saver - Ready to install from factory
Side Plate
Damper with Side Plate
Damper with Sleeve
Actuators
Control Damper Training
Actuators control the position of the damper based on signalsfrom the: Building Automation System (BAS), Thermostats & Controllers, Pressure Switches and Relays.
Location • External or Internal Electric • 2-Position Spring Return • Modulating • 24, 120, 230 VACPneumatic • 25 psi control signal
331-4826 (Siemens) 331-2998 (Siemens)
Pneumatic Actuators
NF-120 (Belimo)
Electric Actuators
LMB24-SR (Belimo)
Actuators
Control Damper Training
Actuator selection is based upon the ability of the actuator to adequately open and close the damper and the amount of torque the actuator can supply. This typically depends upon the following:• Overall damper size.• Velocity of air through the damper.• Static pressure against the damper.• Damper blade type - parallel or opposed: -Normally parallel bladed dampers require more torque to open than opposed but require less torque to close than opposed. • Whether the damper has jamb seals or not.
Our dampers are typically rated at 2000fpm and 1” wg.
Actuators
Control Damper Training
Depending upon the damper design, most actuators can be mounted either internally or externally.
External mount actuatorstypically require a side plate or asleeve to mount the actuator.
Internal mounts actuatorsnormally require that thedamper has offset jack shafting.
External Mount
Internal Mount
To determine the proper actuator for a damper.
Control Damper Training
Refer to our catalog sheet entitled Louver and Air Control Dampers, in the Actuators and Accessories section.
1. Calculate the square footage of the damper; example, 48” w x 36” h = 12 square feet.
2. Choose type of actuator - example, 2-position, spring return, 120 volt, no internal switch package.
3. Top left section of our catalog sheet see section 2-Position Spring Return, and then see list of actuators under column entitled 120 VAC Model.
4. Determine if the damper has seals or not: • If yes, use the last column and any actuator rated 12 square feet or above (under 120 VAC) is acceptable i.e. FSNF-120 NF-120 AF-120
Control Damper Training
5. From the list you would typically choose the most economical actuator.
6. If the damper has no seals, use the 2nd last column and follow the same steps to determine the list of actuators.
Note: If the job site conditions are greater than 2,000 fpm and/or 1” wg, contact the factory so we can calculate the requirements and quote the proper actuator.
Control Damper Training
Other Options & AccessoriesLow Leakage Seals • Stainless steel jamb seal and PVC blade edge seal. Locking Quadrants • Allow the damper blade to be manually positioned and locked in place to supply the desired air volume.Flange Frame • For flush mounting to equipment/wall.304 Stainless Steel Construction PI-50 Dual Position Indicator Switch • Provides damper “open” or “closed” signal for fan interlock.
LQ-560SQ-315
Control Damper Training
TestingCommercial Control Dampers must function in the HVAC System so as to not adversely affect it.
Dampers are tested inaccordance with AMCA 500-D.
Dampers are certified and labeledIn accordance with AMCA 511.
Control Damper Training
Test Samples • Leakage: Max-Max, Min-Max, Max-Min. • Pressure Drop: 12x12, 12x48, 48x12, 24x24, 36x36.
Leakage Rating
Pressure Drop • Ducted Inlet & Outlet - AMCA 5.3 Lowest Pressure Drop
• Ducted Inlet Only - AMCA 5.2 • Plenum Mount - AMCA 5.5 Highest Pressure Drop
Maximum Allowed Leakage (cfm/ft2)Class @ 1 in.wg. @ 4 in.wg. 1A 3 8 1 4 8 2 10 20 3 40 80
AMCA 5.3 – Ducted Inlet & Outlet
AMCA 5.2Ducted Inlet
AMCA 5.5 – Plenum Mount
Control Damper Training