cooling tower pt2 engineering data 20110523

10
PT2 Cooling Towers ENGINEERING DATA 1 DIMENSIONAL ENGINEERING DATA 7 PERFORMANCE ENGINEERING DATA 8 STRUCTURAL SUPPORT 9 ALTERNATIVE STRUCTURAL SUPPORT contents

Upload: ofitecnicajg

Post on 26-Oct-2014

104 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Cooling Tower Pt2 Engineering Data 20110523

PT2 Cooling Towers

E N G I N E E R I N G D A T A

1 DIMENSIONAL ENGINEERING DATA

7 PERFORMANCE ENGINEERING DATA

8 STRUCTURAL SUPPORT

9 ALTERNATIVE STRUCTURAL SUPPORT

contents

Page 2: Cooling Tower Pt2 Engineering Data 20110523

1 Q u E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

A

W

H

L

B

Water In

Water Out

Face A Face C

2” Clean Out

Face A for Models PT2-0412 Single Cell Face C Configuration for Models PT2-0412

Engineering DataD I M E N S I O N A L

Model Number{1}

Nominal Weights (lbs) Dimensions

Operating{2} ShippingHeaviest Section L W H A B F

PT2-0412A-1*1 5,260 2,850 2,080 11’-11 3/4” 4’-0” 10’-3 7/8” 3’-2 3/8” 6’-4 3/8” —PT2-0412A-2*1 5,500 3,090 2,320 11’-11 3/4” 4’-0” 11’-3 7/8” 3’-2 3/8” 7’-4 3/8” —

Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at

the time of publication, which should be reconfirmed at the time of purchase.

Notes:

1. Data corresponds to all available motors for this model.

2. Operating weight is based on the water level in the cold water basin at overflow height. If a lower operating weight is needed to meet design

requirements, your local BAC Representative can provide additional assistance.

Page 3: Cooling Tower Pt2 Engineering Data 20110523

E N G I N E E R I N G D A T A : P T 2 C O O L I N G T O W E R S 2

Model Number{1}

Nominal Weights (lbs) Dimensions

Operating{2} ShippingHeaviest Section L W H A B F

PT2-0709A-1*1 6,030 3,270 2,340 8’-11 3/4” 7’-3 1/4” 10’-7 7/8” 3’-8 7/8” 6’-9 1/4” —PT2-0709A-2*1 6,320 3,560 2,630 8’-11 3/4” 7’-3 1/4” 11’-7 7/8” 3’-8 7/8” 7’-9 1/4” —PT2-0709A-3*1 6,610 3,850 2,920 8’-11 3/4” 7’-3 1/4” 12’-7 7/8” 3’-8 7/8” 8’-9 1/4” —PT2-0709A-1*2 12,180 6670 2,340 18’-0 1/2” 7’-3 1/4” 11’-7 7/8” 4’-8 7/8” 7’-9 1/4” 9’-0 3/4”

PT2-0709A-2*2 12,760 7,250 2,630 18’-0 1/2” 7’-3 1/4” 12’-7 7/8” 4’-8 7/8” 8’-9 1/4” 9’-0 3/4”

PT2-0709A-3*2 13,350 7,840 2,920 18’-0 1/2” 7’-3 1/4” 13’-7 7/8” 4’-8 7/8” 9’-9 1/4” 9’-0 3/4”

PT2-0709A-1*3 18,450 10,180 2,340 27’-1 1/4” 7’-3 1/4” 12’-7 7/8” 5’-8 7/8” 8’-9 1/4” 9’-0 3/4”

PT2-0709A-2*3 19,330 11,060 2,630 27’-1 1/4” 7’-3 1/4” 13’-7 7/8” 5’-8 7/8” 9’-9 1/4” 9’-0 3/4”

PT2-0709A-3*3 20,580 12,310 2,920 27’-1 1/4” 7’-3 1/4” 14’-7 7/8” 5’-8 7/8” 10’-9 1/4” 9’-0 3/4”

PT2-0809A-1*1 6,700 3,520 2,570 8’-11 3/4” 8’-5 3/4” 10’-9 3/8” 3’-8 7/8” 6’-10 3/4” —PT2-0809A-2*1 7,000 3,820 2,860 8’-11 3/4” 8’-5 3/4” 11’-9 3/8” 3’-8 7/8” 7’-10 3/4” —PT2-0809A-3*1 7,300 4,120 3,150 8’-11 3/4” 8’-5 3/4” 12’-9 3/8” 3’-8 7/8” 8’-10 3/4” —PT2-0809A-1*2 13,550 7,180 2,570 18’-0 1/2” 8’-5 3/4” 11’-9 3/8” 4’-8 7/8” 7’-10 3/4” 9’-0 3/4”

PT2-0809A-2*2 14,140 7,780 2,860 18’-0 1/2” 8’-5 3/4” 12’-9 3/8” 4’-8 7/8” 8’-10 3/4” 9’-0 3/4”

PT2-0809A-3*2 14,740 8,380 3,160 18’-0 1/2” 8’-5 3/4” 13’-9 3/8” 4’-8 7/8” 9’-10 3/4” 9’-0 3/4”

PT2-0809A-1*3 20,530 10,980 2,570 27’-1 1/4” 8’-5 3/4” 12’-9 3/8” 5’-8 7/8” 8’-9 1/4” 9’-0 3/4”

PT2-0809A-2*3 21,420 11,880 2,860 27’-1 1/4” 8’-5 3/4” 13’-9 3/8” 5’-8 7/8” 8’-9 1/4” 9’-0 3/4”

PT2-0809A-3*3 22,710 13,150 3,160 27’-1 1/4” 8’-5 3/4” 14’-9 3/8” 5’-8 7/8” 10’-10 3/4” 9’-0 3/4”

PT2-0812A-1*1 8,410 4,170 2,900 11’-11 3/4” 8’-5 3/4” 11’-7 3/8” 4’-1 3/8” 7’-3 1/4” —PT2-0812A-2*1 8,740 4,490 3,190 11’-11 3/4” 8’-5 3/4” 12’-7 3/8” 4’-1 3/8” 8’-3 1/4” —PT2-0812A-3*1 9,060 4,810 3,480 11’-11 3/4” 8’-5 3/4” 13’-7 3/8” 4’-1 3/8” 9’-3 1/4” —PT2-0812A-1*2 17,010 8,520 2,900 24’-0 1/2” 8’-5 3/4” 12’-7 3/8” 5’-1 3/8” 8’-3 1/4” 12’-0 3/4”

PT2-0812A-2*2 17,650 9,160 3,190 24’-0 1/2” 8’-5 3/4” 13’-7 3/8” 5’-1 3/8” 9’-3 1/4” 12’-0 3/4”

PT2-0812A-3*2 18,300 9,810 3,480 24’-0 1/2” 8’-5 3/4” 14’-7 3/8” 5’-1 3/8” 10’-3 1/4” 12’-0 3/4”

PT2-0812A-1*3 25,782 13,043 2,900 36’-1 1/4” 8’-5 3/4” 13’-7 3/8” 6’-1 3/8” 9’-3 1/4” 12’-0 3/4”

PT2-0812A-2*3 26,743 14,005 3,190 36’-1 1/4” 8’-5 3/4” 14’-7 3/8” 6’-1 3/8” 10’-3 1/4” 12’-0 3/4”

PT2-0812A-3*3 28,084 15,346 3,480 36’-1 1/4” 8’-5 3/4” 15’-7 3/8” 6’-1 3/8” 11’-3 1/4” 12’-0 3/4”

Water Out

Water In (Qty. 3)

B

H

Cell 1 Cell 2 Cell 3

FL

F

Face C 3-Cell Configuration for Models PT2-0709, PT2-0809, and PT2-0812

Water Out

Water In

Water In (Qty. 2)

Cell 1 Cell 2

A

W 1’-7 1/4”

2” Clean OutH

B

L

H

B

FL

Face A 3-Cell Configuration for Models PT2-0709, PT2-0809, and PT2-0812 (Connections Typical at Each End)

Face A for Models PT2-0709, PT2-0809, and PT2-0812 (For 2-Cell and 3-Cell Configurations,

Connections Typical at Each End)

Water Out

Water In

Water In (Qty. 2)

Cell 1 Cell 2

A

W 1’-7 1/4”

2” Clean OutH

B

L

H

B

FL

Single Cell Face C Configuration for Models PT2-0709, PT2-0809, and PT2-0812

Face C 2-Cell Configuration for Models PT2-0709, PT2-0809, and PT2 0812

Page 4: Cooling Tower Pt2 Engineering Data 20110523

3 Q u E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

P T 2 D I M E N S I O N A L E N G I N E E R I N G D A T A C O N T I N U E D »

A

B

Water Out Water In

W L

2” Clean Out

Cell 1 Cell 2

FL

H

Water In (Qty. 2)

B

H

Cell 1 Cell 2 Cell 3

FL

F

B

H

Water Out

Water In (Qty. 3)

Face A for Models PT2-1009, PT2-1012, and PT2-1212 (For 2-Cell and 3-Cell

Configurations, Connections Typical at Each End)

Face C Single Cell Configuration for Models PT2-1009, PT2-1012, and PT2-1212

Face C 2-Cell Configuration for Models PT2-1009, PT2-1012, and PT2-1212

Face C 3-Cell Configuration for Models PT2-0709, PT2-0809, and PT2-0812

Cell 2 Cell 1

B

H

A

W

Cell 1, Face A Cell 3, Face B

Water Out (Qty. 4)

L

Water In (Qty. 2)

Face A/B Quad Configuration for Models PT2-1009, PT2-1012, and PT2-1212,

Connections Typical at Each End

Face C Quad Configuration for Models PT2-1009, PT2-1012, and PT2-1212,

Connections Typical at Each End

Page 5: Cooling Tower Pt2 Engineering Data 20110523

E N G I N E E R I N G D A T A : P T 2 C O O L I N G T O W E R S 4

Model Number{1}

Nominal Weights (lbs) Dimensions

Operating{2} ShippingHeaviest Section L W H A B F

PT2-1009A-1*1 7,790 4,100 3,110 8’-11 3/4” 9’-10” 12’-11 5/8” 4’-1 3/8” 7’-2 1/4” —PT2-1009A-2*1 8,100 4,410 3,400 8’-11 3/4” 9’-10” 13’-11 5/8” 4’-1 3/8” 8’-2 1/4” —PT2-1009A-3*1 8,410 4,720 3,700 8’-11 3/4” 9’-10” 14’-11 5/8” 4’-1 3/8” 9’-2 1/4” —PT2-1009A-1*2 15,730 8,350 3,110 18’-0 1/2” 9’-10” 13’-11 5/8” 5’-1 3/8” 8’-2 1/4” 9’-0 3/4”

PT2-1009A-2*2 16,350 8,970 3,400 18’-0 1/2” 9’-10” 14’-11 5/8” 5’-1 3/8” 9’-2 1/4” 9’-0 3/4”

PT2-1009A-3*2 16,980 9,600 3,700 18’-0 1/2” 9’-10” 15’-11 5/8” 5’-1 3/8” 10’-2 1/4” 9’-0 3/4”

PT2-1009A-1*3 23,836 12,764 3,110 27’-1 1/4” 9’-10” 14’-11 5/8” 6’-1 3/8” 9’-2 1/4” 9’-0 3/4”

PT2-1009A-2*3 24,763 13,691 3,400 27’-1 1/4” 9’-10” 15’-11 5/8” 6’-1 3/8” 10’-2 1/4” 9’-0 3/4”

PT2-1009A-3*3 26,070 14,998 3,700 27’-1 1/4” 9’-10” 16’-11 5/8” 6’-1 3/8” 11’-2 1/4” 9 ‘-0 3/4

PT2-1009A-1*4 31,976 17,213 3,110 18’-0 1/2” 19’-9” 16’-10 3/8” 7’-1 3/8” 10’-2 1/4” —PT2-1009A-2*4 33,344 18,581 3,400 18’-0 1/2” 19’-9” 17’-10 3/8” 7’-1 3/8” 11’-2 1/4” —PT2-1009A-3*4 35,087 20,324 3,700 18’-0 1/2” 19’-9” 18’-10 3/8” 7’-1 3/8” 12’-2 1/4” —PT2-1012A-1*1 10,120 5,330 4,050 11’-11 3/4” 9’-10” 13’-2 5/8” 4’-4 3/8” 7’-5 1/4” —PT2-1012A-2*1 10,530 5,730 4,430 11’-11 3/4” 9’-10” 14’-2 5/8” 4’-4 3/8” 8’-5 1/4” —PT2-1012A-3*1 10,930 6,130 4,810 11’-11 3/4” 9’-10” 15’-2 5/8” 4’-4 3/8” 9’-5 1/4” —PT2-1012A-1*2 20,450 10,860 4,050 24’-0 1/2” 9’-10” 14’-2 5/8” 5’-4 3/8” 8’-5 1/4” 12’-0 3/4”

PT2-1012A-2*2 21,260 11,660 4,430 24’-0 1/2” 9’-10” 15’-2 5/8” 5’-4 3/8” 9’-5 1/4” 12’-0 3/4”

PT2-1012A-3*2 22,060 12,470 4,810 24’-0 1/2” 9’-10” 16’-2 5/8” 5’-4 3/8” 10’-5 1/4” 12’-0 3/4”

PT2-1012A-1*3 30,987 16,593 4,050 36’-1 1/4” 9’-10” 15’-2 5/8” 6’-4 3/8” 9’-5 1/4” 12’-0 3/4”

PT2-1012A-2*3 32,192 17,799 4,430 36’-1 1/4” 9’-10” 16’-2 5/8” 6’-4 3/8” 10’-5 1/4” 12’-0 3/4”

PT2-1012A-3*3 33,891 19,498 4,810 36’-1 1/4” 9’-10” 17’-2 5/8” 6’-4 3/8” 11’-5 1/4” 12’-0 3/4”

PT2-1012A-1*4 41,568 22,377 4,050 24’-0 1/2” 19’-9” 17’-10 3/8” 7’-4 3/8” 10’-5 1/4” —PT2-1012A-2*4 43,347 24,156 4,430 24’-0 1/2” 19’-9” 18’-10 3/8” 7’-4 3/8” 11’-5 1/4” —PT2-1012A-3*4 45,613 26,421 4,810 24’-0 1/2” 19’-9” 19’-10 3/8” 7’-4 3/8” 12’-5 1/4” —PT2-1212A-1*1 11,210 5,970 4,170 11’-11 3/4” 11’-10” 13’-10 3/8” 4’-10 3/8” 7’-11 1/4” —PT2-1212A-2*1 11,760 6,520 4,720 11’-11 3/4” 11’-10” 14’-10 3/8” 4’-10 3/8” 8’-11 1/4” —PT2-1212A-3*1 12,310 7,070 5,270 11’-11 3/4” 11’-10” 15’-10 3/8” 4’-10 3/8” 9’-11 1/4” —PT2-1212A-1*2 22,550 12,070 4,170 24’-0 1/2” 11’-10” 14’-10 3/8” 5’-10 3/8” 8’-11 1/4” 12 -0 3/4”

PT2-1212A-2*2 23,670 13,180 4,720 24’-0 1/2” 11’-10” 15’-10 3/8” 5’-10 3/8” 9’-11 1/4” 12’-0 3/4”

PT2-1212A-3*2 24,770 14,280 5,270 24’-0 1/2” 11’-10” 16’-10 3/8” 5’-10 3/8” 10’-11 1/4” 12 -0 3/4”

PT2-1212A-1*3 34,044 18,320 4,170 36’-1 1/4” 11’-10” 15’-10 3/8” 6’-10 3/8” 9’-11 1/4” 12 -0 3/4”

PT2-1212A-2*3 35,704 19,980 4,720 36’-1 1/4” 11’-10” 16’-10 3/8” 6’-10 3/8” 10’-11 1/4” 12’-0 3/4”

PT2-1212A-3*3 37,364 21,640 5,270 36’-1 1/4” 11’-10” 17’-10 3/8” 6’-10 3/8” 11’-11 1/4” 12’-0 3/4”

PT2-1212A-1*4 45,541 24,574 4,170 24’-0 1/2” 23’-9” 17’-10 3/8” 7’-10 3/8” 10’-11 1/4” —PT2-1212A-2*4 47,754 26,787 4,720 24’-0 1/2” 23’-9” 18’-10 3/8” 7’-10 3/8” 11’-11 1/4” —PT2-1212A-3*4 49,967 29,000 5,270 24’-0 1/2” 23’-9” 19’-10 3/8” 7’-10 3/8” 12’-11 1/4” —

Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at

the time of publication, which should be reconfirmed at the time of purchase.

Notes:

1. Data corresponds to all available motors for this model.

2. Operating weight is based on the water level in the cold water basin at overflow height. If a lower operating weight is needed to meet design

requirements, your local BAC Representative can provide additional assistance.

Page 6: Cooling Tower Pt2 Engineering Data 20110523

5 Q u E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

P T 2 D I M E N S I O N A L E N G I N E E R I N G D A T A C O N T I N U E D »

A

W

Water OutB

H

L

Water InB

H

FL

Water In (Qty. 2)

Cell 1 Cell 2Cell 1

2” Clean Out

Face A for PT2-1218A-**1 and PT2-1218A-**2

(For 2-Cell Configurations, Connections Typical at Each End)

Face C for Single Cell Configuration for Models PT2-1218A-**1

Face C 2-Cell Configuration for Models PT2-1218A-**2

A

W

Cell 1, Face A Cell 2, Face B

Water Out (Qty. 2)

Cell 2, Face C

Water In (Qty. 2)

B

H

L

Face A/B of 2-Cell Configuration for Models PT2-1218A-**T (Connections Typical at Each End)

Face C of 2-Cell Configuration for Models PT2-1218A-**T

Face A 3-Cell Configuration for Models PT2-1218A-**3,

Connections Typical at Each End

Plan View of 2-Cell Configuration for Models PT2-1218A-**T

Plan View of 2-Cell Configuration for Models PT2-1218A-**2

Face C

Face C

Face D

Face D

Face

A

Face

AFa

ce B

Face

B

Cell 1

Cell 2

L

W

Face D

Face C

Face

A

Face

B

Cell 1 Cell 2

Face D

Face C

Face

B

Face

A

L

W

Page 7: Cooling Tower Pt2 Engineering Data 20110523

E N G I N E E R I N G D A T A : P T 2 C O O L I N G T O W E R S 6

Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at

the time of publication, which should be reconfirmed at the time of purchase.

Notes:

1. Data corresponds to all available motors for this model.

2. Operating weight is based on the water level in the cold water basin at overflow height. If a lower operating weight is needed to meet design

requirements, your local BAC Representative can provide additional assistance.

Model Number{1}

Nominal Weights (lbs) Dimensions

Operating{2} ShippingHeaviest Section L W H A B F

PT2-1218A-1*1 20,190 10,800 7,090 17’-11 3/4” 11’-10” 14'-8 1/8” 5’-9 5/8” 8’-9 5/8” —PT2-1218A-2*1 20,930 11,540 7,830 17’-11 3/4” 11’-10” 15'-8 1/8” 5’-9 5/8” 9’-9 5/8” —PT2-1218A-3*1 21,670 12,280 8,570 17’-11 3/4” 11’-10” 16'-8 1/8” 5’-9 5/8” 10’-9 5/8” —PT2-1218A-1*2 40,600 21,820 7,090 36’-0 1/2” 11’-10” 15'-8 1/8” 6’-9 5/8” 9’-9 5/8” 18’-0 3/4”

PT2-1218A-2*2 42,080 23,300 7,830 36’-0 1/2” 11’-10” 16'-8 1/8” 6’-9 5/8” 10’-9 5/8” 18’-0 3/4”

PT2-1218A-3*2 43,560 24,780 8,570 36’-0 1/2” 11’-10” 17'-8 1/8” 6’-9 5/8” 11’-9 5/8” 18’-0 3/4”

PT2-1218A-1*T 40,720 21,940 7,090 17’-11 3/4” 23’-9” 16'-2 1/8” 7’-3 5/8” 10’-3 5/8” —PT2-1218A-2*T 42,200 23,420 7,830 17’-11 3/4” 23’-9” 17'-2 1/8” 7’-3 5/8” 11’-3 5/8” —PT2-1218A-3*T 43,680 24,900 8,570 17’-11 3/4” 23’-9” 18'-2 1/8” 7’-3 5/8” 12’-3 5/8” —PT2-1218A-1*3 61,080 32,910 7,090 54’-1 1/4” 11’-10” 16'-2 1/8” 7’-3 5/8” 10’-3 5/8” 18’-0 3/4”

PT2-1218A-2*3 63,300 35,130 7,830 54’-1 1/4” 11’-10” 17'-2 1/8” 7’-3 5/8” 11’-3 5/8” 18’-0 3/4”

PT2-1218A-3*3 65,520 37,350 8,570 54’-1 1/4” 11’-10” 18'-2 1/8” 7’-3 5/8” 12’-3 5/8” 18’-0 3/4”

PT2-1218A-1*4 81,880 44,320 7,090 36’-0 1/2” 23’-9” 17'-2 1/8” 8’-3 5/8” 11’-3 5/8” —PT2-1218A-2*4 84,840 47,280 7,830 36’-0 1/2” 23’-9” 18'-2 1/8” 8’-3 5/8” 12’-3 5/8” —PT2-1218A-3*4 87,800 50,240 8,570 36’-0 1/2” 23’-9” 19'-2 1/8” 8’-3 5/8” 13’-3 5/8” —

B

H

FL

FW

Water Out (Qty. 3)

Cell 1 Cell 1 Cell 2 Cell 3

Water In (Qty. 3)

A

2” Clean Out

Face C 3-Cell Configuration for Models PT2-1218A-**3Face A 3-Cell Configuration for

Models PT2-1218A-**3, Connections Typical at Each End

Cell 1, Face A Cell 2, Face B

Water Out (Qty. 4)

A

W

Water In (Qty. 4)

Cell 3 Cell 4

L

B

H

Face A/B Quad Configuration for Models PT2-1218A-**4, Connections Typical at Each End

Face C Quad Configuration for Models PT2-1218A-**4 , Connections Typical at Each End

Page 8: Cooling Tower Pt2 Engineering Data 20110523

7 Q u E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

Model Number[1]

Airflow Per Cell(CFM)

1 Cell 2 Cell: PT2-XXXXA-**2[2] 2 Cell: PT2-1218A-**T [2] 3 Cell 4 Cell

Nominal Tonnage[3]

Motor Qty. and HP

Nominal Tonnage[3]

Motor Qty. and HP

Nominal Tonnage[3]

Motor Qty. and HP

Nominal Tonnage[3]

Motor Qty. and HP

Nominal Tonnage[3]

Motor Qty. and HP

PT2-0412A-1H*PT2-0412A-2J*

30,75033,520

117149

(2) 5(2) 7.5

——

——

——

——

——

——

——

——

PT2-0709A-1K*PT2-0709A-2L*PT2-0709A-3L*

43,91046,50043,520

157199210

(1) 10(1) 15(1) 15

316400423

(2) 10(2) 15(2) 20

———

———

481606640

(3) 10(3) 15(3) 20

———

———

PT2-0809A-1K*PT2-0809A-2L*PT2-0809A-3M*

47,00050,34051,820

168215250

(1) 10(1) 15(1) 20

338433503

(2) 10(2) 15(2) 20

———

———

514656761

(3) 10(3) 15(3) 20

———

———

PT2-0812A-1M*PT2-0812A-2N*PT2-0812A-3O*

74,36073,72072,490

265315350

(1) 20(1) 25(1) 30

536635704

(2) 20(2) 25(2) 30

———

———

816963

1,066

(3) 20(3) 25(3) 30

———

———

PT2-1009A-1L*PT2-1009A-2M*PT2-1009A-3N*

62,51062,86076,360

223268301

(1) 15(1) 20(1) 25

446537602

(2) 15(2) 20(2) 25

———

———

679814911

(3) 15(3) 20(3) 25

9011,0821,211

(4) 15(4) 20(4) 25

PT2-1012A-1M*PT2-1012A-2O*PT2-1012A-3O*

81,73086,26080,690

292368389

(1) 20(1) 30(1) 30

586740781

(2) 20(2) 30(2) 30

———

———

8901,1201,182

(3) 20(3) 30(3) 30

1,1731,4811,564

(4) 20(4) 30(4) 30

PT2-1212A-1N*PT2-1212A-2O*PT2-1212A-3P*

101,160101,190104,080

361432502

(1) 25(1) 30(1) 40

721863

1,004

(2) 25(2) 30(2) 40

———

———

1,0921,3051,515

(3) 25(3) 30(3) 40

1,4411,7262,007

(4) 25(4) 30(4) 40

PT2-1218A-1K*PT2-1218A-1L*PT2-1218A-1M*PT2-1218A-1N*PT2-1218A-1O*PT2-1218A-1P*PT2-1218A-2K*PT2-1218A-2L*PT2-1218A-2M*PT2-1218A-2N*PT2-1218A-2O*PT2-1218A-2P*PT2-1218A-2Q*PT2-1218A-3K*PT2-1218A-3L*PT2-1218A-3M*PT2-1218A-3N*PT2-1218A-3O*PT2-1218A-3P*PT2-1218A-3Q*PT2-1218A-3R*PT2-1218A-3S*

99,330113,210124,140133,280141,220154,63093,890

106,970117,260125,870133,330145,940156,46089,340

101,590111,200119,210126,150137,830147,550155,940163,410

355404442474502550402456500536568622667427485531569603660708750787

(2) 5(2) 7.5(2) 10

(2) 15[4]

(2) 15(2) 20(2) 5

(2) 7.5(2) 10

(2) 15[4]

(2) 15(2) 20(2) 25(2) 5

(2) 7.5(2) 10

(2) 15[4]

(2) 15(2) 20(2) 25(2) 30(2) 35

713811887952

1,0081,104805914

1,0011,0741,1371,2451,336854971

1,0631,1401,2071,3221,4181,5021,577

(4) 5(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 5

(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 25(4) 5

(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 25(4) 30(4) 35

711808884949

1,0051,100803912999

1,0721,1351,2431,333852969

1,0601,1381,2051,3191,4151,4991,574

(4) 5(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 5

(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 25(4) 5

(4) 7.5(4) 10

(4) 15[4]

(4) 15(4) 20(4) 25(4) 30(4) 35

1,0721,2181,3341,4311,5151,6591,2091,3741,5041,6131,7091,8712,0071,2831,4581,5961,7121,8131,9862,1302,2562,368

(6) 5(6) 7.5(6) 10

(6) 15[4]

(6) 15(6) 20(6) 5

(6) 7.5(6) 10

(6) 15[4]

(6) 15(6) 20(6) 25(6) 5

(6) 7.5(6) 10

(6) 15[4]

(6) 15(6) 20(6) 25(6) 30(6) 35

1,4001,5911,7421,8691,9792,1671,5871,8031,9742,1172,2432,4552,6341,6871,9172,0992,2522,3852,6112,8012,9673,115

(8) 5(8) 7.5(8) 10

(8) 15[4]

(8) 15(8) 20(8) 5

(8) 7.5(8) 10

(8) 15[4]

(8) 15(8) 20(8) 25(8) 5

(8) 7.5(8) 10

(8) 15[4]

(8) 15(8) 20(8) 25(8) 30(8) 35

Engineering Data

Notes:

1. * in Model Number below indicates number of cells.

2. For a plan view of Models PT2-1218A-**2 and

PT2-1218A-**T, see Page 5.

3. Nominal tons of cooling represents 3 GPM of water from 95°F

to 85°F at a 78°F entering wet-bulb temperature.

4. The cell will have a break horsepower of 25 HP.

5. Up-to-date engineering data, free product selection software,

and more can be found at www.BaltimoreAircoil.com.

P E R F O R M A N C E

Page 9: Cooling Tower Pt2 Engineering Data 20110523

E N G I N E E R I N G D A T A : P T 2 C O O L I N G T O W E R S 8

Structural Support

The recommended support arrangement for the PT2 Cooling Tower consists of parallel I-beams positioned as shown on the drawing. Besides providing adequate support, the steel also serves to raise the unit above any solid foundation to assure access to the bottom of the tower. The PT2 Cooling Tower may also be supported on columns at the anchor bolt locations shown in Plan A.

A minimum bearing surface of 12 in2 (77,742mm2) must be provided under each of the concentrated load points (See Note 5). To support a PT2 Cooling Tower on columns with an alternate steel support arrangement, or the optional structurally upgraded unit, consult your local BAC Representative.

L

W

C

D D

A B

B

E E F

Single Cell Standard Unit Only

Model Number L W A B C D E F

PT2-0412 11'-11 3/4” 4'-0” 3'-9 3/4” 1 1/8” 10'-5 1/4” 9 1/4” — —

PT2-0709 8'-11 3/4” 7'-3 1/4” 7'-1” 1 1/8” 7'-5 1/4” 9 1/4” — —

PT2-0809 8'-11 3/4” 8'-5 3/4” 8'-3 1/2” 1 1/8” 7'-5 1/4” 9 1/4” — —

PT2-0812 11'-11 3/4” 8'-5 3/4” 8'-3 1/2” 1 1/8” 10'-5 1/4” 9 1/4” — —

PT2-1009 8'-11 3/4” 9'-10” 9'-7 3/4” 1 1/8” 7'-5 1/4” 9 1/4” — —

PT2-1012 11'-11 3/4” 9'-10” 9'-7 3/4” 1 1/8” 10'-5 1/4” 9 1/4” — —

PT2-1212 11'-11 3/4” 11'-10” 11'-7 3/4” 1 1/8” 10'-5 1/4” 9 1/4” — —

PT2-1218 17'-11 3/4” 11'-10” 11'-7 3/4” 1 1/8” 17'-3 3/4" 4" 5'-8 3/32" 5'-11 1/2"

S I N G L E C E L L S T A N D A R D U N I T O N LY

Notes:

1. Contact your local BAC Representative for

multi-cell or structurally upgraded unit

steel support.

2. Support beams and anchor bolts to be

selected and installed by others.

3. All support steel must be level at the top.

4. Beam size should be calculated in

accordance with accepted structural

practice. Maximum deflection of beam

under unit to be 1/360 of span, not

to exceed 1/2”. Use 65% of operating

weight as a uniform load on each beam.

The length of the beam must be at least

equal to the length of the basin. Refer to

engineering data for basin dimensions.

Support data and maximum allowed

deflection is tabulated in the table to

the left.

5. If vibration isolators are used, a rail

or channel must be provided between

the unit and the isolators to provide

continuous support. Refer to vibration

isolators drawings for the length of the

rails and mounting hole. Locations, which

may differ from the length and the hole

location of the unit itself.

Page 10: Cooling Tower Pt2 Engineering Data 20110523

9 Q u E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

Structural Support

For replacement installations, the PT2 Cooling Tower has been designed to match the supporting steel of many existing counterflow and crossflow cooling towers without modifications. Shown below are the most common steel support arrangements which can be accommodated by the PT2. IBC wind and seismic load ratings are not available on alternate steel support arrangements. If individual point support is required, or if the steel arrangement is not shown as below, consult your local BAC Representative for assistance.

Notes:

1. Contact your local BAC Representative for

multi-cell or structurally upgraded unit

steel support.

2. Support beams and anchor bolts to be

selected and installed by others.

3. All support steel must be level at the top.

4. Beam size should be calculated in

accordance with accepted structural

practice. Maximum deflection of beam

under unit to be 1/360 of span, not

to exceed 1/2”. Use 65% of operating

weight as a uniform load on each beam.

The length of the beam must be at least

equal to the length of the basin. Refer to

engineering data for basin dimensions.

Support data and maximum allowed

deflection is tabulated in the table to the

right.

5. If vibration isolators are used, a rail

or channel must be provided between

the unit and the isolators to provide

continuous support. Refer to vibration

isolators drawings for the length of the

rails and mounting hole. Locations, which

may differ from the length and the hole

location of the unit itself.

A LT E R N A T I V E

Model Number L W A B C D E F G

PT2-0412 11' 11 3/4” 4' 0” 3' 4” 4” 11' 9 1/2” 1 1/8” — — —

PT2-0709 8' 11 3/4” 7' 3 1/4” 6' 7 1/4” 4” 8' 9 1/2” 1 1/8” — — —

PT2-0809 8' 11 3/4” 8' 5 3/4” 7' 9 3/4” 4” 8' 9 1/2” 1 1/8” — — —

PT2-0812 11' 11 3/4” 8' 5 3/4” 7' 9 3/4” 4” 11' 9 1/2” 1 1/8” — — —

PT2-1009 8' 11 3/4” 9' 10” 9' 2” 4” 8' 9 1/2” 1 1/8” — — —

PT2-1012 11' 11 3/4” 9' 10” 9' 2” 4” 11' 9 1/2” 1 1/8” — — —

PT2-1212 11' 11 3/4” 11' 10” 11' 2” 4” 11' 9 1/2” 1 1/8” — — —

PT2-1218 17' 11 3/4” 11' 10” 11' 2” 4" 17'-9 1/2" 1 1/8” 5'-11" 5'-11 1/2" 5'-7"

S I N G L E C E L L S T A N D A R D U N I T – A LT E R N A T I V E S T E E L S U P P O R T

W

L

C

E F

E

G G

A

D D

B B

Single Cell Standard Unit – Alternative Steel Support