cooling tower winter operating procedures
TRANSCRIPT
Step 1-watch the weather
If the water temperature falls below
55 degrees, your fans should be
shut down one at a time
Your cooling tower cold water
temperature should be maintained at
a minimum of…
With all fans off, remember that
splash-out may occur
Step 2-Be aware of splash-out
from your cooling tower
Your cooling tower should now be
equipped with closure tarpaulins
(if available)
Step 3-protect your tower
from the wind
These should be installed at the
air inlet opening on the
windward side of your tower.
The same tower inspection method
should be followed as your
pre-starting procedures.
Step 4-double check
In addition, a visual inspection of the
air inlet area should be done during
the coldest hours of the day to note
any additional ice buildup or damage.
Any Ice buildup on the perimeter
columns or the bottom of the fill of your
cooling tower should be noted and
frequently monitored.
Step 5-watch for ice
If ice buildup becomes excessive, reverse
operating procedures may be needed.
**DO NOT in any case try to physically remove the ice
buildup. Melting leaves components in good condition.
Physical removal of ice will result in more damage.
**Before moving a head with this step, see you
documentation provided by the motor starter and controls
vendor to check if your tower is capable of reverse operation.
Step 6a-Rotate in reverse
If your cooling tower has reverse
operation, meaning the fan can
rotate in reverse, this will help push
air down through the tower
components from the fan stack
through the air inlet. This pushes
warm air to the air inlet opening for
melting ice buildup.
**Reverse operation should only be performed as a last
resort and on the cells with SEVERE ice build-up.
Step 6b-Rotate in reverse
Monitor the reverse mode operation
CONTINUOUSLY.
The reverse mode is to be activated
for NO MORE than 30 minutes.
**Because air flow is reversed, splash-out will occur through
the air-inlet area. Louvers with heavy ice will split and
break, this too will cause splash-out.
Step 6c - Rotate in reverse
Visually check fans to ensure no ice build up has
occurred, then you may start your fans in reverse.
Flow water for 15 minutes with the fans shut off
to prevent ice buildup in the plenum area.
After you have run your fan in reverse operation for
no more than 30 min, allow an extra 2 min before
operating your fan in forward operation. Repeat
switching off between reverse and forward operations.
**It is acceptable to begin the reverse direction when the fan is wind-
milling in the forward direction. The nearly zero-speed torque applied to
the mechanical equipment is not excessive.
Reverse
Forward
Water Flow
If the cold water temperature is less than 55 degrees, you need to shut
your fans one at a time.
Lets Review
With the cold water temperature below 55 degrees, and all of your fans
shut down, tarpaulins should be placed at the air inlet opening on the
windward side of the cooling tower. Blocking the wind reduces ice buildup.
Double check: the same inspection method should be followed as
under the pre-starting procedures.
If ice buildup is excessive, check your documentation supplied by the
motor starter and controls vendor for the reverse operating function.
If your tower can perform reverse operating procedures, do so only as
a last resort. Remember reverse mode is to only be activated for NO
MORE than 30 min. Remember splash-out will occur. Remember to
allow 2 min. between forward and reverse operations.
Receive more Information…
Download Cooling Tower Depot’s full
article about Winter Operating
Procedures
Become a Cooling Tower Depot (CTD)
member today for exclusive deals and
updates on your cooling towers.
JOIN FOR FREE
DOWNLOAD
Still have questions?Want to know more about your Cooling
Tower Winter Operating Procedures?
Get in touch with us at:
(720) 746-1234
www.coolingtowerdepot.com