coordianción de aislamiento

Upload: alberto-bonsanto

Post on 04-Apr-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/29/2019 Coordiancin de Aislamiento

    1/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 1 -

    Procedure for Insulation Coordination in Four Steps

    [IEC 60071-1]

    Flow chart acc. to IEC 60071-1(Figure 1)

  • 7/29/2019 Coordiancin de Aislamiento

    2/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 2 -

    Procedure for Insulation Coordination in Four Steps

    Determination of the coordination withstand voltages Ucw

    The coordination withstand voltages are the lowest values of withstand voltages ofeach overvoltage class, for which the expected low failure rate of the equipment is notexceeded over its full lifetime.

    Derived from the representative overvoltages Urp by the coordination factor Kc.

    [IEC 60071-1]

    Typical forGermany:0.1% per year 1 failure in1000 years

  • 7/29/2019 Coordiancin de Aislamiento

    3/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 3 -

    Insulation Strength Characteristics

    Factors influencing the dielectric strength of the insulation:

    magnitude, shape, duration and polarity of the applied voltage electric field distribution in the insulation

    homogeneous or non-homogeneous electric field electrodes adjacent to the considered gap and their potential type of insulation

    gaseous liquid solid combination of two or all of them impurity content and the presence of local inhomogeneities

    physical state of the insulation temperature pressure

    other ambient conditions mechanical stress

    history of the insulation (aging, damage) chemical effects

    conductor surface effects

    Factors influencing the dielectric strength of the insulation:

    magnitude, shape, duration and polarity of the applied voltage electric field distribution in the insulation

    homogeneous or non-homogeneous electric field electrodes adjacent to the considered gap and their potential type of insulation

    gaseous liquid solid

    combination of two or all of them impurity content and the presence of local inhomogeneities

    physical state of the insulation temperature

    pressure

    other ambient conditions mechanical stress history of the insulation (aging, damage)

    chemical effects conductor surface effects

  • 7/29/2019 Coordiancin de Aislamiento

    4/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 4 -

    Insulation Strength Characteristics

    Standard atmospheric conditions acc. to IEC 60060-1

    Temperature: 20 C

    Pressure: 1013 hPa

    Absolute humidity: 11 g/m3

    Temperature: 20 C

    Pressure: 1013 hPa

    Absolute humidity: 11 g/m3

  • 7/29/2019 Coordiancin de Aislamiento

    5/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 5 -

    Insulation Strength Characteristics

    Topics to be covered in the following:

    Insulators under polluted conditions

    Probability of flashover (Normal and Weibull distributions)

    Behavior of parallel insulation

    Coordination procedure: deterministic and statistical approach

    Correction with altitude of installation

    Clearances in air; "gap factors"

  • 7/29/2019 Coordiancin de Aislamiento

    6/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 6 -

    Pre-conditionsPre-conditions

    Performance of Insulators under Pollution

    Surface layers

    dust carbon black salt (coastal areas) chemicals (industry, rural areas: fertilizers)

    dust carbon black salt (coastal areas) chemicals (industry, rural areas: fertilizers)

    no problem in dry condition

    after long rain periods: only moderate effect on flashover performance

    most critical:

    Humidification after a long dry periodHumidification after a long dry period

    typical time of the day for insulator flashovers: morning hours (dew!)

  • 7/29/2019 Coordiancin de Aislamiento

    7/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 7 -

    Development of pollution flashoverDevelopment of pollution flashover

    Performance of Insulators under Pollution

    dry zone by inhomogeneity of the layer

    enlargement of the dry zone by heating of the zoneedges (increased current density)

    dry band

    flashover of the dry band

    enlargement of the dry band by arc heating

    (max. temperature at foot points)

  • 7/29/2019 Coordiancin de Aislamiento

    8/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 8 -

    Development of pollution flashoverDevelopment of pollution flashover

    Performance of Insulators under Pollution

    Voltage distribution

    a) with dry bands b) dry bands bridgedby partial arcs

    voltage bridged

    voltage drop increased

    for further details see HVT 2!

  • 7/29/2019 Coordiancin de Aislamiento

    9/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 9 -

    Performance of Insulators under Pollution

    Layer conductivity K is the most important parameter!Layer conductivity K is the most important parameter!

    K= ds ... specific layer conductivity

    ds... thickness of layer

    K= 5 S "light to medium pollution"K= 10 S "medium to heavy pollution"K= 40 S "very heavy pollution"

    Influence of layer conductivityInfluence of layer conductivity for details see IEC 60507

  • 7/29/2019 Coordiancin de Aislamiento

    10/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 10 -

    Determination of layer conductivity frommeasured conductance and insulator geometry

    Determination of layer conductivity frommeasured conductance and insulator geometry

    Performance of Insulators under Pollution

    2 dd

    d d / 2

    r s KG

    l l r

    = =

    Measurement of conductance Gof the full insulator

    shed core

    creepage

    distance lk

    insulator length lV

    Gl

    =general:

  • 7/29/2019 Coordiancin de Aislamiento

    11/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 11 -

    Performance of Insulators under Pollution

    k

    0

    d

    2

    l

    KG

    l

    r

    =

    k

    0

    d

    2

    l

    lF

    r=

    G... conductance of total insulator surface

    form factor"form factor"

    K= FGK= FG

    (IEC 60507*))

    form factor to be determined by

    graphical procedure, describedin IEC 60507

    Determination of layer conductivity frommeasured conductance and insulator geometry

    Determination of layer conductivity frommeasured conductance and insulator geometry

    *) IEC 60507, 2nd Ed. 1991-04: "Artificial pollution tests onhigh-voltage insulators to be used on a.c. systems"

  • 7/29/2019 Coordiancin de Aislamiento

    12/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 12 -

    Decrease in flashover voltage by conductive layersDecrease in flashover voltage by conductive layers

    Performance of Insulators under Pollution

    fo, rain

    0.7 ... 0.9 fo, dry

    Ufo, polluted 0.2 ... 0.3 Ufo,dry

    An overhead line insulator must be desigend about five times as long asrequired to withstand operating stresses under dry conditions!

    An overhead line insulator must be desigend about five times as long as

    required to withstand operating stresses under dry conditions!

    Um = 123 kV

    L-E = 100 kV

    d = 5 kV/cm l = 20 cm would be sufficient (dry!)

    Actual length: ca. 1100 mm

  • 7/29/2019 Coordiancin de Aislamiento

    13/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 13 -

    pCountermeasuresCountermeasures

    Performance of Insulators under Pollution

    ShedsSheds

    s ... flashover or arcing distance

    lk ... creepage distance

    li ... insulator length

    p ... shed overhang

    t ... shed spacing

    Terms ...

  • 7/29/2019 Coordiancin de Aislamiento

    14/61

  • 7/29/2019 Coordiancin de Aislamiento

    15/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 15 -

    Actual Situation for IEC 60815 (as per February 2009)

  • 7/29/2019 Coordiancin de Aislamiento

    16/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 16 -

    Actual Situation for IEC 60815

  • 7/29/2019 Coordiancin de Aislamiento

    17/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 17 -

    Actual Situation for IEC 60815

  • 7/29/2019 Coordiancin de Aislamiento

    18/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 18 -

    Actual Situation for IEC 60815

    Example of a change in IEC 60815-1:2008 compared with 60815:1986

  • 7/29/2019 Coordiancin de Aislamiento

    19/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 19 -

    Performance of Insulators under Pollution

    31 mm/kV for very heavy" pollution severity (IV)25 mm/kV for heavy" pollution severity (III)20 mm/kV for "medium" pollution severity (II)

    16 mm/kV for "light" pollution severity (I)

    31 mm/kV for very heavy" pollution severity (IV)25 mm/kV for heavy" pollution severity (III)

    20 mm/kV for "medium" pollution severity (II)16 mm/kV for "light" pollution severity (I)

    CountermeasuresCountermeasures

    Correction of these values necessary depending on insulator's average diameter Dm*)

    Correction factor kD (derived from service experience):

    *) for definition of Dm see IEC 60815

    Dm (mm) kD< 300 1

    300 - 500 1.1

    > 500 1.2

    Pollution performance gets worsewith increasing diameter!

  • 7/29/2019 Coordiancin de Aislamiento

    20/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 20 -

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    21/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 21 -

    Performance of Insulators under Pollution

    Pollution level Examples of typical environments

    I - Light

    - Areas without industries and with low density of houses equipped with heating plants- Areas with low density of industries or houses but subjected to frequent winds and/or

    rainfall- Agricultural areas

    1)

    - Mountainous areasAll these areas shall be situated at least 10 km to 20 km from the sea and shall not be

    exposed to winds directly from the sea2)

    II - Medium

    - Areas with industries not producing particularly polluting smoke and/or with averagedensity of houses equipped with heating plants- Areas with high density of houses and/or industries but subjected to frequent windsand/or rainfall

    - Areas exposed to wind from the sea but not too close to the coast (at least severalkilometres distant) 2)

    III - Heavy- Areas with high density of industries and suburbs of large cities with high density ofheating plants producing pollution- Areas close to the sea or in any case exposed to relatively strong winds from the sea

    2)

    IV - Very heavy

    - Areas generally of moderate extent, subjected to conductive dusts and to industrial smokeproducing particularly thick conductive deposits- Areas generally of moderate extent, very close to the coast and exposed to sea-sprayor to very strong and polluting winds from the sea- Desert areas, characterized by no rain for long periods, exposed to strong windscarrying sand and salt, and subjected to regular condensation

    1) Use of fertilizers by spraying, or the burning of crop residues, can lead to a higher pollution level due to dispersalby wind.

    2) Distances from sea coast depend on the topography of the coastal area and on the extreme wind conditions.

    IEC 60815:1986, Table 1IEC 60815:1986, Table 1

  • 7/29/2019 Coordiancin de Aislamiento

    22/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 22 -

    Shed profilesShed profiles

    Performance of Insulators under Pollution

    Some typical shed profiles (from IEC 60815; explanation of the parameters see there).From left to right: normal shed profile, alternating shed profile, underrib sheds (fog profile),

    cap-and-pin insulators

    Some typical shed profiles (from IEC 60815; explanation of the parameters see there).From left to right: normal shed profile, alternating shed profile, underrib sheds (fog profile),cap-and-pin insulators

    IEC 60815

  • 7/29/2019 Coordiancin de Aislamiento

    23/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 23 -

    Performance of Insulators under Pollution

    Recommendations of IEC 60815 - ExampleShed profilesShed profiles

    c 30 mm

    p1p2 15 mm

    s/p1 0.65 (in case of plain, non-underripped sheds)

    lx/dx < 5

    C.F. 3.5 (pollution classes I + II) 4 (pollution classes III + IV)

    C.F.= creepage factor = lt/stlt = total creepage distancest = arcing distance (arcing horns not considered)

    IEC 60815

  • 7/29/2019 Coordiancin de Aislamiento

    24/61

  • 7/29/2019 Coordiancin de Aislamiento

    25/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 25 -

    Performance of Insulators under Pollution

    Shed profilesShed profiles Example of user'sexperience

    From:

    Raouf Znaidi: "ServiceExperience and MaintenanceRequirements for Different Typesof Insulators in Tunisia", WorldCongress on Insulators, Arrestersand Bushings, Hong Kong, Nov.27-30, 2005

  • 7/29/2019 Coordiancin de Aislamiento

    26/61

  • 7/29/2019 Coordiancin de Aislamiento

    27/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 27 -

    Semi-conducting glazingSemi-conducting glazing

    Performance of Insulators under Pollution

    Idea: to avoid dry-band arcing by resistive bypass

    No flashover due to bypass current

    surface current

    Drawback: stable semiconducting glazing difficult to produce

  • 7/29/2019 Coordiancin de Aislamiento

    28/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 28 -

    Semi-conducting glazingSemi-conducting glazing

    Performance of Insulators under Pollution

    Under development: for composite insulators by coating filled with micro-varistors

    -varistors

  • 7/29/2019 Coordiancin de Aislamiento

    29/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 29 -

    Composite insulatorsComposite insulators

    Performance of Insulators under Pollution

    introduced in the beginning of the 1970s today virtually" state of the art

    problems": long time performance not yet clear,"brittle fracture", animal attacks

    Shed material:

    EPDM (Ethylene-Propylene-Diene-Monomer)

    only in distribution

    Silicone rubber (SIR)

    FRP core

    extruded SIR sheath

    push-over SIR sheds

    crimped-on metal end fitting

  • 7/29/2019 Coordiancin de Aislamiento

    30/61

  • 7/29/2019 Coordiancin de Aislamiento

    31/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 31 -

    From an EPRI Questionnaire in North America (publ. in 2003)

  • 7/29/2019 Coordiancin de Aislamiento

    32/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 32 -

    From an EPRI Questionnaire in North America (publ. in 2003)

    compare this with the"bathtub curve"of failure no evidence for aging

  • 7/29/2019 Coordiancin de Aislamiento

    33/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 33 -

    From an EPRI Questionnaire in North America (publ. in 2003)

  • 7/29/2019 Coordiancin de Aislamiento

    34/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 34 -

    From an EPRI Questionnaire in North America (publ. in 2003)

  • 7/29/2019 Coordiancin de Aislamiento

    35/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 35 -

    HydrophobicityHydrophobicity

    Performance of Insulators under Pollution

    One of the most important properties of composite insulators

    with regard to pollution performance isHydrophobicityHydrophobicity

  • 7/29/2019 Coordiancin de Aislamiento

    36/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 36 -

    HydrophobicityHydrophobicity

    Performance of Insulators under Pollution

    Advancing angle

    Receding angle= most important for characterization

    of hydrophobicity

    Receding angle= most important for characterization

    of hydrophobicity

    Properties change under the influence of electrical field actual research!

  • 7/29/2019 Coordiancin de Aislamiento

    37/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 37 -

    HydrophobicityHydrophobicity

    Performance of Insulators under Pollution

    IEC/TS 62073

    Wettability classes*)

    *) Based on the "STRI Guide" (of STRI, Ludvika/Sweden)

  • 7/29/2019 Coordiancin de Aislamiento

    38/61

  • 7/29/2019 Coordiancin de Aislamiento

    39/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 39 -

    Natural Test SitesNatural Test Sites

    Weather Aging Tests for Polymeric Insulators *)

    Example: Koeburg, RSA

    Realistic test conditions, but no acceleration

    factors

    long test times necessary (several years)

    "(In)famous" test sites:

    Koeburg, RSA (Atlantic Ocean) Dungeness, UK (The Channel)

    Martiguez, F (Mediterranean Sea)

    *) NOTE: often the term NCI =non ceramic insulators isbeing used

  • 7/29/2019 Coordiancin de Aislamiento

    40/61

  • 7/29/2019 Coordiancin de Aislamiento

    41/61

  • 7/29/2019 Coordiancin de Aislamiento

    42/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 42 -

    The "Tracking and Erosion Test" acc. to IEC 61109The "Tracking and Erosion Test" acc. to IEC 61109

    Weather Aging Tests for Polymeric Insulators

    Examples of test chambers

  • 7/29/2019 Coordiancin de Aislamiento

    43/61

  • 7/29/2019 Coordiancin de Aislamiento

    44/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 44 -

    Cyclic TestsCyclic Tests

    Weather Aging Tests for Polymeric Insulators

    Cyclic tests usually consist in applying, in addition to voltage stress, various stresses in a cyclic

    manner:

    - solar radiation simulation;- artificial rain;

    - dry heat;

    - damp heat (near saturation);

    - high dampness at room temperature (saturation has to be obtained);

    - salt fog at low concentration.Furthermore, temperature variations may cause some degree of mechanical stress, especially

    at the level of insulator interfaces and also give rise to condensation phenomena, which are

    repeated several times in the course of a cycle.

    For power frequency test voltage, a test transformer shall be used. The test circuit when loaded

    with a resistive current of 250 mA (r.m.s.) on the high voltage side shall experience a maximum

    voltage drop of 5 %. The protection level shall be set at 1 A (r.m.s.).

    Problem: no general agreement on one particular test!Problem: no general agreement on one particular test! Examples next slides:

  • 7/29/2019 Coordiancin de Aislamiento

    45/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 45 -

    Cyclic TestsCyclic Tests

    Weather Aging Tests for Polymeric Insulators

    Practical testproblem: rainand solarradiation at thesame time!

  • 7/29/2019 Coordiancin de Aislamiento

    46/61

    h f l l

  • 7/29/2019 Coordiancin de Aislamiento

    47/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 47 -

    Cyclic TestsCyclic Tests

    Weather Aging Tests for Polymeric Insulators

    "EPRI" cycle: a year in service is considered to be represented by 10 days of summercycle and 11 days of winter cycle. A duration of 5040 h is required for the whole test,10 summer/winter cycles of 21 days each.

    O h A i T f P l i I l

  • 7/29/2019 Coordiancin de Aislamiento

    48/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 48 -

    Wheel Test acc. to IEC 62217Wheel Test acc. to IEC 62217

    Other Aging Tests for Polymeric Insulators

    The test specimens shall be cleaned with de-ionized water before starting the test. The testspecimens are mounted on the wheel as shown in Figure A.1 below. They go through fourpositions in one cycle. Each test specimen remains stationary for about 40 s in each of the

    four positions. The 90 rotation from one position to the next takes about 8 s. In the first partof the cycle the insulator is dipped into a saline solution. The second part of the test cyclepermits the excess saline solution to drip off the specimen ensuring that the light wetting ofthe surface gives rise to sparking across dry bands that will form during the third part of thecycle. In that part the specimen is submitted to a power frequency voltage. In the last part ofthe cycle the surface of the specimen that had been heated by the dry band sparking isallowed to cool.

    Electrical stress: The power frequency test voltage in kV is determined by dividing theactual creepage distance in millimetres by 28,6.

    NaCl content of de-ionized water: 1,40 kg/m 0,06 kg/mAmbient temperature: 20 C 5 KTest duration: 30 000 cycles

    The test is regarded as passed, if on both test specimens: no tracking occurs for composite insulators: erosion depth is less than 3 mm and does not reach the core; if applicable for resin insulators: erosion depth is less than 3 mm; no shed, housing or interface is punctured.

    Extremely severe test!

    Oth A i T t f P l i I l t

  • 7/29/2019 Coordiancin de Aislamiento

    49/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 49 -

    Wheel TestWheel Test

    Other Aging Tests for Polymeric Insulators

    P f f I l t d P ll ti

  • 7/29/2019 Coordiancin de Aislamiento

    50/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 50 -

    "Silicone Bonus""Silicone Bonus"

    Performance of Insulators under Pollution

    For NCIs with permanent (recovering) hydrophobic characteristics a "silicone bonus" may beapplied as a reduction factor of creepage distance (C.D.) compared with ceramic insulators:

    Class 1 : 70 % 75 % of C.D. of ceramic insulators

    Class 2 : 80 % of C.D. of ceramic insulators (not applicable in coastal areas!)

    Class 3 : same C.D. as for ceramic insulators

    Class 4 : in general, application of NCI should be carefully checked for each

    individual application

    Class 1 : 70 % 75 % of C.D. of ceramic insulators

    Class 2 : 80 % of C.D. of ceramic insulators (not applicable in coastal areas!)

    Class 3 : same C.D. as for ceramic insulatorsClass 4 : in general, application of NCI should be carefully checked for each

    individual application

    P f m nc f P l m ic Insul t s

  • 7/29/2019 Coordiancin de Aislamiento

    51/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 51 -

    Silicone rubber as insulator materialSilicone rubber as insulator material

    Performance of Polymeric Insulators

    Other problems ....

    Moss, algea

    Performance of Polymeric Insulators

  • 7/29/2019 Coordiancin de Aislamiento

    52/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 52 -

    Silicone rubber as insulator materialSilicone rubber as insulator material

    Other problems ....

    Animal attack (parrots, cockattoos, termites)

    Example: AustraliaExample: Australia

    Performance of Polymeric Insulators

    Performance of Polymeric Insulators

  • 7/29/2019 Coordiancin de Aislamiento

    53/61

    FachgebietHochspannungstechnik

    Overvoltage Protection and Insulation Coordination / Chapter 6 - 53 -

    Silicone rubber as insulator materialSilicone rubber as insulator material

    Other problems ....

    Animal attack (parrots, cockattoos, termites)

    Example: AustraliaExample: Australia

    Performance of Polymeric Insulators

    Performance of Polymeric Insulators

  • 7/29/2019 Coordiancin de Aislamiento

    54/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 54 -

    Brittle fractureBrittle fracture

    Performance of Polymeric Insulators

    From:

    M. Kuhl: "FRP Rods for Brittle Fracture Resistant CompositeInsulators",http://www.lappinsulator.com/downloadcenter/technical.asp

    Countermeasures:

    ECR glass (electro-chemical resistant)

    quality of sealing at triple point field stress reduction by grading rings

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    55/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 55 -

    Performance of Insulators under Pollution

    2 different methods:

    Salt fog methodSalt fog method

    Solid layer methodSolid layer method

    Artificial pollution testsArtificial pollution tests

    IEC standard 60507IEC standard 60507

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    56/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 56 -

    Salt fog methodSalt fog method

    Performance of Insulators under Pollution

    Test specimen energized at operating voltage under conductive salt fog exposureTest specimen energized at operating voltage under conductive salt fog exposure

    Salt mass concentration between 2.5 kg/m3 und 224 kg/m3Salt mass concentration between 2.5 kg/m3 und 224 kg/m3

    (1 kg/m3 corresponds to 1 g/l)

    Classification by withstand salt mass concentrationClassification by withstand salt mass concentration

    Test specimen must not flash over within a specified time of exposureTest specimen must not flash over within a specified time of exposure

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    57/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 57 -

    Solid layer methodSolid layer method

    Performance of Insulators under Pollution

    Test specimen is energized in a coldfog chamber and then exposed tohumidity

    Test specimen is energized in a coldfog chamber and then exposed tohumidity

    Layer conductivity between 3 S and 80 SLayer conductivity between 3 S and 80 S

    Classification by withstand layer conductivity or withstand salt deposit densityClassification by withstand layer conductivity or withstand salt deposit density

    Solid layer of specified conductivity is applied in wet condition and driedSolid layer of specified conductivity is applied in wet condition and dried

    Test specimen is exposed tohumidity in a cold fog chamberand then energized

    Test specimen is exposed tohumidity in a cold fog chamberand then energized

    Test specimen must not flash over within a specified time of exposure

    Test specimen must not flash over within a specified time of exposure

    Salt Deposit Density (SDD) between 0.03 mg/cm2 and 0.60 mg/cm2Salt Deposit Density (SDD) between 0.03 mg/cm2 and 0.60 mg/cm2

  • 7/29/2019 Coordiancin de Aislamiento

    58/61

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    59/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 59 -

    Radial Field Stress under PollutionRadial Field Stress under Pollution

    Performance of Insulators under Pollution

    MO column

    Conductivelayer

    Gas or solid

    Solid

    Uaxial,int

    Uradial

    Arises if there is an internal active part with a

    given, constant axial voltage distribution; risk of

    internal PD in case of internal gas volume

    puncture in case of pure solid insulation

    MO-Scheiben

    Porzellangehuse-Innenwand

    MO discs

    porcelain housing, inner wall

    Photo: PD in aporcelain housedsurge arrester

    Performance of Insulators under Pollution

  • 7/29/2019 Coordiancin de Aislamiento

    60/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 60 -

    Dielectric and Thermal EffectsDielectric and Thermal Effects

    f m f

    Internal partialdischarges

    changes in internalatmosphere

    risk of deterioration

    of all internal parts

    Internal partialdischarges

    changes in internalatmosphere

    risk of deterioration

    of all internal parts

    Risk of partialheating of internal

    active elements

    Risk of partialheating of internalactive elements

    Risk of external flashoversRisk of external flashovers

    Outer surface discharges

    Risk of partial heating ofinternal active elements

    Outer surface discharges

    Risk of partial heating ofinternal active elements

    Example: 800-kV surge arrester

    Emerging Insulator Standards

  • 7/29/2019 Coordiancin de Aislamiento

    61/61

    FachgebietHochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 6 - 61 -

    g g

    From:

    Claude de Tourreil: "New IECstandards: their Impact on futureSelection of CompositeInsulators", World Congress onInsulators, Arresters andBushings, Hong Kong, Nov. 27-30, 2005