FIT-410.01 R0 D01/06/2010 Project: Bermuda Villas SN. SPECIFIED CONDITIONS Location UNIT TYPE CFM QTY TMBH SMBH DCFM TR VILLA TYPE - A [ 5 VILLAS] 1 AC-GF-FCU-01 Ducted 18 480 5 17.99 15.8 685 1.499 2 AC-GF-FCU-02 Ducted 18 640 5 17.46 16.36 779 1.455 3 AC-GF-FCU-03 Ducted 32 640 5 30.9 25.29 981 2.575 4 AC-GF-FCU-04 Ducted 72 1920 5 67.36 61 2757 5.613 5 AC-GF-FCU-05 Ducted 60 1600 5 55.28 51.44 2426 4.607 6 AC-FF-FCU-01 Ducted 18 480 5 19.06 17.97 862 1.588 7 AC-FF-FCU-02 Ducted 24 480 5 25.41 24.31 1189 2.118 8 AC-FF-FCU-03 Ducted 12 480 5 13.04 11.94 551 1.087 9 AC-FF-FCU-04 Ducted 24 640 5 11.2 10.83 494 0.933 10 AC-FF-FCU-05 Ducted 36 960 5 29.84 28.75 1418 2.487 11 AC-FF-FCU-06 Ducted 32 800 5 28.9 27.25 588 2.408 55 Note: 1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 ºF (21.1 ºC) DB / 60 ºF (15.60 ºC) WB Design conditions selected based on 27/19 air on coil & 46 deg C ambient temp. Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 ºF AS PER HEAT LOAD CALCULATIONS REQUIREMENT TMBH (NOM) Refrigerent Type: R-407 C

Upload: bala-krishna-galla

Post on 10-Nov-2015

212 views

Category:

Documents


0 download

DESCRIPTION

vvcb

TRANSCRIPT

Type AProject: Bermuda Villas

SN.SPECIFIED CONDITIONSAS PER HEAT LOAD CALCULATIONS REQUIREMENTLocation UNIT TYPET.KWS.KWLPSTMBH (NOM)S.MBHCFMQTYTMBHSMBHDCFMTRVILLA TYPE - A [ 5 VILLAS]1AC-GF-FCU-01Ducted180480517.9915.86851.499SU-12AC-GF-FCU-02Ducted180640517.4616.367791.455SU-13AC-GF-FCU-03Ducted32640530.925.299812.575SU-34AC-GF-FCU-04Ducted721920567.366127575.613SU-85AC-GF-FCU-05Ducted601600555.2851.4424264.607SU-76AC-FF-FCU-01Ducted180480519.0617.978621.588SU-27AC-FF-FCU-02Ducted24480525.4124.3111892.118SU-18AC-FF-FCU-03Ducted12480513.0411.945511.087SU-19AC-FF-FCU-04Ducted240640511.210.834940.933SU-110AC-FF-FCU-05Ducted360960529.8428.7514182.487SU-311AC-FF-FCU-06Ducted32800528.927.255882.408SU-355Note:1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB Design conditions selected based on 27/19 air on coil & 46 deg C ambient temp. Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 F Refrigerent Type: R-407 C

&9FIT-410.01 R0 D01/06/2010

Type BProject: Bermuda Villas

SN.SPECIFIED CONDITIONSAS PER HEAT LOAD CALCULATIONS REQUIREMENTLocation UNIT TYPET.KWS.KWLPSTMBH (NOM)S.MBHCFMQTYTMBHSMBHDCFMTRVILLA TYPE - B [ 20 VILLAS]1AC-GF-FCU-01Ducted1804802014.6213.728961.22SU-12AC-GF-FCU-02Ducted1804802015.7815.3310011.32SU-13AC-GF-FCU-03Ducted246402022.8820.8413611.91SU-24AC-GF-FCU-04Ducted6016002063.1561.840375.26SU-75AC-GF-FCU-05Ducted369602038.136.0623553.18SU-46AC-FF-FCU-01Ducted3008002027.9727.5217982.33SU-27AC-FF-FCU-02Ducted246402020.2319.7812921.69SU-28AC-FF-FCU-03Ducted3008002027.2726.8217522.27SU-29AC-FF-FCU-04Ducted36011202038.713802624993.23SU-410AC-FF-FCU-05Ducted3611202038.2337.124233.19SU-4200Note:1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 F Refrigerent Type: R-407 C

&9FIT-410.01 R0 D01/06/2010

Type CProject: Bermuda Villas

SN.SPECIFIED CONDITIONSAS PER HEAT LOAD CALCULATIONS REQUIREMENTLocation UNIT TYPET.KWS.KWLPSTMBH (NOM)S.MBHCFMQTYTMBHSMBHDCFMVILLA TYPE - C [23 VILLAS]1AC-GF-FCU-01Ducted1804802314.6213.728961.22SU-12AC-GF-FCU-02Ducted1804802315.7815.3310011.32SU-13AC-GF-FCU-03Ducted2406402322.8820.8413611.91SU-24AC-GF-FCU-04Ducted7216002363.1561.840375.26SU-75AC-GF-FCU-05Ducted3609602338.136.0623553.18SU-46AC-FF-FCU-01Ducted248002314.2213.126121.19SU-17AC-FF-FCU-02Ducted184802318.6617.568411.56SU-18AC-FF-FCU-03Ducted4211202323.8222.7211071.99SU-29AC-FF-FCU-04Ducted4812802331.4727.6211982.62SU-3207Note:1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 F Refrigerent Type: R-407 C

&9FIT-410.01 R0 D01/06/2010

Type DProject: Bermuda Villas

SN.SPECIFIED CONDITIONSAS PER HEAT LOAD CALCULATIONS REQUIREMENTLocation UNIT TYPET.KWS.KWLPSTMBH (NOM)S.MBHCFMQTYTMBHSMBHDCFMTRVILLA TYPE - C [ 61 VILLAS]1AC-GF-SP-01Split60160618.046.942930.67SU-92AC-GF-FCU-02Ducted2406406129.5927.3912832.47SU-33AC-GF-FCU-03Ducted72019206161.45726815.12SU-76AC-FF-FCU-01Ducted369606130.7529.1114042.56SU-37AC-FF-FCU-02Ducted4211206145.3442.0519743.78SU-58AC-FF-FCU-03Ducted184806116.5115.427301.38SU-1366Note:1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 F Refrigerent Type: R-407 C

&9FIT-410.01 R0 D01/06/2010

Type EProject: Bermuda Villas

SN.SPECIFIED CONDITIONSAS PER HEAT LOAD CALCULATIONS REQUIREMENTLocation UNIT TYPET.KWS.KWLPSTMBH (NOM)S.MBHCFMQTYTMBHSMBHDCFMTRVILLA TYPE - C [ 48 VILLAS]1AC-GF-FCU-01Split1203204810.959.854430.91SU-92AC-GF-FCU-02Ducted42012804858.6653.1724184.89SU-76AC-FF-FCU-01Ducted184804817.616.57861.47SU-17AC-FF-FCU-02Ducted308004822.8117.876301.90SU-28AC-FF-FCU-03Ducted246404824.9622.7710452.08SU-2240Note:1. Selected Capacities are based on the following conditions: Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB Apparatus dew point temperature 55 deg F, Bypass factor 0.1 Ambient Temperature 115 F Refrigerent Type: R-407 C

&9FIT-410.01 R0 D01/06/2010