ct55/ct55-spc falcon integration - rle technologies · falcon product integration guide 10061 rev...
TRANSCRIPT
-
SHEET: 1 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
CT55/CT55-SPC Falcon Integration
1. Set Input Type to an
Analog 4-20 mA Input.
2. For a 0-100 Amp setting, use
a gain of 25 and an offset of
-25.
3. For other settings, use the
integrated gain/offset
calculator.
FMS Configuration
Figure 1.1: FMS Wiring with CT55
Figure 1.2: F-Series Wiring with CT55
1. Set Input Type to an Analog
4-20 mA Input.
2. For a 0-100 Amps setting, use
a gain of 25 and an offset of
25.
3. For other settings, use the
integrated gain/offset
calculator.
F-Series Configuration
Figure 1.3: FMS CT55 Input Configuration Interface
Figure 1.4: F-Series CT55 Input Configuration
Interface
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
+-
+-
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
12 3
12 3
-
SHEET: 2 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
AFS-(WM/DM) Falcon Integration
FMS Configuration
Figure 2.1: FMS Wiring with AFS-xx
1 2 3
SW1
SW2
SW3
F-Series Configuration
1 2 3
Figure 2.2: F-Series Wiring with AFS-xx
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
Figure 2.4: F-Series AFS-xx Input Configuration Interface
Figure 2.3: FMS AFS-xx Input Configuration Interface
23 4
1
23 4
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
1. Set Jumper Switches on AFS-XX to appropriate
settings.
Output Selection SW1: 4-20mA Output
Working Range SW2: 0-2000 Ft/Min Range
0-3000 Ft/Min Range
0-4000 Ft/Min Range
Response Time SW3: Fast
Slow
2. Set FMS Input Channel to an Analog 4-20 mA.
3. For a 0-2000 Ft/Min Range, use a gain of 500 and an
offset of -500.
4. For other settings, use the integrated gain/offset
calculator.
-
SHEET: 3 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
Figure 3.5: F-Series AFS-D Input Configuration
Interface
AFS-D Falcon Integration
Set Input Type to a NC
Digital Contact for each
AFS-D wired into the
Falcon. Assign an on/
off label for each sensor
connected.
FMS Configuration
Figure 3.1: FMS Wiring with AFS-D
Figure 3.2: F-Series Wiring with AFS-D
Set Input Type to a NC
Digital Contact for each
AFS-D wired into the
F3400/1000. Assign your
on/off label for each sensor
connected.
F-Series Configuration
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
Set Input Type to Alarm On
Open for each AFS-D
wired into the F110 and
assign a label.
F110 Configuration
See
Manual
For
Setup
1 2 3 4 5 6 7 8
Sw
itch
Se
nso
r
Po
rts 1
- 8
Figure 3.3: F110 Wiring with AFS-D
Figure 3.6: F110 AFS-D Input Configuration
Interface
Figure 3.4: FMS AFS-D Input Configuration Interface
-
SHEET: 4 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
MD3 Falcon Integration
Figure 4.1: FMS Wiring with MD3
Figure 4.2: F-Series Wiring with MD3
Supplied
12VDC
Wall Adapter
Power Supply
NC Contact
NC Contact
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2
+ - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
Set Input Type to a Digital NC
Input Type for each MD3 wired
into the Falcon.
FMS Configuration
Set Input Type to a Digital NC
Input Type for each MD3
wired into the F3400/1000.
F-Series Configuration
Set Input Type to Alarm on
Open for each MD3 wired into
the F110.
F110 Configuration
Figure 4.6: F110 MD3 Input Configuration Interface
See
Manual
For
Setup
1 2 3 4 5 6 7 8
Sw
itch
Se
nso
r
Po
rts 1
- 8
Supplied
12VDC
Wall Adapter
Power Supply
NC Contact
Figure 4.3: F110 Wiring with MD3
Figure 4.4: FMS MD3 Input Configuration Interface
Figure 4.5: F-Series MD3 Input Configuration Interface
-
SHEET: 5 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
MDS Falcon Integration
Set Input Type to a Digital NC
Input Type for each MDS wired
into the Falcon.
FMS Configuration
Figure 5.1: FMS Wiring with MDS
Figure 5.2: F-Series Wiring with MDS
Set Input Type to a Digital NC
Input Type for each MDS wired
into the F3400/1000.
F-Series Configuration
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
Set Input Type to Alarm on
Open for each MDS wired into
the F110.
F110 Configuration
See
Manual
For
Setup
1 2 3 4 5 6 7 8
Sw
itch
Se
nso
r
Po
rts 1
- 8
Figure 5.3:F110 Wiring with MDS
Figure 5.5: F-Series MDS Input Configuration Interface
Figure 5.6: F110 MDS Input Configuration Interface
Figure: 5.4 Falcon MDS Input Configuration Interface
-
SHEET: 6 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
+-
CO
MNO
+
SMK Falcon Integration
Set Input Type to a
NO Digital Contact for
each SMK wired into
the Falcon.
FMS Configuration
Figure 6.1: FMS Wiring with SMK
Figure 6.2: F-Series Wiring with SMK
Set Input Type to a NO Digital Contact for each SMK wired
into the F3400/1000. Only
channels 5 thru 32 can be used
with the F3400 and Channels 5
thru 8 for the F1000.
F-Series Configuration
External
12 to 24VAC
or VDC
Power Supply
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
+-
CO
MNO
+
Set Input Type to Alarm on
Closed for each SMK wired
into the F110.
F110 Configuration
External
12 to 24VAC
or VDC
Power Supply
+-
CO
MNO
+
See
Manual
For
Setup
1 2 3 4 5 6 7 8
Sw
itch
Se
nso
r
Po
rts 1
- 8
Figure 6.3: F110 Wiring with SMKFigure 6.6:F110 SMK Input Configuration Interface
Figure 6.4: FMS SMK Input Configuration Interface
Figure 6.5: F-Series SMK Input Configuration Interface
-
SHEET: 7 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - C + - + -
HD150 & HD150-2 Falcon Integration
Set Input Type to a
Digital NO Input type for
each HD150/HD150-2
Relay Output wired into
the Falcon.
FMS Configuration
Figure 7.1: FMS Wiring with HD150/HD150-2
Figure 7.2: F-Series Wiring with HD150/HD150-2
Set Input Type to a
Digital NO Input type for
each HD150/HD150-2
Relay Output wired into
the F3400/1000.
F-Series Configuration
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
Power
(White)
Low
(Yellow)
High
(Red)
External
12 to 24VAC or VDC
Power SupplyPower
(White)
Low
(Yellow)
High
(Red)
External
12 to 24VAC or VDC
Power SupplyPower
(White)
Low
(Yellow)
High
(Red)
Figure 7.3: F110 Wiring with HD150/HD150-2
See
Manual
For
Setup
1 2 3 4 5 6 7 8
Sw
itch
Se
nso
r
Po
rts 1
- 8
Set Input Type to Alarm
On Closed for each
HD150/HD150-2 Relay
Output wired into the
F110.
F110 Configuration
Figure 7.6: F110 HD150/150-2 Input Configuration Interface
Figure 7.5: F-Series Hd150/150-2 Input Configuration Interface
Figure 7.4: F-Series HD150/150-2 Input Configuration Interface
-
SHEET: 8 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
KPO Falcon Integration
Enter in Keypad users and corresponding codes in
the Falcon’s Keypad/DTMF Access User
Configuration menu.
FMS Configuration
Figure 8.1: FMS Wiring with KPO
P4 RJ11
TELCO
P5 RJ45
NETWORK
IOIOIP3 RS232
COM2
IOIOIP2 RS232
COM1
SW1+ - GND
RS485 COM1
IOIOICOM1 SELECT
K2 RX RX
485
K1 TX TX 232
RELAY COM1 COM2
48
5 T
ER
MS
EL
M/S
TB5 KEYPAD
TB4
NC NO CRELAY 1
NC NO CRELAY 2
1 2ON
1 2 3
4 5 6
7 8 9
* 0 #
Pin
1
Pin
2
Pin
3
Pin
4
Pin
5
Pin
6
Pin
7
Pin
8
RLE - KPO Keypad
Falcon TB5-1
Falcon TB5-2
Falcon TB5-3
Falcon TB5-4
Falcon TB5-5
Falcon TB5-6
Falcon TB5-7
Keypad Pin 3 - Orange
Keypad Pin 4 - Green
Keypad Pin 5 - Grey
Keypad Pin 1 - Red
Keypad Pin 2 - White
Keypad Pin 8 - Yellow
Keypad Pin 7 - Blue
Keypad Pin 6 - BlackNo Connection
Column 1
Column 2
Column 3
Row 1
Row 2
Row 3
Row 4
Figure 8.2: FMS Keypad Configuration Interface
-
SHEET: 9 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
FMS to T120D Falcon Integration
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
PW
R(4
-20
SE
ND
)
CO
MM
ON
RH
OU
T (
4-2
0 R
TN
)
T O
UT
(4
-20
RT
N)
RT
D/O
VE
RR
IDE
RT
D/O
VE
RR
IDE
SL
IDE
R R
IGH
T
SL
IDE
R W
IPE
R
SL
IDE
R L
EF
T
BACK PIECE CENTER PIECE (WITH CIRCUIT BOARD)
SW1
mAVolts
TEMP 10/5V
TEMP RANGE
50-95/32-122
TEMP F/C
Output Select
Figure 9.2: 50-95F Range Setup Figure 9.3: 32-122F Range Setup
RH 10/5V
1. Set the switch position to mA. Set the temperature range to
50-95 or 32-122. The sensor is shipped from the factory with
the switch in the volts position and the temperature range is
set for 50-95F. The switch position must be set to the mA
position.
2. Wire the sensor to the CH # being used.
4. Verify the "Calc" value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the T120D Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current (+/-
1%).
3. If measured current does not match calculated current then
check wiring and check T120D jumper and switch
settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon Calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
Figure 9.1: FMS Wiring with the T120D
1
3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and offset values. For the 50-95F
range use Gain 11.25, Offset 38.75. For 32-122F range use
Gain 22, Offset 10.
2
33
Example if Room Temp is 70F and your sensor has a range of 50-95
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
Formula for calculating the correct RAW value
44
-
SHEET: 10 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
FMS to TH140/TH140D Falcon Integration
Figure 10.2: Temperature Setup Figure 10.3: Humidity Setup
1. Set the switch position to mA. Set the temperature range to
50-95 or 32-122. The Sensor is shipped from the factory with
the switch in the volts position and the temperature range is
set for 50-95F. The switch position must be set to the mA
position.
2. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the TH140 Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
Example if Room Temp is 70F and your sensor has a range of 50-95
3. If measured current current does not match calculated current
then check wiring and check TH140/TH140D jumper and switch
settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA = Room Humidity
100x 16 + 4
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
PW
R(4
-20
SE
ND
)
CO
MM
ON
RH
OU
T (
4-2
0 R
TN
)
T O
UT
(4
-20
RT
N)
RT
D/O
VE
RR
IDE
RT
D/O
VE
RR
IDE
SL
IDE
R R
IGH
T
SL
IDE
R W
IPE
R
SL
IDE
R L
EF
T
BACK PIECE CENTER PIECE (WITH CIRCUIT BOARD)
SW1
mAVolts
TEMP 10/5V
TEMP RANGE
50-95/32-122
TEMP F/C
Output Select
RH 10/5V
Figure 10.1: FMS Wiring with the TH140/TH140D
1
3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and Offset values. For the 50-95F
range use Gain 11.25, Offset 38.75. For 32-122F range use
Gain 22, Offset 10.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
3 4
5 5
2
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
Formula for calculating the correct RAW value
50 – 95 Degree F Range
-
SHEET: 11 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
F-Series to T120D Falcon Integration
PW
R(4
-20
SE
ND
)
CO
MM
ON
RH
OU
T (
4-2
0 R
TN
)
T O
UT
(4
-20
RT
N)
RT
D/O
VE
RR
IDE
RT
D/O
VE
RR
IDE
SL
IDE
R R
IGH
T
SL
IDE
R W
IPE
R
SL
IDE
R L
EF
T
BACK PIECE CENTER PIECE (WITH CIRCUIT BOARD)
SW1
mAVolts
TEMP 10/5V
TEMP RANGE
50-95/32-122
TEMP F/C
Output Select
Figure 11.2: 50-95F Range Setup Figure 11.3: 32-122F Range Setup
RH 10/5V
1. Set the Switch Position to mA. Set the temperature range to
50-95 or 32-122. The sensor is shipped from the factory with
the switch in the volts position and the temperature range is
set for 50-95F. The switch position must be set to the mA
position.
2. Wire the sensor as shown.
4. Verify the "Calc" value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
5. Calculate the T120D Output current for temperature.
TROUBLESHOOTING
6. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current (+/-
1%)
Example if Room Temp is 70F
mA @ 70F = 11.11mA mA @ 69F = 10.75mA
7. If measured current current does not match calculated current
then check wiring and check T120D jumper and switch
settings.
8. Compare the measured current matches the current reading in
the Falcon.
9. Check the wiring if the Falcon current reading does not match
the measured current reading.
10. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
11. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
12. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
Figure 11.1: F-Series Wiring with T120D
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - C + - + - 3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the 50-95F
range use Gain 11, Offset 39. For 32-122F range use Gain 22,
Offset 10.
3
4
3
4
12
Example if Room Temp is 70F and your sensor has a range of 50-95
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
-
SHEET: 12 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
F-Series to TH140/TH140D Falcon Integration
1. Set the Switch Position to mA. Set the temperature range to 50-95 or 32-
122. The Sensor is shipped from the factory with the switch in the volts
position and the temperature range is set for 50-95F. The switch position
must be set to the mA position.
3. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and
enter the Gain and Offset values. For the 50-95F range use Gain 11,
Offset 39. For 32-122F range use Gain 22, Offset 10.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-20mA" and
enter the Gain of 25 and offset of -25.
2. Wire the sensor as shown.
5. Verify the "Calc" value displays the correct room temperature/humidity.
The temperature/humidity can also be viewed on the Falcon main page.
SETUP
1. Calculate the TH140 Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a current
meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check
wiring and check TH140/TH140D jumper and switch settings.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the
measured current reading.
6. If the Falcon current reading matches the measured current and the
Falcon calculated value does not match the room temperature then the
offset and gain values are wrong. Double check the Gain and Offset
values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or
below the room temperature then adjust the offset by 1 or 2. Do not
adjust the gain. Only tweak the offset once the previous troubleshooting
steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE
Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the following formula to
calculate the humidity mA output.
mA = Room Humidity
100x 16 + 4
PW
R(4
-20
SE
ND
)
CO
MM
ON
RH
OU
T (
4-2
0 R
TN
)
T O
UT
(4
-20
RT
N)
RT
D/O
VE
RR
IDE
RT
D/O
VE
RR
IDE
SL
IDE
R R
IGH
T
SL
IDE
R W
IPE
R
SL
IDE
R L
EF
T
BACK PIECE CENTER PIECE (WITH CIRCUIT BOARD)
SW1
mAVolts
TEMP 10/5V
TEMP RANGE
50-95/32-122
TEMP F/C
Output Select
Figure 12.2: Temperature Setup Figure 12.3: Humidity Setup
RH 10/5V
Figure 12.1: F-Series Wiring with TH140/
TH140D
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - + -
3
5
4
5
12
Example if Room Temp is 70F and your sensor has a range of 50-95
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
50 – 95 Degree F Range
-
SHEET: 13 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
FMS BAPI Temperature/Humidity Falcon Integration
Figure 13.2: Temperature Setup Figure 13.3: Humidity Setup
1. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the BAPI Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
3. If measured current current does not match calculated current
then check wiring and check the BAPI switch settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA = Room Humidity
100x 16 + 4
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
Figure 13.1: Falcon Wiring with the BAPI
Temperature/Humidity sensor
2. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the 32-
120F range use Gain 22, Offset -10.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
4
5
V3
.1 C
op
yrig
ht 2
00
7
BA
PI
GN
D
V+
CH
1
CH
2
3. For other temperature ranges, use the Calculator function on
the webpage Te
mp
era
ture
Hu
mid
ity
3
5
1
2
Example if Room Temp is 70F and your sensor has a range of 32-120
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 32) / (120 - 32)) x 16 + 4 = 10.90
32 - 120 Degree F Range
-
SHEET: 14 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - + -
F-Series BAPI Temperature/Humidity Falcon Integration
Figure 14.2: Temperature Setup Figure 14.3: Humidity Setup
1. Wire the sensor as shown.
5. Verify the "Calc" value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the BAPI Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
3. If measured current current does not match calculated current
then check wiring and check the BAPI switch settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon Calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA
=
Room Humidity
100x 16 + 4
Figure 14.1: Falcon Wiring with the F-Series_BAPI
Temperature/Humidity sensor
2. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the 32-
120F range use Gain 22, Offset 10.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
4
5
V3.1
Co
pyrig
ht
20
07
BA
PI
GN
D
V+
CH
1
CH
2
3. For other temperature ranges, use the Calculator function on
the webpage. Te
mp
era
ture
Hu
mid
ity
3
5
1
2
Example if Room Temp is 70F and your sensor has a range of 32-110
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 32) / (120 - 32)) x 16 + 4 = 10.90
32 - 120 Degree F Range
-
SHEET: 15 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
FMS Dwyer Temperature/Humidity Falcon Integration
Figure 14.2: Temperature Setup Figure 14.3: Humidity Setup
1. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the Dwyer Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
3. If measured current current does not match calculated current
then check wiring.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA = Room Humidity
100x 16 + 4
2. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the -40 -
140F range use Gain 45, Offset -85.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
4
5
3. For other temperature ranges, use the Calculator function on
the webpage
3
5
2
Example if Room Temp is 70F and your sensor has a range of -40 - 140
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - -40) / (140 - -40)) x 16 + 4 = 13.77
-40 - 140 Degree F Range
TE
MP
RE
CE
IVE
R
RH
RE
CE
IVE
RP
WR
+
P1
VDCTB1
VDC
+ -
EXTERNAL
24VDC
+ +Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
Figure 14.1: Falcon Wiring with the Dwyer
Temperature/Humidity sensor
1
-
SHEET: 16 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
Falcon Product Integration Guide
10061 Rev 1.1a (7/2013)
F-Series Dwyer Temperature/Humidity Falcon Integration
Figure 15.2: Temperature Setup Figure 15.3: Humidity Setup
1. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the Dwyer Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
3. If measured current current does not match calculated current
then check wiring.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA = Room Humidity
100x 16 + 4
2. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the -40 -
140F range use Gain 45, Offset -85.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
4
5
3. For other temperature ranges, use the Calculator function on
the webpage
3
52
Example if Room Temp is 70F and your sensor has a range of -40 - 140
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - -40) / (140 - -40)) x 16 + 4 = 13.77
-40 - 140 Degree F Range
P5 RJ11
TELCO
P4 RJ45
NETWORK
IOIOIP2 RS232
COM1
RS485 COM1
TX (4 Wire)
+ - GND
R
X
T
X
48
5 T
ER
M
2 W
IRE
TB2 + - C
ON
4 W
IRE+ - GND
RX (4 Wire)
TB3 TB4Ch1 Ch2
+ -
Ch5 Ch6
Ch3 Ch4 Ch7 Ch8
Relay
NC NO C
NC NO C
Relay
1 2
+ - + - C
+ - + -
TE
MP
RE
CE
IVE
R
RH
RE
CE
IVE
RP
WR
+
Figure 15.1: F-Series Wiring with the Dwyer
Temperature/Humidity sensor
1
Falcon Integration Guidev1.1a.vsdCT55AFS(WM/DM)AFS-DMD3MDSSMKHD150/HD150-2KPOFMS_T120DFMS_TH140/TH140DF-Series to T120DF-Series to TH140/TH140DFMS to BAPIF-Series to BAPIFMS to DwyerF-Series to Dwyer