FONT Meeting 2 nd August 2013. CTF3 May 2013 Data Analysis. Phase Profile Plots and ADC Droop Correction with IIR Filter. Overview. Phase profile with unfiltered Mixer/Diode. Calibration with IIR filter, Mixer/ sqrt (Diode). Phase profile with filtered, Mixer/ sqrt (Diode). - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: CTF3 May 2013 Data Analysis

Jack Roberts 1

CTF3 May 2013 Data Analysis

Phase Profile Plots and ADC Droop Correction with IIR Filter

02/08/2013

FONT Meeting 2nd August 2013

Page 2: CTF3 May 2013 Data Analysis

Jack Roberts 2

Overview

• Phase profile with unfiltered Mixer/Diode.• Calibration with IIR filter, Mixer/sqrt(Diode).• Phase profile with filtered, Mixer/sqrt(Diode).• Unfiltered vs. Filtered phase reconstruction.• Mean pulse to pulse phase stability.

02/08/2013

Page 3: CTF3 May 2013 Data Analysis

Jack Roberts 3

Recap: Unfiltered Mixer/Diode Calibration

• Cancel ADC droop by using Mixer/Diode instead of Mixer/sqrt(Diode).

• Absorb beam current A in to calibration constant a.

• Fitted values for a:– M1: 1.67– M2: 3.11– M3: 1.92

02/08/2013

3 4 8 9Mixer∝ 𝐴sin (𝜙 ) exp (− 𝑡 /𝜏 )

Diode∝ 𝐴2 exp (−𝑡 /𝜏 )

sin (𝜙 )= 1𝑐𝐴MixerDiode

=1𝑎MixerDiode

• Best resolution near zero crossings of LO scan.

• Plots for the points circled here are outlined in red.

• All the plots are mean subtracted.

CALIBRATION LO SCAN

Page 4: CTF3 May 2013 Data Analysis

Jack Roberts 4

Phase Profile – No filtering, Mixer/Diode Calibration.

02/08/2013

Page 5: CTF3 May 2013 Data Analysis

Jack Roberts 5

Phase Profile – No filtering, Mixer/Diode Calibration

02/08/2013

Page 6: CTF3 May 2013 Data Analysis

Jack Roberts 6

Phase Profile – No filtering, Mixer/Diode Calibration

02/08/2013

• Good agreement between M1 and M3 near zero crossings of ADC output in LO scan.

• Saturation effects near min/max of ADC output in LO scan due to sin(phi)>1 values.

Page 7: CTF3 May 2013 Data Analysis

Jack Roberts 7

ADC Droop Exponential Fit

02/08/2013

• Fit an exponential to the diode data then use the fitted decay constants in an IIR filter:

• Fitted values for τ (in 357 MHz samples), Diode ADCs:- M1: 518 ± 1- M2: 440 ± 1- M3: 457 ± 2

• Also have droop in mixer channel but can’t fit exponential to it.- Use the mean of the diode ADCs: τ = 472. - Can get these values from lab tests (on going).

• Fitted values for τ can vary up to ~20% dependent on sampling window used, LO phase etc.

• Resolution seems fairly insensitive to τ.

Diode=𝐴2 exp (− 𝑡 /𝜏 )

Page 8: CTF3 May 2013 Data Analysis

Jack Roberts 8

ADC Droop Exponential Fit

02/08/2013

• Left: Points are mean diode channel data for each LO phase setting. Black lines are the exponential fit using the fitted decay constants.

• Seeing cross-talk from Mixer?

Page 9: CTF3 May 2013 Data Analysis

Jack Roberts 9

• Implement an IIR filter to remove the exponential droop using the fitted decay constants:

• Can now perform a calibration using Mixer/sqrt(Diode) as planned:

• Fitted values for a:• M1: 52.5• M2: 84.1• M3: 56.9

IIR Filter

02/08/2013

1

)()(k

xkxky

Mixer∝ 𝐴sin (𝜙 ) Diode∝ 𝐴2 sin (𝜙 )=1𝑎Mixer

√Diode

Page 10: CTF3 May 2013 Data Analysis

Jack Roberts 10

Phase Profile – Filtered, Mixer/sqrt(Diode) Calibration

02/08/2013

Page 11: CTF3 May 2013 Data Analysis

Jack Roberts 1102/08/2013

Phase Profile – Filtered, Mixer/sqrt(Diode) Calibration

Page 12: CTF3 May 2013 Data Analysis

Jack Roberts 1202/08/2013

Phase Profile – Filtered, Mixer/sqrt(Diode) Calibration

• At a first glance, very similar to the unfiltered calibration plots.

Page 13: CTF3 May 2013 Data Analysis

Jack Roberts 13

Resolution Comparison – Filtered vs. Unfiltered

02/08/2013

• Resolution appears to be a bit better for the filtered calibration.

Page 14: CTF3 May 2013 Data Analysis

Jack Roberts 14

Comparison – Unfiltered vs. Filtered

02/08/2013

M1

Page 15: CTF3 May 2013 Data Analysis

Jack Roberts 1502/08/2013

M1Comparison – Unfiltered vs. Filtered

Page 16: CTF3 May 2013 Data Analysis

Jack Roberts 1602/08/2013

M1Comparison – Unfiltered vs. Filtered

Page 17: CTF3 May 2013 Data Analysis

Jack Roberts 1702/08/2013

M2Comparison – Unfiltered vs. Filtered

Page 18: CTF3 May 2013 Data Analysis

Jack Roberts 1802/08/2013

M2Comparison – Unfiltered vs. Filtered

Page 19: CTF3 May 2013 Data Analysis

Jack Roberts 1902/08/2013

M2Comparison – Unfiltered vs. Filtered

Page 20: CTF3 May 2013 Data Analysis

Jack Roberts 2002/08/2013

M3Comparison – Unfiltered vs. Filtered

Page 21: CTF3 May 2013 Data Analysis

Jack Roberts 2102/08/2013

M3Comparison – Unfiltered vs. Filtered

Page 22: CTF3 May 2013 Data Analysis

Jack Roberts 22

M3

02/08/2013

Comparison – Unfiltered vs. Filtered

• There are differences in the relative scale of the reconstructed phase from the two calibrations.

Page 23: CTF3 May 2013 Data Analysis

Jack Roberts 23

Filtered vs. Unfiltered Calibration Constant

02/08/2013

• Filtered/unfiltered calibration constants divided by mean to make them comparable.

• Only mean value used in phase reconstruction.

• Differences vs. sample no. will cause phase shifts.

Mean

Mean

Mean

Page 24: CTF3 May 2013 Data Analysis

Jack Roberts 24

Mean Pulse Phase Stability

02/08/2013

Page 25: CTF3 May 2013 Data Analysis

Jack Roberts 2502/08/2013

Mean Pulse Phase Stability

Page 26: CTF3 May 2013 Data Analysis

Jack Roberts 2602/08/2013

Mean Pulse Phase Stability

• Only short runs, but around 0.5o – 1.0o of jitter in the mean pulse phase.

Page 27: CTF3 May 2013 Data Analysis

Jack Roberts 27

Summary• The IIR filter appears to do a good job but lab tests needed to

accurately determine decay constants.• Difference in relative scale of reconstructed phase for unfiltered

Mixer/Diode and filtered Mixer/sqrt(Diode) calibrations.• Can look in to cross-talk between the mixer and diode.

• Side notes:– Installation of kickers, rearrangement of magnets etc. in TL2 for

the feedforward system in progress.– M2 can’t be repaired due to radiation. Planned to test using

horizontal pickups instead of vertical. 4th monitor will be built.– May be delays in installing M3 in its final location.– Thinking about how to integrate FONT DAQ with CTF3 data.

02/08/2013