ctk co., ltd. - napad.pl€¦ · ctk co., ltd. this document may be altered or revised by ctk co.,...

56

Upload: others

Post on 16-Apr-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document
Page 2: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 1 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

EMC TEST REPORT For CE Test Report No. : 2010020060 Date of Issue : February 9, 2010 Model/Type No. : SDC-435P and SCB-2000P Kind of Product : CCD CAMERA Applicant : SAMSUNG TECHWIN CO., LTD. Applicant Address : #145-3, Sangdaewon 1-Dong, Sungnam-Shi, Kyonggi-Do, Korea Manufacturer : 1. SAMSUNG TECHWIN CO., LTD. 2. TIANJIN SAMSUNG TECHWIN OPTO-ELECTRONICS CO., LTD. Manufacturer Address : 1. #42 Seongju-Dong, Changwon-Shi, Kyungsangnam-Do, Korea 2. #No. 11 Wei Liu road Micro-electronic industrial park Teda Tianjin China Contact Person : Mr. Young-Soon, Choi (Manager) Telephone : +82-31-740-8731 Received Date : May 25, 2009 Test period : Start : May 26, 2009 End : June 15, 2009 Test Results : In Compliance Not in Compliance The test results presented in this report relate only to the object tested. Tested by Reviewed by

Young-Kug, Song EMC Test Engineer

James Hong EMC Technical Manager

Date: February 9, 2010 Date: February 9, 2010

Page 3: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 2 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

REPORT REVISION HISTORY

Date Revision Page No June 18, 2009 Issued (2009060035) All

Issued (2010020060) February 9, 2010

Addition of Model Name : SCB-2000P All

This report shall not be reproduced except in full, without the written approval of CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document. Any alteration of this document not carried out by CTK Co., Ltd. will constitute fraud and shall nullify the document.

Page 4: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 3 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

TABLE OF CONTENTS REPORT REVISION HISTORY..........................................................................................2 1.0 General Product Description ...............................................................................4 1.1 Model Differences .............................................................................................4 1.2 Device Modifications .........................................................................................4 1.3 EUT Configuration(s).........................................................................................5 1.4 Test Software...................................................................................................6 1.5 EUT Operating Mode(s) .....................................................................................6 1.6 Configuration ...................................................................................................7 1.7 Calibration Details of Equipment Used for Measurement .........................................8 1.8 Test Facility......................................................................................................8 1.9 Laboratory Accreditations and Listings .................................................................8 2.0 Emissions Test Regulations.................................................................................9 2.1 Conducted Voltage Emissions ........................................................................... 10 2.2 Radiated Electric Field Emissions....................................................................... 11 2.3 Harmonic Current Emissions and Voltage Fluctuations and Flicker .......................... 12 3.0 Immunity Test Regulations............................................................................... 13 3.1 Criteria for compliance .................................................................................... 14 3.2 Electrostatic Discharge .................................................................................... 16 3.3 Radiated Electromagnetic Fields........................................................................ 18 3.4 Fast Transients Bursts ..................................................................................... 21 3.5 Slow High Energy Voltage Surge ....................................................................... 23 3.6 Conducted Disturbance.................................................................................... 26 3.7 Mains Supply Voltage Variations........................................................................ 29 3.8 Mains Supply Voltage Dips and Short Interruptions.............................................. 30 APPENDIX A - Test Setup Photos and Configuration ......................................................... 32

Conducted Voltage Emissions ................................................................................. 32 Radiated Electric Field Emissions............................................................................. 33 Harmonic Current Emissions and Voltage Fluctuations and Flicker ................................ 34 Electrostatic Discharge .......................................................................................... 35 Radiated Electromagnetic Fields.............................................................................. 36 Fast Transients Bursts ........................................................................................... 37 Slow High Energy Voltage Surge ............................................................................. 38 Conducted Disturbance.......................................................................................... 39 Mains Supply Voltage Dips and Short Interruptions.................................................... 40

APPENDIX B – TEST DATA ........................................................................................... 41 Conducted Voltage Emissions (for EUT Input Power : 12 Vdc)...................................... 41 Conducted Voltage Emissions (for EUT Input Power : 24 Vac)...................................... 43 Radiated Electric Field Emissions (for EUT Input Power : 12 Vdc) ................................. 45 Radiated Electric Field Emissions (for EUT Input Power : 24 Vac) ................................. 46 Harmonic Current Emissions and Voltage Fluctuations and Flicker ................................ 47

APPENDIX C – EUT Photographs ................................................................................... 49 EUT External Photographs...................................................................................... 50 EUT Internal Photographs ...................................................................................... 51 PCB .................................................................................................................... 52

Page 5: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 4 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

1.0 General Product Description 1.0.1 Tested Equipment

Unless otherwise indicated, all tests were conducted on Model SDC-435P.

Tests performed on Model SDC-435P were considered to be representative of Model SCB-2000P.

1.0.2 Equipment Size, Mobility and Identification

Dimensions: Approx. 58(W) by 52(H) by 121(D) mm inch Mobility: Hand-held Table-top Built-in Traveling Stationary Serial No.: Prototype

1.0.3 Electrical Ratings

EUT Input: 12 Vdc, 24 Vac

Output: -

1.0.4 Test Voltage & Frequency

Unless indicated otherwise on the individual data sheet or test results, the test voltage and frequency was as indicated below.

Voltage: 230 Vac Frequency: 50 Hz

1.0.5 Clock & Other Frequencies Utilized 28.6364 MHz

1.1 Model Differences

SDC-435P and SCB-2000P are no technical difference from each model except for Model Name because of marketing purposes.

1.2 Device Modifications The following modifications were necessary for compliance:

Not applicable

Page 6: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 5 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

1.3 EUT Configuration(s) See Appendix A for individual test set-up configuration(s). The following peripheral devices and/or interface cables were connected during the measurement: [EUT Input Power : 12 Vdc]

Peripheral Devices

Device Manufacturer Model No. Serial No. CCTV MONITOR HITRON SYSTEMS INC. CVM1574FNKR CM7110021 SWITCHING ADAPTER Dee Van Electronics(ShenZhen)Co., Ltd. DSA-60W-12 1 12048 3707

Cable Description

# Description Ferrite Core

Length (m) Other Details

1 SWITCHING ADAPTER power cable, Unshielded

No 1.8 Connect to AC power

2 EUT DC Input cable, Unshielded Yes 1.8 Between SWITCHING ADAPTER and EUT 3 CCTV MONITOR power cable, Unshielded No 1.8 Connect to AC power 4 BNC cable, Shielded No 3.0 Between CCTV MONITOR and EUT 5 CCTV LENS cable, Unshielded No 0.1 Between the EUT and CCTV LENS

[EUT Input Power : 24 Vac]

Peripheral Devices

Device Manufacturer Model No. Serial No. CCTV MONITOR HITRON SYSTEMS INC. CVM1574FNKR CM7110021 AC/AC Adaptor Dream Electronic Co., Ltd. STA-230 -

Cable Description

# Description Ferrite Core

Length (m) Other Details

1 AC/AC Adaptor power cable, Unshielded

No 1.8 Connect to AC power

2 EUT AC Input cable, Unshielded No 1.8 Between AC/AC Adaptor and EUT 3 CCTV MONITOR power cable, Unshielded No 1.8 Connect to AC power 4 BNC cable, Shielded No 3.0 Between CCTV MONITOR and EUT 5 CCTV LENS cable, Unshielded No 0.1 Between the EUT and CCTV LENS

Page 7: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 6 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

1.4 Test Software EMC Test V 1.0 Display Test Patterns – V1.5

Ping.exe Not applicable

1.5 EUT Operating Mode(s) Equipment under test was operated during the measurement under the following conditions:

Standby Scrolling ‘H’ Display circles pattern Read / Write Practice operation – Monitoring the EUT’s video signal.

Page 8: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 7 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

1.6 Configuration [EUT Input Power : 12 Vdc]

[EUT Input Power : 24 Vac]

AC Power

SWITCHING ADAPTER

EUT (SDC-435P)

CCTV MONITOR

AC Power

AC/AC Adaptor

EUT (SDC-435P)

CCTV MONITOR

3

1

4 2

1

2

3

4

CCTV LENS

CCTV LENS

5

5

Page 9: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 8 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

1.7 Calibration Details of Equipment Used for Measurement Test equipment and test accessories are calibrated on regular basis. The maximum time between calibrations is one year or what is recommended by the manufacturer, whichever is less. All test equipment calibrations are traceable to the Korea Research Institute of Standards and Science (KRISS), therefore, all test data recorded in this report is traceable to KRISS.

1.8 Test Facility The measurement facility is located at 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea. The sites are constructed in conformance with the requirements of ANSI C63.7, ANSI C63.4 and CISPR Publication 22.

1.9 Laboratory Accreditations and Listings

Country Agency Scope of Accreditation Logo USA FCC 3 & 10 meter Open Area Test Sites and one

conducted site to perform FCC Part 15/18 measurements.

93250

JAPAN VCCI 10 meter Open Area Test Site and one conducted site.

R-948, C-986

KOREA KCC EMI (10 meter Open Area Test Site and two conducted sites) EMS (ESD, RS, EFT/Burst, Surge, CS, Magnetic, Dips and interruptions)

No. 51, KR0025

Page 10: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 9 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

2.0 Emissions Test Regulations The emissions tests were performed according to following regulations:

EMC – Directive 2004/108/EC

EN 61000-6-3:2007

EN 61000-6-4:2007

EN 55011:2007 +A2:2007 Group 1 Group 2 Class A Class B

EN 55013:2001 +A1:2003 +A2:2006

EN 55014-1:2006

EN 55015:2006

EN 61204-3:2000 Class A Class B

EN 61131-2:2003

EN 61326-1:2006 Class A Class B

EN 55022:2006 Class A Class B

EN 61000-3-2:2006

EN 61000-3-3:1995 +A1:2001 +A2:2005

VCCI V-3/2008.04 Class A Class B

AS/NZS CISPR22:2006 Class A Class B

FCC Part 15 Subpart B Class A Class B

CISPR 22:2006 Class A Class B

Page 11: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 10 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

2.1 Conducted Voltage Emissions Test Date June 5, 2009 Test Location Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Field Strength Meter Rohde & Schwarz ESHS30 828144/002 2010-02-27 LISN EMCO 3825/2 9607-2575 2009-08-19 LISN EMCO 3825/2 9409-2246 2009-08-19 Field Strength Meter Rohde & Schwarz ESHS30 862024/001 2010-03-04 LISN Rohde & Schwarz ESH3-Z5 100207 2009-12-12 LISN EMCO 3825/2 9206-1971 2009-12-12

Frequency Range of Measurement

150 kHz to 30 MHz Instrument Settings IF Band Width: 9 kHz Test Results The requirements are:

MET (for EUT Input Power: 12 Vdc) Frequency

(MHz) Measured Data

(dBuV) Margin (dB)

Remark

16.38 45.3 27.7 Quasi-peak

MET (for EUT Input Power: 24 Vac) Frequency

(MHz) Measured Data

(dBuV) Margin (dB)

Remark

0.16 56.1 9.9 Average

NOT MET Frequency

(MHz) Measured Data

(dBuV) Margin (dB)

Remark

NOT APPLICABLE Remarks

See Appendix B for test data.

Page 12: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 11 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

2.2 Radiated Electric Field Emissions Test Date May 26, 2009 Test Location Testing was performed at a test distance of 10 meter Open Area Test Site Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Field Strength Meter Rohde & Schwarz ESVS30 829673/015 2010-02-03 ULTRA Broadband Antenna Rohde & Schwarz HL562 361324/014 2010-06-20 Biconical Antenna EMCO 3110 9202-1510 2010-05-07 Log-periodic Antenna EMCO 3146 9607-4567 2010-05-07

Frequency Range of Measurement 30 MHz to 1 GHz Instrument Settings IF Band Width: 120 kHz Test Results The requirements are: MET (for EUT Input Power: 12 Vdc)

Frequency (MHz)

Measured Data (dBuV)

Margin (dB)

Remark

51.73 28.8 11.2 Quasi-peak

MET (for EUT Input Power: 24 Vac) Frequency

(MHz) Measured Data

(dBuV) Margin (dB)

Remark

199.74 27.5 12.5 Quasi-peak

NOT MET Frequency

(MHz) Measured Data

(dBuV/m) Margin (dB)

Remark

NOT APPLICABLE Remarks See Appendix B for test data.

Page 13: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 12 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

2.3 Harmonic Current Emissions and Voltage Fluctuations and Flicker

Test Date June 5, 2009

Test Location Shielded Room

Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date

Power Quality Test System SCHAFFNER ProfLine 2103 54350, 200048-202EK

2010-03-31

Classification Of Equipment for Harmonic Current Emissions Class A Class B Class C Class D Test Results Harmonic requirements are:

[For EUT Input Power: 12 Vdc] MET NOT MET NOT APPLICABLE

[For EUT Input Power: 24 Vac] MET NOT MET NOT APPLICABLE Flicker requirements are:

[For EUT Input Power: 12 Vdc] MET NOT MET NOT APPLICABLE

[For EUT Input Power: 24 Vac] MET NOT MET NOT APPLICABLE Remarks

See Appendix B for test data.

Page 14: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 13 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.0 Immunity Test Regulations

The immunity tests were performed according to following regulations:

EMC – Directive 2004/108/EC

EN 61000-6-1:2007

EN 61000-6-2:2005

EN 50130-4:1995 +A1:1998 +A2:2003

EN 61204-3:2000 Low severity level – residencial, commecial or light-industrial environments High severity level – industrial environment

EN 55014-2:1997 +A1:2001

EN 55024:1998 +A1:2001 +A2:2003

EN 60601-1-2:2007

EN 61326-1:2006

EN 61000-4-2:1995 +A1:1998 +A2:2001 EN 61000-4-3:2006 EN 61000-4-4:2004 EN 61000-4-5:2006 EN 61000-4-6:2007 EN 61000-4-8:1993 +A1:2001 EN 61000-4-11:2004

Page 15: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 14 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.1 Criteria for compliance Criteria for compliance was based on the following guidelines:

Test Item Criteria for compliance Electrostatic Discharge There shall be no damage, malfunction or change of status due to the

conditioning. Flickering of an indicator during the application of the discharges is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change. The EUT shall meet the acceptance criteria for the functional test, after the conditioning.

Radiated Electromagnetic Fields

There shall be no damage, malfunction or change of status due to the conditioning. Flickering of an indicator during the conditioning is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change, and no such flickering of indicators occurs at a field strength of 3 V/m. For components of CCTV systems, where the status is monitored by observing the TV picture, then deterioration of the picture is allowed at 10 V/m, providing. a) there is no permanent damage or change to the EUT (e.g. no corruption of

memory or changes to programmable settings etc.); b) at 3 V/m, any deterioration of the picture is so minor that the system

could still be used; and c) there is no observable deterioration of the picture at 1 V/m.

For components with radio links, it is accepted that communications via the radio link may not be possible during the conditioning within the transmitter and receiver exclusion bands defined in the relevant part of ETSI EN 301 489 for that type of radio link equipment. If the EUT is designed to detect and indicate this loss of communication, then this indication is permitted, providing it is in accordance with the manufacturer’s specification. It may be necessary to use appropriate filters to ensure that failures out of the exclusion bands are not due to harmonics generated by the test system. The EUT shall meet the acceptance criteria for the functional test, after the conditioning.

Fast Transients Bursts There shall be no damage, malfunction or change of status due to the conditioning. Flickering of an indicator during the application of the bursts is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change. The EUT shall meet the acceptance criteria for the functional test, after the conditioning.

Slow High Energy Voltage Surge

There shall be no damage, malfunction or change of status due to the conditioning. Flickering of an indicator during the application of the surges is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change. The EUT shall meet the acceptance criteria for the functional test, after the conditioning.

Page 16: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 15 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Conducted Disturbance

There shall be no damage, malfunction or change of status due to the conditioning. Flickering of an indicator during the conditioning is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change, and no such flickering of indicators occurs at Uo = 130 dBuV. For components of CCTV systems, where the status is monitored by observing the TV picture, then deterioration of the picture is allowed at Uo = 140 dBuV, providing: a) there is no permanent damage or change to the EUT (e.g. no corruption of

memory or changes to programmable settings etc.); b) at Uo = 130 dBuV, any deterioration of the picture is so minor that the

system could still be used, and; c) there is no observable deterioration of the picture at Uo = 120 dBuV.

The EUT shall meet the acceptance criteria for the functional test, after the

conditioning.

Mains Supply Voltage Variations

There shall be no damage, malfunction or change of status due to the different supply voltage conditions. The EUT shall meet the acceptance criteria for the functional test, during the conditioning.

Mains Supply Voltage Dips and Short Interruptions

There shall be no damage, malfunction or change of status due to the conditioning. Flickering of an indicator during the conditioning is permissible, providing that there is no residual change in the EUT or any change in outputs, which could be interpreted by associated equipment as a change. The EUT shall meet the acceptance criteria for the functional test, after the conditioning.

Page 17: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 16 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.2 Electrostatic Discharge

Reference Standard EN 61000-4-2:1995 +A1:1998 +A2:2001

Test Date June 9, 2009 Test Location EMS-ESD: Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date ESD Simulator Noiseken ESS-2000 0199C02387 2010-04-16 ESD Gun Noiseken TC-815R ESS0898829 2010-04-16

Test Specifications Discharge Factor: ≥ 1 s Discharge Impedance: 330 ohm / 150 pF Kind of Discharge: Air, Contact (direct and indirect) Polarity: Positive and Negative

Number of Discharge: ≥ 10 at all locations Discharge Voltage: Contact Air HCP VCP 2 kV 2 kV 2 kV 2 kV 4 kV 4 kV 4 kV 4 kV 6 kV 6 kV 6 kV 6 kV 8 kV 8 kV 8 kV 8 kV 15 kV 15 kV 15 kV 15 kV Notes: HCP: Horizontal coupling plane VCP: Vertical coupling plane Test Data

Test Conditions: Temperature: 24 °C Relative Humidity: 42 % Atmospheric Pressure: 996 mbar

Page 18: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 17 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Location of Discharge:

Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks

During the contact ± 6 kV test on the BNC port, white dots appeared.

Air

Contact

Page 19: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 18 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.3 Radiated Electromagnetic Fields

Reference Standard EN 61000-4-3:2006

Test Date June 9, 2009 Test Location EMS-RS: Fully anechoic chamber Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Power Meter Agilent E4418B MY45104818 2010-03-31 Control Unit System Controller Noiseken NA25MF1G2010 A00148 N/A Power Sensor HP 8482A US37293310 2009-08-19 BAND 1 Power Amplifier Noiseken NA25MF1G2010 A00148 2010-05-13 BAND 2 Power Amplifier Noiseken NA25MF1G2010 A00148 2010-05-13 P.S. UNIT Power Supply Noiseken NA25MF1G2010 A00148 N/A RF AMPLIFIER Noiseken NA1GF3G50 A70540 2010-05-13 Signal Generator R&S SML03 103171 2010-02-25 Bilog Antenna Schaffner-Chase CBL6111C 2551 N/A Double Ridged Broadband Horn Antenna SCHWARZBECK MESS BBHA 9120 E BBHA 9120 E 337 N/A

Test Specifications Antenna Polarization: Horizontal & vertical unless indicated otherwise Antenna Distance: 3 m Field Strength: 1 V/m 3 V/m 10 V/m Frequency Range: 27 MHz to 500 MHz 80 MHz to 2 GHz 26 MHz to 1 GHz Modulation: AM, 80 %, 1 kHz sine wave

PM, 1 Hz (0.5 s ON : 0.5 s OFF) Frequency step: 1 % step # of Sides Radiated: 4 6

Page 20: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 19 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Test Data

AM, 80 %, 1 kHz sine wave

Dwell Time: 3 s at 1 V/m

Observation Side Exposed Horizontal Vertical

Front No any function degraded No any function degraded Right No any function degraded No any function degraded Back No any function degraded No any function degraded Left No any function degraded No any function degraded Top No any function degraded No any function degraded

Bottom No any function degraded No any function degraded

Dwell Time: 3 s at 3 V/m Observation

Side Exposed Horizontal Vertical Front The horizontal line noise appeared The horizontal line noise appeared Right The horizontal line noise appeared The horizontal line noise appeared Back The horizontal line noise appeared The horizontal line noise appeared Left The horizontal line noise appeared The horizontal line noise appeared Top The horizontal line noise appeared The horizontal line noise appeared

Bottom The horizontal line noise appeared The horizontal line noise appeared

Dwell Time: 3 s at 10 V/m Observation

Side Exposed Horizontal Vertical Front The horizontal line noise appeared The horizontal line noise appeared Right The horizontal line noise appeared The horizontal line noise appeared Back The horizontal line noise appeared The horizontal line noise appeared Left The horizontal line noise appeared The horizontal line noise appeared Top The horizontal line noise appeared The horizontal line noise appeared

Bottom The horizontal line noise appeared The horizontal line noise appeared

Page 21: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 20 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

PM, 1 Hz (0.5 s ON : 0.5 s OFF)

Dwell Time: 3 s at 1 V/m

Observation Side Exposed Horizontal Vertical

Front No any function degraded No any function degraded Right No any function degraded No any function degraded Back No any function degraded No any function degraded Left No any function degraded No any function degraded Top No any function degraded No any function degraded

Bottom No any function degraded No any function degraded Dwell Time: 3 s at 3 V/m

Observation Side Exposed Horizontal Vertical

Front The horizontal line noise appeared The horizontal line noise appeared Right The horizontal line noise appeared The horizontal line noise appeared Back The horizontal line noise appeared The horizontal line noise appeared Left The horizontal line noise appeared The horizontal line noise appeared Top The horizontal line noise appeared The horizontal line noise appeared

Bottom The horizontal line noise appeared The horizontal line noise appeared

Dwell Time: 3 s at 10 V/m Observation

Side Exposed Horizontal Vertical Front The horizontal line noise appeared The horizontal line noise appeared Right The horizontal line noise appeared The horizontal line noise appeared Back The horizontal line noise appeared The horizontal line noise appeared Left The horizontal line noise appeared The horizontal line noise appeared Top The horizontal line noise appeared The horizontal line noise appeared

Bottom The horizontal line noise appeared The horizontal line noise appeared Note: “Blank” = Not performed Test Conditions: Temperature: 24 °C Relative Humidity: 54 % Atmospheric Pressure: 996 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks See above observations in tables.

Page 22: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 21 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.4 Fast Transients Bursts

Reference Standard EN 61000-4-4:2004

Test Date June 5, 2009 Test Location EMS-EFT: Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Fast Transient Noise Simulator Noiseken FNS-AX II 7079B00212 2009-07-07 Capacitive Coupling Clamp Noiseken 15-00001A - N/A

Test Specifications Pulse Amplitude & Polarity: ± 0.5 kV ± 1.0 kV

(Power Lines) ± 2.0 kV Pulse Amplitude & Polarity: ± 0.25 kV ± 0.5 kV (Signal Lines) ± 1.0 kV

Burst Period: 300 ms 2 s Repetition Rate: 5 kHz Duration of Test Voltage: ≥ 1 min

Page 23: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 22 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Test Data Input a.c. power ports – Coupling/Decoupling Network used

OBSERVATIONS (±) Burst (kV) Mode of Application

0.5 L1 & L2 & PE No any function degraded

OBSERVATIONS (±) Burst (kV) Mode of Application

1.0 L1 & L2 & PE The white dots appeared

OBSERVATIONS (±) Burst (kV) Mode of Application

2.0 L1 & L2 & PE The white dots appeared

Signal ports and telecommunication ports – Coupling Clamp used

OBSERVATIONS (±) Burst (kV) Mode of Application

0.25 BNC cable No any function degraded

OBSERVATIONS (±) Burst (kV) Mode of Application

0.5 1.0 BNC cable The white dots appeared

Note: “Blank” = Not performed Test Conditions: Temperature: 23 °C Relative Humidity: 50 % Atmospheric Pressure: 987 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks See above observations in tables.

Page 24: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 23 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.5 Slow High Energy Voltage Surge

Reference Standard EN 61000-4-5:2006

Test Date June 8, 2009 Test Location EMS-Surge: Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Lightning Surge Simulator Noiseken LSS-6030 0189E00251 2009-08-18 Surge Generator EM Test AG TSS 500 1100-05 2010-01-13 Coupling Network EM Test AG CNV 508 S1 0601-06 N/A Coupling Network EM Test AG CNV 508 S2 0601-07 N/A

Test Specifications Power Lines

Source Impedance: 12 Ω for common mode and 2 Ω for differential mode

Surge Amplitude: Common Mode 0.5, 1.0 & 2.0 kV

Differential Mode 0.5 & 1.0 kV Number of Surges: 5 surges per angle Angle: 0°, 90°, 180°, 270° (input a.c. power port) Polarity: Positive & Negative Repetition Rate: 1 surge per min

Signal Lines (Unshielded) Source Impedance: 42 Ω for common mode

Surge Amplitude: Common Mode 0.5 & 1.0 kV

Number of Surges: 5 Surges per mode

Polarity: Positive & Negative

Repetition Rate: 1 surge per min

Page 25: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 24 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Signal Lines (Shielded)

Source Impedance: 2 Ω for common mode

Surge Amplitude: Common Mode 0.5 & 1.0 kV

Number of Surges: 5 Surges per mode

Polarity: Positive & Negative

Repetition Rate: 1 surge per min Test Data

Power Lines Line to Earth – Common Mode

OBSERVATIONS (±) Surge (kV) Mode of Application

0.5 1.0 2.0 L1 to PE No any function degraded L2 to PE No any function degraded

Line to Line – Differential Mode

OBSERVATIONS (±) Surge (kV) Mode of Application

0.5 1.0 L1 to L2 No any function degraded L2 to L1 No any function degraded

Signal Lines (Unshielded)

Line to Earth – Common Mode OBSERVATIONS (±) Surge (kV) Mode of Application

0.5 1.0

Signal Lines (Shielded)

Line to Earth – Common Mode OBSERVATIONS (±) Surge (kV) Mode of Application

0.5 1.0 BNC cable No any function degraded

Page 26: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 25 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Note: “Blank” = Not performed Test Conditions: Temperature: 24 °C Relative Humidity: 43 % Atmospheric Pressure: 997 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks See above observations in tables.

Page 27: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 26 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.6 Conducted Disturbance

Reference Standard EN 61000-4-6:2007

Test Date June 15, 2009 Test Location EMS-CS: Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Power Sensor Agilent E9304A MY41497499 2009-07-09 RF Power Amplifier Schaffner-Chase CBA954815 1011 2009-09-03 Power Sensor HP 8482A US37293309 2009-08-19 Signal Generator HP 8657D 3332A00555 2009-08-18 Function Generator HP 33120A US36009168 2009-08-18 Attenuator BIRD 100-A-FFN-06 9933 2009-08-19 RF-SYNTHESIZER/AMPLIFIER Schaffner NSG2070-1 1068 2010-01-12 Attenuator Schaffner INA2070-1 2068 2010-01-12 CDN Noiseken NCDN-M2-32A 2001 2010-01-12 CDN Noiseken NCDN-M3-32A 2016 2010-01-12 CDN Noiseken NCDN-T2 2001 2010-01-12 CDN Noiseken NCDN-T4 2002 2010-01-12 CDN Noiseken NCDN-T8 2015 2010-01-12 CDN Noiseken NCDN-C1-50-BNC 2001 2010-01-12 EM Clamp Noiseken NEM-23 275 2010-02-03

Test Specifications Frequency range: 150 kHz to 100 MHz 10 kHz to 30 MHz 150 kHz to 230 MHz 10 kHz to 100 MHz Voltage Level: 1 Vrms 3 Vrms 10 Vrms Modulation: AM, 80 %, 1 kHz sine wave PM, 1 Hz (0.5 s ON : 0.5 s OFF) Frequency step: 1 % step

Page 28: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 27 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Test Data

AM, 80 %, 1 kHz sine wave

Dwell Time: 3 s at 1 V

Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) No any function degraded BNC cable CDN(C1) No any function degraded

Dwell Time: 3 s at 3 V

Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) The horizontal line noise appeared BNC cable CDN(C1) The horizontal line noise appeared

Dwell Time: 3 s at 10 V

Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) The horizontal line noise appeared BNC cable CDN(C1) The horizontal line noise appeared

PM, 1 Hz (0.5 s ON : 0.5 s OFF)

Dwell Time: 3 s at 1 V Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) No any function degraded BNC cable CDN(C1) No any function degraded

Dwell Time: 3 s at 3 V

Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) The horizontal line noise appeared BNC cable CDN(C1) The horizontal line noise appeared

Dwell Time: 3 s at 10 V

Coupling Location (Line Stressed) Coupling Method Observation

Input a.c. power port CDN(M3) The horizontal line noise appeared BNC cable CDN(C1) The horizontal line noise appeared

Page 29: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 28 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Notes: CDN = Coupling Decoupling Network EMC = Electro Magnetic Clamp “blank” = Not performed Test Conditions: Temperature: 23 °C Relative Humidity: 49 % Atmospheric Pressure: 994 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks See above observations in tables.

Page 30: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 29 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.7 Mains Supply Voltage Variations

Reference Standard EN 50130-4:1995 +A1:1998 +A2 :2003 Test Date June 9, 2009 Test Location Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Constant Voltage Constant Frequency NewTech CVCF 3 kW 4269 N/A

Test Specifications Supply voltage max.: Unom + 10 % Supply voltage min. : Unom - 15 % Unom = Nominal mains voltage (230 Vac) Test Data Input a.c. power ports

Mode of Application Observation Supply voltage max. (253 Vac) No any function degraded

Supply voltage min. (195.5 Vac) No any function degraded Test Conditions: Temperature: 22 °C Relative Humidity: 52 % Atmospheric Pressure: 996 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks

See above observations in tables.

Page 31: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 30 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

3.8 Mains Supply Voltage Dips and Short Interruptions

Reference Standard EN 61000-4-11:2004

Test Date June 9, 2009 Test Location EMS-Voltage dip: Shielded Room Test Equipment

Name of Equipment Manufacturer Model No. Serial No. Due Date Simulator SCHAFFNER BEST PLUS SC2697A012 2010-03-31

Test Specifications & Observations/Remarks Voltage Dips and Short Interruptions Test Level Duration [in period/ms (50 Hz)] Observation 0 %Ut 0.5 /10 No any function degraded (100 % dip) 1.0 /20 No any function degraded

5.0 /100 No any function degraded 10 /200

25 /500 50 /1000

250 /5000 40 %Ut 0.5 /10 No any function degraded (60 % dip) 1.5 /30 No any function degraded

5.0 /100 10 /200 No any function degraded

25 /500 50 /1000

70 %Ut 0.5 /10 No any function degraded

(30 % dip) 1.5 /30 No any function degraded 5.0 /100

10 /200 No any function degraded 25 /500

50 /1000

Page 32: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 31 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Test Conditions: Temperature: 22 °C Relative Humidity: 52 % Atmospheric Pressure: 996 mbar Test Results MET Required Performance Criteria

NOT MET Required Performance Criteria Remarks See above observations in tables.

Page 33: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 32 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

APPENDIX A - Test Setup Photos and Configuration Conducted Voltage Emissions

Page 34: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 33 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Radiated Electric Field Emissions

Page 35: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 34 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Harmonic Current Emissions and Voltage Fluctuations and Flicker

Page 36: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 35 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Electrostatic Discharge

Page 37: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 36 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Radiated Electromagnetic Fields

[ 80 MHz to 1GHz]

[ Above 1GHz]

Page 38: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 37 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Fast Transients Bursts

Page 39: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 38 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Slow High Energy Voltage Surge

Page 40: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 39 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Conducted Disturbance

Page 41: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 40 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Mains Supply Voltage Dips and Short Interruptions

Page 42: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 41 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

APPENDIX B – TEST DATA Conducted Voltage Emissions (for EUT Input Power : 12 Vdc)

Limit Reading Result Margin Limit Reading Result Margin

[MHz] LISN Cable [dBuV] [dBuV] [dBuV] [dB] [dBuV] [dBuV] [dBuV] [dB]

16.38 0.7 0.6 N 73.0 44.0 45.3 27.7 60.0 30.2 31.5 28.5

16.50 0.7 0.6 H 73.0 42.5 43.8 29.2 60.0 29.5 30.8 29.2

18.24 0.8 0.7 H 73.0 36.1 37.6 35.4 60.0 28.1 29.6 30.4

18.30 0.8 0.7 N 73.0 37.4 38.9 34.1 60.0 28.0 29.5 30.5

18.80 0.8 0.7 N 73.0 39.2 40.7 32.3 60.0 28.1 29.6 30.4

18.88 0.8 0.7 H 73.0 37.8 39.3 33.7 60.0 28.2 29.7 30.3

#N/A #N/A N 79.0 #N/A 34.8 44.2 66.0 #N/A 32.8 33.3

#N/A #N/A N 79.0 #N/A 34.9 44.1 66.0 #N/A 32.5 33.5

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 40.0 26.0

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 41.0 25.0

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 42.0 24.0

#N/A #N/A H 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A H 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

H : HOT, N : NEUTRAL

Average

FactorFrequency

Correction

Line

Quasi-peak

Page 43: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 42 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

[HOT]

[NEUTRAL]

Page 44: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 43 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Conducted Voltage Emissions (for EUT Input Power : 24 Vac)

Limit Reading Result Margin Limit Reading Result Margin

[MHz] LISN Cable [dBuV] [dBuV] [dBuV] [dB] [dBuV] [dBuV] [dBuV] [dB]

0.16 0.1 0.2 H 79.0 62.0 62.3 16.7 66.0 55.8 56.1 9.9

0.32 0.1 0.2 N 79.0 59.5 59.8 19.2 66.0 55.2 55.5 10.5

0.33 0.1 0.2 H 79.0 54.8 55.1 23.9 66.0 50.9 51.2 14.8

0.49 0.1 0.3 N 79.0 54.7 55.1 23.9 66.0 49.3 49.7 16.3

6.11 0.3 0.5 H 73.0 53.9 54.7 18.3 60.0 27.8 28.6 31.4

7.51 0.3 0.6 N 73.0 54.6 55.5 17.5 60.0 19.4 20.3 39.7

#N/A #N/A N 79.0 #N/A 34.8 44.2 66.0 #N/A 32.8 33.3

#N/A #N/A N 79.0 #N/A 34.9 44.1 66.0 #N/A 32.5 33.5

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 40.0 26.0

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 41.0 25.0

#N/A #N/A H 79.0 #N/A 45.0 34.0 66.0 #N/A 42.0 24.0

#N/A #N/A H 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A H 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

#N/A #N/A N 79.0 #N/A 79.0 66.0 #N/A 66.0

H : HOT, N : NEUTRAL

Average

FactorFrequency

Correction

Line

Quasi-peak

Page 45: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 44 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

[HOT]

[NEUTRAL]

Page 46: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 45 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Radiated Electric Field Emissions (for EUT Input Power : 12 Vdc)

[MHz] [dBuV/m] [m] Antenna Cable [dBuV/m] [dBuV/m] [dB]

51.73 20.8 V 1.0 7.0 1.0 40.0 28.8 11.2

68.71 14.3 V 1.0 6.1 1.4 40.0 21.8 18.2

170.64 14.0 H 3.8 7.0 2.8 40.0 23.8 16.2

199.76 17.3 H 3.7 7.4 3.2 40.0 27.9 12.1

248.21 17.1 H 3.5 9.4 3.7 47.0 30.2 16.8

318.54 12.4 H 3.1 11.5 4.6 47.0 28.5 18.5

2.8 V 2.3 #N/A #N/A 40.0 #N/A #N/A

H 2.5 #N/A #N/A 40.0 #N/A #N/A

H 2.2 #N/A #N/A 40.0 #N/A #N/A

V 2.4 #N/A #N/A 40.0 #N/A #N/A

V 2.8 #N/A #N/A 40.0 #N/A #N/A

H 1.7 #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

#N/A #N/A 40.0 #N/A #N/A

H : Horizontal, V : Vertical

MarginFactor

Frequency ReadingPol.

HeightCorrection

Limits Result

Page 47: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 46 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Radiated Electric Field Emissions (for EUT Input Power : 24 Vac)

[MHz] [dBuV/m] [m] Antenna Cable [dBuV/m] [dBuV/m] [dB]

129.38 9.3 H 3.9 9.1 2.4 40.0 20.8 19.2

163.38 15.2 V 1.0 7.1 2.8 40.0 25.1 14.9

170.61 14.3 H 3.5 7.0 2.8 40.0 24.1 15.9

185.17 9.1 V 1.3 6.9 3.0 40.0 19.0 21.0

199.74 16.9 V 1.3 7.4 3.2 40.0 27.5 12.5

226.37 10.3 V 1.8 8.6 3.5 40.0 22.4 17.6

2.8 V 2.3 #N/A #N/A 40.0 #N/A #N/A

H 2.5 #N/A #N/A 40.0 #N/A #N/A

H 2.2 #N/A #N/A 40.0 #N/A #N/A

V 2.4 #N/A #N/A 40.0 #N/A #N/A

V 2.8 #N/A #N/A 40.0 #N/A #N/A

H 1.7 #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

V #N/A #N/A 40.0 #N/A #N/A

#N/A #N/A 40.0 #N/A #N/A

Frequency ReadingPol.

HeightCorrection

Limits Result

H : Horizontal, V : Vertical

MarginFactor

Page 48: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 47 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Harmonic Current Emissions and Voltage Fluctuations and Flicker

Flicker Test Summary per EN/IEC61000-3-3 (Run time) [for EUT Input Power : 12 Vdc]

Test duration (min): 10

Test Result: Pass

Psti and limit line European Limits

0.00

0.25

0.50

0.75

1.00

Pst

15:05:36

Time is too short for Plt plot

Parameter values recorded during the test:

Vrms at the end of test (Volt) : 229.48

Highest dt (%): 0.00 Test limit (%): 3.30 Pass

Time(mS) > dt: 0.0 Test limit (mS): 500.0 Pass

Highest dc (%): 0.00 Test limit (%): 3.30 Pass

Highest dmax (%): 0.00 Test limit (%): 4.00 Pass

Highest Pst (10 min. period): 0.001 Test limit: 1.000 Pass

Highest Plt (2 hr. period): 0.001 Test limit: 0.650 Pass

Page 49: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 48 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Flicker Test Summary per EN/IEC61000-3-3 (Run time)

[for EUT Input Power : 24 Vac]

Test duration (min): 10

Test Result: Pass

Psti and limit line European Limits

0.00

0.25

0.50

0.75

1.00

Pst

15:24:01

Time is too short for Plt plot

Parameter values recorded during the test:

Vrms at the end of test (Volt) : 229.45

Highest dt (%): 0.00 Test limit (%): 3.30 Pass

Time(mS) > dt: 0.0 Test limit (mS): 500.0 Pass

Highest dc (%): 0.00 Test limit (%): 3.30 Pass

Highest dmax (%): 0.00 Test limit (%): 4.00 Pass

Highest Pst (10 min. period): 0.001 Test limit: 1.000 Pass

Highest Plt (2 hr. period): 0.001 Test limit: 0.650 Pass

Page 50: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 49 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

APPENDIX C – EUT Photographs

Page 51: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 50 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

EUT External Photographs

Page 52: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 51 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

EUT Internal Photographs

Page 53: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 52 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

PCB

Page 54: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 53 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Page 55: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 54 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)

Page 56: CTK Co., Ltd. - NAPAD.pl€¦ · CTK Co., Ltd. This document may be altered or revised by CTK Co., Ltd. personnel only, and shall be noted in the revision section of the document

CTK Co., Ltd. 386-1, Ho-dong, Cheoin-gu, Yongin-si, Gyeonggi-do, 449-100, Korea

Tel: +82-31-339-9970 Fax: +82-31-339-9855 www.e-ctk.com

Test Report No.: 2010020060 Date: February 9, 2010

Page 55 of 55

This Report shall not be reproduced except in full without the written approval of CTK Form No.: CTK-RF-EC-EN55022&EN50130-4(Rev.4.5)