data center energy use: metrics and rating systems

19
Data Center Energy Data Center Energy Use, Metrics and Use, Metrics and Rating Systems Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007

Upload: datacenters

Post on 08-Aug-2015

277 views

Category:

Technology


1 download

TRANSCRIPT

Data Center Energy Use, Data Center Energy Use, Metrics and Rating SystemsMetrics and Rating Systems

Steve GreenbergEnergy Management Engineer

Environmental Energy Technologies Division

Lawrence Berkeley National Laboratory

October 31, 2007

EETD DivRev 2004 page 2

Today’s AgendaToday’s Agenda

• Introduction• Energy Usage in Data Centers

—Opportunities for Improvement—Selecting a Performance Metric—Rating Systems

• Implementing a Metric• Next Steps

EETD DivRev 2004 page 3

The Data Center ChallengeThe Data Center Challenge

• Data Centers 15-40x the energy intensity of typical office buildings

• A single rack of servers can be 20 kW —$17k per year (at $.10/kWh) per rack—Hundreds of racks per center

• Where are the opportunities?—25 data centers benchmarked

EETD DivRev 2004 page 4

Typical Data Center DesignTypical Data Center Design

local distribution lines

to the building, 480 V

HVAC system

lights, office space, etc.

UPS PDU computer racks

backup diesel generators

Electricity Flows in Data CentersElectricity Flows in Data Centers

computerequipment

uninterruptible

load

UPS = Uninterruptible Power Supply

PDU = Power Distribution Unit;

EETD DivRev 2004 page 5

Data Center MetricsData Center Metrics

• High-level — IT/total —useful work/total

• Subsystem—Power distribution —HVAC—Lighting

• Facility performance (other than energy)

EETD DivRev 2004 page 6

High-level Facility MetricsHigh-level Facility Metrics

Source: The Green Grid Data Center Power Efficiency Metrics. ©2007. Used with permission

E.g. Green Grid, PUE and DCiE

EETD DivRev 2004 page 7

High-level Facility MetricsHigh-level Facility Metrics

• E.g. Uptime Institute:

“Site Infrastructure Power Overhead Multiplier (SI-POM)” = Total/IT

Source: “Four Metrics Define Data Center “Greenness” “,Uptime Institute, 2007.

EETD DivRev 2004 page 8

Percentage of electricity delivered Percentage of electricity delivered to IT equipmentto IT equipment

IT Power to Total Data Center Power

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

Data Center Number

Ra

tio

Average .57

Higher is better

Source: LBNL Benchmarking

EETD DivRev 2004 page 9

Total Data Center Power/IT Power

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Center Number

Rat

io

Average 1.83

Lower is better

Source: LBNL Benchmarking

Total Power/IT PowerTotal Power/IT Power

EETD DivRev 2004 page 10

Other Data Center MetricsOther Data Center Metrics

• Watts per square foot• Power distribution: UPS efficiency, IT power supply

efficiency— Uptime: IT Hardware Power Overhead Multiplier (ITac/ITdc)

• HVAC— IT total/HVAC total

— Fan watts/cfm

— Pump watts/gpm

— Chiller plant (or chiller or overall HVAC) kW/ton

• Lighting watts/square foot• ANCIS: Rack cooling index (fraction of IT within

recommended temperature range)• ANCIS: Return temperature index (RAT-SAT)/ITΔT

EETD DivRev 2004 page 11

IT equipment load densityIT equipment load density

IT Equipment Load Intensity

0

10

20

30

40

50

60

70

80

90

100

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Data Center Number

Wa

tts

/sq

. ft

.

2003 BenchmarksAve. ~ 25

2005 BenchmarksAve. ~ 52

EETD DivRev 2004 page 12

HVAC system effectivenessHVAC system effectiveness

HVAC Effectiveness Index

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

1 2 3 4 5 6 7 8 9 10 11 12 14 16 17 18 19 20 21 22

Data Center Number

Ra

tio

of

IT E

qu

ipm

en

t

Po

we

r to

HV

AC

Po

we

r

We observed a wide variation in HVAC performance

EETD DivRev 2004 page 13

Efficiency of Information Technology Power Supplies and Efficiency of Information Technology Power Supplies and Uninterruptible Power SuppliesUninterruptible Power Supplies

Factory Measurements of UPS Efficiency

70%

75%

80%

85%

90%

95%

100%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Percent of Rated Active Power Load

Eff

icie

ncy

Flywheel UPS

Double-Conversion UPS

Delta-Conversion UPS

(tested using linear loads)

45%

50%

55%

60%

65%

70%

75%

80%

85%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

% of Nameplate Power Output

% E

ffic

ien

cy

Average of All Servers

Power supplies in IT equipment generate much of the heat. Highly efficient supplies can reduce IT equipment load by 15% or more.

UPS efficiency also varies a lot.

(Do they need the same environment as the IT equipment or can their conditions be relaxed?)

EETD DivRev 2004 page 14

Summary of Opportunities for Energy Summary of Opportunities for Energy EfficiencyEfficiency

• Air management• Right-sizing• Central plant optimization• Efficient air handling• Free cooling• Humidity control• UPSs and power supplies• On-site generation• Liquid cooling• Design and M&O processes

EETD DivRev 2004 page 15

Benchmarking for Energy Performance Benchmarking for Energy Performance ImprovementImprovement

Energy benchmarking can be effective in helping to identify better performing designs and strategies. As new strategies are implemented (e.g. liquid cooling), energy benchmarking will enable comparison of performance.

EETD DivRev 2004 page 16

Rating Systems Rating Systems for Energy Efficient Data Centersfor Energy Efficient Data Centers

Options:

• Rating system for new data centers based on design criteria

• Recognition program for upper quartile energy efficient performance for existing data centers

• Performance label for existing data centers, with requirement for continuous improvement

EETD DivRev 2004 page 17

Rating system based on design criteriaRating system based on design criteria

• Model: LEED-New Construction• Labs21 developed a LEED-based rating system for

laboratories – basis for proposed LEED for Labs• LBNL is working with the California Energy

Commission on creating credits for data centers• Principle focus on energy efficiency• Secondary focus on site, materials, water, indoor

environment• Must achieve a minimum number of points to be

certified• Documentation required for each point• Additional levels of achievement possible• Does not address post-construction performance

EETD DivRev 2004 page 18

Recognition program for energy efficient performanceRecognition program for energy efficient performance

• Model: ENERGY STAR for Buildings• Would need statistical model for existing data centers that

included process as well as building performance• Exclusive focus on energy efficiency• Performance rating of ≥75 points on a scale of 1-100 based on

statistical data

• Application requires — Company to benchmark itself against performance index— Professional engineer verifies and prepares statement of

performance

• Label is good for one year• Reapplication required to maintain ENERGY STAR

EETD DivRev 2004 page 19

Performance label for continuous Performance label for continuous improvementimprovement

• Model: Facility certification for energy efficiency • Under development for industrial plants- 2009 pilot• Model suitable for existing data centers• Comprehensive for processes and building• Exclusive focus on energy efficiency• Certification requires:

— Compliance with energy management standard— Minimum implementation of recommendations that meet company

IRR— 5% energy intensity reduction over 2 years— Verification of energy savings required

• Re-certification every 3 years; 7.5% energy intensity reduction requirement