TS082x SeriesChallenger Data Gathering Panels
www.interlogix.com.au
TecomTM Series / Data Gathering Panels
Features
• TS0820/TS0824 - 8 zone inputs
• TS0827 - 4 zone inputs
• 8-input DGPs can be expanded to 32 inputs
• 8-input DGPs can be used with TS0840, TS0841, or TS0842 expanders to add 8 or 16 relays or outputs
• DGPs are polled for online state
• 1 siren output (except when used at DGP address 15)
• Tamper input
Overview
TS082x series of data gathering panels (DGPs) are used to expand the number of inputs and outputs (or relays) on the Challenger system.
DGPs allow installers to easily terminate wiring connections for inputs and relay outputs at locations away from the panel.
Up to 15 DGPs can be connected directly to each Challenger control panel over a reliable RS-485 data bus, thereby minimizing cable runs.
If a communications failure occurs, the data gathering panel remembers its last alarm, helping to identify possible reasons for faults.
The TS0820 and TS0824 includes 8 standard inputs and a sirenoutput.Thisstandardconfigurationcanbeexpandedto 32 inputs and 16 outputs.
The TS0827 is an economy DGP that has similar features but offers only four inputs and no integrated power supply or siren output. No expansion is possible.
DGPs and other expansion modules can be mounted in Challenger metal housings.
TS0820-DS-131030-4
TS082x SeriesChallenger Data Gathering Panels
InterlogixNational Sales Enquiries 1300 361 479
271-273 Wellington Road Mulgrave Vic 3170T +61 3 9239 1200 F +61 3 9239 1298
Ordering informationTS0820 AC DGP board with Plug Pack and TS0304 EnclosureTS0820B AC DGP, board onlyTS0824 DC DGP, board onlyTS0827 DC four-input DGP, board only
System Block Diagram
SpecificationsTS0820 TS0824 TS0827
Power supply AC DC DCCurrent consumption (Add10mAforeachexpanderfitted) 120mA 120mA 45mA
Voltage 16.8VAC 13.8VDC 13.8VDCInputs 8 to 32 8 to 32 4Siren output 1 1 No sirenMaximum outputs 16 16 0Maximum number per panel 15 15 15Dynamic battery testing Yes Not applicable Not applicableMax. distance from panel(may be extended with LAN isolation interfaces) 1,500 m 1,500 m 1,500 m
Data bus monitoring Yes Yes YesPCB size Size A Size A Size BEnclosure TS0304 No enclosure No enclosureEnvironmentalOperating temperature 0-500C 0-500C 0-500C
Humidity 95% non-condensing
95% non-condensing
95% non-condensing
Regulatory ACMA C-Tick for Australia and New Zealand
Specifications subject to change without notice.
© 2013 Interlogix. All rights reserved. Interlogix is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation.