determing sil level

Upload: manish-mehta

Post on 02-Apr-2018

226 views

Category:

Documents


2 download

TRANSCRIPT

  • 7/27/2019 Determing SIL Level

    1/86

    Determining the SIL level of a SafetyInstrumented Function (SIF)

    Website: www.gmintsrl.com

    Email: [email protected]

    SIL

  • 7/27/2019 Determing SIL Level

    2/86

    2

    Standard Definitions

    IEC 61508 Title: Standard for Functional Safety of Electrical / Electronic /Programmable Electronic Safety-Related System

    IEC 61508 was conceived to define and harmonize a methodto reduce risks for human beings and/or reduce valuable loss for allindustrial and non industrial environments.

    IEC 61511 Title: Safety Instrumented Systems for the Process Industry

    IEC 61511 was developed as a Process Sector implementation of IEC 61508

    Following the above standard is the minimum necessary condition to obtain plantsafety. However this, alone, does not guarantee that the process will be safe.

    NOT implementing these safety standards will certainly lead to an UNSAFEprocess.

  • 7/27/2019 Determing SIL Level

    3/86

    What is Safety?

    Freedom from unacceptable risks

  • 7/27/2019 Determing SIL Level

    4/86

    Safety Integrity Levels IEC 61508

  • 7/27/2019 Determing SIL Level

    5/86

    Risk Reduction

    Frequency of accidents w ithout protection 1RRF =

    Frequency of tolerable accidents PFDavg=

  • 7/27/2019 Determing SIL Level

    6/86

  • 7/27/2019 Determing SIL Level

    7/86

    A.L.A.R.P.

  • 7/27/2019 Determing SIL Level

    8/86

    Hazardous Operative Analysis (HAZOP)

    Debutanizer Column Node: Reboiler Section

    Required SIFs are usually indicated in the P&ID (Piping and Instrumentation Diagrams)or in the PFD (Process Flow Diagram).

  • 7/27/2019 Determing SIL Level

    9/86

    Layer Of Protection Analysis (LOPA)

    Figure 72, Sample Process for LOPA Example

    Figure 73, Event tree for LOPA example

    Hexane

    Storage

    Tank

    PSV

    LV

    LC

    Next

    process

    Dike

    BPCS loop

    failureDike Probability of ignition

    Probability of personnel

    in areaProbability of fatality

    No significant event

    Success

    P=0.99 No significant event

    P=0.1 No P=0Fire

    Failure P=0.01 No P=0.5Fire, no fatality

    Yes P=1.0 No P=0.5

    Yes P=0.5 Fire with fatality

    Yes P=0.5

  • 7/27/2019 Determing SIL Level

    10/86

    Layer Of Protection Analysis (LOPA)LOPA WORKSHEET

    Scenario Number Equipment Number Scenario Title: Hexane Surge Tank Overflow.

    Spill not contained by the dike

    Date Description Probability Frequency (per year)

    Consequence

    Description/Category

    Release of hexane outside the dike due to tank

    overflow and failure of dike with potential for

    ignition and fatality

    Risk tolerance Criteria(Category or Frequency)

    Maximum tolerable risk of serious fire

    Maximum tolerable risk of fatal injury

    < 1 x 10-4

    < 1 x 10-5

    Initiating Event

    (typically a frequency)

    BPCS loop failure 1 x 10-1

    Enabling Event or Condition N/A

    Conditional Modifiers (if applicable)

    Probability of ignition 1

    Probability of personnel in area 0.5

    Probability of fatal injury 0.5

    Other N/A

    Frequency of unmitigated consequence 2.5 x 10-2

    Independent Protection Layers

    Dike (existing) 1 x 10-2

    Safeguards (non-IPLs)

    Human action not an IPL as it depends upon

    BPCS generated alarm.

    (BPCS failure considered as initiating event)

    Total PFD for all IPLs 1 x 10-2

    Frequency of Mitigated Consequence 2.5 x 10-4

    Risk Tolerance Criteria Met? (Yes/No): No. SIF required

    Action required: Add SIF with PFD of at least 4 x 10-2 (Risk Reduction Factor > 25) Responsible Group / Person: Engineering / J.Q.

    Public, by July 2005 Maintain dike as an IPL (inspection, maintenance, etc)

    Notes: Add action items to action tracking database

  • 7/27/2019 Determing SIL Level

    11/86

    Benefits Vs. Costs in the ALARP blue Zone

    NO SIS NO SIS SIS SIS

    SIS NT

    F EV F EVBenefits=

    Costs COST COST

    +

    Where: B-C ratio : The ratio of benefits to costs FNO-SIS : Frequency of the unwanted event without a SIS. EVNO-SIS : Total expected value of loss of the event without aSIS.

    FSIS : Frequency of the unwanted event with a SIS. EVSIS : Total expected value of loss of the event with a SIS. COSTSIS : Total lifecycle cost of the SIS (annualized). COSTNT : Cost incurred due to nuisance trip (annualized)

    Example:A SIS is being installed to prevent a fire that will cost the company $1,000,000.The frequency prior to application of SIS has been calculated in one every 10 years.

    After SIS installation the expected frequency is one every 1000 years,and its annualized cost is approximately $66.000.Cost for nuisance trip is negligible, being F&G normally de-energized.What is the benefit-to-cost ratio for the F&G project?The Benefits/Costs relation will be:

    A benefit-to-cost ratio of 1.5 means that for every $1 of investment the plant owner can expect $1.5 in return.

    1 1

    Benefits = ( 1000000) - ( 1000000) = 9900010 1000

    Costs = (66000 + 0) = 66000

    Benefits 99000= = 1.5

    Costs 66000

  • 7/27/2019 Determing SIL Level

    12/86

    Risk Reduction with Protection Layers

  • 7/27/2019 Determing SIL Level

    13/86

    Layers of Protection

  • 7/27/2019 Determing SIL Level

    14/86

    Risk Protection Balance

    The Risk Must be balanced by the Protection Layers

    (Optimal Safety Balance)

    1 2 3 4

    RISK

    1. Plant, Process and Environment

    PREVENTION

    2. DCS

    3. SIS / ESD

    4. Physical Protections

  • 7/27/2019 Determing SIL Level

    15/86

    MTBF

    MTTF is an indication of theaverage successful operating timeof a device (system) before afailure in any mode.

    MTBF: Mean Time Between FailuresMTBF = MTTF + MTTRMTTF = MTBF - MTTRMTTR: Mean Time To Repair

    Since (MTBF >> MTTR)MTBF MTTF

    (very close in values)

  • 7/27/2019 Determing SIL Level

    16/86

    Availability

    99,999101000000

    99,9910100000

    99,91010000

    99101000

    Availability (%)Repair time (Hrs)Availability time (hrs)

    What does an availability of 99,99% for a specific component orsystem really stand for? That the component or system could stopworking one time ..

    .. every month with a repair time of 4.3 minutes.

    .. every year with a repair time of 53 minutes.

    .. every 10 years with a repair time of 8.8 hours.

  • 7/27/2019 Determing SIL Level

    17/86

    MTBF and Failure Rate

    Failures per unit timeFailure Rate = =

    Number of components exposed to functional failure

    1MTBF =

    Successful Unsuccessful

    UNRELIABILITY

    UNAVAILABILITY

    RELIABILITYAVAILABILITY

    MTTRMTTF

    Venn Diagram: Reliability-Unreliability;

    Availability-Unreliabili ty and relations with MTTF and MTTR

  • 7/27/2019 Determing SIL Level

    18/86

    MTBF and Failure Rate

    Relation between MTBF and Failure Rate

    Failure per unit time 1

    = ----------------------------- = ------------

    Quantity Exposed MTBF

    1 Quantity ExposedMTBF = ------ = ----------------------------

    Failure per unit time

  • 7/27/2019 Determing SIL Level

    19/86

    MTBF - Example

    Instantaneous failure rate is commonly used as measure of reliability.

    Eg. 300 Isolators have been operating for 10 years. 3 failures haveoccurred. The average failure rate of the isolators is:

    Failure per unit time 3 = ------------------------------- = ----------------- =

    Quantity Exposed 300*10*8760

    = 0.0000000115 per hour = 0.001 per year= 11,5 FIT (Failure per billion hours) =

    = 11,5 probabilities of failure in one billion hours.= 0.001 probability of failure per year

    MTBF = 1 / = 1000 years (for constant failure rate)

  • 7/27/2019 Determing SIL Level

    20/86

    FIT

    Failure In Time is the number of failures per

    one billion device hours.

    1 FIT == 1 Failure in 109 hours

    = 10-9

    Failures per hour

  • 7/27/2019 Determing SIL Level

    21/86

    Failure Rate Categories

    0,8 mA

    20 mA

    4 mA

    du

    dd/sd

    su

    du

    dd/sd

    Example for a 4-20 mA signal

    tot = safe + dangerous s = sd + su

    d = dd + du tot = sd + su + dd + du

    Where:

    sd = Safe detectedsu = Safe undetecteddd = Dangerous detecteddu = Dangerous undetected

    tot = safe + dangerous(MTBF = MTBFs + MTBFd) safe: spurious trip (nuisance trip) dangerous: safety trip

  • 7/27/2019 Determing SIL Level

    22/86

    Example of FMEDA Analysis

    FailureModes

    EffectsDiagnostic

    Analysis

  • 7/27/2019 Determing SIL Level

    23/86

    D1014 SIL 3Analysis

    D1014 module

    Isolated Hart compatible

    Repeater power supply

  • 7/27/2019 Determing SIL Level

    24/86

    Safe Failure Fraction (SFF)

    Type A components are described as simpledevices with well-known failure modes and asolid history of operation.

    Type B devices are complex components withpotentially unknown failure modes, e.g.microprocessors, ASICs, etc.

    DD SD SU

    DD DU SD SU

    DU

    DD DU SD SU

    + + SFF = =

    + + +

    = 1- + + +

  • 7/27/2019 Determing SIL Level

    25/86

    System architectures

  • 7/27/2019 Determing SIL Level

    26/86

    PFDavg simplified equations

  • 7/27/2019 Determing SIL Level

    27/86

    Common fault / Beta Factor

    For redundant subsystems using electroniccomponents, the value of ranges from 1%

    to 10 %.

    The second term of the equations is thePFDavg value contribution due to the factor, derived from the 1oo1 architecture.

    Example:du = 0.01 / yr; TI = 1 yr; = 0.05

    For 1oo2 the equation is:

    Example:du = 0.01 / yr; TI = 1 yr; = 0.05

    For 1oo2 the equation is:( ) ( ) ( )

    [ ] ( )

    2

    2

    1 113 2

    1 10 95 0 01 0 05 0 01 1

    3 2

    0 00003 0 00025 0 00028

    DU DUTI TI

    . . . .

    . . . / yr

    + =

    = + =

    = + =

  • 7/27/2019 Determing SIL Level

    28/86

    Considerations on Factor

    Comparisons using different values of factor:

    Considerations:

    The value 0.00003 is 166.6 times lower than 0.005.

    The value 0.000082 is 61 times lower than 0.005.

    The value 0.00028 is 17.8 times lower than 0.005.

    The value 0.000527 is 9.48 times lower than 0.005. Without factor the PFDavg, of 1oo2 architecture, is 166.6 times better than PFDavg value of 1oo1 architecture.

    With 1% factor the PFDavg, of 1oo2 architecture, is 61 times better than PFDavg value of 1oo1 architecture.

    With 5% factor the PFDavg, of 1oo2 architecture, is 17.8 times better than PFDavg value of 1oo1 architecture.

    With 10% factor the PFDavg, of 1oo2 architecture, is 9.48 time better than PFDavg value of 1oo1 architecture.

  • 7/27/2019 Determing SIL Level

    29/86

    PFDavg 1oo1 Calculation

    Equation for 1oo1 loop

    Where:

    RT = repair time in hours (conventionally 8 hours)

    T1 = T proof test, time between circuit functional tests (1-5-10 years)

    dd = failure rate for detected dangerous failures

    du = failure rate for undetected dangerous failures

  • 7/27/2019 Determing SIL Level

    30/86

    PFD Versus T- proof time interval (TI)

    PFD degrades in time.

    The probability of failure of any equipment (therefore the PFD of a SIF)increases with time (linearly for constant failure rate).

  • 7/27/2019 Determing SIL Level

    31/86

    How PFD changes in time

    Since PFD increases with time, its value can be kept undercontrol by actuating maintenance proof tests at certain time

    intervals. A periodic test at T-proof interval (as specified by the

    manufacturer), is capable of identifying any non directly

    detectable failure mechanisms in the equipment (dangerousundetected failures);Note: The grade of the test effectiveness affects the value towhich the PFDavg is set afterwards.

    The grade of the test effectiveness affects the value to whichthe PFDavg is set afterwards.

  • 7/27/2019 Determing SIL Level

    32/86

    How PFD changes in time

    If the effectiveness is (99-100%) the equipment can be considered asnew, from a probability of failure point of view, if it is lower then 100%(70-80-90%), then the SIL level could expire and not reach the required

    SIL level.

  • 7/27/2019 Determing SIL Level

    33/86

    Periodic test for D1014 50%

  • 7/27/2019 Determing SIL Level

    34/86

    Periodic test for D1014 99%

  • 7/27/2019 Determing SIL Level

    35/86

    PFDavg weight in SIF

    Each subsystems PFDavg has apercentage value in relation tothe total.

    Component manufacturers list, intheir functional safety manual,the value of PFDavg obtained byauthorized certification bodieslike TUV, EXIDA, FM, etc.

    These bodies apply aconventional weighing of thePFDavg of the component inconsequence of the importance

    that it has in the entire loop, asreported in the following Table:20%

    10%

    25%

    35%

    10%

    TX

    Barrier

    PLC

    Valve

    PS

  • 7/27/2019 Determing SIL Level

    36/86

    Safety Instrumented Systems (SIS)

    A simple SIS, with one logicsolver, is a safety function as

    shown in the picture.

    A SIS is made up of multipleSIFs: one for each potentiallydangerous condition.

    Its objective is to collect andanalyzes data information fromsensors to determine if adangerous condition occurs, andconsequently to start a shutdown

    sequence to bring the process toa safe state.

    A potentially dangerouscondition is called "demand.

  • 7/27/2019 Determing SIL Level

    37/86

    The majority of SIS are based on the concept of de-energizing to trip.In normal working conditions input and output are energized(F&G systems are the opposite)

    For each SIF, the required Risk Reduction Factor (RRF) is determined.

    IEC 61508 and IEC 61511,

    recognized Standards,

    cover in detail these safety aspects.

    Safety Instrumented Systems (SIS)

  • 7/27/2019 Determing SIL Level

    38/86

    PFDavg 1oo1 Calculation

    Equation for 1oo1 loop

    Where:

    RT = repair time in hours (conventionally 8 hours)

    T1 = T proof test, time between circuit functional tests (1-5-10 years)

    dd = failure rate for detected dangerous failures

    du = failure rate for undetected dangerous failures

  • 7/27/2019 Determing SIL Level

    39/86

    Loop PFDavg calculation

    If T1 = 1 year then

    but being dd * 8 far smaller than du * 4380

  • 7/27/2019 Determing SIL Level

    40/86

    SIF Example

    Calculate values of MTBF, PFDavg, RRFfor a possible SIL level of the following SIF.

    These values are given by the manufacturers:Tx: MTBF = 102 yrs; DU = 0,00080 / yr; DD = 0,0010 / yr; S = 0,00800 / yrBarrier: MTBF = 314 yrs; DU = 0,00019 / yr; DD = 0,0014 / yr; S = 0,00159 / yrPLC: MTBF = 685 yrs; DU = 0,00001 / yr; DD = 0,0001 / yr; S = 0,00135 / yrSupply: MTBF = 167 yrs; DU = 0,00070 / yr; DD = 0,0000 / yr; S = 0,00530 / yr

    Valve: MTBF = 12 yrs; DU = 0,02183 / yr; DD = 0,0200 / yr; S = 0,00400 / yr

    S t bl f SIL 1

  • 7/27/2019 Determing SIL Level

    41/86

    Summary table for SIL 1

    SIL 1-85100 %0.0117650.023530.02250.05774170.1037

    710

    Total(SIF)

    SIL 388.3 %28572.97 %0.0003500.000700.00000.005301890.00600167PowerSupply

    SIL 273.8 %9292.87 %0.0109150.021830.02000.04150240.0833312Valve

    SIL 399.3 %2000000.04 %0.0000050.000010.00010.001357410.00146685PLC

    SIL 394.0 %105260.81 %0.0000950.000190.00140.001596290.00318314BarrierD1014S

    SIL 291.8 %25003.40 %0.0004000.000800.00100.008001250.00980102Tx

    SILLevel

    SFFRRF =

    1/PFDavg

    % of totalPFDavg

    PFDavg1oo1 =DU/2

    DU

    / yrDD

    / yrS

    / yrMTBFs=1/ S (yr)

    / yr =1/MTBF

    MTBF

    (yr)

    Sub-system

    S f S

  • 7/27/2019 Determing SIL Level

    42/86

    Summary table for SIL 2

    SIL 2-225100 %0.0044520.008900.009100.02994330.0479421Total(SIF)

    SIL 388.3 %28577.86 %0.0003500.000700.00000.005301890.00600167Power

    Supply

    SIL 273.8 %27880.91 %0.0036020.007200.00660.01370730.0275036Valve

    4 MonthsTProof

    SIL 399.3 %2000000.11 %0.0000050.000010.00010.001357410.00146685PLC

    SIL 394.0 %105262.13 %0.0000950.000190.00140.001596290.00318314BarrierD1014S

    SIL 291.8 %25008.98 %0.0004000.000800.00100.008001250.00980102Tx

    SILLevel

    SFFRRF =

    1/PFDavg

    % oftotal

    PFDavg

    PFDavg1oo1 =DU/2

    DU

    / yrDD

    / yrS

    / yrMTBFs=1/ S (yr)

    =1/MTBFper yr

    MTBF

    (yr)

    Sub-system

    SIF PFD f t ti

  • 7/27/2019 Determing SIL Level

    43/86

    SIFs PFDavg confrontation

    SIL 1 SIL 2

    80,91%

    8,98%

    7,86%

    2,13%

    0,11%

    92,87%

    3,40%

    2,97%

    0,81%

    0,04%

    TXBarrier

    PLCValve

    PS

    T f t bl f SIL 2 SIF

  • 7/27/2019 Determing SIL Level

    44/86

    T-proof table for SIL 2 SIF

    Since the SIF has a safety integrity level SIL 2 the periodicproof tests can be performed according to the following

    table:

    4 monthsValve

    20 yrsPLC

    10 yrsBarrier

    1 yrsTransmitterT-proof test time intervalSubsystem

    2nd SIF E l

  • 7/27/2019 Determing SIL Level

    45/86

    2nd SIF Example

    Calculate values of MTBF, PFDavg, RRFfor a possible SIL level of the following SIF.

    These values are given by the manufacturers:Tx: MTBF = 102 yrs; DU = 0,00080 / yr; DD = 0,0010 / yr; S = 0,00800 / yrBarrier: MTBF = 314 yrs; DU = 0,00019 / yr; DD = 0,0014 / yr; S = 0,00159 / yrPLC: MTBF = 685 yrs; DU = 0,00001 / yr; DD = 0,0001 / yr; S = 0,00135 / yrSupply: MTBF = 167 yrs; DU = 0,00070 / yr; DD = 0,0000 / yr; S = 0,00530 / yr

    Valve: MTBF = 12 yrs; DU = 0,02183 / yr; DD = 0,0200 / yr; S = 0,00400 / yr

    Considering the same data used in the 1oo2 architecture as

    in the first example but introducing a factor of 5% (0.05)on redundant sub-systems.

    T bl 1 2

  • 7/27/2019 Determing SIL Level

    46/86

    Table 1oo2

    SIL 3-8.513600.0007352817850.011765Total (SIF)

    SIL 388.3 %94.3566700.0000176518928570.000350Power

    Supply *

    SIL 373.8 %1214540.0006876824920.010915Valve

    1 year T-Proof

    SIL 399.3 %7412000000.000005007412000000.000005PLC

    SIL 494.0 %314.42100510.00000476629105260.000095Barrier

    D1014D *

    SIL 391.8 %62.5495280.0000201912525000.000400Tx *

    SILLevel

    SFFMTBFs1oo2

    RRF1oo2

    PFDavg1oo2[1]

    MTBFs1oo1

    RRF1oo1

    PFDavg1oo1

    Subsystem

    S t bl 1 2

  • 7/27/2019 Determing SIL Level

    47/86

    Summary table 1oo2

    Note 1:

    The Table highlights advantages of 1oo2 system architecture on 1oo1.Safety integrity level of the SIF has moved from SIL 1 to SIL 3 maintaining the same

    T-proof test time interval of 1 year.

    Note 2:

    Using such system configuration, the risk reduction factor is highly increased. If aSIL 2 level is required instead of SIL 3, it would be possible to extend the T-proof

    test time interval (TI).

    SIL 21360.0073527551oo2|TI=10

    SIL 22720.0036763771oo2|TI=5

    SIL 24530.002205821oo2|TI=3

    SIL 313600.000735281oo2|TI=1

    Max SIL LevelRRFPFDavg 1oo2System

    Table 10a shows how the 1oo2 SIFwould change for TI = 3, 5 &10 years.

    Table 1oo2 only Final Element

  • 7/27/2019 Determing SIL Level

    48/86

    Table 1oo2 only Final Element

    SIL 2-108290.0012053317850.011765Total (SIF)

    SIL 288.3 %189566700.0000176518928570.000350Power

    Supply

    SIL 373.8 %1214540.0006876824920.010915Valve

    1 yr T-proof

    SIL 399.3 %7412000000.0000057412000000.000005PLC

    SIL 394.0 %629105260.000095629105260.000095Barrier

    D1014D

    SIL 291.8 %12525000.00040012525000.000400Tx

    SIL LevelSFFMTBFsRRFPFDavg

    1oo2 (Valve Only)

    MTBFs

    1oo1

    RRF

    1oo1

    PFDavg

    1oo1Subsystem

    PLC Channel 1

    Inputcircuit

    Logic Solvercommoncircuits

    Outputcircuit

    +

    _

    Finalelement

    Finalelement

    Tx 1

    ISBarrierCh. 1

    The valves redundancyallows the SIF to reach SIL 2

    level with a more thansatisfactory RRF value.

    Consideration 1oo2 only Final Element

  • 7/27/2019 Determing SIL Level

    49/86

    Adding a redundant valve; Supposing a factor of5%, the RFF is =1454.

    The PFDavg value is now 1/1454 = 0.00068 and fora test proof time interval or 1 year (SIL 3).

    The SIL value of the total SIF becomes 0.0012 with

    RRF = 829.

    Considerations:

    Adjusting the T-proof time and the redundancy offinal element it is possible to obtain a better SIL levelof the SIF, and even to advance it to SIL 3.

    Consideration 1oo2 only Final Element

    Summary table 1oo2 Final Element

  • 7/27/2019 Determing SIL Level

    50/86

    Summary table 1oo2 Final Element

    Note 1:

    The Table highlights advantages of 1oo2 system architecture of the final element.

    Safety integrity level of the SIF has moved from SIL 1 to a good SIL 2 maintainingthe same T-proof test time interval of 1 year.

    SIL 1820. 01205331oo2|TI=10

    SIL 21650.006026651oo2|TI=5

    SIL 22760.003615991oo2|TI=3

    SIL 28290.001205331oo2|TI=1

    Max SIL LevelRRFPFDavg 1oo2System

    Table 10b shows how the 1oo2 FinalElement SIF would change for TI = 3,

    5 & 10 years.

    3rd SIF Example

  • 7/27/2019 Determing SIL Level

    51/86

    3rd SIF Example

    Calculate values of MTBF, PFDavg, RRFfor a possible SIL level of the following SIF.

    These values are given by the manufacturers:Tx: MTBF = 102 yrs; DU = 0,00080 / yr; DD = 0,0010 / yr; S = 0,00800 / yrBarrier: MTBF = 314 yrs; DU = 0,00019 / yr; DD = 0,0014 / yr; S = 0,00159 / yrPLC: MTBF = 685 yrs; DU = 0,00001 / yr; DD = 0,0001 / yr; S = 0,00135 / yrSupply: MTBF = 167 yrs; DU = 0,00070 / yr; DD = 0,0000 / yr; S = 0,00530 / yr

    Valve: MTBF = 12 yrs; DU = 0,02183 / yr; DD = 0,0200 / yr; S = 0,00400 / yr

    Considering the same data used in the 2oo3 architecture as

    in the first example but introducing a factor of 5% (0.05)on redundant sub-systems.

    Table 2oo3

  • 7/27/2019 Determing SIL Level

    52/86

    Table 2oo3

    Summary table 2oo3

  • 7/27/2019 Determing SIL Level

    53/86

    Summary table 2oo3

    Note 1:

    The advantages of 2oo3 system architecture on 1oo1 are different then thoseobtained with a 1oo2.

    Safety integrity level of the SIF has in fact moved from SIL 1 to SIL 2 maintainingthe same T-proof test time interval of 1 year.The very high value of RRF shows that SIL 2 can be easily maintained evenwith longer TI intervals.

    Note 2:

    Using such system configuration, the risk reduction factor is highly increased. If aSIL 2 level is required instead of SIL 3, it would be possible to extend the T-prooftest time interval (TI).

    SIL 1800. 01024142oo3|TI=10

    SIL 21950.00512072oo3|TI=5

    SIL 23250.003072422oo3|TI=3

    SIL 29760.001024142oo3|TI=1

    Max SIL LevelRRFPFDavg 1oo2System

    Table 10c shows how the 2oo3 SIFwould change for TI = 3, 5 &10 years.

    Comparison between System Architectures

  • 7/27/2019 Determing SIL Level

    54/86

    Redundant Architecture IncreaseSIL level

    2oo3 Architecture is primarilyjustified due to the MTBFs highvalue

    This means that production willalmost never not be interrupted byspurious/nuisance trips

    1oo2 Architecture is simpler, costeffective and with a slightly betterRRF.

    But the MTBFs is very poor

    Choice is also to be madeconsidering possible T-proof time

    SIF

    Architecture

    MTBFS

    (yr)PFDavg RRF

    Max.

    SIL Level

    1oo1 170.01176

    585 SIL 1

    1oo2 8.50.00073

    51360 SIL 3

    2oo3 555460.00102

    4976 SIL 2

    Table 13, Comparison between systemarchitectures

    Comparison between System Architectures

    Comparison tables for PFDavg values

  • 7/27/2019 Determing SIL Level

    55/86

    in different system architectures

    Architecture du/yr PFDavg RRFPossible

    SIL level

    1oo1 0.01 0.005900000 169 SIL 2

    1oo2 0.01 0.000042350 23613 SIL 4

    2oo2 0.01 0.010900000 92 SIL 1

    2oo3 0.01 0.000127049 7871 SIL 3

    Architecture du/yr PFDavg RRFPossible

    SIL level

    1oo1 0.01 0.015300000 65 SIL 1

    1oo2 0.01 0.000309005 3236 SIL 3

    2oo2 0.01 0.030300000 33 SIL 1

    2oo3 0.01 0.000927016 1079 SIL 3

    Architecture du/yr PFDavg RRFPossible

    SIL level

    1oo1 0.01 0.025180 39 SIL 1

    1oo2 0.01 0.000842 1187 SIL 3

    2oo2 0.01 0.050180 20 SIL 1

    2oo3 0.01 0.002527 396 SIL 2

    Architecture du/yr PFDavg RRFPossible

    SIL level

    1oo1 0.01 0.050090 20 SIL 1

    1oo2 0.01 0.003342 299 SIL 2

    2oo2 0.01 0.100090 10 SIL 0

    2oo3 0.01 0.010027 99 SIL 1

    Table 14, TI = 1 yr, TD = 0.0009 yr(8 hrs)

    Table 15, TI = 3 yr, TD = 0.0009 yr(8 hrs)

    Table 16, TI = 5 yr, TD = 0.0009 yr(8 hrs)

    Table 17, TI = 10 yr, TD = 0.0009 yr(8 hrs)

    4th SIF Example

  • 7/27/2019 Determing SIL Level

    56/86

    4 SIF Example

    Calculate SIL Level for a SIF with two Emergency StopSwitches and a Safety Relay

    Object:Calculate, and select components for a SIL 3 SIF with:

    Two Emergency Stop Switches with 2 NC contacts.

    Using = 5% for the two redundant NC contacts of the Switch. In conjunction with a SIL 3 Safety Relay. With a T-proof time of 10 yrs & NE load conditions, (de-energize to trip).

    24 Vdc. supply voltage.

    4th SIF Example

  • 7/27/2019 Determing SIL Level

    57/86

    4 SIF Example

    Standards Considerations

    An electromechanical component, like a Emergency Stop Switch, is usually

    not classified, or certified, according IEC 61508 Standards.More typically: IEC 60300-3-5 and IEC 61649.According to these standards to determine d (probability of dangerousfailures per hours) it is necessary to use the B10 value.B10 is the average time, or number of cycles, required to fail 10% of the

    components under test. A typical value could be 500.000 cycles

    The formula to be used is:

    d = 0.1 x fm / B10

    Where fm is the frequency of use, for the specific application, per hours.

    In case of an Emergency Stop Switch we estimate 10 times per year;

    Hence, 10 time in 10.000 hours equal to 0.001.

    4th SIF Example

  • 7/27/2019 Determing SIL Level

    58/86

    4 SIF Example

    Calculation ofd: d = 0.1 x fm / B10

    d = 0.0001 / 500000 = 0.0000000002 per hr = 0.000002 per yr

    d for 10 years is = 0.00002

    PFDavg for 10 years is 0.00001 for a single contact.

    (PFDavg = d/2)

    Using two contacts connected in series, with factor of 5%

    PFDavg for 10 years is 0.00001 x 0.05 = 0.0000005

    (Simplified factor formula PFDavg x )

    4th SIF Example

  • 7/27/2019 Determing SIL Level

    59/86

    4 SIF Example

    Basic calculation Formula:

    PFDavg = 0.5 du per year

    [PFDavg]10 = 5 du per 10 yrsRRF = 1/ PFDavg.

    [PFDavg]10 1oo2 / factor 5% +/- = [PFDavg]10 x 0.05

    SIL 383330.000120.000260.000026Total SIF

    SIL 333.3330.000030.000060.000006PSD12101 + 1 spare module

    SIL 314.2850.000070.000160.000016D1092S SIL 3 relay

    SIL 3100.0000.000010.000020.000002Safety SW2

    SIL 3100.0000.000010.000020.000002Safety SW1

    SIL levelper 10 yrs

    RRFPFDavgper 10 yrs

    [du ]per 10 yrs

    duper yr

    Components

    4th SIF Example

  • 7/27/2019 Determing SIL Level

    60/86

    p

    We have made the following consideration for the calculation:

    B10 Value 500.000 Cycles.

    NC, Heavy duty, Gold plated and Sealed contacts. 50 mA constant current provided by SIL relay; To keep contacts clean.

    SIL relay value from TUV certification.

    Beta Factor 5 %

    Life Time 10 Years

    PFDavg: Equations and examples

  • 7/27/2019 Determing SIL Level

    61/86

    g q p

    For each component of the SIF, when the effectiveness of periodic proof test to reveal dangerous failures, is100%, the PFDavg simplified equation, is:

    when the effectiveness is not 100%, the PFDavg simplified equation is:

    where:Et: periodic testing effectiveness to reveal dangerous failures (e.g. 90%)

    SL: system, or component, test proof interval with 99-100% effectiveness, or between two completereplacement of the device, or the lifetime of the system, or device, if it will never fully tested orreplaced.

    for TI = 1 yr and SL = 12 years, the PFDavg simplified equation is:

    DU

    TIPFDavg =

    2

    DU DU

    TI SLPFDavg = (Et ) + (1- Et)

    2 2

    DUDUTI=1,SL=12

    12PFDavg =(Et )+ (1-Et)

    2 2

    PFDavg: Equations and examples

  • 7/27/2019 Determing SIL Level

    62/86

    DUDUTI=1,SL=12

    12PFDavg = (Et ) + (1- Et)

    2 2

    Example a:

    du = 0,01 / yrTI = 1 yrEt = 90% = 0,9SL = 12 yr

    At installation:

    PFDavg = 0,01 / 2 = 0,005RRF = 1 / PFDavg = 1 / 0,005 = 200

    After one year:PFDavg = (0,9 x 0,01 / 2) + (0,1 x 0,01 x 6 ) = 0,0105RRF = 1 / PFDavg = 1 / 0,0105 = 95

    Note: after one year (or after each periodic test) SIL 2 level has become SIL 1.

    PFDavg: Equations and examples

  • 7/27/2019 Determing SIL Level

    63/86

    g q p

    DUDUTI=1,SL=12

    12PFDavg =(Et )+ (1-Et)

    2 2

    Example b:

    du = 0,01 / yrTI = 1 yr

    Et = 99% = 0,99SL = 12 yrs

    After one year:

    PFDavg = (0,99 x 0,01 / 2) + (0,01 x 0,01 x 6) = 0,0056

    RRF = 1 / PFDavg = 1 / 0,006 = 178Note: after one year (or after each periodic test interval)

    SIL2 level is still maintained.

    PFDavg: Equations and examples

  • 7/27/2019 Determing SIL Level

    64/86

    DUDUTI=1,SL=12

    12PFDavg =(Et )+ (1-Et)

    2 2

    Example c:

    du = 0,01 / yrTI = 1 yr

    Et = 50% = 0,5SL = 12 yrs

    After one year:

    PFDavg = (0,5 x 0,01 / 2) + (0,5 x 0,01 x 6) = 0,0325

    RRF = 1 / PFDavg = 1 / 0,006 = 30Note: after one year (or after each periodic test interval)

    SIL2 become SIL 1

    PFDavg: Equations and examples

  • 7/27/2019 Determing SIL Level

    65/86

    DUDUTI=1,SL=12

    12PFDavg =(Et )+ (1-Et)

    2 2

    Example c:

    du = 0,01 / yrTI = 1 yr

    Et = 50% = 0,5SL = 3 yrs

    After one year:

    PFDavg = (0,5 x 0,01 / 2) + (0,5 x 0,01 x 1,5) = 0,01

    RRF = 1 / PFDavg = 1 / 0,006 = 100Note: after one year (or after each periodic test interval)

    SIL2 remain at its minimum level

    Test interval duration influence on PFDavg

  • 7/27/2019 Determing SIL Level

    66/86

    To test a safety system online (e.g. while theprocess is still running), a portion of the safetysystem must be placed in bypass in order toprevent nuisance trips. The length of the manualproof test duration can have a significant impact

    on the overall performance of a safety system.

    During the test, a simplex 1oo1 system must betaken offline. Its availability during the test istherefore zero. Redundant systems , however,

    do not have to be completely placed in bypassfor testing. One leg, or slice, or a dual redundantsystem can be place in bypass at a time.

    Indeed a dual system is reduced to simplex

    during a test, and a triplicate system is reducedto dual.

    DU

    TIPFDavg =

    2

    DU

    TI TDPFDavg = +

    2 TI

    Test interval duration influence on PFDavg

  • 7/27/2019 Determing SIL Level

    67/86

    Example c:

    du = 0,002 / yrTI = 1 yrTD = 8 hrs (time interval)PFDavg = 0,001 + 0,0009 = 0,0019;RRF = 1/ 0,0019 = 526(useful forSIL 2 level)

    Example d:

    du = 0,002 / yrTI = 1 yrTD = 96 hrsPFDavg = 0,001 + 0,01 = 0,011;RRF = 1/ 0,011 = 90(useful forSIL 1 level)

    Note:

    The combination of both, effectiveness and test duration, brings to thefollowing PFDavg equation for a 1oo1 architecture.

    DU

    TIPFDavg =

    2

    DUDUTI=1,SL=12

    12PFDavg = (Et ) + (1- Et)

    2 2

    DU DU

    TD SLPFDavg = (Et ) + + (1- Et) 2 TI 2

    DU

    TI TDPFDavg = +

    2 TI

    True or False?

  • 7/27/2019 Determing SIL Level

    68/86

    SIL rating does not change in time.

    FALSE!

    SIL integrity levels depend on the probability of failurewhich increases with time.

    True or False?

  • 7/27/2019 Determing SIL Level

    69/86

    Safety Manual must be provided

    by the component manufacturer.

    TRUE!Safety Manual is an integral document to the SIL

    rating of any component. It defines the assumption

    behind the certification and the conditions of the SILrating as well as provide proper maintenanceinformation.

    True or False?

  • 7/27/2019 Determing SIL Level

    70/86

    Two products both claiming SIL 2 offer

    the same level of safety.

    FALSE!

    1) PFDavg or RRF value of a SIL level ranges in a factor of 10.Example: SIL 2 means from RRF = 100 to 1000.

    2) SIL ratings are time related.Example: SIL 2 rating for 10 yrs differs from SIL 2 for 1 yr.

    True or False?

  • 7/27/2019 Determing SIL Level

    71/86

    Periodic test is required to maintain

    the SIL Level.

    TRUE!

    Since some failures are undetected in operating conditions(dangerous undetected failures) Tests are required to

    restore the SIF in as-new condition (effectiveness 100%)

    Periodic Tests are essential for maintaining the SIL level.

    True or False?

  • 7/27/2019 Determing SIL Level

    72/86

    T-Proof Time Interval are specified by

    the Plant Maintenance Personnel.

    FALSE!

    It is specified in the Hardware Specification and is decided bythe manufacture and verified by the certification agency.

    True or False?

  • 7/27/2019 Determing SIL Level

    73/86

    Component Type (A & B) are definedby the customer (User)..

    FALSE!

    The component class is defined by the Manufacturer.

    True or False?

  • 7/27/2019 Determing SIL Level

    74/86

    Shorter T-proof time intervalsimprove SIL ratings.

    TRUE!

    Reducing time intervals between T-proof tests decreases theprobability of failure (PFDavg) in time.

    Example: SIL 1 for 1 yr may become SIL 2 for 3 months.

    True or False?

  • 7/27/2019 Determing SIL Level

    75/86

    PFDavg value of the SIF is thehighest of all components PFDavg

    FALSE!

    The PFDavg value of the safety function (SIF) is the sum ofPFDavg values of all its components (subsystems).

    True or False?

  • 7/27/2019 Determing SIL Level

    76/86

    SFF % and PFD both must matchthe SIF SIL Requirement .

    TRUE!The SFF value of each of the SIF component mustbe within the table A or B requirement to claim a

    given SIL level.

    The SIF total PFD must also match that of therequired RRF

    True or False?

  • 7/27/2019 Determing SIL Level

    77/86

    It is possible to make software

    changes without an ImpactAnalysis

    FALSE!

    Safety Impact Analysis must be performed for anyhardware or software change in the plant!

    True or False?

  • 7/27/2019 Determing SIL Level

    78/86

    SIL 3 equipment can be usefulin SIL 2 functions.

    TRUE!

    Using a higher SIL level than necessary allows to reducefrequency of T-proof tests and has a lower incidence on the

    total PFDavg of the SIF.

    Example: SIL 3 for 1 yr could become SIL 2 for 10 yrs.

    True or False?

  • 7/27/2019 Determing SIL Level

    79/86

    Maintenance must be considered inthe design phase.

    TRUE!

    A safety function under maintenance is unavailable thereforethe length of the repair time must be considered.

    The improvement obtained applying redundant architecturesis temporarily lost.

    True or False?

  • 7/27/2019 Determing SIL Level

    80/86

    All failures have thesame effect on safety.

    FALSE!

    Failures can be SAFE or DANGEROUS.The first lead to a spurious trip which does not harm, but

    induces a stopping of production.

    The second instead will render the safety functionunavailable.

    True or False?

  • 7/27/2019 Determing SIL Level

    81/86

    MTBF includes time for repair.

    TRUE!

    MTBF = MTTF + MTTR.For most applications, MTTR is negligible therefore

    MTBF MTTF.However in high demand applications,

    even a few hours of unavailability are criticaland should be taken into account.

    True or False?

  • 7/27/2019 Determing SIL Level

    82/86

    All redundant system architecturesimprove safety.

    FALSE!

    Redundant Architectures have different effectson SAFE and DANGEROUS failure rates.

    Example: 1oo2 improves dangerous failure ratesbut worsens safe failure rates. 2oo2 is the opposite

    True or False?

  • 7/27/2019 Determing SIL Level

    83/86

    Safety Manual Provides for T-Prooftest procedure but not the test

    effectiveness percentage.

    FALSE!

    Test Effectiveness (TE) must be specified along with the

    T-proof procedure and must be used in calculating recurringSIL level

    True or False?

  • 7/27/2019 Determing SIL Level

    84/86

    SIL level and relating RRF aredefined by HSE (Health Safety Executive)

    TRUE!

    A team composed of Management, Plant, Process,Instrument, Maintenance, Quality Engineers is responsible

    for determining RRF factor for each SIF

    True or False?

  • 7/27/2019 Determing SIL Level

    85/86

    HSE Engineers have theresponsibility to maintain the SIL

    level during plant life time

    FALSE!

    Maintenance Engineer are responsible to maintain the SIl

    level as mandated by initial calculations.For SIL 2 SIFs their work must be reviewed by a separate

    department. For SIL 3 or 4 SIFs by an external agency.

  • 7/27/2019 Determing SIL Level

    86/86

    G.M. International S.r.l

    Via San Fiorano, 70

    20058 Villasanta (Milano)

    ITALY

    www.gmintsrl.com

    [email protected]