determining wind and snow loads for solar panels
DESCRIPTION
determining wind and snow loads for solar panelsTRANSCRIPT
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
DETERMINING WIND AND SNOWLOADS FOR SOLAR PANELS
Americas Authority on Solar
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
The purpose of this paper is to discuss the mechanical
design of photovoltaic systems for wind and snow
loads in the United States, and provide guidance
using The American Society of Civil Engineers (ASCE)
Minimum Design Loads for Buildings and Other
Structures, ASCE 7-05 and ASCE 7-10 as appropriate.
With the introduction of the ASCE 7-10, there are two
potential design principles used for calculating wind
and snow loads for PV systems in the U.S. until all state
building codes have transitioned to ASCE 7-10. This
paper will show how to calculate for wind and snow
loads using both design principles.
SolarWorld modules have been tested according
to UL and IEC standards and the maximum design
loads for various mounting methods are provided
in the Sunmodule User Instruction guide. Once we
have gone through the sample calculations and
have the applicable wind and snow loads, we will
compare them to SolarWorlds higher mechanical
load capacities to ensure that the Sunmodule sola
modules are in compliance.
As one of the largest and most established vertically integrated photovoltaic
(PV) manufacturers on the planet, SolarWorld is intimately involved with everystep of the solar PV value chain from raw silicon to installed systems to end of
life recycling. This complete knowledge base combined with our extensive
history provide the critical insight required to lead the solar industry on
technical topics.
INTRODUCTION
Determining wind and snow loads for solar panels
The design methodology in this document has been third party reviewed. Please see certied letter at the end of this document for more details.
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
U.S. model building codes have used ASCE 7-05 as thebasis for several years, which largely follows the design
principles of Allowable Stress Design. Recently ASCE
7-10 was published and has become the basis for the
2012 series of the International Codes (I-Codes). ASCE
7-10 represents a shift in design principles toward Load
Resistance Factor Design. A few states have already
adopted the 2012 International Building Code 2012
(IBC) that includes references to ASCE 7-10 and, for trst time, specically mentions PV systems. There are
several key differences between these two versions
of ASCE 7 standards. This paper provides sample
calculations following both ASCE 7 standards that ar
reected in the 2012 IBC and earlier versions.
Figure 1. A typical rooftop solar installation.
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
IBC 2012 (ASCE 7-10) Code References
1509.7.1Wind resistance. Rooftop mounted pho-tovoltaic systems shall be designed for wind loads
for component and cladding in accordance with
Chapter 16 using an effective wind area based on
the dimensions of a single unit frame.
1603.1.4 Wind Design data.The following information
related to wind loads shall be shown, regardless of
whether wind loads govern the design of the lateral
force resisting system of the structure:
1) Ultimate design wind speed, V
2) Risk category
3) Wind Exposure
4) Internal pressure coefcient
5) Component and cladding
1608.1Design snow loads shall be determined
in accordance with Chapter 7 of ASCE 7, but
the design roof load shall not be less than that
determined by section 1607.
1609.1.1Determination of wind loads. Wind loads
on every building or structure shall be determined
in accordance with Chapter 26 to 36 of ASCE 7 or
provisions of the alternate all-heights method in
section 1606.6.
1609.4.1Wind Directions and Sectors. For each
selected wind direction at which the wind loads
are to be evaluated, the exposure of the building
or structure shall be determined for the two upwind
sectors extending 45 degrees either side of the
selected wind direction. The exposures in these two
sectors shall be determined in accordance with
Section 1609.4.2 and 1609.4.3 and the exposure
resulting in the highest wind loads shall be used to
represent wind from that direction.
IBC 2009 (ASCE 7-05) Code References
1608.1Design snow loads shall be determinedin accordance with Chapter 7 of ASCE 7, but
the design roof load shall not be less than that
determined by Section 1607.
1603.1.4 Wind Design Data
1) Basic wind
2) Wind importance factor
3) Wind exposure
4) The applicable internal pressure coefcient
5) Components and cladding
1609.1.1Wind loads on every building or structure
shall be determined in accordance with Chapter 6
of ASCE 7.
Table 1609.3.1, which converts from 3-second gust
to fastest-mile wind speeds.
1609.4.1Wind Directions and Sectors
1) Select wind direction for wind loads to be evaluat
2) Two upwind sectors extending 45 degrees from eit
side of the chosen wind direction are the markers.
3) Use Section 1609.4.2 and Section 1609.4.3 to
determine the exposure in those sectors.
4) The exposure with the highest wind loads is cho
for that wind direction.
1609.4.2Surface Roughness Categories
1) Surface roughness B: Urban, suburban, wooded
closely spaced obstructions.
2) Surface roughness C: Open terrain with few
obstructions (generally less than 30 feet), at op
country, grasslands, water surfaces in hurricane
prone regions.
3) Surface roughness D: Flat areas and water surfa
outside of hurricane prone regions, smooth mud
ats, salt ats, unbroken ice.
Below are the portions of the code that will be referenced in the sample calculations:
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
In this paper, examples explain step-by-step
procedures for calculating wind and snow loads
on PV systems with the following qualications in
accordance with ASCE.
The recommended chapter references for ASCE 7-05 are:
Chapter 2 Load Combinations
Chapter 6 Wind Load Calculations
Chapter 7 Snow Load Calculations
In ASCE 7 -10, the chapters have been re-organized
and provide more detailed guidance on certain
topics. The recommended chapter references are:
Chapter 2 Load Combinations
Chapter 7 Snow Load Calculations
Chapters 26 31 Wind Load Calculations
Example calculations:
In the following examples, we outline how a designer
should calculate the effect of wind and snow loads
on a PV module for residential and commercial
buildings based on few assumptions and using the
Low-Rise Building Simplied Procedure.
ASCE 7-05: Section 6.4
ASCE 7-10: Section 30.5
In the Simplied Method the system must have the
following qualications (see ASCE 7.05 section 6.4.1.2
or ASCE 7-10 section 30.5.1 for further explanation):
The modules shall be parallel to surface of the roof
with no more than 10 inches of space between
the roof surface and bottom of the PV module.
The building height must be less than 60 feet.
The building must be enclosed, not open or
partially enclosed structure like carport.
The building is regular shaped with no unusual
geometrical irregularity in spatial form, for
example a geodesic dome.
The building is not in an extreme geographic
location such as a narrow canyon a steep cliff.
The building has a at or gable roof with a pitch
less than 45 degrees or a hip roof with a pitch le
than 27 degrees.
In case of designing more complicated projects th
following sections are recommended:
ASCE 7-05: Section 6.5.13.2
ASCE 7-10: Section 30.8
Example 1 - Residential Structure in Colorado:
System Details:
Location: Colorado
Terrain: Urban, suburban, wooded, closely spac
obstructions
Exposure: Class B
Building Type: Single-story residential (10- to 15-feet t
Mean height of roof: ~12.33 feet
Building Shape: Gable roof with 30 pitch (7:12)
System: Two Rail System; attached module at fo
points along the long side between 1/8 to 1/4
points as described in the SolarWorld Sunmodul
User Instruction guide
Module area: 18.05 ft (Reference: Sunmodule
datasheet)
Module weight: 46.7 lbs (Reference: Sunmodule
datasheet)
Site ground snow load (Pg): 20 psf
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
SYMBOLS AND NOTATIONS
Wind
I = Importance factor
Kzt= Topographic factor
P = Design pressure to be used in determination of
wind loads for buildings
Pnet30
= Net design wind pressure for exposure B at
h = 30 feet and I = 1.0
V = Basic wind speed
= Adjustment factor for building height and
exposure
Zone 1 = Interiors of the roof (Middle)
Zone 2 = Ends of the roof (Edge)
Zone 3 = Corners of the roof
Snow
Ce= Exposure factor
Cs= Slope factor
Ct= Thermal factor
I = Importance factor
Pf= Snow load on at roof
Pg= Ground snow load
Ps= Sloped roof snow load
Load Combination
D* = Dead load
E = Earthquake load
F = Load due to uids with well-dened pressure
and maximum heights
H = Load due to lateral earth pressure, groundwater pressure or pressure of bulk materials
L = Live load
Lr= Roof live load
R = Rain load
S* = Snow load
T = Self-straining load
W* = Wind load
* In this white paper we only use dead, snow and wind loads.
Gable RoofHip Roof
Interior Zones
Roofs - Zone 1
Interior Zones
Roofs - Zone 2
Interior Zones
Roofs - Zone 3
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012)
Steps in wind design:
1. Determine risk category from Table 1.5-1
Risk category type II
2. Determine the basic wind speed, V, for applicable
risk category (see Figure 26.5-1 A, B, C)
Wind speed in Colorado is V = 115 mph
(excluding special wind regions)
3. Determine wind load parameters:
Exposure category B, C or D from Section 26.7
Exposure B
Topographic factor, Kzt, from Section 26.8 and
Figure 26.8-1
Kzt= 1.0
4. Determine wind pressure at h = 30 ft, Pnet30
, from
gure 30.5-1
5. Determine adjustment for building height and
exposure, , from Figure 30.5-1
Adjustment factor for Exposure B is = 1.00
6. Determine adjusted wind pressure, Pnet
, from
Equation 30.5-1
Pnet
= Kzt
Pnet30
Wind effective area is the pressure area on themodule that is distributed between four mounting
clamps. Each mid-clamp takes one-quarter of the
pressure and holds two modules which are equal to
one-half area of one module.
Area of module is 18.05 square feet.
Effective area is ~10 square feet.
Pnet
for wind speed of 115 mph and the wind
effective area of 10 ft2:
ASCE 7-05 (IBC 2009)
Steps in wind design:
1. Determine risk category from Table 1.5-1
Risk category type II
2. Determine the basic wind speed, V, for
applicable risk category (see Figure 6-1 A, B, C)
Wind speed in Colorado is V = 90 mph
(excluding special wind regions)
3. Determine wind load parameters:
Exposure category B, C or D from Section 6.5.
Exposure B
Topographic factor, Kzt, from Section 6.5.7.2
Kzt= 1.0
4. Determine wind pressure at h = 30 ft, Pnet30
, from
Figure 6.3
5. Determine adjustment for building height and
exposure, , from Figure 6.3
Adjustment factor for Exposure B is = 1.00
6. Determine adjusted wind pressure, Pnet
, from
Equation 6-1
Pnet
= Kzt
Pnet30
Wind effective area is the pressure area on themodule that is distributed between four mounting
clamps. Each mid-clamp takes one-quarter of the
pressure and holds two modules which are equal t
one-half area of one module.
Area of module is 18.05 square feet.
Effective area is ~10 square feet.
Pnet
for wind speed of 90 mph and the wind effecti
area of 10 ft2
:
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012) (Cont'd)
Zone 1
Downward: +21.8 psf
Upward: -23.8 psf
Pnet
= Kzt
Pnet30
PDown
= 1 * 1 * 21.8 = 21.8 psf
Pup
= 1 * 1 * -23.8 = -23.8 psf
Zone 2
Downward: +21.8 psf
Upward: -27.8 psf
Pnet
= Kzt
Pnet30
PDown
= 1 * 1 * 21.8 = 21.8 psf
Pup
= 1 * 1 * -27.8 = -27.8 psf
Zone 3
Downward: +21.8 psf
Upward: -27.8 psf
Pnet
= Kzt
Pnet30
PDown
= 1 * 1 * 21.8 = 21.8 psf
Pup
= 1 * 1 * -27.8 = -27.8 psf
Steps in snow design:
1. For sloped roof snow loads Ps= C
sx P
f
2. Pfis calculated using Equation 7.3-1
Pf= 0.7 x C
ex C
tx I
sx P
g
3. When ground snow load is less than or equal to
20 psf then the minimum Pfvalue is I * 20 psf. (7.3.4)
4. Find exposure factor from Table 7-2, in category B
and fully exposed roof
Ce= 0.9
ASCE 7-05 (IBC 2009) (Cont'd)
Zone 1
Downward: +13.3 psf
Upward: -14.6 psf
Pnet
= Kzt
Pnet30
PDown
= 1 * 1 * 13.3 = 13.3 psf
Pup
= 1 * 1 * -14.6 = -14.6 psf
Zone 2
Downward: +13.3 psf
Upward: -17psf
Pnet
= Kzt
Pnet30
PDown
= 1 * 1 * 13.3 = 13.3 psf
Pup
= 1 * 1 * -17 = -17 psf
Zone 3
Downward: +13.3 psf
Upward: -17psf
Pnet
= Kzt
Pnet30
PDown= 1 * 1 * 13.3 = 13.3 psf
Pup
= 1 * 1 * -17 = -17 psf
Steps in snow design:
1. For sloped roof snow loads Ps= C
sx P
f
2. Pfis calculated using Equation 7.3-1
Pf= 0.7 x C
ex C
tx I
sx P
g
3. When ground snow load is less than or equal to
20 psf then the minimum Pfvalue is I * 20 psf. (7.3.4
4. Find exposure factor from Table 7-2, in categor
and fully exposed roof
Ce= 0.9
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012) (Cont'd)
5. Determine thermal factor using Table 7-3, for
unheated and open air structures
Ct= 1.2
6. Find the importance factory from Table 1.5-2
Is= 1.00 (7-10)
7. Using Section 7.4 determine Cs. Using above
values and = 30
Cs= 0.73
Pf
= 0.7 x Ce
x Ct
x Is
x Pg
Pg 20 lbs
Pgis the ground snow load and cannot be used
instead of the nal snow load Pffor the sloped roof
in our load combinations' equations. We need to
calculate the sloped roof snow load as follows:
Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20
Ps= C
sx P
f
Ps
= 0.73 * 20 = 14.6 psf
Load Combinations: (LRFD)
Basic combinations Section 2.3.2, according to ASCE
7-10 structures, components and foundations shall
be designed so that their design strength equals
or exceeds the effects of the factored loads in the
following combinations:
1) 1.4D
2) 1.2D+ 1.6L+ 0.5 (Lror S or R)
3) 1.2D+ 1.6 (Lror S or R) + (L or 0.5W)
4) 1.2D+ 1.0W+ L+ 0.5 (LRor S or R)
5) 1.2D+ 1.0E+ L+ 0.2S
6) 0.9D+ 1.0W
7) 0.9D+ 1.0E
ASCE 7-05 (IBC 2009) (Cont'd)
5. Determine thermal factor using Table 7-3, for
unheated and open air structures
Ct= 1.2
6. Find the importance factory from Table 7-4
Is= 1.0 (7-05)
7. Using Section 7.4 determine Cs. Using above
values and = 30
Cs= 0.73
Pf
= 0.7 x Ce
x Ct
x Is
x Pg
Pg 20 lbs
Pgis the ground snow load and cannot be used
instead of the nal snow load Pffor the sloped roo
in our load combinations equations. We need to
calculate the sloped roof snow load as follows:
Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20
Ps= C
sx P
f
Ps
= 0.73 * 20 = 14.6 psf
Load Combinations: (ASD)
Basic combinations Section 2.3, according to ASC
7-05 loads listed herein shall be considered to act i
the following combinations; whichever produces t
most unfavorable effect in the building, foundatio
or structural member being considered. Effects of
one or more loads on acting shall be considered.
1) D + F
2) D + H + F + L + T
3) D + H + F + (Lror S or R)
4) D + H + F + 0.75 (L + T) + 0.75 (Lror S or R)
5) D + H + F + (W or 0.7 E)
6) D + H + F + 0.75 (W or 0.7 E) + .75L + .75 ( Lror S or
7) 0.6D + W + H
8) 0.6D + 0.7E + H
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012) (Cont'd)
The highest values for upward and downward
pressures will govern the design.
Load Case 3)
1.2 * 2.59 + 1.6 (14.6) + 0.5 (21.8) = 37.4 psf
Load Case 6)
0.9 * 2.59 + 1.0 (-27.8) = -25.7 psf
The next step is to check that the module can
withstand the design loads for this two-rail mounting
conguration. The designer should refer to themodule installation instructions where the design
loads for different mounting congurations are
provided.
When two rails are supporting the module with top-
down clamps, the module design capacity is:
Downward: +113 psf
Upward: -64 psf
These values are well above the governing design
loads of:
Downward: +37.4 psf
Upward: -25.7 psf
To distribute the combined loads on the module
that are transferring to the rails, please refer to the
Mounting User Instruction guide and ASCE 7-10
section 30.4.
ASCE 7-05 (IBC 2009) (Cont'd)
The highest values for upward and downward
pressures will govern the design.
Load Case 6)
2.59 + 0.75 (14.6) + 0.75 (13.3) = 23.5 psf
Load Case 7)
0.6 (2.59) + 1.0 (-17.0) = -15.45 psf
The next step is to check that the module can
withstand the design loads for this two-rail mountin
conguration. The designer should refer to themodule installation instructions where the design
loads for different mounting congurations are
provided.
When two rails are supporting the module with top
down clamps, the module design capacity is:
Downward: +55 psf
Upward: 33 psf
These values are well above the governing design
loads of:
Downward: +23.5 psf
Upward: -15.45 psf
To distribute the combined loads on the module
that are transferring to the rails, please refer to the
Mounting User Instruction guide and ASCE 7-05
section 6.5.12.2.
Fmin, max Fmin, max
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
Example calculations
In the following example we outline how a designer
should calculate the effect of wind and snow on a
PV module for commercial buildings based on fewassumptions and using Main Wind-force Resisting
Systems design.
ASCE 7-05: Section 6.5.12.4.1
ASCE 7-10: Section 30.4
Example 2- Commercial Structure in Colorado:
Location: Colorado
Terrain: Urban, suburban, wooded, closely
spaced obstructions
Exposure: Class B
Building Type: Two-story Commercial (25 fee
tall)
Mean height of roof: ~25.33 feet Building Shape: Gable roof with 5 pitch (1:
System: Two Rail System; attached module
four points along the long side between 1/8
to 1/4 points as described in the SolarWorld
Sunmodule User Instruction guide
Module area: 18.05 ft. (Reference: Sunmod
Datasheet)
Module weight: 46.7 lbs (Reference:
Sunmodule Datasheet) Site ground snow load (P
g): 20 psf
SYMBOLS AND NOTATIONS
Wind
Cn= New pressure coefcient to be used in
determination of wind loads
G = Gust effect factor
I = Importance factor
Kd= Wind directionality factor
Kz = Velocity pressure exposure coefcient
evaluated at height z
Kzt= Topographic factor
P = Design pressure to be used in determination of
wind loads for buildings
qh = Velocity pressure evaluated at height z = h = Tilt angle of the module
Snow
Ce= Exposure factor
Cs= Slope factor
Ct= Thermal factor
I = Importance factor
Pf= Snow load on at roof
Pg= Ground snow load
Ps= Sloped roof snow load
Load Combination
D* = Dead load
E = Earthquake load
F = Load due to uids with well-dened pressure
and maximum heights
H = Load due to lateral earth pressure, ground
water pressure or pressure of bulk materials
L = Live load
Lr= Roof live load
R = Rain load
S* = Snow load
T = Self-straining load
W* = Wind load
* In this white paper we only use dead, snow and wind loads.
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012)
Steps in wind design:
1. Determine risk category from Table 1.5-1
Risk category type II
2. Determine the basic wind speed, V, for applicable
risk category (see Figure 26.5-1 A, B, C)
Wind speed in Colorado is V = 115 mph
(excluding special wind regions)
3. Determine wind load parameters:
Wind Directionality factor, Kd, see Section 26.6
Main wind-force resisting system
components and cladding, Kd= 0.85
Exposure category B, C or D from Section 26.7
Exposure B
Topographic factor, Kzt, from Section 26.8 and
Figure 26.8-1
Kzt= 1.0
4. Determine velocity pressure exposure coefcient,
Kzof K
h, see Table 30.3-1
For exposure B and height of 25 ft, Kz= 0.7
5. Determine velocity pressure, qh, Eq. 30.3-1
qh= 0.00256x K
zx K
ztx K
dx V2
6. Determine net pressure coefcient, GCp
See Fig. 30.4-2A
Downward: GCp= 0.3
Upward: GCp= -1.0 (zone 1)
-1.8 (zone 2)
-2.8 (zone 3)
ASCE 7-05 (IBC 2009)
Steps in wind design:
1. Determine risk category from Table 1.5-1
Risk category type II
2. Determine the basic wind speed, V, for applica
risk category (see Figure 6.1 A, B, C)
Wind speed in Colorado is V = 90 mph
(excluding special wind regions)
3. Determine wind load parameters:
Wind Directionality factor, Kd, see Section 6.5.
Main wind-force resisting system
components and cladding, Kd= 0.85
Exposure category B, C or D from Section 6.5.
Exposure B
Topographic factor, Kzt, from Section 6.5.7.2
Kzt= 1.0
4. Determine velocity pressure exposure coefcie
Kzof K
h, see Table 6-3
For exposure B and height of 25 ft, Kz= 0.
5. Determine velocity pressure, qh, Eq. 6-15
qh= 0.00256x K
zx K
ztx K
dx V2x 1
6. Determine net pressure coefcient, GCp
See Fig. 6-11B
Downward: GCp= 0.3
Upward: GCp= -1.0 (zone 1)
-1.8 (zone 2)
-2.8 (zone 3)
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels
ASCE 7-10 (IBC 2012) (Cont'd)
7. Calculate wind pressure, p, Eq. 30.8-1
p = qhGCp
qh= 0.00256xk
zx k
ztx k
dx V2
qh= 0.00256 * 0.7 * 1 * 0.85 * 1152 = 20.14 psf
pdown
= 20.14 * 0.3 = 6.04 psf
pup
= 20.14 * (-2.8) = 56 psf
Steps in Snow design:
1. For sloped roof snow loads Ps= C
sx P
f
2. Pfis calculated using Equation 7.3-1
Pf= 0.7x C
ex C
tx I
sx P
g
3. When ground snow load is less than or equal 20
psf then the minimum Pfvalue is I * 20 psf (7.3.4)
4. Find exposure factor from Table 7-2, in category B
and fully exposed roof
Ce= 0.9
5. Determine Thermal factor using Table 7-3, for
unheated and open air structures
Ct= 1.2
6. Find the importance factory from Table 1.5-2
Is= 1.00 (7-10)
7. Using Section 7.4 determine Cs. Using above
values and = 5
Cs=1.0
Pf= 0.7 x C
ex C
tx I
sx P
g
ASCE 7-05 (IBC 2009)(Cont'd)
7. Calculate wind pressure, p, Eq. 6-26
p = qhGCp
qh= 0.00256 x k
zx k
ztx k
dx V2
qh= 0.00256 * 0.7 * 1 * 0.85 *902= 12.34 psf
pd= 12.34 * 0.3 = 3.7 psf psf
pu= 12.34 * (-2.8) = 34.6 psf
Steps in Snow design:
1. For sloped roof snow loads Ps= C
sx P
f
2. Pfis calculated using Equation 7.3-1
Pf= 0.7 x Cex C
tx I
sx P
g
3. When ground snow load is less than or equal 20
psf then the minimum Pfvalue is I * 20 psf (7.3.4)
4. Find exposure factor from Table 7-2, in categor
and fully exposed roof
Ce= 0.9
5. Determine Thermal factor using Table 7-3, for
unheated and open air structures
Ct= 1.2
6. Find the importance factory from Table 7-4
Is= 1.0 (7-05)
7. Using section 7.4 determine Cs. Using above
values and = 5
Cs=1.0
Pf= 0.7 C
e C
t I
s P
g
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels |
ASCE 7-10 (IBC 2012) (Cont'd)
Pg 20 lbs
Pgis the ground snow load and cannot be usedinstead of the nal snow load for the sloped roof
in our load combinations equations. We need to
calculate the sloped roof snow load as follows:
Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20
Ps= C
sx P
f
To nd out the effect of snow load perpendicular to the
plane of module we multiply the Ps
value by COS ().
Ps= 1 * 20 * COS (5) = 19.9 psf
Load combinations: (LRFD)
Basic combinations section 2.3.2, according to ASCE
7-10 structures, components and foundations shall
be designed so that their design strength equals or
exceeds the effects of the factored loads in following
combinations:
1) 1.4D
2) 1.2D + 1.6L + 0.5 (Lror S or R)
3) 1.2D + 1.6 (Lror S or R) + (Lor 0.5W)
4) 1.2D + 1.0W+ L+ 0.5 (Lror S or R)
5) 1.2D + 1.0E+ L+ 0.2S
6) 0.9D + 1.0W
7) 0.9D + 1.0E
The highest values for upward and downward
pressures will govern the design.
ASCE 7-05 (IBC 2009)(Cont'd)
Pg 20 lbs
Pgis the ground snow load and cannot be usedinstead of the nal snow load for the sloped roof
in our load combinations equations. We need to
calculate the sloped roof snow load as follows:
Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20
Ps= C
sx P
f
To nd out the effect of snow load perpendicular to
plane of module we multiply the Ps
value by COS ()
Ps= 1 * 20 * COS (5) = 19.9 psf
Load Combinations: (ASD)
Basic combinations section 2.3.2, according to ASC
7-05 loads listed herein shall be considered to act i
the following combinations; whichever produces t
most unfavorable effect in the building, foundatio
or structural member being considered. Effects of
one or more loads on acting shall be considered.
1) D + F
2) D + H + F + L + T
3) D + H + F + (Lr or S or R)
4) D + H + F + 0.75 (L + T) + 0.75 (Lr or S or R)
5) D + H + F + (W or 0.7E)
6) D + H + F + 0.75 (W OR 0.7E) + .75L + .75 (Lr or S or
7) 0.6D + W + H
8) 0.6D + 0.7E + H
The highest values for upward and downward
pressures will govern the design.
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels |
ASCE 7-10 (IBC 2012) (Cont'd)
Load Case 3)
1.2 * 2.59 + 1.6 (19.9) + 0.5 (6.04) = 38 psf
Load Case 6)
0.9 * 2.59 + 1.0 (-56) = -53.7 psf
The next step is to check that the module can
withstand the design loads for this two-rail mounting
conguration. The designer should refer to the
module installation instructions where the design
loads for different mounting congurations are
provided.
For the case of two rails simply supporting the module
with top-down clamps, the module design capacity is:
Downward: +113 psf
Upward: -64 psf
These values are above the governing design loads
of:
Downward: +38 psf
Upward: -53.7 psf
To distribute the combined loads which are
transferring to the rails please refer to the Mounting
User Instruction and ASCE 7-10 section 30.4.
ASCE 7-05 (IBC 2009)(Cont'd)
Load Case 6)
2.59 + 0.75 (19.9) + 0.75 (3.7) = 20.3 psf
Load Case 7)
0.6 (2.59) + 1.0 (-34.6) = -33 psf
The next step is to check that the module can
withstand the design loads for this two-rail mountin
conguration. The designer should refer to the
module installation instructions where the design
loads for different mounting congurations are
provided.
For the case of two rails simply supporting the mod
with top-down clamps, the module design capacity
Downward: +55 psf
Upward: -33 psf
These values are above the governing design load
of:
Downward: +20.3 psf
Upward: -33 psf
To distribute the combined loads which are
transferring to the rails please refer to the Mounting
User Instruction and ASCE 7.05 section 6.5.12.2.
Fmin, maxFmin, max
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
Determining wind and snow loads for solar panels SW-02-5156US-MEC 04-2013 |
As this white paper illustrates, SolarWorld Sunmodules easily meet many high wind and snow load requirements
within the United States and therefore are ideal for installation in most climates. The ability to meet these
requirements is essential when designing solar systems that are expected to perform in various weather
conditions for at least 25 years. As Americas solar leader for over 35 years, SolarWorlds quality standards are
unmatched in the industry. Unlike most other solar manufacturers in the market today, our systems have prov
performance in real world conditions for over 25 years.
References
1. Minimum design loads for buildings and other structures. Reston, VA: American Society of Civil Engineers/
Structural Engineering Institute, 2006. Print.
2. Minimum design loads for buildings and other structures. Reston, Va.: American Society of Civil Engineers :
2010. Print.
3. International building code 2009. Country Club Hills, Ill.: International Code Council, 2009. Print.
4. International building code 2006. New Jersey ed. Country Club Hills, IL: The Council, 2007. Print.
-
5/20/2018 Determining Wind and Snow Loads for Solar Panels
t
etter of
ate:
roject:
PS Job
o:
rom:
t the re
resente
Version
rescribe
ccordan
005 i
ngineer
esign m
ach said
his lette
s discus
he site s
ethodol
re publi
nsure it
lease fe
incerel
atthewngineer
Approv
umber:
uest of
in Solar
7). The
d wind a
ce with e
imum D
s (ASCE
ethodolo
building
r is in ap
sed in th
ecific lo
ogy for
hed. Be
matches
el free to
,
B. Gillised Powe
l Sola
Dec
Sola
12-
Ami
Sola
465Ca
MatEngi
olarWo
Worlds
aper pr
d snow
ither the
sign Lo
7-05), o
gy and e
code.
proval o
referen
ading co
oof mou
cause of
with the
contact
s, P.E.,Solutio
STR
World
mber 3
r Modul
WD003
r Sheikh
rWorld
Adohrarillo, C
hew Gilneered
ld, Engi
White
sents th
loads fo
2009 (a
ds for
the 201
amples
the gen
ed pape
nditions
nted sol
this, EP
most cu
e with
EED As
CTUR
esign L
, 2012
Design
mericas
ane93012
issower So
eered P
aper tit
recom
solar m
d 2006)
uildings
2 IBC
presente
eral desi
. It is th
for each
r system
recom
rent cod
any ques
L LET
ads Me
Loads
(SolarW
utions (
wer Sol
ed:Det
ended d
dules m
Internat
and Oth
hich re
in this
n metho
e respon
project.
s has co
ends pe
require
ions. T
ENM
ER OF
hodolo
ethodol
orld)
PS)
tions (
rmining
sign me
ounted o
onal Bui
r Struct
ferences
aper are
dology
ibility o
Please n
tinually
iodicall
ents an
ank you
INEETTHEWB
879 S
PA
APPRO
y Revie
gy Revi
PS) has
Wind an
hodolog
n and fl
lding Co
resby t
ASCE 7
consiste
or flush
f the pro
ote that t
changed
reviewi
d indust
.
ED PO. GILLISS,
CAMO
O ROB
(805)
VAL
ew
eviewe
Snow
y for det
sh to a r
de (IBC)
e Ameri
10. EP
nt with t
oof mou
ect engi
he indus
over rec
ng the st
y recom
WER S ROFESSI
E CAN
ES, CA
23-132
12/31/1
the desi
oads fo
erminin
oof surfa
- which
can Soci
has fou
he desig
nted sol
eer of r
ry reco
ent years
ated met
endati
OLUT NALENGI
ON R
93446
4
gn meth
Solar P
the cod
ce in
referenc
ety of Ci
d that t
intenti
r modul
cord to
mended
as new
hodolog
ns.
ONSNEER
.
Page 1
dology
anels
es the
vil
e
ns of
es only
ddress
design
studies
to