determining wind and snow loads for solar panels

Upload: pazz0

Post on 10-Oct-2015

82 views

Category:

Documents


10 download

DESCRIPTION

determining wind and snow loads for solar panels

TRANSCRIPT

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    DETERMINING WIND AND SNOWLOADS FOR SOLAR PANELS

    Americas Authority on Solar

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    The purpose of this paper is to discuss the mechanical

    design of photovoltaic systems for wind and snow

    loads in the United States, and provide guidance

    using The American Society of Civil Engineers (ASCE)

    Minimum Design Loads for Buildings and Other

    Structures, ASCE 7-05 and ASCE 7-10 as appropriate.

    With the introduction of the ASCE 7-10, there are two

    potential design principles used for calculating wind

    and snow loads for PV systems in the U.S. until all state

    building codes have transitioned to ASCE 7-10. This

    paper will show how to calculate for wind and snow

    loads using both design principles.

    SolarWorld modules have been tested according

    to UL and IEC standards and the maximum design

    loads for various mounting methods are provided

    in the Sunmodule User Instruction guide. Once we

    have gone through the sample calculations and

    have the applicable wind and snow loads, we will

    compare them to SolarWorlds higher mechanical

    load capacities to ensure that the Sunmodule sola

    modules are in compliance.

    As one of the largest and most established vertically integrated photovoltaic

    (PV) manufacturers on the planet, SolarWorld is intimately involved with everystep of the solar PV value chain from raw silicon to installed systems to end of

    life recycling. This complete knowledge base combined with our extensive

    history provide the critical insight required to lead the solar industry on

    technical topics.

    INTRODUCTION

    Determining wind and snow loads for solar panels

    The design methodology in this document has been third party reviewed. Please see certied letter at the end of this document for more details.

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    U.S. model building codes have used ASCE 7-05 as thebasis for several years, which largely follows the design

    principles of Allowable Stress Design. Recently ASCE

    7-10 was published and has become the basis for the

    2012 series of the International Codes (I-Codes). ASCE

    7-10 represents a shift in design principles toward Load

    Resistance Factor Design. A few states have already

    adopted the 2012 International Building Code 2012

    (IBC) that includes references to ASCE 7-10 and, for trst time, specically mentions PV systems. There are

    several key differences between these two versions

    of ASCE 7 standards. This paper provides sample

    calculations following both ASCE 7 standards that ar

    reected in the 2012 IBC and earlier versions.

    Figure 1. A typical rooftop solar installation.

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    IBC 2012 (ASCE 7-10) Code References

    1509.7.1Wind resistance. Rooftop mounted pho-tovoltaic systems shall be designed for wind loads

    for component and cladding in accordance with

    Chapter 16 using an effective wind area based on

    the dimensions of a single unit frame.

    1603.1.4 Wind Design data.The following information

    related to wind loads shall be shown, regardless of

    whether wind loads govern the design of the lateral

    force resisting system of the structure:

    1) Ultimate design wind speed, V

    2) Risk category

    3) Wind Exposure

    4) Internal pressure coefcient

    5) Component and cladding

    1608.1Design snow loads shall be determined

    in accordance with Chapter 7 of ASCE 7, but

    the design roof load shall not be less than that

    determined by section 1607.

    1609.1.1Determination of wind loads. Wind loads

    on every building or structure shall be determined

    in accordance with Chapter 26 to 36 of ASCE 7 or

    provisions of the alternate all-heights method in

    section 1606.6.

    1609.4.1Wind Directions and Sectors. For each

    selected wind direction at which the wind loads

    are to be evaluated, the exposure of the building

    or structure shall be determined for the two upwind

    sectors extending 45 degrees either side of the

    selected wind direction. The exposures in these two

    sectors shall be determined in accordance with

    Section 1609.4.2 and 1609.4.3 and the exposure

    resulting in the highest wind loads shall be used to

    represent wind from that direction.

    IBC 2009 (ASCE 7-05) Code References

    1608.1Design snow loads shall be determinedin accordance with Chapter 7 of ASCE 7, but

    the design roof load shall not be less than that

    determined by Section 1607.

    1603.1.4 Wind Design Data

    1) Basic wind

    2) Wind importance factor

    3) Wind exposure

    4) The applicable internal pressure coefcient

    5) Components and cladding

    1609.1.1Wind loads on every building or structure

    shall be determined in accordance with Chapter 6

    of ASCE 7.

    Table 1609.3.1, which converts from 3-second gust

    to fastest-mile wind speeds.

    1609.4.1Wind Directions and Sectors

    1) Select wind direction for wind loads to be evaluat

    2) Two upwind sectors extending 45 degrees from eit

    side of the chosen wind direction are the markers.

    3) Use Section 1609.4.2 and Section 1609.4.3 to

    determine the exposure in those sectors.

    4) The exposure with the highest wind loads is cho

    for that wind direction.

    1609.4.2Surface Roughness Categories

    1) Surface roughness B: Urban, suburban, wooded

    closely spaced obstructions.

    2) Surface roughness C: Open terrain with few

    obstructions (generally less than 30 feet), at op

    country, grasslands, water surfaces in hurricane

    prone regions.

    3) Surface roughness D: Flat areas and water surfa

    outside of hurricane prone regions, smooth mud

    ats, salt ats, unbroken ice.

    Below are the portions of the code that will be referenced in the sample calculations:

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    In this paper, examples explain step-by-step

    procedures for calculating wind and snow loads

    on PV systems with the following qualications in

    accordance with ASCE.

    The recommended chapter references for ASCE 7-05 are:

    Chapter 2 Load Combinations

    Chapter 6 Wind Load Calculations

    Chapter 7 Snow Load Calculations

    In ASCE 7 -10, the chapters have been re-organized

    and provide more detailed guidance on certain

    topics. The recommended chapter references are:

    Chapter 2 Load Combinations

    Chapter 7 Snow Load Calculations

    Chapters 26 31 Wind Load Calculations

    Example calculations:

    In the following examples, we outline how a designer

    should calculate the effect of wind and snow loads

    on a PV module for residential and commercial

    buildings based on few assumptions and using the

    Low-Rise Building Simplied Procedure.

    ASCE 7-05: Section 6.4

    ASCE 7-10: Section 30.5

    In the Simplied Method the system must have the

    following qualications (see ASCE 7.05 section 6.4.1.2

    or ASCE 7-10 section 30.5.1 for further explanation):

    The modules shall be parallel to surface of the roof

    with no more than 10 inches of space between

    the roof surface and bottom of the PV module.

    The building height must be less than 60 feet.

    The building must be enclosed, not open or

    partially enclosed structure like carport.

    The building is regular shaped with no unusual

    geometrical irregularity in spatial form, for

    example a geodesic dome.

    The building is not in an extreme geographic

    location such as a narrow canyon a steep cliff.

    The building has a at or gable roof with a pitch

    less than 45 degrees or a hip roof with a pitch le

    than 27 degrees.

    In case of designing more complicated projects th

    following sections are recommended:

    ASCE 7-05: Section 6.5.13.2

    ASCE 7-10: Section 30.8

    Example 1 - Residential Structure in Colorado:

    System Details:

    Location: Colorado

    Terrain: Urban, suburban, wooded, closely spac

    obstructions

    Exposure: Class B

    Building Type: Single-story residential (10- to 15-feet t

    Mean height of roof: ~12.33 feet

    Building Shape: Gable roof with 30 pitch (7:12)

    System: Two Rail System; attached module at fo

    points along the long side between 1/8 to 1/4

    points as described in the SolarWorld Sunmodul

    User Instruction guide

    Module area: 18.05 ft (Reference: Sunmodule

    datasheet)

    Module weight: 46.7 lbs (Reference: Sunmodule

    datasheet)

    Site ground snow load (Pg): 20 psf

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    SYMBOLS AND NOTATIONS

    Wind

    I = Importance factor

    Kzt= Topographic factor

    P = Design pressure to be used in determination of

    wind loads for buildings

    Pnet30

    = Net design wind pressure for exposure B at

    h = 30 feet and I = 1.0

    V = Basic wind speed

    = Adjustment factor for building height and

    exposure

    Zone 1 = Interiors of the roof (Middle)

    Zone 2 = Ends of the roof (Edge)

    Zone 3 = Corners of the roof

    Snow

    Ce= Exposure factor

    Cs= Slope factor

    Ct= Thermal factor

    I = Importance factor

    Pf= Snow load on at roof

    Pg= Ground snow load

    Ps= Sloped roof snow load

    Load Combination

    D* = Dead load

    E = Earthquake load

    F = Load due to uids with well-dened pressure

    and maximum heights

    H = Load due to lateral earth pressure, groundwater pressure or pressure of bulk materials

    L = Live load

    Lr= Roof live load

    R = Rain load

    S* = Snow load

    T = Self-straining load

    W* = Wind load

    * In this white paper we only use dead, snow and wind loads.

    Gable RoofHip Roof

    Interior Zones

    Roofs - Zone 1

    Interior Zones

    Roofs - Zone 2

    Interior Zones

    Roofs - Zone 3

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012)

    Steps in wind design:

    1. Determine risk category from Table 1.5-1

    Risk category type II

    2. Determine the basic wind speed, V, for applicable

    risk category (see Figure 26.5-1 A, B, C)

    Wind speed in Colorado is V = 115 mph

    (excluding special wind regions)

    3. Determine wind load parameters:

    Exposure category B, C or D from Section 26.7

    Exposure B

    Topographic factor, Kzt, from Section 26.8 and

    Figure 26.8-1

    Kzt= 1.0

    4. Determine wind pressure at h = 30 ft, Pnet30

    , from

    gure 30.5-1

    5. Determine adjustment for building height and

    exposure, , from Figure 30.5-1

    Adjustment factor for Exposure B is = 1.00

    6. Determine adjusted wind pressure, Pnet

    , from

    Equation 30.5-1

    Pnet

    = Kzt

    Pnet30

    Wind effective area is the pressure area on themodule that is distributed between four mounting

    clamps. Each mid-clamp takes one-quarter of the

    pressure and holds two modules which are equal to

    one-half area of one module.

    Area of module is 18.05 square feet.

    Effective area is ~10 square feet.

    Pnet

    for wind speed of 115 mph and the wind

    effective area of 10 ft2:

    ASCE 7-05 (IBC 2009)

    Steps in wind design:

    1. Determine risk category from Table 1.5-1

    Risk category type II

    2. Determine the basic wind speed, V, for

    applicable risk category (see Figure 6-1 A, B, C)

    Wind speed in Colorado is V = 90 mph

    (excluding special wind regions)

    3. Determine wind load parameters:

    Exposure category B, C or D from Section 6.5.

    Exposure B

    Topographic factor, Kzt, from Section 6.5.7.2

    Kzt= 1.0

    4. Determine wind pressure at h = 30 ft, Pnet30

    , from

    Figure 6.3

    5. Determine adjustment for building height and

    exposure, , from Figure 6.3

    Adjustment factor for Exposure B is = 1.00

    6. Determine adjusted wind pressure, Pnet

    , from

    Equation 6-1

    Pnet

    = Kzt

    Pnet30

    Wind effective area is the pressure area on themodule that is distributed between four mounting

    clamps. Each mid-clamp takes one-quarter of the

    pressure and holds two modules which are equal t

    one-half area of one module.

    Area of module is 18.05 square feet.

    Effective area is ~10 square feet.

    Pnet

    for wind speed of 90 mph and the wind effecti

    area of 10 ft2

    :

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012) (Cont'd)

    Zone 1

    Downward: +21.8 psf

    Upward: -23.8 psf

    Pnet

    = Kzt

    Pnet30

    PDown

    = 1 * 1 * 21.8 = 21.8 psf

    Pup

    = 1 * 1 * -23.8 = -23.8 psf

    Zone 2

    Downward: +21.8 psf

    Upward: -27.8 psf

    Pnet

    = Kzt

    Pnet30

    PDown

    = 1 * 1 * 21.8 = 21.8 psf

    Pup

    = 1 * 1 * -27.8 = -27.8 psf

    Zone 3

    Downward: +21.8 psf

    Upward: -27.8 psf

    Pnet

    = Kzt

    Pnet30

    PDown

    = 1 * 1 * 21.8 = 21.8 psf

    Pup

    = 1 * 1 * -27.8 = -27.8 psf

    Steps in snow design:

    1. For sloped roof snow loads Ps= C

    sx P

    f

    2. Pfis calculated using Equation 7.3-1

    Pf= 0.7 x C

    ex C

    tx I

    sx P

    g

    3. When ground snow load is less than or equal to

    20 psf then the minimum Pfvalue is I * 20 psf. (7.3.4)

    4. Find exposure factor from Table 7-2, in category B

    and fully exposed roof

    Ce= 0.9

    ASCE 7-05 (IBC 2009) (Cont'd)

    Zone 1

    Downward: +13.3 psf

    Upward: -14.6 psf

    Pnet

    = Kzt

    Pnet30

    PDown

    = 1 * 1 * 13.3 = 13.3 psf

    Pup

    = 1 * 1 * -14.6 = -14.6 psf

    Zone 2

    Downward: +13.3 psf

    Upward: -17psf

    Pnet

    = Kzt

    Pnet30

    PDown

    = 1 * 1 * 13.3 = 13.3 psf

    Pup

    = 1 * 1 * -17 = -17 psf

    Zone 3

    Downward: +13.3 psf

    Upward: -17psf

    Pnet

    = Kzt

    Pnet30

    PDown= 1 * 1 * 13.3 = 13.3 psf

    Pup

    = 1 * 1 * -17 = -17 psf

    Steps in snow design:

    1. For sloped roof snow loads Ps= C

    sx P

    f

    2. Pfis calculated using Equation 7.3-1

    Pf= 0.7 x C

    ex C

    tx I

    sx P

    g

    3. When ground snow load is less than or equal to

    20 psf then the minimum Pfvalue is I * 20 psf. (7.3.4

    4. Find exposure factor from Table 7-2, in categor

    and fully exposed roof

    Ce= 0.9

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012) (Cont'd)

    5. Determine thermal factor using Table 7-3, for

    unheated and open air structures

    Ct= 1.2

    6. Find the importance factory from Table 1.5-2

    Is= 1.00 (7-10)

    7. Using Section 7.4 determine Cs. Using above

    values and = 30

    Cs= 0.73

    Pf

    = 0.7 x Ce

    x Ct

    x Is

    x Pg

    Pg 20 lbs

    Pgis the ground snow load and cannot be used

    instead of the nal snow load Pffor the sloped roof

    in our load combinations' equations. We need to

    calculate the sloped roof snow load as follows:

    Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20

    Ps= C

    sx P

    f

    Ps

    = 0.73 * 20 = 14.6 psf

    Load Combinations: (LRFD)

    Basic combinations Section 2.3.2, according to ASCE

    7-10 structures, components and foundations shall

    be designed so that their design strength equals

    or exceeds the effects of the factored loads in the

    following combinations:

    1) 1.4D

    2) 1.2D+ 1.6L+ 0.5 (Lror S or R)

    3) 1.2D+ 1.6 (Lror S or R) + (L or 0.5W)

    4) 1.2D+ 1.0W+ L+ 0.5 (LRor S or R)

    5) 1.2D+ 1.0E+ L+ 0.2S

    6) 0.9D+ 1.0W

    7) 0.9D+ 1.0E

    ASCE 7-05 (IBC 2009) (Cont'd)

    5. Determine thermal factor using Table 7-3, for

    unheated and open air structures

    Ct= 1.2

    6. Find the importance factory from Table 7-4

    Is= 1.0 (7-05)

    7. Using Section 7.4 determine Cs. Using above

    values and = 30

    Cs= 0.73

    Pf

    = 0.7 x Ce

    x Ct

    x Is

    x Pg

    Pg 20 lbs

    Pgis the ground snow load and cannot be used

    instead of the nal snow load Pffor the sloped roo

    in our load combinations equations. We need to

    calculate the sloped roof snow load as follows:

    Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20

    Ps= C

    sx P

    f

    Ps

    = 0.73 * 20 = 14.6 psf

    Load Combinations: (ASD)

    Basic combinations Section 2.3, according to ASC

    7-05 loads listed herein shall be considered to act i

    the following combinations; whichever produces t

    most unfavorable effect in the building, foundatio

    or structural member being considered. Effects of

    one or more loads on acting shall be considered.

    1) D + F

    2) D + H + F + L + T

    3) D + H + F + (Lror S or R)

    4) D + H + F + 0.75 (L + T) + 0.75 (Lror S or R)

    5) D + H + F + (W or 0.7 E)

    6) D + H + F + 0.75 (W or 0.7 E) + .75L + .75 ( Lror S or

    7) 0.6D + W + H

    8) 0.6D + 0.7E + H

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012) (Cont'd)

    The highest values for upward and downward

    pressures will govern the design.

    Load Case 3)

    1.2 * 2.59 + 1.6 (14.6) + 0.5 (21.8) = 37.4 psf

    Load Case 6)

    0.9 * 2.59 + 1.0 (-27.8) = -25.7 psf

    The next step is to check that the module can

    withstand the design loads for this two-rail mounting

    conguration. The designer should refer to themodule installation instructions where the design

    loads for different mounting congurations are

    provided.

    When two rails are supporting the module with top-

    down clamps, the module design capacity is:

    Downward: +113 psf

    Upward: -64 psf

    These values are well above the governing design

    loads of:

    Downward: +37.4 psf

    Upward: -25.7 psf

    To distribute the combined loads on the module

    that are transferring to the rails, please refer to the

    Mounting User Instruction guide and ASCE 7-10

    section 30.4.

    ASCE 7-05 (IBC 2009) (Cont'd)

    The highest values for upward and downward

    pressures will govern the design.

    Load Case 6)

    2.59 + 0.75 (14.6) + 0.75 (13.3) = 23.5 psf

    Load Case 7)

    0.6 (2.59) + 1.0 (-17.0) = -15.45 psf

    The next step is to check that the module can

    withstand the design loads for this two-rail mountin

    conguration. The designer should refer to themodule installation instructions where the design

    loads for different mounting congurations are

    provided.

    When two rails are supporting the module with top

    down clamps, the module design capacity is:

    Downward: +55 psf

    Upward: 33 psf

    These values are well above the governing design

    loads of:

    Downward: +23.5 psf

    Upward: -15.45 psf

    To distribute the combined loads on the module

    that are transferring to the rails, please refer to the

    Mounting User Instruction guide and ASCE 7-05

    section 6.5.12.2.

    Fmin, max Fmin, max

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    Example calculations

    In the following example we outline how a designer

    should calculate the effect of wind and snow on a

    PV module for commercial buildings based on fewassumptions and using Main Wind-force Resisting

    Systems design.

    ASCE 7-05: Section 6.5.12.4.1

    ASCE 7-10: Section 30.4

    Example 2- Commercial Structure in Colorado:

    Location: Colorado

    Terrain: Urban, suburban, wooded, closely

    spaced obstructions

    Exposure: Class B

    Building Type: Two-story Commercial (25 fee

    tall)

    Mean height of roof: ~25.33 feet Building Shape: Gable roof with 5 pitch (1:

    System: Two Rail System; attached module

    four points along the long side between 1/8

    to 1/4 points as described in the SolarWorld

    Sunmodule User Instruction guide

    Module area: 18.05 ft. (Reference: Sunmod

    Datasheet)

    Module weight: 46.7 lbs (Reference:

    Sunmodule Datasheet) Site ground snow load (P

    g): 20 psf

    SYMBOLS AND NOTATIONS

    Wind

    Cn= New pressure coefcient to be used in

    determination of wind loads

    G = Gust effect factor

    I = Importance factor

    Kd= Wind directionality factor

    Kz = Velocity pressure exposure coefcient

    evaluated at height z

    Kzt= Topographic factor

    P = Design pressure to be used in determination of

    wind loads for buildings

    qh = Velocity pressure evaluated at height z = h = Tilt angle of the module

    Snow

    Ce= Exposure factor

    Cs= Slope factor

    Ct= Thermal factor

    I = Importance factor

    Pf= Snow load on at roof

    Pg= Ground snow load

    Ps= Sloped roof snow load

    Load Combination

    D* = Dead load

    E = Earthquake load

    F = Load due to uids with well-dened pressure

    and maximum heights

    H = Load due to lateral earth pressure, ground

    water pressure or pressure of bulk materials

    L = Live load

    Lr= Roof live load

    R = Rain load

    S* = Snow load

    T = Self-straining load

    W* = Wind load

    * In this white paper we only use dead, snow and wind loads.

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012)

    Steps in wind design:

    1. Determine risk category from Table 1.5-1

    Risk category type II

    2. Determine the basic wind speed, V, for applicable

    risk category (see Figure 26.5-1 A, B, C)

    Wind speed in Colorado is V = 115 mph

    (excluding special wind regions)

    3. Determine wind load parameters:

    Wind Directionality factor, Kd, see Section 26.6

    Main wind-force resisting system

    components and cladding, Kd= 0.85

    Exposure category B, C or D from Section 26.7

    Exposure B

    Topographic factor, Kzt, from Section 26.8 and

    Figure 26.8-1

    Kzt= 1.0

    4. Determine velocity pressure exposure coefcient,

    Kzof K

    h, see Table 30.3-1

    For exposure B and height of 25 ft, Kz= 0.7

    5. Determine velocity pressure, qh, Eq. 30.3-1

    qh= 0.00256x K

    zx K

    ztx K

    dx V2

    6. Determine net pressure coefcient, GCp

    See Fig. 30.4-2A

    Downward: GCp= 0.3

    Upward: GCp= -1.0 (zone 1)

    -1.8 (zone 2)

    -2.8 (zone 3)

    ASCE 7-05 (IBC 2009)

    Steps in wind design:

    1. Determine risk category from Table 1.5-1

    Risk category type II

    2. Determine the basic wind speed, V, for applica

    risk category (see Figure 6.1 A, B, C)

    Wind speed in Colorado is V = 90 mph

    (excluding special wind regions)

    3. Determine wind load parameters:

    Wind Directionality factor, Kd, see Section 6.5.

    Main wind-force resisting system

    components and cladding, Kd= 0.85

    Exposure category B, C or D from Section 6.5.

    Exposure B

    Topographic factor, Kzt, from Section 6.5.7.2

    Kzt= 1.0

    4. Determine velocity pressure exposure coefcie

    Kzof K

    h, see Table 6-3

    For exposure B and height of 25 ft, Kz= 0.

    5. Determine velocity pressure, qh, Eq. 6-15

    qh= 0.00256x K

    zx K

    ztx K

    dx V2x 1

    6. Determine net pressure coefcient, GCp

    See Fig. 6-11B

    Downward: GCp= 0.3

    Upward: GCp= -1.0 (zone 1)

    -1.8 (zone 2)

    -2.8 (zone 3)

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels

    ASCE 7-10 (IBC 2012) (Cont'd)

    7. Calculate wind pressure, p, Eq. 30.8-1

    p = qhGCp

    qh= 0.00256xk

    zx k

    ztx k

    dx V2

    qh= 0.00256 * 0.7 * 1 * 0.85 * 1152 = 20.14 psf

    pdown

    = 20.14 * 0.3 = 6.04 psf

    pup

    = 20.14 * (-2.8) = 56 psf

    Steps in Snow design:

    1. For sloped roof snow loads Ps= C

    sx P

    f

    2. Pfis calculated using Equation 7.3-1

    Pf= 0.7x C

    ex C

    tx I

    sx P

    g

    3. When ground snow load is less than or equal 20

    psf then the minimum Pfvalue is I * 20 psf (7.3.4)

    4. Find exposure factor from Table 7-2, in category B

    and fully exposed roof

    Ce= 0.9

    5. Determine Thermal factor using Table 7-3, for

    unheated and open air structures

    Ct= 1.2

    6. Find the importance factory from Table 1.5-2

    Is= 1.00 (7-10)

    7. Using Section 7.4 determine Cs. Using above

    values and = 5

    Cs=1.0

    Pf= 0.7 x C

    ex C

    tx I

    sx P

    g

    ASCE 7-05 (IBC 2009)(Cont'd)

    7. Calculate wind pressure, p, Eq. 6-26

    p = qhGCp

    qh= 0.00256 x k

    zx k

    ztx k

    dx V2

    qh= 0.00256 * 0.7 * 1 * 0.85 *902= 12.34 psf

    pd= 12.34 * 0.3 = 3.7 psf psf

    pu= 12.34 * (-2.8) = 34.6 psf

    Steps in Snow design:

    1. For sloped roof snow loads Ps= C

    sx P

    f

    2. Pfis calculated using Equation 7.3-1

    Pf= 0.7 x Cex C

    tx I

    sx P

    g

    3. When ground snow load is less than or equal 20

    psf then the minimum Pfvalue is I * 20 psf (7.3.4)

    4. Find exposure factor from Table 7-2, in categor

    and fully exposed roof

    Ce= 0.9

    5. Determine Thermal factor using Table 7-3, for

    unheated and open air structures

    Ct= 1.2

    6. Find the importance factory from Table 7-4

    Is= 1.0 (7-05)

    7. Using section 7.4 determine Cs. Using above

    values and = 5

    Cs=1.0

    Pf= 0.7 C

    e C

    t I

    s P

    g

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels |

    ASCE 7-10 (IBC 2012) (Cont'd)

    Pg 20 lbs

    Pgis the ground snow load and cannot be usedinstead of the nal snow load for the sloped roof

    in our load combinations equations. We need to

    calculate the sloped roof snow load as follows:

    Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20

    Ps= C

    sx P

    f

    To nd out the effect of snow load perpendicular to the

    plane of module we multiply the Ps

    value by COS ().

    Ps= 1 * 20 * COS (5) = 19.9 psf

    Load combinations: (LRFD)

    Basic combinations section 2.3.2, according to ASCE

    7-10 structures, components and foundations shall

    be designed so that their design strength equals or

    exceeds the effects of the factored loads in following

    combinations:

    1) 1.4D

    2) 1.2D + 1.6L + 0.5 (Lror S or R)

    3) 1.2D + 1.6 (Lror S or R) + (Lor 0.5W)

    4) 1.2D + 1.0W+ L+ 0.5 (Lror S or R)

    5) 1.2D + 1.0E+ L+ 0.2S

    6) 0.9D + 1.0W

    7) 0.9D + 1.0E

    The highest values for upward and downward

    pressures will govern the design.

    ASCE 7-05 (IBC 2009)(Cont'd)

    Pg 20 lbs

    Pgis the ground snow load and cannot be usedinstead of the nal snow load for the sloped roof

    in our load combinations equations. We need to

    calculate the sloped roof snow load as follows:

    Pf= 0.7 * 0.9 * 1.2 * 1 * 20 = 15.12 psf or 1 * 20

    Ps= C

    sx P

    f

    To nd out the effect of snow load perpendicular to

    plane of module we multiply the Ps

    value by COS ()

    Ps= 1 * 20 * COS (5) = 19.9 psf

    Load Combinations: (ASD)

    Basic combinations section 2.3.2, according to ASC

    7-05 loads listed herein shall be considered to act i

    the following combinations; whichever produces t

    most unfavorable effect in the building, foundatio

    or structural member being considered. Effects of

    one or more loads on acting shall be considered.

    1) D + F

    2) D + H + F + L + T

    3) D + H + F + (Lr or S or R)

    4) D + H + F + 0.75 (L + T) + 0.75 (Lr or S or R)

    5) D + H + F + (W or 0.7E)

    6) D + H + F + 0.75 (W OR 0.7E) + .75L + .75 (Lr or S or

    7) 0.6D + W + H

    8) 0.6D + 0.7E + H

    The highest values for upward and downward

    pressures will govern the design.

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels |

    ASCE 7-10 (IBC 2012) (Cont'd)

    Load Case 3)

    1.2 * 2.59 + 1.6 (19.9) + 0.5 (6.04) = 38 psf

    Load Case 6)

    0.9 * 2.59 + 1.0 (-56) = -53.7 psf

    The next step is to check that the module can

    withstand the design loads for this two-rail mounting

    conguration. The designer should refer to the

    module installation instructions where the design

    loads for different mounting congurations are

    provided.

    For the case of two rails simply supporting the module

    with top-down clamps, the module design capacity is:

    Downward: +113 psf

    Upward: -64 psf

    These values are above the governing design loads

    of:

    Downward: +38 psf

    Upward: -53.7 psf

    To distribute the combined loads which are

    transferring to the rails please refer to the Mounting

    User Instruction and ASCE 7-10 section 30.4.

    ASCE 7-05 (IBC 2009)(Cont'd)

    Load Case 6)

    2.59 + 0.75 (19.9) + 0.75 (3.7) = 20.3 psf

    Load Case 7)

    0.6 (2.59) + 1.0 (-34.6) = -33 psf

    The next step is to check that the module can

    withstand the design loads for this two-rail mountin

    conguration. The designer should refer to the

    module installation instructions where the design

    loads for different mounting congurations are

    provided.

    For the case of two rails simply supporting the mod

    with top-down clamps, the module design capacity

    Downward: +55 psf

    Upward: -33 psf

    These values are above the governing design load

    of:

    Downward: +20.3 psf

    Upward: -33 psf

    To distribute the combined loads which are

    transferring to the rails please refer to the Mounting

    User Instruction and ASCE 7.05 section 6.5.12.2.

    Fmin, maxFmin, max

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    Determining wind and snow loads for solar panels SW-02-5156US-MEC 04-2013 |

    As this white paper illustrates, SolarWorld Sunmodules easily meet many high wind and snow load requirements

    within the United States and therefore are ideal for installation in most climates. The ability to meet these

    requirements is essential when designing solar systems that are expected to perform in various weather

    conditions for at least 25 years. As Americas solar leader for over 35 years, SolarWorlds quality standards are

    unmatched in the industry. Unlike most other solar manufacturers in the market today, our systems have prov

    performance in real world conditions for over 25 years.

    References

    1. Minimum design loads for buildings and other structures. Reston, VA: American Society of Civil Engineers/

    Structural Engineering Institute, 2006. Print.

    2. Minimum design loads for buildings and other structures. Reston, Va.: American Society of Civil Engineers :

    2010. Print.

    3. International building code 2009. Country Club Hills, Ill.: International Code Council, 2009. Print.

    4. International building code 2006. New Jersey ed. Country Club Hills, IL: The Council, 2007. Print.

  • 5/20/2018 Determining Wind and Snow Loads for Solar Panels

    t

    etter of

    ate:

    roject:

    PS Job

    o:

    rom:

    t the re

    resente

    Version

    rescribe

    ccordan

    005 i

    ngineer

    esign m

    ach said

    his lette

    s discus

    he site s

    ethodol

    re publi

    nsure it

    lease fe

    incerel

    atthewngineer

    Approv

    umber:

    uest of

    in Solar

    7). The

    d wind a

    ce with e

    imum D

    s (ASCE

    ethodolo

    building

    r is in ap

    sed in th

    ecific lo

    ogy for

    hed. Be

    matches

    el free to

    ,

    B. Gillised Powe

    l Sola

    Dec

    Sola

    12-

    Ami

    Sola

    465Ca

    MatEngi

    olarWo

    Worlds

    aper pr

    d snow

    ither the

    sign Lo

    7-05), o

    gy and e

    code.

    proval o

    referen

    ading co

    oof mou

    cause of

    with the

    contact

    s, P.E.,Solutio

    STR

    World

    mber 3

    r Modul

    WD003

    r Sheikh

    rWorld

    Adohrarillo, C

    hew Gilneered

    ld, Engi

    White

    sents th

    loads fo

    2009 (a

    ds for

    the 201

    amples

    the gen

    ed pape

    nditions

    nted sol

    this, EP

    most cu

    e with

    EED As

    CTUR

    esign L

    , 2012

    Design

    mericas

    ane93012

    issower So

    eered P

    aper tit

    recom

    solar m

    d 2006)

    uildings

    2 IBC

    presente

    eral desi

    . It is th

    for each

    r system

    recom

    rent cod

    any ques

    L LET

    ads Me

    Loads

    (SolarW

    utions (

    wer Sol

    ed:Det

    ended d

    dules m

    Internat

    and Oth

    hich re

    in this

    n metho

    e respon

    project.

    s has co

    ends pe

    require

    ions. T

    ENM

    ER OF

    hodolo

    ethodol

    orld)

    PS)

    tions (

    rmining

    sign me

    ounted o

    onal Bui

    r Struct

    ferences

    aper are

    dology

    ibility o

    Please n

    tinually

    iodicall

    ents an

    ank you

    INEETTHEWB

    879 S

    PA

    APPRO

    y Revie

    gy Revi

    PS) has

    Wind an

    hodolog

    n and fl

    lding Co

    resby t

    ASCE 7

    consiste

    or flush

    f the pro

    ote that t

    changed

    reviewi

    d indust

    .

    ED PO. GILLISS,

    CAMO

    O ROB

    (805)

    VAL

    ew

    eviewe

    Snow

    y for det

    sh to a r

    de (IBC)

    e Ameri

    10. EP

    nt with t

    oof mou

    ect engi

    he indus

    over rec

    ng the st

    y recom

    WER S ROFESSI

    E CAN

    ES, CA

    23-132

    12/31/1

    the desi

    oads fo

    erminin

    oof surfa

    - which

    can Soci

    has fou

    he desig

    nted sol

    eer of r

    ry reco

    ent years

    ated met

    endati

    OLUT NALENGI

    ON R

    93446

    4

    gn meth

    Solar P

    the cod

    ce in

    referenc

    ety of Ci

    d that t

    intenti

    r modul

    cord to

    mended

    as new

    hodolog

    ns.

    ONSNEER

    .

    Page 1

    dology

    anels

    es the

    vil

    e

    ns of

    es only

    ddress

    design

    studies

    to