DEVELOPMENT OF A MODEL OF THE ALPHA / BETA 765kV LINE FOR THE EVALUATION OF AUTO-RECLOSING by PETER ROBERT VAN HEERDEN Submitted in partial fulfilment of the requirements for the Degree of MSc (POWER AND ENERGY SYSTEMS) FACULTY OF ENGINEERING University of Kwazulu-Natal Supervisors: Prof. R Zivanovic Prof. N M Ijumba February 2009

Upload: others

Post on 02-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

D E V E L O P M E N T O F A MODEL OF THE ALPHA / BETA 765kV LINE FOR THE EVALUATION O F

AUTO-RECLOSING

by

PETER ROBERT VAN HEERDEN

Submitted in partial fulfilment of the requirements for the

Degree of

MSc (POWER AND ENERGY SYSTEMS)

FACULTY OF ENGINEERING University of Kwazulu-Natal

Supervisors: Prof. R Zivanovic Prof. N M Ijumba

February 2009

Page 2: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

DECLARATION

I, the undersigned declare that the material presented in this dissertation is

my own work, except where specific acknowledgement is made in the form

of a reference

P R van Heerden

Student No. 204001288

18/03/2009

Page 3: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

ABSTRACT

The intention of this dissertation is to determine, on the Eskom system, if the pre-insertion

closing resistors installed on the Alpha-Beta 765 kV line breakers are preventing overvoltages

from being caused during auto-reclosing. Other possible solutions of reclosing protection are

investigated. It has been shown on two occasions, from actual field data that overvoltages have

occurred on the lines after reclosing. High overvoltages on this network could be the cause of

the many reactor failures that have occurred.

A mathematical model of the Alpha-Beta 765kV system was produced on Matlab/Simulink to

simulate the resonance of the line during opening and then the effect on the voltage when

reclosing takes place. The effects of installing pre-insertion resistors to reduce overvoltages on

reclosing were analysed, as well as looking at controlled reclosing at the optimal voltage across

the line breakers.

It was shown from the studies, that pre-insertion resistors do limit the overvoltages to within the

surge capabilities of the line (10% overvoltage) and that the cause of the previous overvoltages

were actually due to insertion resistor operations failure. It was also shown that the method of

controlled closing at optimal voltage across the breakers is also a successful method of

preventing overvoltages. This dissertation also evaluates a design specification for a switching

relay for controlled re-closing of the line.

11

Page 4: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

ACKNOWLEDGEMENTS

I would like to express my sincere gratitude and appreciation to:

- My mentor, Prof Rastko Zivanovic.

- Armien Edwards for assistance in the design of the switching relay.

- Brian Berry for help in formatting the document.

- Eskom, for financial support.

Page 5: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

TABLE OF CONTENTS

CHAPTER 1: INTRODUCTION & BACKGROUND 1

1.1 Introduction 1

1.2 Background 1 1.2.1 Problem Overview 1 1.2.2 Methods for controlling overvoltages whilst switching shunt compensated, EHV lines 3

CHAPTER 2: INVESTIGATION INTO BC HYDRO'S USE OF CONTROLLED CLOSING ON SHUNT REACTOR COMPENSATED LINES 6

2.1 BC Hydro 500 kV line configuration 6

2.2 Resonant voltage signal produced on the open shunt reactor compensated line 7

2.3 Feasibility study of controlled reactor switching on the B. C. Hydro 500 kV line 8

2.3.1 Electromagnetic Transient Program (EMTP) Studies 8

2.4 Closing Control Device Strategy 11

2.5 Line Switching Tests 12

2.6 Interphase Coupling Phenomena 15

2.7 Conclusions 16

CHAPTER 3: SIMULATION MODEL OF THE ALPHA-BETA 765KV SYSTEM 18

3.1 Simulation Model Design 18

3.2 Testing of the Simulation Model 19 3.2.1 Comparison between study and case study results 21

CHAPTER 4: ALPHA-BETA 765KV SYSTEM SIMULATION 23

4.1 Simulation Aim 23

4.2 Simulation Methodology 23

4.3 Simulation Results 23 4.3.1 Simulation 1 - Reclosing at minimum differential voltage with pre-insertion resistors

included 23 4.3.2 Simulation 2 - Reclosing at minimum differential voltage without pre-insertion resistors

included 25 4.3.3 Simulation 3 - Reclosing at maximum differential voltage with pre-insertion resistors

included 26 4.3.4 Simulation 4 - Reclosing at maximum differential voltage without pre-insertion resistors

included 28

4.4 Interpretation of Simulation Results 30

IV

Page 6: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 5: DESIGN SPECIFICATIONS FOR A CONTROLLED SWITCHING RELAY 31

5.1 Switching Constraints 31

5.2 Relay Functional Overview 32 5.2.1 Analogue Input Quantities 32 5.2.2 Frequency Tracking and Phasor Calculation 32 5.2.3 Relay Algorithm and Output Decision Logic 32

5.3 Algorithm Functional Design and Implementation 33 5.3.1 Analogue Input Design 33 5.3.2 Frequency Tracking 34 5.3.3 Decision Variables and Logic 36

CHAPTER 6: CONCLUSION 44

V

Page 7: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

LIST OF FIGURES PAGE

FIGURE 1: ONE LINE DIAGRAM OF ALPHA-BETA 765 KV SYSTEM 2 FIGURE 2: ACTUAL RING DOWN BEFORE AND AFTER BREAKER CLOSED 26/05/2006 3 FIGURE 3: THE EXTRACTED RING DOWN VOLTAGE WAVEFORM 4 FIGURE 4: (A) 50 HZ SINE WAVE, (B) 40 HZ SINE WAVE, (C) DIFFERENCE BETWEEN

WAVE (A) AND (B) 5 FIGURE 5: BC HYDRO 500KV LINE ARRANGEMENT 6 FIGURE 6: RESONATING RING-DOWN VOLTAGE SIGNAL FOR VARIOUS DEGREES OF

COMPENSATION 7 FIGURE 7: CUMULATIVE FREQUENCY DISTRIBUTIONS FOR OVERVOLTAGES AT

REMOTE LINE END 9 FIGURE 8: OVERVOLTAGE PROFILES ALONG TRANSMISSION LINES 10 FIGURE 9: CLOSING STROKE FOR SYSTEM BREAKER SUPERIMPOSED ON MEASURED

VOLTAGE ACROSS CIRCUIT BREAKERS 12 FIGURE 10: CONTROLLED AUTO-RECLOSING WITH TWO SHUNT REACTORS

CONNECTED 13 FIGURE 1 1: CONTROLLED AUTO-RECLOSING WITH ONE SHUNT REACTOR CONNECTED

AT LEAD END 14 FIGURE 12: EXAMPLE OF COUPLING BETWEEN PHASES 15 FIGURE 13: INTERPHASE COUPLING BETWEEN PHASES DURING CONTACT CLOSURE.. 16 FIGURE 14: ALPHA-BETA 765KV SYSTEM MODEL IN SIMULINK 18 FIGURE 15: MODEL BREAKER WITH A 450 OHM PRE-INSERTION RESISTOR CONNECTED

IN PARALLEL 19 FIGURE 16: RESONANT RING DOWN VOLTAGE AFTER OPENING 20 FIGURE 17: ACTUAL RING DOWN BEFORE AND AFTER BREAKER CLOSED 26/05/06 20 FIGURE 18: THE EXTRACTED RING DOWN VOLTAGE WAVEFORM 21 FIGURE 19: VOLTAGE ACROSS OPEN CIRCUIT BREAKER - DEGREE OF COMPENSATION

80% CASE STUDY 21 FIGURE 20: VOLTAGE ACROSS OPEN CIRCUIT BREAKER - DEGREE OF COMPENSATION

60% 22 FIGURE 21: THE ALPHA - BETA LINE BREAKER RECLOSING AT MINIMUM VOLTAGE

WITH THE INCLUSION OF PRE-INSERTION RESISTORS AT ALPHA 24 FIGURE 22: THE ALPHA-BETA LINE BREAKER RECLOSING AT MINIMUM VOLTAGE

WITH THE INCLUSION OF PRE-INSERTION RESISTORS AT BETA 24 FIGURE 23: DIFFERENCE IN VOLTAGE BETWEEN LINE AND BUSBAR AT ALPHA 25 FIGURE 24: THE ALPHA - BETA LINE BREAKER RECLOSING AT MINIMUM VOLTAGE

WITHOUT THE INCLUSION OF PRE-INSERTION RESISTORS AT ALPHA 25 FIGURE 25: THE ALPHA - BETA LINE BREAKER RECLOSING AT MINIMUM VOLTAGE

WITHOUT THE INCLUSION OF PRE-INSERTION RESISTORS AT BETA 26 FIGURE 26: DIFFERENCE IN VOLTAGE BETWEEN LINE AND BUSBAR AT ALPHA BEFORE

RECLOSING 26 FIGURE 27: THE ALPHA - BETA LINE BREAKER RECLOSING AT MAXIMUM VOLTAGE

WITH THE INCLUSION OF PRE-INSERTION RESISTORS AT ALPHA 27 FIGURE 28: THE ALPHA - BETA LINE BREAKER RECLOSING AT MAXIMUM VOLTAGE

WITH THE INCLUSION OF PRE-INSERTION RESISTORS AT BETA 27 FIGURE 29: DIFFERENCE IN VOLTAGE BETWEEN LINE AND BUSBAR AT ALPHA BEFORE

RECLOSING 28 FIGURE 30: THE ALPHA - BETA LINE BREAKER RECLOSING AT MAXIMUM VOLTAGE

WITHOUT THE INCLUSION OF PRE-INSERTION RESISTORS AT ALPHA 28 FIGURE 31: THE ALPHA - BETA LINE BREAKER RECLOSING AT MAXIMUM VOLTAGE

WITHOUT THE INCLUSION OF PRE-INSERTION RESISTORS AT BETA 29 FIGURE 32: DIFFERENCE IN VOLTAGE BETWEEN LINE AND BUSBAR AT ALPHA BEFORE

RECLOSING 29 FIGURE 33: DIFFERENTIAL VOLTAGE ACROSS THE BREAKER AT ALPHA WITH THE LINE

COMPENSATED BY BOTH LINE RE ACTORS 31 FIGURE 34: RELAY MODEL IN SIMULINK 33 FIGURE 35: FILTER DESIGN PARAMETERS 34

vi

Page 8: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

FIGURE 36: FILTER PERFORMANCE 34 FIGURE 37: FREQUENCY TRACKING PERFORMANCE WITH AN INITIAL ESTIMATE OF

50HZ ON BREAKER OPENING 35 FIGURE 38: FREQUENCY TRACKING PERFORMANCE WITH SMOOTHING FUNCTION AND

GOOD INITIAL ESTIMATE OF FREQUENCY 35 FIGURE 39: MODIFIED SIMULINK DISCRETE 1 -PHASE PHASE LOCKED LOOP FUNCTION..

36 FIGURE 40: INSTANTANEOUS AND RMS DIFFERENTIAL VOLTAGE COMPARISON 37 FIGURE 41: MINIMUM RMS DIFFERENTIAL THRESHOLD DETECTOR PERFORMANCE... 38 FIGURE 42: DELTA DIFFERENTIAL VOLTAGE MEASUREMENT LOGIC 38 FIGURE 43: DELTA DIFFERENTIAL VOLTAGE MEASUREMENT COMPARISON 39 FIGURE 44: INTEGRATED DELTA DIFFERENTIAL VOLTAGE MEASUREMENT

COMPARISON 39 FIGURE 45: INTEGRATED DELTA DIFFERENTIAL VOLTAGE MINIMUM DETECTION 40 FIGURE 46: MINIMUM NUMBER OF COUNTS BEFORE THE OUTPUT LOGIC 40 FIGURE 47: LOGIC FOR CALCULATING THE BEAT FREQUENCY 41 FIGURE 48: CALCULATED BEAT FREQUENCY 41 FIGURE 49: INSTANTANEOUS AND SAMPLED RESULTS FOR THE BEAT FREQUENCY

PERIOD 41 FIGURE 50: LOGIC TO CALCULATE CLOSING TIME BASED ON THE PREDICTED TIME... 42 FIGURE 51: COUNTER LOGIC AND FINAL CLOSING LOGIC 43 FIGURE 52: CLOSING LOGIC PERFORMANCE WITH A COUNT OF TWO SETTING 43

vii

Page 9: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 1: INTRODUCTION & BACKGROUND

1.1 Introduction

The aim of this project is to determine whether the use of pre-insertion resistors on Eskom's 765

kV, Alpha-Beta transmission line is an effective method of protection against switching transients.

This study is brought about due to the excessive damage caused to the line reactors. Other methods

of protection are investigated and a model of the Alpha-Beta system is constructed. The model is

then used to determine the effect of the different types of protection.

1.2 Background

As mentioned before, this research is focused around Eskom's Alpha-Beta Transmission lines. It is

therefore imperative that some background to the lines' configuration, existing protection scheme

and problems which have occurred on these lines are discussed. Alternative protection schemes are

then discussed.

1.2.1 Problem Overview

Presently in Eskom, the 765 kV, Alpha-Beta transmission line is an important corridor within the

South African national grid. Should one of these parallel lines be disconnected, the stability of the

entire South African network would be affected. The Alpha-Beta corridor is important because it

connects the North-East and Cape Regions. The North-East region contains the majority of the

country's generation capacity (a total of approximately 25000 MW) [1 ]. The Cape region, however,

lacks sufficient generation and thus to meet its demand, power is imported from the North-East

region via the Alpha-Beta corridor. Should this supply be interrupted, it would result in over 3000

MW of load being shed in the Cape region [1]. It is therefore imperative that these lines are well

protected to avoid unnecessary interruptions.

There have, however, been recorded incidents where these lines have tripped and failed to

reconnect due to the failure of the existing protection scheme. In order to understand the protection

scheme, the configuration of the Alpha-Beta line is first explained.

1.2.1.1 Alpha-Beta Transmission Line Configuration

The 765 kV Alpha-Beta lines are approximately 435 km long and have a maximum apparent power

rating of 6495 MVA [ 1 ], [2]. Their long length and Extra High Voltage (EHV) cause the lines to be

capacitive under light-load conditions [3]. To compensate for this effect, line reactors are installed

on both sides of the line [l].This can be seen from Figure 1 which shows a one line representation

of the Alpha-Beta line. These reactors are then used to prevent overvoltages when the line is lightly

loaded or if load is suddenly lost as well as to decrease the Ferranti effect [3].

1

Page 10: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Tutuka 1

Tutuka 2

Tutuka 3

Majuba 1

Alpha

i

Beta

<m

<n>

Hydra 2

Perseus 2

Perseus 3

Hydra 1

Figure 1: One line Diagram of Alpha-Beta 765 kV System

1.2.1.2 Alpha-Beta Protection Scheme Overview

There are breakers at each side of the line which will open, should a fault occur anywhere along the

line. These breakers will attempt to reconnect via the Automatic Reclose (ARC) scheme after one

second for a single-phase fault, or three seconds for a three-phase fault [1]. However, when the

lines are opened, an exponentially decaying transient voltage waveform will remain on the lines.

This is due to the capacitive and reactive components of the line causing resonance [3J. The

resonant frequency is between 30 Hz and 45 Hz, and is dependant on the line parameters and the

level of compensation [4].

This effect can cause an overvoltage surge when the line attempts to automatically reclose. This is

because the transient voltage will be superimposed on the source voltage creating dangerous

overvoltages along the line and on the shunt reactors. Resistors are therefore switched in parallel

with the breakers and will connect 2 to 8 ms before the line breakers close, in order to dampen the

overvoltage. These resistors are typically accompanied by surge arrestors which also help to reduce

the overvoltage. These resistors are known as Pre-insertion Resistors and are valued at 450 ohms at

both ends of the Alpha-Beta line [1].

1.2.1.3 Alpha-Beta Pre-insertion Resistor Failures

Although the use of pre-insertion resistors is a world-wide practice, there are many recorded

incidents of them failing to decrease the overvoltage. The steep overvoltages, caused during

switching, are unevenly distributed along the reactor winding and thus cause a high risk of

insulation failure. There were nine single pole reactor failures on the Alpha-Beta lines between

1999 and 2002. These failures were all due to insulation failure. The costs associated with these

failures were in excess of R 30 million.

2

Page 11: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

White Phase Volt White 435 3KV/ cm

900 0

6110 0

X«)'J-

-3(i0.C;

-900.0-

Jinno-

V

.!;

'K i l l P:25fi l U K i 0.75'' ].«(;! !.25t !.*•)'; : . " « 2.000 [s]

Figure 2: Actual ring down before and after breaker closed 26/05/2006 [4]

Two occasions (26/05/1997 and 26/01/1999) where the pre-insertion resistors failed to close before

the breaker, on the Alpha-Beta line, are examined. The 26/01/1999 incident occurred due to a three

phase line fault, which resulted in all the breakers opening at both the Alpha and Beta end. The line

was able to reclose after 3 seconds but an overvoltage, in the order of 1.7 p.u, was experienced. In

the 26/05/1997 incident, the breakers at Alpha opened for a fault on the line and reclosed after 3

seconds. However, the breakers on the Beta end failed to close due to an auto-reclose (ARC) relay

failure [4].

The transient voltages from an incident which occurred on 26/05/2006 can be seen in Figure 2. It is

evident from the figure that a resonant frequency does occur after the line is opened. Figure 3

shows an extract of the ring down voltage from Figure 2. It is then observed that the ring down

voltage has an amplitude of 186.4 kV and a resonant frequency of 43.23 Hz. This data was

obtained from the field and then manipulated using the methods detailed in Appendix A.

1.2.2 Methods for controlling overvoltages whilst switching shunt reactor compensated, EHV lines

Presently, there are seven countries using or intending to use 765 kV transmission systems. They

are Russia, India, China, Korea, Canada, Brazil and South Africa. For these systems, there are two

methods which are used to control the surges caused by the resonant frequency on the shunt

compensated lines. These can be either the more commonly used method of pre-insertion resistors

or the uncommon method of controlled shunt reactor compensated line switching [5]. These

methods are discussed and compared below.

3

Page 12: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

V V V 0.10 0 12 0 U 0.16 DIE

« S )

Figure 3: The extracted ring down voltage waveform [4]

1.2.2.1 Pre-insertion resistors

Information was obtained by contacting the above-mentioned power utilities and enquiring as to

the method presently in use for the auto-reclosing of their 765 kV shunt compensated lines. Further

investigation indicated that all the above utilities make use of pre-insertion resistors whilst closing

the breakers.

The most commonly used protection measure for reclosing on EHV shunt compensated lines, is the

use of metal oxide (Mol) surge arrestors combined with pre-insertion closing resistors. The

problem with this solution is that it is both expensive and mechanically complex. The mechanical

complexity results in the solution requiring extensive maintenance and thus it is prone to failure

and unplanned outages [5].

1.2.2.2 Controlled shunt reactor compensated line switching

As discussed previously, the compensated line will hold a resonant ring-down voltage when

opened. This resonant signal has a specific frequency which is typically between 30 and 45 Hz [6].

Since the frequencies of the open line and the busbar (which remains at the grid frequency) differ, a

waveform containing beats will occur in the voltage across the open breaker. This can be seen from

Figure 4, (a) represents the 50 Hz busbar system frequency, (b) represents the open line's resonant

frequency (an example of 40 Hz is chosen) and (c) represents the difference between the two

waves. It can be seen in (c) that beats form.

The basic idea behind controlled shunt reactor switching is to close the line, at the point when the

voltage difference between the line and busbar is within the minimum of the beat cycle. This

should therefore minimise the overvoltage surge which occurs when closing these lines.

> £ • •

S: re t» O,

O

e 0! ZT,

re o

2c:

ICC

• U K )

2C0 0.01 0.06 0 0>

Tirnfc

4

Page 13: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Figure 4: Theoretical example of a beating waveform (a) 50 Hz sine wave, (b) 40 hz sine wave, (c) difference between waves (a) and (b)

5

Page 14: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 2: INVESTIGATION INTO BC HYDRO'S USE OF CONTROLLED CLOSING ON SHUNT REACTOR COMPENSATED

LINES

Presently, the Canadian power utility, BC Hydro, is the only utility which makes use of controlled

shunt reactor switching. This utility made use of the controlled closing methodology on its 500kV

network. BC Hydro has implemented this system over several lines in their 500 kV network,

however, only one such transmission line is studied. BC Hydro's latest 500kV transmission line,

which was constructed during 1993 and 1994, is discussed [7J.

2.1 BC Hydro 500 kV line configuration

The 500 kV BC Hydro line is 330km long and the configuration of this line can be seen in Figure 5

[7]. It is evident from the figure that the line is compensated using a mid-line series capacitor bank

as well as reactors on either side of the line. The mid-line capacitor bank is rated at 605 Mvar, but

is bypassed during auto-reclosing. The shunt reactors are rated as 550kV, 135 Mvar at each end.

The lead end is fixed and ungrounded through a metal oxide varistor and the remote end is

switchable and grounded through a neutral reactor [5]. The circuit breakers are 500kV single

pressure SF6 type with spring-hydraulic operating mechanisms with required mechanical operating

time consistency over the ambient temperature range of -50°C to +40°|7]. The time consistency is

relevant because controlled switching is highly dependent on time.

Figure 5: BC Hydro 500kV line arrangement [7]

6

Page 15: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

2.2 Resonant voltage signal produced on the open shunt reactor compensated line

As the line is opened, an exponentially decreasing resonant voltage signal is formed. The resonant

frequency of the voltage signal is usually lower than the power frequency and dependent on the

inductance of the shunt reactors and the capacitance of the line [7].

t\ n /i, i 11 i ! j\ i) M n n

\i \ M l'\ 1 ' M M ' \' r ' A,' \i \l U U \ i * '

J *

'i !i I; J! " H

, » > ,

J U r l l i f lMr

I i'h .! I Si 11'/-;.-, ) i ! i l ! Hi! l i l i h r i ' ! i f ) i l ! l [t Ihl fV

Mi i f '

« v - « i - - i ' i i t > ' . j - v i r i i i f i i i f i n / ii ii !i MMr tflil||Mil^!

» , , j J

r i A .'. M j ' ,,rWi /', M r •*l ' I M 'i ; I : ; ' ) l ! I j 'H I j ® l r j f l l 1 i^\ I \y\ / | (

V i f I ,' ' '•' ! ;' I J l' V W ! } 'V V 1 J

t,i V h i; V t1'

a) no compensations and line with trapped charge (1.lp.u.) b) degree of compensation 80% c) degree of compensation 30%

Figure 6: Resonating ring-down voltage signal for various degrees of compensation [7]

The tripping of an unloaded uncompensated transmission line leaves a d.c. voltage on the line and a

voltage minimum across the circuit breaker will occur every half-cycle assuming no decay of the

line voltage (Figure 6 (a)) [7].

7

Page 16: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

With both shunt reactors connected on the BC Hydro line, the signal resonates at approximately 45

Hz. In this case, the voltage appearing across the open circuit breaker exhibits a very distinct

beating pattern (see Figure 6 (b)) [7].

With only one of the shunt reactors connected, the resonant frequency drops to approximately 33

Hz and the voltage pattern is less distinct than the previous case [7]. This voltage signal is not

obviously recognizable as a periodic beating pattem (see Figure 6 (c)). The reason for this is the

reduced damping of both the aerial and ground modes due to larger phase impedance and near

infinite ground impedance with the ungrounded shunt reactor neutral.

2.3 Feasibility study of controlled reactor switching on the B. C. Hydro 500 kV line

Due to the protection constraints of the line, a decision was made to limit the switching surge level

of the line to 1.7 p.u. This limit is defined as a 2 % value, i.e. there is a probability of 2 % or less

that the 1.7 p.u limit will be exceeded. Traditionally, pre-insertion resistors would be installed to

achieve this constraint [5]. However, due to the mechanical complexity and maintenance associated

with pre-insertion resistors, an investigation into a controlled reactor switching scheme was

conducted.

2.3.1 Electromagnetic Transient Program (EMTP) Studies

A large number of Electromagnetic Transient Program (EMTP) studies were run to define and

specify the requirements for the overall controlled switching scheme [5]. All the protection

schemes applicable to the scenario were studied in order to compare results. The following

protection scheme cases were studied:

- Closing with no switching surge control

Closing with the use of pre-insertion resistors

- Control with staggered closing (half-cycle time delay between close signal application to

successive poles/phases)

- Control with staggered closing using surge arresters with a 1.5 p.u. protective level, two (at line

terminations) or three (at line terminations and mid-line)

- Controlled point-of-wave closing using staggered closing and three surge arresters connected

as noted above.

Figure 7 compares the results of the EMTP studies by way of the cumulative frequency

distributions of the switching surge overvoltage at the remote end for the different cases (a better

description would probably be 'Cumulative Frequency (%)' on the y-axis). In all the cases, a shunt

8

Page 17: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

reactor is connected at the lead end only. It is evident from the figure that the value of adding

surge arresters is quite significant and with the addition of controlled closing, the 1.7 p.u surge

limit is achieved. Note that for purposes of the study, controlled closing means closing at a 60Hz

source side voltage zero crossing, rather than at a minimum beat voltage point across the circuit

breaker. The implication of this is that the overvoltage distribution curve for actual controlled

closing at the minimum beat voltage across the circuit breaker will show an increase in

performance (i.e. it will be to the left of the shown curves). Viewed in terms of mitigation, the

curves show that in the extreme case with the control device out of service, the risk of exceeding

1.7 p.u. increases only to 10% which is considered acceptable [5].

2.C 2.2

ru «.<j»9_ v:».**ra.(! A . - 45tf *vj

a) no switching surge control b) with 400 Q closing resistors c) with 1.5 p.u. surge arresters at line terminations and staggered closing d) as for (c) and additional surge arrester at mid-line e) with controlled closing and surge arrester per (d) above

Figure 7: Cumulative frequency distributions for overvoltages at remote line end [51

The voltage profile along the transmission line was also examined in the studies. Figure 8 shows

this voltage profile for a number of the studied overvoltage control options. By consideration of

both Figure 7 and Figure 8, it is evident that only the controlled closing with the three surge

arrester option will meet the 1.7 p.u. limit at every point along the transmission line.

9

Page 18: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

203 240 2W0 320 XV *

!1;S FANCE f-RCV LE/.Q END [Kr.M

a) with 400 Q, closing resistors b) with 1.5 p.u. surge arresters at line terminals and staggered closing c) as for (b) with additional surge arrester at mid-line

Figure 8: Overvoltage profiles along transmission lines [5]

Specialised surge arresters are used compared to standard surge arrestors normally applied on a

500 KV system. A comparison of ratings is shown in Table 1 based on IEC 99-4[8].

These surge arrestors are considered specialised for a number of reasons:

1. The ratio of system voltage to surge arrestor rated voltage is 1.48 versus a typical value of

1.39 or less.

2. The ratio of Continuous Operating Voltage (COV) to rated voltage is 0.8 versus a typical

value of about 0.85

3. The switching surge protective level is 1.575 p.u. versus a typical value of approximately

1.8 p.u.

4. The energy absorption capability is higher than that normally required on EHV systems.

However, the rating is conservative since two consecutive surges of the noted magnitude

are highly improbable.

10

Page 19: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Requirement

Continuous Operating Voltage (kV rms)

Rated Voltage (kV rms)

Switching Surge Protective Level at 2 kA, kV peak

Line Class

Energy Absorption Duty Cycle

Temporary Overvoltage Capability

Standard

Surge Arrester

318

396

792

5

1.98 M J - 60 s -

1.98 MJ

Per IEC 99-4 or

better at rated

voltage

Special

Surge Arrester

318

372

709

6.7 (equivalent at

protective level)

2.5 MJ - 60s - 2.5

MJ

Per IEC 99-4 or

better at rated

voltage

Table 1: Comparison of Requirements for Standard and Specialised Surge Arresters on B.C. Hydro 500kV System [51

2.4 Closing Control Device Strategy

A control device (relay) was designed to measure the transient voltage signal and trigger the

breakers to close within the beat minimum on all the phases. The beat minimum is approximately

20 ms in duration and can be seen in Figure 9 as the "window of opportunity". Closing within the

window of opportunity is mandatory. If the control device aims to close the breaker within the

window of opportunity but misses, the overvoltage will exceed the surge capabilities of the line [6J.

It is therefore important that the control device is accurate and robust.

The strategy for the closing device is to delay the closing command appropriately such that closing

or prestrike of the contacts occur in the desired time window [6]. The control device utilises an

algorithm that recognises and analyses the voltage signal across the circuit breaker and then

predicts the occurrence of future optimal instants for closing (i.e. the beat minima) [6]. After de-

energization of the line, up to 300 ms are available for the control device to analyse the

characteristics of the voltage signal across the circuit breaker [61. Possible closing windows can

then be predicted. The scheme must incorporate mitigation measures to cover all possible

contingencies within the allocated computation time (approximately 300 ms) [6J. These

contingencies range from control device unavailability to failure to determine the optimal closing

instant [6]. Every circuit breaker has a certain closing time in the range of 50 ms. This means that

after the control device issues the closing command, it takes another 50 ms until the contacts

actually close [6]. Hence, the control device has to predict the shape of the voltage signal at least

50 ms into the future. The signal across the circuit breaker is periodically repeated at least two to

11

Page 20: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

M ,., • . 130 kV/ms CBCSosing stoke Presfrlke poirit „

I W \ — JJ_. W =i; — -ft ?5_. -j- — . _ .

;-, i i— Mir- r ~ V i — - - / % V ' ~ ' • v—^ • —

__ i — ' • : . • ; i f i t " ' r '.. i i 1 i

I , - ^ i — i ^ j | ^ * f l — \ ^ \ y . - . ^ . f . - ^ I » r r - i f «-—— i /--

•'••• : '--- _ t | — Jr-j-WirRtDW iM uppoitvinity 1 i ~

S t —^T"7 v~--_"_"_ Z\L Z i WD ' Voltage Acrojr*43rsa-k»t

Time (ms)

Figure 9: Closing stroke for system breaker superimposed on measured voltage across circuit breakers [7]

three times during the acquisition time of 300 ms after the line is de-energised; therefore, a fairly

accurate prediction of the future waveform can be made [7].

In terms of functionality and of being fail-safe with respect to auto-reclosing of the circuit breaker,

the control device is required to meet the following requirements:

- Work when either one and two shunt reactors are connected

- Bypass in the event of control device failure (e.g. loss of power, malfunction of the process,

etc.)

- Reclose at 60 Hz source side zero crossing, if the optimum closing instant is not selected on

application of the close signal

- Successfully complete Transient Network Analyser (TNA) and EMTP based testing before

installation.

2.5 Line Switching Tests

A series of line switching tests were carried out to verify the performance of the design concepts

and associated hardware [5]. Two line condition cases were considered, in the first case, the shunt

reactors were connected at both line ends; in the second case, only the fixed shunt reactor at the

lead end of the line was connected.

12

Page 21: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

BOO . O

- B O O . O B O O O

V R A o (kV) - S O O B O O . O

-BOO . O

: ° ]wiWWVW\/WW\AAM/\^^

— / H H ^ ^ - 2 . O J

e o o . o

.?«;•; j/wwwwwwwwwvwwwwwwwvw^

tKvf°:° IWWWIMAAAMA^^ — BOO . O .1

<*!°:°] ######^HMIV 1" 2 . O _,

CKAJ ° - ° - f ^ v ^ v r v ^ — - ' -"•• - - V W W " l / \ A / * J -

o . o 1 L

° - ° -—eoo.o J

eoo . o -

a o o . o V T C

( K V ) - B O

S O O . O

2 . O I L C r

( k A ) - 2 . O

- / l /WW/W/X/j-

lOO E OO SOO 4 0 0 5 0 0 S O O 7DO S O O 300 lOOO

VTA, B, C source side phase voltages VRA, B, C line side phase voltages VBA, B, C voltages across circuit breaker poles ILA, B, C line currents

Figure 10: Controlled auto-reclosing with two shunt reactors connected [5]

With two shunt reactors connected, the line oscillates at about 45 Hz on being switched out. The

voltage across the circuit breaker has a very pronounced beat with distinctive and repetitive

maximum and minimum amplitude points. The control device closed each pole of the circuit

breaker independently at a zero crossing within the beat minimum. As seen in Figure 10, this

resulted in no overvoltages and thus no energy was absorbed by the line surge arresters [5].

With one shunt reactor connected (low compensation as discussed earlier) the line oscillates at

approximately 33 Hz on being switched out. However, the voltage across the circuit breaker has a

less pronounced beat making it difficult to determine the periodic maximum and minimum

amplitude points. The control device therefore experienced difficulty in achieving optimal closing

on two poles (see Figure 11).

13

Page 22: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

VTA tkV) U - B O O B O O . O

V R A „ _ C K V ] 0 °

B O O . O G O O . O

V B A (K V) - B O

s . o 1 I A„ „

-a . o B O O . O

,zz?° - -- B O O .O B O O . O

\/\A.: £ . ^ / V W W

]M/WWWWWWWWWWW^

c*v?° ° ]/ i/WWW\AAAAAAAAAAAAAAAAAAAJi/W\W - 8 D O . O J

yvWiAA

s o o . o ..

— o O O , C J 8 0 0 O

: ^?o ' o W^AW\AAAA^^vv^^^V\AA,^^AAy^/^^A/^^ ,V

VvYVWW\rf/T\WWW^ — s o o _ o _.

— B O O . O 2 . O _,

i K A ) . J - W V V / V * / ^ .. _ y W W > -E>

O L-wv/

1 0 0 ? o o 3 0 0 -aoo s o o B O O 7 0 0 B O O s o o • "I I ME Cms J

VTA, B , C source side phase voltages VRA, B, C line side phase voltages VBA, B, C voltages across circuit breaker poles ILA, B, C line currents

Figure 11: Controlled auto-reclosing with one shunt reactor connected at lead end [51

The reclosing in all such instances was successful, however, overvoltages did occur. As expected,

the measured overvoltages did not exceed 1.7 p.u. in any instance and the worst case single-shot

energy absorption by a line surge arrester was approximately 1 MJ [7]. This is well below the rated

energy absorption capability of the surge arrester. This was because of the one feature of the

control device. That is, if the device has not chosen an optimal closing instant by the time the close

signal is applied, then a special default mode is activated to mitigate this circumstance. In this

mode, the closing target is a zero crossing of the source side voltage.

The control device and overall controlled switching scheme has been in-service since March 1995

and has functioned correctly without incident at the time that the paper was published (April 1997)

[7]. To improve performance for the one shunt reactor case, the control device software was

upgraded and successfully tested in November 1997 [7J.

14

Page 23: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

tkV)

tkA)

tkV)

(kA)

(kV)

(kA)

9 0 O

VBA, B,C - source side phase voltage ILA, B,C - line currents

Figure 12: Example of coupling between phases [51

2.6 Interphase Coupling Phenomena

Interphase coupling phenomena are caused by capacitive coupling and by coupling through the

neutral of the reactors, for the case where the reactor is grounded through a neutral reactor. This

means that as the first phase is reenergized during the reclosing operation, a phase shift due to

coupling occurs in the second and third phases. Figure 12 shows an example of the circuit breaker

closing on one phase and influencing the oscillation on another phase [6]. The same effect occurs

in the third phase again when the second phase is reenergized. The second and third phase voltages

show a dynamic phase shift. This causes a significant deviation from the original signal used by the

control device to predict the optimum closing instant which means that a signal measurement error

could possibly occur [6]. This deviation is shown in Figure 13. It is evident from the figure that the

coupling effect is significantly less in the second phase to close than this in the third (healthy)

phase to close [6].

15

Page 24: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Compensation of this error can be done only by adding a correction factor programmed into the

control device provided that the deviation from the optimal closing moment is consistent.

However, numerous EMTP simulations showed that the considered effect scatters statistically.

This means that neither a simple nor more complex systematic correlation between line

characteristics, switching angles and deviation from the optimal closing is derivable [6]. The value

of increase in the second phase is negligible and that in the third phase to close is not more than

20%. Both values are not too high and thus the maximum possible error will still allow the breaker

to close within the surge limits of the line [6]. The effect of coupling becomes relevant only if all

three phases are unfaulted during auto-reclosing, which is rarely the case. Therefore, for the

development of the control device such coupling effects were neglected [6].

Figure 13: Interphase coupling between phases during contact closure [6]

2.7 Conclusions

The following conclusions are drawn about the use of pre-insertion resistors or controlled breaker

closing using surge arresters on the BC Hydro 500 kV line.

Switching surge limitation on EHV systems can be achieved by making use of pre-insertion

resistors with line surge arresters and traditionally, pre-insertion resistors are used. Switching surge

limitation on systems can, however, be achieved through the combined use of line surge arresters

and controlled circuit breaker closing. This scheme displaces the use of circuit breaker closing

16

Page 25: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

resistors. Specific requirements are placed on the components of the scheme and the control device

provides fail-safe or default modes to guarantee that the circuit breaker will close. In the event of

such mode closing, a higher than design risk for exceeding the switching surge limitation level

must be accepted. The controlled closing scheme allows for the use of lower line insulation levels

which induces cost savings. Extensive field testing provided evidence of the scheme's robust

design and operation.

17

Page 26: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 3: SIMULATION MODEL OF THE ALPHA-BETA 765KV SYSTEM

3.1 Simulation Model Design

In order to predict the effects of faults and the reclosing of the Alpha-beta line with or without pre-

insertion resistors, a simulation model was designed. The distributed parameter line model was

used to represent the transmission line, as this is the preferred model for greater accuracy over

longer length lines (>250km) [10]. The distributed line parameters are determined from the

physical line parameters, i.e. resistivity, length, Geometric Mean Radius (GMR), etc. These

parameters are obtained from the manufacturer, and the model parameters are calculated by the

program detailed in Appendix B.

A Matlab-Simulink model is then constructed using the line parameters. The Simulink model is

shown in Figure 14. The two parallel transmission lines are clearly visible from the figure and both

lines use the distributed parameter model. To emulate the voltage transformer (VT) measurement, a

3 phase V-l measurement model was used to measure the voltage across the breakers.

StiluralJe 1 rsnrfonner E

Voltage Meaairernonn

Figure 14: Alpha-Beta 765kV system model in Simulink

The top line is compensated using two line reactors, whereas the bottom line is compensated with

the primary windings of saturable transformers. This is done to represent the effects of the reactors

saturating because there is no saturable reactor model in Simulink. The transformer is open

circuited on the secondary side and star connected to earth on the primary side. The parameters

used for the saturable transformers are obtained from the saturation curve provided by ABB.

Page 27: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

A load of 2500 MW and 500 Mvar is attached to the Beta substation, and a generating input of

2600 MW is supplied to the Alpha substation. The source block models at the Alpha and Beta

substations implement 3 voltage sources connected in star with the neutral internally grounded. The

inductance value is specified by the source inductive shunt circuit X/R level ratio. These values

were obtained via the PSS/E system model presently representing the Eskom transmission network

and are based on a typical operating condition for the line [1 ]. The breaker models on either side of

the line were adapted by putting two breakers in parallel, one with an internal resistance of 450

ohms. This parallel branch represents the pre-insertion resistor which closes 8 msec, before the

source breaker. The breaker block is shown in Figure 15. A further description of the block

parameters and model configuration is detailed in Appendix C.

O CDB CD'

If? 3-Phase

Breaker Ftea stance

TH Breater6

< m o

< fi o

4 CD O

Breater l

7W A2 B1 B2 C1 C2

•CD - ^ • C D

Cb

Figure 15:

Subsyaem

Model breaker with a 450 ohm pre-insertion resistor connected in parallel

3.2 Testing of the Simulation Model

In order to ensure that the model's output is accurate, a past incident must be recreated. The

measured and simulated values can then be compared to determine the simulation error. The

incident which occurred on 26/01/1999 was chosen [4]. During this incident, a three phase line

fault caused all the phase breakers to open at both Alpha and Beta substations. The ring down

voltage waveform was extracted and is displayed in Figure 16.

19

Page 28: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

.'IfIf . ,

'•% : o r • i -

tt) • 1 D

cp !' _ J C '•' : . I . . I . •

4 ) .' ' '

- ' • f • ,' > . ' '

' ' f * H i ', • * * ' J ' ' ' ' ' i 1 1 . . ! . _ . . ._ I_. _J _.! . . . J . . i ' c? o.-i o.Ci :\e 0 7 o.t o.e

Time (s)

Figure 16: Resonant ring down voltage after opening [4]

Data from another incident (26/05/2006) was recorded [4]. Figure 17 shows the actual reclosing of

the Alpha breaker onto the ring down voltage after 3 seconds. The breaker opened for a fault on the

line and reclosed after 3 seconds. However, the Beta breaker failed to reciose and thus the Alpha

breaker reopened. Figure 18 shows an extract from the ring down voltage shown in Figure 17.

900.0

-900.0:

-nnun-

Figure 17: Actual ring down before and after breaker closed 26/05/06 f4]

The amplitudes and frequencies from each incident are calculated using Matlab and the program

code appears in Appendix A. The actual ring down frequency from the two incidents is calculated

to be 43.23 Hz. Running the simulation under the same conditions yields a ring down frequency of

42.5 Hz as seen in Figure 20. Therefore, the simulation results differ from the measured results by

0.73 Hz (+1.7 % error). This provides confidence in the accuracy of both the simulation model and

simulation results.

O - / I." '

••40!

White Phase Volt White 435.3KV/ cm

20

Page 29: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

32C

I =g -i;Ki' >

2C0 ' v;

y / \ '

0.08 o.io o.i;

l ime (rns)

10 0.18

Figure 18: The extracted ring down voltage waveform [4]

3.2.1 Comparison between study and case study results

The figures (Figure 19 and Figure 20) below show the comparison between the voltage measured

across the breakers of the BC Hydro 500 kV system in the case study and the Eskom 765kV system

in this study. The BC Hydro 500 kV system is 80% compensated and the Eskom 765kV system is

60% compensated, explaining the slight difference in the resonant frequency of 45Hz on the BC

Hydro system and 43Hz on the Eskom system.

The overvoltages resulting from the compensation are not compared, as the purpose of this study is

to find where the minimum voltage occurs to enable the closing of the breakers without the use of

pre-insertion resistors. The case study presented was performed to investigate how compensation

affects the closing voltage for controlled switching.

% \ | !' r 1

I • I

| ! j i I I j j i h , , / i ! i i j i i j

1 : i - i I ! : I I I ' ' ' ' !

S

* i i !

Figure 19: Voltage across open circuit breaker - Degree of Compensation 80% Case Study (BC Hydro) [6]

21

Page 30: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

x 10

> 0 5

Voltage across open ,breaker is minimium

I i, \i\

Ir '.]•

Il l Ml

\} I

M 1

11

m Kl'l

I * i

l l . i

'id

iii

ik i l I 1 i

I . I

II i I1

I;

ill 1 i

0.2 0.6 0.8 Time in seconds

Figure 20: Voltage across open circuit breaker - Degree of Compensation 60% (ESKOM)

22

Page 31: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 4: ALPHA-BETA 765KV SYSTEM SIMULATION

4.1 Simulation Aim

The aim of the simulations is to determine what effects the various protection schemes will have

on the transient voltages. Both the pre-insertion resistor and controlled shunt reactor switching

schemes will be simulated to determine which scheme yields the best results.

4.2 Simulation Methodology

Several simulations are undertaken to emulate the various protection schemes and system

conditions. In each case a fault is simulated by simply opening the breakers at both the Alpha

and Beta sides of the line. For the purpose of the line reclosing, only two frequencies are

relevant: the power system frequency on the breaker source-side and the fundamental ring down

frequency on the line-side. The voltages at the source and at the line breaker sides are of similar

magnitude, and the voltage measured across the breaker has a beating form. The following

conditions are simulated.

• Reclosing at minimum differential voltage between busbar and line with pre-insertion

resistors included.

• Reclosing at minimum differential voltage between busbar and line without pre-

insertion resistors included.

• Reclosing at maximum differential voltage between busbar and line with pre-insertion

resistors included.

• Reclosing at maximum differential voltage between busbar and line without pre-

insertion resistors included.

Note that when the pre-insertion resistors are used, they are connected 8 ms before the line

breakers are closed.

4.3 Simulation Results

4.3.1 Simulation 1 - Reclosing at minimum differential voltage with pre-insertion resistors included

This simulation is used to determine the voltage transient effects caused when the pre-insertion

resistors are used. The line breakers are closed at 0.8 sec. when the beating differential voltage

across the line breaker (Seen in Figure 23) is at a minimum. It is evident from both Figure 21

23

Page 32: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

and Figure 22 that the overvoltages are + 1 0 % of the system voltage at Alpha and Beta. This

overvoltage is within the surge capabilities of the equipment on the line [2].

x 10v

0.6 0.8 Time h seconds

Figure 21: The Alpha breaker reclosing at minimum voltage with the inclusion of pre-insertion resistors

> 2<~-

'.D 0

l'i!!!M!!!'i!: II l l l j i ipjM

It I I I

ii

I I*. "i.'1 i1 I

I l l l ^ t ^ i J i m * ijii«i.;.f;

overvol tage 10%

!l HI

!!l I

'! ' M i l l 1 ' 1 ' I J l i l l '

0.2 0.4 0.6 0.8 T ime in seconds

1.2

Figure 22: The Beta breaker reclosing at minimum voltage with the inclusion of pre-insertion resistors

24

Page 33: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

i i : 1 1.2 1.4

Figure 23: Difference in voltage between line and busbar at Alpha

4.3.2 Simulation 2 - Reclosing at minimum differential voltage without pre-insertion resistors included

This simulation is used to determine the voltage transient effects caused when the pre-insertion

resistors are not used but the line is reclosed when the differential voltage across the breaker is

at a minimum. The line breakers are closed at 0.8 sec. when the beating differential voltage

across the line breaker (Seen in Figure 26) is at a minimum. It is evident from both Figure 24

and Figure 25 that the overvoltages are +10 % of the system voltage at Alpha and Beta. This

overvoltage is within the surge capabilities of the equipment on the line[2].

;-^- -overvol tage 1 0%

Figure 24: The Alpha breaker reclosing at minimum voltage without the inclusion of pre-insertion resistors.

x i c r

0.5 -

Voltage across open [breaker is miri imium

"!/ I, ' • ^ i ; '

i

tf

if J !

li

Ijl'ljli I fil

J I

m '<M

HI II

i ' i

v w

0.6 0.8 Time in seconds

25

Page 34: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

< 1 0

111"! 1 ;v| n l

| O

2

•A

6 ;

I |

*l"

I1

1

III

i1

!

i

i. i II

liSil"

jiltl HI i

i

1 !i I 1 I i ' ! i'' !i 11 i i

[!'i I f l l i 'Jill j

I 1 1 1

1 '

r

! M i i . i ,

i i| f ji|i I I l ) ! |

H !iw h W\ tl 1 1 | '| !: i

l i l i ' ii ii ' P

il h i t 'J \i f '1 Ml 1 i

! | M 1 1 i i i

i i ' •

i • J ,i i II

:| In i '

' l i 1 ' !! ji'jIIJl

+ai- -overvoltage 10%

! i ,i

i '

11 i

i

HUH I

||

If 11,

!'l Ii

,li I I

1

V I I

i 1 ] •

1:

if > Ii

;-

i

!

ii

1 iPli I hi 1

1

|) l

i i;i 1

is'i in

i

i

i

s 1

'i

1

Il i i

ill'1

fi ||

III I I I !

(•

1 1

j j i • i •i

SPl'f ti in

i l l II I:, i

ii 1!

: 1 III

" I3' i i i i

Mi

|l

i1

i

i

0.6 0.8 T ime in seconds

Figure 25: The Beta breaker reclosing at minimum voltage without the inclusion of pre-insertion resistors

C.5

0

-C.5

- l .S

x 10 '

Voltage across cpen ,breakei * minim um

- ! i

i

ii

i i

- jji-

1 i1

- 1 ) 1

il 1 1 - i

II

1/ i • i i i ' i i :

U

II m:--[\ h ,f • I f ! . !

ill IS 1 pi Ii! Y

i , ii l.'i"l 1 ' I 1

I' lit) 1 | II'

1 M1

ii'l l i l f tP lwi\

1

vv! - I l - - ' f- : • -ipJ:iii M

i m\\\

IP If If If •j i- l i i:l

I:

_._!. _

. ..L

» .1

Hill,., |;

' 1 i

i . . . . . . .

iiffl; pi li I'1- :

• ' t - - i i -

| l|'; :

I I ' ; ; .

D.6 0.8 T ime in seconds

Figure 26: Difference in voltage between line and busbar at Alpha before reclosing

4.3.3 Simulation 3 - Reclosing at maximum differential voltage with pre-insertion resistors included

This simulation is used to determine the voltage transient effects caused when the pre-insertion

resistors are used but the line is reclosed when the differential voltage across the breaker is at a

maximum. The line breakers are closed at 0.9 sec. when the beating differential voltage across

26

Page 35: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

the line breaker (Seen in Figure 29) is at a maximum, ll is evident from both Figure 27 and

Figure 28 that the overvoltages are +10 % of the system voltage at Alpha and Beta. This

overvoltage is within the surge capabilities of the equipment on the line [2],

x 1CT

jv . 2

-6

.Point of.sv.'ttcbung:

ill ! -!i i l ,! ! 11 j

I I I ) illl'H't'lfiVRii i

I I H l U P I I'I T U ' - ' • -I -rl- l:l- il H1 rfll Hiii • \M

l!

:, i j; - t - i

1 0 % ove rvo l tage

111

1 - ' h i ' M '• i i

Resonan t v/3hage

i i 0 6 0 8 ~ir-iR n s^r.oncl5=

ili'.illll!

Figure 27: The Alpha breaker reclosing at maximum voltage with the inclusion of pre-insertion resistors

I I t 1 hi n

1, , '!.• 1 M l i I1

i 1 Ml - 1 - i

''! in, •

:;

1 il 'h 'i

':? J i i l l 1 1 >\ 1

Mil Hi i i l , 1

is 'ip Hi1'1

H s;i i ! 1,1 i ' M " . ' ;

; , , ] h ; i ( '

j

0 2

Point of sw i t ch ing :

i :

MM | J!

i i • •

li m | Mil \ i -

ii1 i :i ' 4 ! '

1

0-4

. i l i ' : . \ I M ' l l r H . l . l .

I ' : , i:,-'i . :; '"i !-4l i

I I I I 1 I 1 , 1 1 , j ' . ! '• 1 1

' I ' l 'Hi '•, I ! j , ,

1

1 1 il ;ii 1

1 M Mi it!"'MM ii !

. ' ' IP 1 : 11 1 :r 1

•' i i

• / h i 1 -v ' 1' 1 , 1. !

1 11 . ' ! ' 1 ' 1 ' i '

i J , 1 „ ; i i i ' ihv; [ ; ! i i ! 1 8 ' : ' j i • 1 i 1 ' t

Resonan t vo l tage

1 1

0.6 0.8 T ime ir i secon ds

- 1 0 % ovecvo

I I i I \ A 1 I I 1 1 1 i ; l l

! I IM ' 1 '1 'H ' I ' l l jl j i | : !| 1 [1

ll 1

ii III ' 'iiiill' :i

(i . | l | l ( l i . . i i

mil' I ' 1 1

n I In

I • i

|||!|

• I

I 111!.

I tage

i ! I

I Mi

11'l

i l l 1

1. 1

|i| iii

1 1 .

i 1.2

1

"

i

Figure 28: The Beta line breaker reclosing at maximum voltage with the inclusion of pre-insertion resistors

27

Page 36: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

3.&

Figure 29: Difference in voltage between line and busbar at Alpha before reclosing

4.3.4 Simulation 4 - Reclosing at maximum differential voltage without pre-insertion resistors included

This simulation is used to determine the voltage transient effects caused when the pre-insertion

resistors are not used (i.e. the pre-insertion resistors fail to close) but the line is reclosed when

the differential voltage across the breaker is at a maximum. The line breakers are closed at 0.9

sec. when the beating differential voltage across the line breaker (Seen in Figure 32) is at a

maximum. It is evident from both Figure 30 and Figure 31 that the overvoltages are

approximately +50 % of the system voltage at Alpha and Beta. This overvoltage is not within

the surge capabilities of the equipment on the line and therefore there is a chance that the

components will be damaged [2]

o o

point of swi tch ing

fll'i.l Hi . . ' , '.",!. " I'"'"'-'- '

i|

i (i

hi; t II I Ii ;

III •

iil (SfCltiijIltliUli 11 §M WW

1 ii lililll 1, illill - I 1 I1 tillIIij i

i !i i 11 ! I si 1 i l " 'MM

J i

h ' ! l U ' ' ' It:' 1 i " "

"• '" l " : •". : r e s o n a n t v o l t a g

r i 1

fiirt

lii",! S I H

< - . ."". :oyervo ! ta j

I • •

1

Hi II p i t if 1 : i: : ' '< 1 I

llii'l In i 111,11,1 1 1 1

i 1 ' 1 ! : i i i j111

I

e 1

i

If I ' l l .,, J1!!

11 Illill.

e

Ii" l f -i i ! | l ' 11

I1" ni l

....

0.6 0.8 Time in seconds

Figure 30: The Alpha line breaker reclosing at maximum voltage without the inclusion of pre-insertion resistors

28

Page 37: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

" 2

point of swi tching

'Hi

i1

iiiiii i hi

r .'.'-ii in

i

i:' ill niil'PW

!|! | | ! f | i | l !! ih ' I I I ! ! h i « «>'' mm if

H'i!! i i i i i i

i

resonant vofltage

0.6 OS T ime in seconds

Figure 31: The Beta breaker reclosing at maximum voltage without the inclusion of pre-insertion resistors

— 0 . 6 - 1 - •

Closed at voltage maximum

m HI

I'r

C.S 0 8 Tirve :~i seconds

Figure 32: Difference in voltage between line and busbar at Alpha before reclosing

29

Page 38: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

4.4 Interpretation of Simulation Results

Several conclusions can be drawn from the four simulations presented above. It is concluded

that pre-insertion resistors are able to reduce the transient overvoltage to within the surge

capabilities of the line. However, should the resistors fail to close, the overvoltage exceeds the

line surge capabilities and damage can be done to its components. Controlled switching within

the beat minimum without the use of pre-insertion resistors, also yields an overvoltage which is

within the surge capabilities of the line. It is therefore concluded, from a theoretical perspective,

that controlled switching is a viable means of transient protection on the Alpha-Beta lines.

30

Page 39: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 5: DESIGN SPECIFICATIONS FOR A CONTROLLED SWITCHING RELAY

The convenience of controlled switching devices for use on the Alpha-Beta line is evident from

the discussion in the previous chapters. Such a device is not yet readily available and must

therefore be designed. A design specification for this device is given in order to initiate the

design process of such a device. These devices will possibly be used for the future 765 kV

transmission network in South Africa.

5.1 Switching Constraints

There are several criteria which must be met in order for the proposed protection scheme to

function correctly. The relay must measure the differential voltage across the line breaker and

attempt to reclose within the beat minimum for each phase. This objective is highly dependent

on time and thus all possible time errors and constraints must be considered.

It is evident from Figure 33 that the beat minimum or reclosing period exists for approximately

50 ms on the Alpha-Beta line when it is compensated by both reactors on each end of the line.

This means that if the breaker is set to close in the middle of the beat minimum, a closing error

of up to ±25 ms can occur without stressing the line equipment. The errors due to the sampling

and measurement of the voltage signal must therefore not produce a closing error of more than

±25 ms.

-6 x 10

o >

-1.5

Figure 33: Differential voltage across the breaker at Alpha with the line compensated by both line reactors.

31

Page 40: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Other errors could occur due to the varying time taken to close a breaker. The relevant breakers

have a closing time of approximately 50 ms [7]. This means that there is a 50 ms gap between

the issuing of the close command by the relay, and the closing of the breaker. However this time

can vary by as much as ±1 ms with a standard deviation (a) of 0.6 ms for a compensated

line [7].

5.2 Relay Functional Overview

A relay consists of three main functions as well as a group of auxiliary functions where the main

functions are the input sampling of the voltages on the busbar and line side, the hardware

filtering of these quantities to cutoff any unwanted frequencies, frequency tracking of the

waveforms, computation of the phasor quantities, computation of decisional variables and lastly

the computation of the close logic output. The auxiliary functions include the control logic,

auto-verification, event recording, synchronization and communication.

A description of the primary functions is presented hereunder.

5.2.1 Analogue Input Quantities

These consists of three busbar voltage transformer input quantities and a single channel line side

voltage transformer input quantity connected as a phase-to-phase measurement. The analogue

input circuitry is responsible for converting these power system voltage waveforms into digital

form for use by the relay processors. These consist of hardware filters and analogue to digital

converters with appropriate sampling circuitry.

5.2.2 Frequency Tracking and Phasor Calculation

Frequency tracking is an essential component of any relay to ensure that the sampling period for

digitally calculating the phasor quantities is correct as the power system frequency varies. The

phasor quantities are are typically calculated using techniques such as the full cycle Discrete

Fourier Transform.

5.2.3 Relay Algorithm and Output Decision Logic

This is the main software function of the relay and consists of various signal processing, logic

operations, level detection techniques that allow the algorithm to be fine tuned for a wide range

of applications.

32

Page 41: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

5.3 Algorithm Functional Design and Implementation

A Matlab Simulink model has been developed for the proposed algorithm based on the design

criteria discussed earlier. The Simulink model is shown in Figure 34.

Figure 34: Relay model in Simulink

The busbar and voltage input waveforms are generated from the Matlab-Simulink power system

model discussed in Chapter 3. These quantities are then passed to a low-pass filter and then

frequency tracked using a phase locked loop Simulink block for the A phase only. This provides

the frequency for correct calculation of the phasor voltage quantities which represents the

system voltages in terms of rms magnitude and angle quantities. These quantities are used to

calculate the beat frequency of the difference voltage across the circuit breaker. The function

also calculates a rms voltage from the discrete sample values for the beat voltage. These filtered

analogue quantities are used to calculate decision variables such as the delta voltage (rate of

change of voltage over a set period), closing time predictor and threshold detector which feeds

the control close output logic decision. These components are discussed below:

5.3.1 Analogue Input Design

The voltage inputs are sampled at 48 samples/cycle, which is typical for a modern numerical

relay, passed through a gain function which represents the voltage transformer ratio for the

application and a low pass filter with a cut-off of 200Hz which is up to the 4th harmonic. The

performance of the filter is shown below showing a small phase error at nominal frequencies.

33

Page 42: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Discrete 2nd-Order

Filter 3

Figure 35: Filter design parameters

Bode Diagram

Figure 36: Filter Performance

5.3.2 Frequency Tracking

The frequency on the line side on breaker opening is at nominal 50Hz and immediately after

breaker opening is at frequencies of between 30Hz and 45Hz depending on the level of

compensation. Simulation results for the Eskom example shows frequencies in the order of

33Hz and 43Hz for the condition where one or two reactors are in service. The frequency

tracking algorithm starting from an initial frequency of 50Hz would take time to track to the

resonant frequency as shown below for the 43.23Hz example. Here the breaker is opened for 0.8

seconds and the initial frequency was at 50Hz and as can be seen the function struggles to track

the frequency very quickly. In fact the requirement is that the tracking algorithm should lock

onto the frequency by the arrival of the first minima which could be within 150msec. It is

34

Page 43: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

proposed that the breaker status trip and reactor status bits be mapped to the function to change

the initial frequency estimate on breaker opening. The performance is shown below where the

breaker is opened for 0.8 seconds and the initial frequency was estimated at 43Hz so therefore

the function quickly locks onto this frequency.

frequency Hz

Figure 37: Frequency tracking performance with an initial estimate of 50Hz on breaker opening

frequency,

Hz

Figure 38: Frequency tracking performance with smoothing function and good initial estimate of frequency

35

Page 44: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

As can be seen from Figure 38, the resonant frequency is not constant and causes oscillations in

the estimate. To smooth the frequency over a few cycles, the standard PLL function was

modified with a weighted moving average function which block samples and holds the most

recent samples for averaging.

Discrete 1-phase PLL

Discrete

Variable Frequency

Mean ralje

PI w w

Discrete

PI Con'roller

Discrete

Rate

Discrete

Rale Limher

\^}-*

. . i l l l l l l l l l l l l l

Weiglitec

Mow rig A*rage

-*& Discrete

2 n-3-Order

Filter

-+CD

S;n_Cos

LK±) Freq

Note: sin (a )* cos( b )= 1/2" sin(a+b) +1 /2 ' sin ia-bi

Figure 39: Modified Simulink Discrete 1-phase phase locked loop function

5.3.3 Decision Variables and Logic

The decision variables are the primary quantities used to describe and detect the phenomena and

used to feed the actual decision logic. Three quantities have been derived from the measured

data namely, the rms value of the differential voltage across the line breaker, the beat frequency

and period of the differential voltage and the rate of change of frequency of the differential

voltage measured over a number of cycles.

5.3.3.1 Differential RMS Voltage Threshold

The rms voltage is calculated from the measured instantaneous voltage inputs and calculated

over a running window of one cycle of the fundamental frequency.

36

Page 45: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

200

Voltage

kV o

200 0 0.1

Instantaneous Differential Voltage

RMS Voltage

200

100

0.9

Figure 40: Instantaneous and RMS Differential Voltage comparison

The voltage minimum of the rms value corresponds very well to the instantaneous differential

voltage and is used to track and provide a robust signal for when the voltage minimum occurs. It

is also used as minimum rms voltage threshold detector below which the voltage must be to

allow the closing logic to proceed. This is a settable threshold which can be modified depending

on the application requirements. The performance of the minimum threshold detection logic is

shown below.

37

Page 46: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

200 ( r

Voltage kV o

Instantaneous Differential Voltage

i i f

0.1 0.2 0.3 0.4 0.5 0.6 time (sec)

0.9 1

Figure 41: Minimum rms differential threshold detector performance

5.3.3.2 Delta Differential RMS Voltage

This function calculates an average rms differential voltage over a user settable buffer size (in

cycles), stores it and then calculates a delta measurement as the difference between two

consecutive average values as follows:

AV/ AT = Vave, blllTer(T) - Vave blI1Ter(T-l)

This tracks the changing measurement and provides a means to check for a gradient change or

zero crossing. The function with its performance is shown in the following figures:

Q >

&

PEP

III!! Weijhtad

Figure 42: Delta differential voltage measurement logic

38

Page 47: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Voltage

kV 0

5111)

1 Instantaneous differential voltage

1

i

4 i

i i

•) I !j

1. 1 * ,

/

ill' V

II "'

! j

Nl

;'

f i l

1

1 ' 'i

IP

i i I

1 1 1

V

i

^

il ( Delta diffential voltage

y / ft

0.2 0.3 0.4 0.5

Time (sec)

0.6 0.7 0.8

Figure 43: Delta differential voltage measurement comparison

The delta measurement quantity is further integrated to provide a robust signal for detecting the

minimum differential voltage point and provides a trigger input for the resonant frequency

function discussed next. The integrated signal is delayed by a cycle but this is compensated for

in the output logic decision.

voltage

kV

Figure 44: Integrated delta differential voltage measurement comparison

39

Page 48: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

The trigger is determined from the voltage minimum of the integrated waveform and provides a

consistent signal for detecting the voltage minimum. This in turn is used to trigger a counter

which is used to determine a minimum number of counts before the output logic is allowed to

issue a close command.

Voltage (kV) ?"

/ \ 1 1 .' 1

1

1 i

/' 1 ;

.11,. _±

Integrated delta differential voltage

/ ; •

'''• ' 1 / '

: • \ ; 1

1 . . * •

n

• \ ! 1 I I

imum detects

i . . . „. ...J..

1

trigger

i i

11 II ^ 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

time (sec)

Figure 45: Integrated delta differential voltage minimum detection

Trigger

i. threshold detector

0 0 1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

Figure 46: Minimum number of counts before the output logic

5.3.3.3 Beat frequency and period function

Trigger

Minimum Counter

This is calculated as the difference in frequency of the busbar frequency and line frequency,

which is the beat frequency and represents the resonant frequency of the ringdown voltage (i.e.

the beat frequency). This is shown as follows:

40

Page 49: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Bus_Frequoncy

From Workspace

• leatfrequency

To Workspaces

J Divid

beatperiod

To Workspace2

Line Frequency

From Workspacel

From_Delta_Measurement _Trigger

Discrete Sample & Hold

From Workspace2

Figure 47: Logic for calculating the beat frequency

Hz

h e a l f r e q u e n c y

Figure 48: Calculated Beat frequency

Busxoltages I 1

0 2 0 . 3 0 . 4 0 . 5 0 .6 0 . 7 0 . 8 0.1

0 2

0 IB

0 16

0 14

0 12 beat period(sec)

0 02

I)

~i r-

Instantaneous Output

Sample-Hold Output

0 2 0.3 0.4 0.5 0 6 0.7 time (sec)

0.8 0.9 1

Figure 49: Instantaneous and sampled results for the beat frequency period

The actual beat frequency varies with time as seen in Figure 48 thus the instantaneous value for

its period follows the same trend. The actual beat period value used in the decision logic is

41

Page 50: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

sampled at the instant the minimum differential voltage occurs using a trigger from the delta

differential rms voltage function and then using a sample and hold logic to provide an average

measurement over the beat period.

5.3.3.4 Closing Logic Function

The final closing logic is shown below and combines the output from the counter function and

the predicted closing time which is the beat period minus the compensation time with a running

timer which starts on a voltage minimum detection trigger and resets on the next trigger. This

allows the running time to be compared to the predicted closing time and a closing decision is

allowed if the running timer has exceeded the predicted closing time.

The closing condition is therefore only valid if the following conditions are met:

1. The number of minimum counts has exceeded a set value of two

2. The rms voltage is below the set threshold

3. The running timer has exceeded the predicted closing time and therefore allows a close

command

beat period

Subtract 5

lata Store

Read

Data Store Write

n

Relational Operator

Data Store Write 1

From Delta trigger

To closing logic

Data Store Memory

Data Store Memory 1

Figure 50: Logic to calculate closing time based on the predicted time

42

Page 51: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

Prom integrated delta function

• ->

->

U> U7z

Detect Increase

U< U/z

Detect Decrease

Trigger tor beat period function Da, f

-*r

— • NOT -

Logical Operator 1

iniB (SI)

Type Convers

A N D

Logical • •

Jpera 01 *

Discrete

I

°n W*1 1_

! '

n Memory

^ Constant 2

From timer logic

Trigger for timer function

+

1 i B Itaae* -3

k .

£ • h

jbtract 4 ' •

2

nstart!

>-—' Relational

Operator 1 L^. 1 ->

A N D

Logical Operator

— 2

Figure 51: Counter logic and final closing logic

The overall performance of the closing logic is shown in the Figure 52 taking note that this is

based on a counter setting of two which means the closing pulse is only given after two

minimum thresholds are detected.

200

i Instantaneous differential voltage ;l

i

| l

" '! V

{

i l l I1

ll

/

1 1 i f

f

1 ..

I ' l l

i

1 • 1

II i ll

i •

1 \\

t 1 J i'l'll

1 1

\'\ 1

i M ji i w

11 . '

• . 1

1

«

, 1

1

1

i 1 )

III nimi • i j 1

|l 1 | 1

' M l

' t

II k r 1 '

l|

1 \ I1 !' x\

| i

;, | : '

lift :l \\\y

>K 1

1 1 _ _ L 1 J 1

> !

i

Closing pulse

/ '

|

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

time (sec)

i

U..'i

u

Figure 52: Closing logic performance with a count of two setting

43

Page 52: DEVELOPMENT OF A MODEL OF THE ALPHA / BETA AUTO …

CHAPTER 6: CONCLUSION

Automatic reclosing on the Alpha-Beta, 765kV, shunt-reactor compensated line can cause very

high transient overvoltages. These overvoltages are caused due to a resonance voltage

remaining on the open line. The resonant signal is caused due to the capacitive and reactive

components of the line and its frequency is therefore dependent on the degree of compensation

used. Traditionally, pre-insertion resistors are used to reduce the transient overvoltages to within

the surge capabilities of the line. A Simulink model of the Alpha-Beta 765kV line was

constructed and used to study the performance of the existing pre-insertion resistor protection

scheme. It has been shown that the resistors are able to reduce the overvoltages to within the

surge capabilities of the line. However, if the pre-insertion resistors fail to operate, the line

components are exposed to dangerous overvoltages. Several such incidents on the Alpha-Beta

line were recorded and analysed.

An alternative protection scheme, which has been used by the BC Hydro utility, was

investigated. The protection scheme involves closing the line breakers at the moment when the

differential voltage between the busbar and line is at a minimum. Simulations of the controlled

closing scheme, on the Alpha-Beta line, proved that it is able to reduce the overvoltages to

within the surge capabilities of the line without the use of pre-insertion resistors. A relay must

be designed to facilitate the controlled closing. This relay will be able to predict the optimal

reclosing moment and then issue the close command to the breaker. The relay must be robust

because the resonant voltage signal is dependent on the specific conditions of the line such as

the degree of compensation and faulted phase.

Since pre-insertion resistors are currently installed on the Alpha-Beta 765kV system, the

controlled closing relays could be installed in conjunction with the resistors. This can be done to

facilitate field testing without jeopardising the stability of the network. Should the solution

prove to be feasible after field testing, the controlled closing methodology could be

implemented throughout Eskom's future 765 kV network. This would directly save costs

because the use of expensive pre-insertion resistors would be unnecessary.

44