diesel generating set cummins series -...

13
DIESEL GENERATING SET Cummins Series Jensonn Power Systems Co., Ltd Jensonn Power Systems Pte Ltd

Upload: hoangdiep

Post on 04-May-2018

292 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

DIESEL GENERATING SET

Cummins Series

Jensonn Power Systems Co., Ltd Jensonn Power Systems Pte Ltd

Page 2: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

PERFORMANCE FEATURES HIGH-PERFORMANCE Jensonn generating system guarantees the following levels of performance:

TEMPERATURE RISE: 125℃ temperature rise at 40℃ ambient.

INSULATION: Class H

VOLTAGE REGULATION: Within±0.5% - Within±1%

FREQUENCY REGULATION: Within 0.5%

VOLTAGE WAVEFORM: Deviation Factor of open-circuit terminal voltage does not exceed 0.06. Telephone Influence Factor(TIF) is less

than 50.

ELECTROMAGNETIC INTERFERENCE LEVEL: Attenuated to meet most commercial requirements.

INSULATION RESISTANCE: Higher than 3 Mega-ohms, measured between armature windings and earth, field windings and earth,

field control circuit and earth.

� The innovative excitation system fitted on all models, in conjunction with the AVR and advanced brushless generator, provides fast voltage

regulation in response to load variations, enabling use soon after start up. This system provides output stability during

load variations.

� Synchronous brushless alternator for minimal wear.

� Designed to function in all climatic conditions.

� Will safely power the most sensitive loads, such as thyristors, invertors and computer systems, without the risk of damage to these loads, due

to the high level electrical characteristics of the generator's output.

ECONOMICAL PERFORMANCE � Easy starting and quick response.

� Applying highly reliable diesel engines with low fuel consumption, manufactured by international leading engine manufacturers.

� Uninterrupted generator operation for up to 12 hours under 75% load

.

USER-FRIENDLYDESIGN

MAINTENANCE MADE SIMPLER

� All daily maintenance requirements can be performed from one side of

the machine. The large doors gives you full access to the engine.

� External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance.

� Large fuel gauge is fitted for simple viewing.

� For major engine overhauls, the bonnet can be simply unbolted, which allows full access to the engine.

TRANSPORTABILITY

� The new designs have achieved significant size and weight reductions over previously models, through improvements in coupling techniques

and alternator design.

� The sturdy weatherproof steel bonnet on a heavy-duty steel skid base allows easy handling by a forklift.

� The balance point lifting hook (lug) fitted on the roof of each machine facilitates easy transportation using a crane.

� All models are modular designed, so that generators can be stacked, thereby making the best use of your valuable storage area.

Page 3: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (28kVA~55kVA)

Model J5G28C J5G41C J5G46C J5G55C

Prime rating(KW/KVA) 20/25 30/37 34/42 40/50

Standby rating(KW/KVA) 22/28 33/41 37/46 44/55

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model PI144E PI144J PI144K UCI224D

Frequency Hz 50

Output Rating(KVA) Continuous 25 40 42.5 50

Standby 27.5 44 47 55

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 380-415

Power Factor 0.8

Voltage Regulation (%) Within ±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model 4B3.9-G1 4BT3.9-G1 4BTA3.9-G2 4BTA3.9-G2

Type Water-cooled, Direct

Injected, Naturally

Aspirated

Water-cooled, Direct

Injected, Turbocharged

Water-cooled, Direct Injected, Turbocharger&

Aftercooler

Output Rating(KW) Continuous 24 36 50 50

Standby 27 40 55 55

No. of Cylinders-Bore × Stroke(mm) 4-102×120 4-102×120 4-102×120 4-102×120

Piston Displacement(L) 3.9 3.9 3.9 3.9

Fuel consumption(L/h) 7.1 10 12.9 12.9

Lube Oil Sump Capacity(L) 10.9 10.9 10.9 10.9

Coolant Capacity(L) 7.2 7.2 8.3 8.3

Battery × Qty 60AH×2 60AH×2 60AH×2 60AH×2

Fuel Tank Capacity(L) 170 170 170 170

Unit

Dimension

Open / Soundproof

Length(mm) 2000 2480 2000 2480 2000 2480 2000 2480

Width(mm) 730 1100 730 1100 730 1100 730 1100

Height(mm) 1500 1740 1500 1740 1500 1740 1500 1740

Dry Weight kg 850 1160 1100 1410 1150 1470 1170 1490

Page 4: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (60kVA~125kVA)

Model J5G60C J5G91C J5G106C J5G125C

Prime rating(KW/KVA) 44/55 68/85 77/96 91/114

Standby rating(KW/KVA) 48/60 73/91 85/106 100/125

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model UCI224E UCI224G UCI274C UCI274D

Frequency Hz 50

Output Rating(KVA) Continuous 60 85 100 120

Standby 63 90.8 110 130

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within ±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model 4BTA3.9-G2 6BT5.9-G1 6BT5.9-G2 6BTA5.9-G2

Type Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Water-cooled, Direct Injected, Turbocharged Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Output Rating(KW) Continuous 50 86 86 106

Standby 55 92 92 116

No. of Cylinders-Bore × Stroke(mm) 4-102×120 6-102×120 6-102×120 6-102×120

Piston Displacement(L) 3.9 5.9 5.9 5.9

Fuel consumption(L/h) 12.9 21.7 22 27

Lube Oil Sump Capacity(L) 10.9 16.4 16.4 16.4

Coolant Capacity(L) 8.3 7.9 7.9 10

Battery × Qty 60AH×2 80AH×2 80AH×2 80AH×2

Fuel Tank Capacity(L) 170 280 280 280

Unit

Dimension

Open / Soundproof

Length(mm) 2100 2480 2550 2930 2550 2930 2550 2930

Width(mm) 730 1100 830 1100 830 1100 830 1100

Height(mm) 1500 1740 1550 1800 1550 1800 1550 1800

Dry Weight kg 1190 1510 1250 1780 1280 1830 1450 1870

Page 5: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (150kVA~220kVA)

Model J5G150C J5G175C J5G200C J5G220C

Prime rating(KW/KVA) 109/136 128/160 145/182 160/200

Standby rating(KW/KVA) 120/150 140/175 160/200 176/220

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model UCI274E UCI274F UCI274G UCI274H

Frequency Hz 50

Output Rating(KVA) Continuous 140 160 182 200

Standby 150 175 200 220

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 380-415

Power Factor 0.8

Voltage Regulation (%) Within ±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model 6BTAA5.9-G2 6CTA8.3-G2 6CTA8.3-G2 6CTAA8.3-G2

Type Water-cooled,Direct

Injected, Turbocharged

and Charge Air Cooled

Water-cooled, Direct Injected, Turbocharger&

Aftercooler

Water-cooled,Direct

Injected, Turbocharged

and Charge Air Cooled

Output Rating(KW) Continuous 120 163 163 183

Standby 130 180 180 203

No. of Cylinders-Bore × Stroke(mm) 6-102×120 6-114×135 6-114×135 6-114×135

Piston Displacement(L) 5.9 8.3 8.3 8.3

Fuel consumption(L/h) 30 42 42 45

Lube Oil Sump Capacity(L) 16.4 27.6 27.6 23.8

Coolant Capacity(L) 10 12.3 12.3 12.3

Battery × Qty 80AH×2 80AH×2 80AH×2 80AH×2

Fuel Tank Capacity(L) 280 250 250 320

Unit

Dimension

Open / Soundproof

Length(mm) 2550 2930 2600 3400 2600 3400 2800 3400

Width(mm) 830 1100 810 1100 810 1100 950 1100

Height(mm) 1550 1800 1550 1960 1550 1960 1650 1960

Dry Weight kg 1550 1930 1650 2080 1710 2330 1760 2520

Page 6: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (250kVA~275kVA)

Model J5G250C J5G275C J5G275C J5G250C

Prime rating(KW/KVA) 182/227 200/250 200/250 182/227

Standby rating( KW/KVA ) 200/250 220/275 220/275 200/250

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model UCDI274J UCDI274K UCDI274K UCDI274J

Frequency Hz 50

Output Rating(KVA) Continuous 230 250 250 230

Standby 260 275 275 260

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 380-415

Power Factor 0.8

Voltage Regulation (%) Within±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model 6LTAA8.9-G2 6LTAA8.9-G2 MTA11-G2A NT855-GA

Type Water-cooled, Direct Injected, Turbocharged and

Charge Air Cooled

Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Water-cooled, Direct

Injected, Turbocharged

Output Rating(KW) Continuous 220 220 234 231

Standby 240 240 257 254

No. of Cylinders-Bore × Stroke(mm) 6-114×145 6-114×145 6-125×147 6-140×152

Piston Displacement(L) 8.9 8.9 10.8 14

Fuel consumption(L/h) 53 53 55 53.4

Lube Oil Sump Capacity(L) 27.6 27.6 39 36.7

Coolant Capacity(L) 11.1 11.1 12.9 18.9

Battery × Qty 80AH×2 80AH×2 120AH×2 120AH×2

Fuel Tank Capacity(L) 320 320 500 500

Unit

Dimension

Open / Soundproof

Length(mm) 2800 3930 2800 3930 3100 4400 3100 4460

Width(mm) 950 1120 950 1120 1100 1130 1100 1100

Height(mm) 1650 2100 1650 2100 1850 2250 1850 2200

Dry Weight kg 1980 2970 1990 2980 2460 3500 3240 3910

Page 7: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (275KVA-350KVA)

Model J5G275C J5G315C J5G350C J5G350C

Prime rating(KW/KVA) 200/250 229/286 255/318 255/318

Standby rating( KW/KVA ) 220/275 252/315 280/350 280/350

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model UCDI274K HCI444D HCI444E HCI444E

Frequency Hz 50

Output Rating(KVA) Continuous 250 300 350 350

Standby 275 330 400 400

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model NT855-GA NTA855-G1A MTAA11-G3 NTA855-G1B

Type Water-cooled, Direct

Injected, Turbocharged

Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Water-cooled,Direct

Injected, Turbocharged

and Charge Air Cooled

Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Output Rating(KW) Continuous 231 264 282 284

Standby 254 291 310 321

No. of Cylinders-Bore × Stroke(mm) 6-140×152 6-140×152 6-125×147 6-140×152

Piston Displacement(L) 14 14 10.8 14

Fuel consumption(L/h) 53.4 61.3 61.3 71.4

Lube Oil Sump Capacity(L) 36.7 36.7 39 38.6

Coolant Capacity(L) 18.9 20.8 9.5 20.8

Battery × Qty 120AH×2 120AH×2 120AH×2 120AH×2

Fuel Tank Capacity(L) 500 500 500 500

Unit

Dimension

Open / Soundproof

Length(mm) 3100 4460 3100 4460 3100 4460 3100 4460

Width(mm) 1100 1100 1100 1100 1100 1100 1100 1100

Height(mm) 1850 2200 1850 2200 1850 2200 1850 2200

Dry Weight kg 3350 4020 3350 4020 2940 3720 3350 4020

Page 8: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (385KVA-450KVA)

Model J5G385C J5G390C J5G404C J5G450C

Prime rating(KW/KVA) 280/350 284/355 -/- -/-

Standby rating(KW/KVA) 308/385 312/390 323/404 352/440

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model HCI444E HCI444FS HCI444FS HCI444F

Frequency Hz 50

Output Rating(KVA) Continuous 350 380 380 400

Standby 400 404 404 450

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model NTA855-G2A NTA855-G4 NTAA855-G7 NTAA855-G7A

Type Water-cooled, Direct Injected, Turbocharger&

Aftercooler

Water-cooled,Direct Injected, Turbocharged, Air-Air

Cooled

Output Rating(KW) Continuous 312 317 343 -/-

Standby 343 357 377 407

No. of Cylinders-Bore × Stroke(mm) 6-140×152 6-140×152 6-140×152 6-140×152

Piston Displacement(L) 14 14 14 14

Fuel consumption(L/h) 71.9 75.3 85.4 89.2

Lube Oil Sump Capacity(L) 36.7 36.7 36.7 36.7

Coolant Capacity(L) 20.8 20.8 20.8 20.8

Battery × Qty 120AH×2 120AH×2 120AH×2 120AH×2

Fuel Tank Capacity(L) 500 500 700 700

Unit

Dimension

Open / Soundproof

Length(mm) 3100 4460 3100 4460 3300 4600 3300 4600

Width(mm) 1100 1100 1100 1100 1155 1350 1155 1350

Height(mm) 1850 2200 1850 2200 1800 2280 1800 2280

Dry Weight kg 3380 4060 3520 4300 3600 - 3870 -

Page 9: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (404KVA-550KVA)

Model J5G404C J5G500C J5G550C J5G550C

Prime rating(KW/KVA) 304/380 364/455 400/500 400/500

Standby rating( KW/KVA ) 323/404 400/500 440/550 440/550

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model HCI444FS HCI544C HCI544D HCI544D

Frequency Hz 50

Output Rating(KVA) Continuous 380 500 550 550

Standby 404 520 590 590

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model KTA19-G2 KTA19-G3 KTA19-G3A KTA19-G4

Type Water-cooled, Direct Injected, Turbocharger& Aftercooler

Output Rating(KW) Continuous 336 403 448 448

Standby 369 448 504 504

No. of Cylinders-Bore × Stroke(mm) 6-159×159 6-159×159 6-159×159 6-159×159

Piston Displacement(L) 18.9 18.9 18.9 18.9

Fuel consumption(L/h) 83 97 107 107

Lube Oil Sump Capacity(L) 50 50 50 50

Coolant Capacity(L) 30 30 30.3 30

Battery × Qty 120AH×2 120AH×2 120AH×2 120AH×2

Fuel Tank Capacity(L) 740 740 740 740

Unit

Dimension

Open / Soundproof

Length(mm) 3350 5030 3350 5030 3350 5030 3350 5030

Width(mm) 1355 1350 1355 1350 1355 1350 1355 1350

Height(mm) 2000 2300 2000 2300 2000 2300 2000 2300

Dry Weight kg 3900 4670 3970 5200 - - 4100 5330

Page 10: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (625KVA-715KVA)

Model J5G625C J5G660C J5G688C J5G712C

Prime rating(KW/KVA) 455/568 -/- -/- 518/647

Standby rating( KW/KVA ) 500/625 528/660 550/688 570/712

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model HCI544E HCI544E HCI544FS HCI544F

Frequency Hz 50

Output Rating(KVA) Continuous 610 610 625 670

Standby 665 665 687.5 738

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within±1.0 %

Excitation Brushless self excited(With AVR)

Insulation Class H

Engine/Cummins

Model KTAA19-G5 KTA19-G8 KTAA19-G6A KT38-G

Type Water-cooled, Direct

Injected, Turbocharged,

Air-Air Cooled

Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Water-cooled, Direct

Injected, Turbocharged,

Air-Air Cooled

Water-cooled, Direct

Injected, Turbocharger&

Aftercooler

Output Rating(KW) Continuous 470 -/- -/- 560

Standby 555 575 610 615

No. of Cylinders-Bore× Stroke(mm) 6-159×159 6-159×159 6-159×159 12-159×159

Piston Displacement(L) 18.9 18.9 18.9 37.8

Fuel consumption(L/h) 113 141 127.8 140

Lube Oil Sump Capacity(L) 50 50 50 135

Coolant Capacity(L) NA 30 NA 118

Battery × Qty 120AH×2 120AH×2 120AH×2 120AH×4

Fuel Tank Capacity(L) 740 740 740 NA

Unit

Dimension

Open / Soundproof

Length(mm) 3720 20ft

container

3350 20ft

container

3350 20ft

container

4200 20ft

container Width(mm) 1640 1355 1355 1860

Height(mm) 2040 2000 2000 2450

Dry Weight kg 4400 5530 - - 4650 5720 6650 7820

Page 11: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (790KVA-1010KVA)

Model J5G790C J5G860C J5G1010C J5G1010C

Prime rating(KW/KVA) 600/750 647/809 735/918 752/940

Standby rating(KW/KVA) 632/790 688/860 808/1010 808/1010

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model LVI634B HCI634G HCI634H HCI634H

Frequency Hz 50

Output Rating(KVA) Continuous 750 810 940 940

Standby 790 860 1010 1010

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within ±1.0% Within ±0.5%

Excitation SEPARATELY EXCITED BY P.M.G.(With AVR)

Insulation Class H

Engine/Cummins

Model KTA38-G2 KTA38-G2B KTA38-G2A KTA38-G5

Type Water-cooled, Direct Injected, Turbocharger& Aftercooler

Output Rating(KW) Continuous 664 711 813 880

Standby 731 789 895 970

No. of Cylinders-Bore× Stroke(mm) 12-159×159 12-159×159 12-159×159 12-159×159

Piston Displacement(L) 37.8 37.8 37.8 37.8

Fuel consumption(L/h) 167 167 191 209

Lube Oil Sump Capacity(L) 135 135.1 135 135

Coolant Capacity(L) 118 123.8 118 124

Battery × Qty 120AH×4 120AH×4 120AH×4 120AH×4

Fuel Tank Capacity(L) NA NA NA NA

Unit

Dimension

Open / Soundproof

Length(mm) 4500 20ft

container

4500 20ft

container

4500 20ft

container

4500 20ft

container Width(mm) 1860 2060 2060 1800

Height(mm) 2450 2450 2450 2200

Dry Weight kg 6950 8230 7000 9280 7340 11200 7380 11500

Page 12: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (1100KVA-1350KVA)

Model J5G1110C J5G1230C J5G1313C J5G1350C

Prime rating(KW/KVA) 818/1023 -/- 1000/1250 1008/1260

Standby rating(KW/KVA) 888/1110 984/1230 1050/1313 1080/1350

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model HCI634J HCI634K LVI634G PI734A

Frequency Hz 50

Output Rating(KVA) Continuous 1030 1135 1250 1260

Standby 1110 1230 1313 1350

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within ±0.5% Within ±1.0% Within ±1.0%

Excitation SEPARATELY EXCITED BY P.M.G.(With AVR)

Insulation Class H

Engine/Cummins

Model KTA38-G5 KTA38-G9 KTA50-G3 KTA50-G3

Type Water-cooled, Direct Injected, Turbocharger& Aftercooler

Output Rating(KW) Continuous 880 -/- 1097 1097

Standby 970 1089 1227 1227

No. of Cylinders-Bore × Stroke(mm) 12-159×159 12-159×159 16-159×159 16-159×159

Piston Displacement(L) 37.8 37.8 50.3 50.3

Fuel consumption(L/h) 209 256 254 254

Lube Oil Sump Capacity(L) 135 135 177 177

Coolant Capacity(L) 124 124 161 161

Battery × Qty 120AH×4 120AH×4 120AH×4 120AH×4

Fuel Tank Capacity(L) NA NA NA NA

Unit

Dimension

Open / Soundproof

Length(mm) 4500 20ft

container

4500 20ft

container

5000 40ft

container

5000 40ft

container Width(mm) 1800 2060 2060 2060

Height(mm) 2200 2500 2600 2600

Dry Weight kg 7550 12110 7900 12500 9800 20800 9800 20800

Page 13: DIESEL GENERATING SET Cummins Series - jensonn.comjensonn.com/Downlaods/English/Support/Download/50Hz... · DIESEL GENERATING SET . Cummins Series . Jensonn Power Systems Co.,

Cummins Series

SPECIFICATION TABLE (1500KVA-1650KVA)

Model J5G1500C J5G1650C

Prime rating(KW/KVA) 1120/1400 1200/1500

Standby rating(KW/KVA) 1200/1500 1320/1650

Power definition

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the

annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these

ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Alternator/Stamford

Model PI734B PI734C

Frequency Hz 50

Output Rating(KVA) Continuous 1400 1550

Standby 1500 1660

No. of Phase 3-Phase, 4-Wire

Related Voltage(V) 400

Power Factor 0.8

Voltage Regulation (%) Within ±1.0%

Excitation SEPARATELY EXCITED BY P.M.G.(With AVR)

Insulation Class H

Engine/Cummins

Model KTA50-G8 KTA50-GS8

Type Water-cooled, Direct Injected, Turbocharger& Aftercooler

Output Rating(KW) Continuous 1200 1287

Standby 1429 1429

No. of Cylinders-Bore × Stroke(mm) 16-159×159 16-159×159

Piston Displacement(L) 50.3 50.3

Fuel consumption(L/h) 289 309

Lube Oil Sump Capacity(L) 204 204

Coolant Capacity(L) 165 165

Battery × Qty 120AH×4 120AH×4

Fuel Tank Capacity(L) NA NA

Unit

Dimension

Open / Soundproof

Length(mm) 5150

40ft container

5150

40ft container Width(mm) 2150 2150

Height(mm) 2450 2450

Dry Weight kg 10500 21400 10500 21400