digital power meter •digital power analyzer •power quality

16
Digital Power Meter Digital Power Meter Digital Power Meter Digital Power Meter Digital Power Meter • Digital Power Analyzer Digital Power Analyzer Digital Power Analyzer Digital Power Analyzer Digital Power Analyzer • Power Quality Analyzer Power Quality Analyzer Power Quality Analyzer Power Quality Analyzer Power Quality Analyzer R-0EDCI-000MR-C0-05/01 INSTRUMENTS

Upload: others

Post on 17-Mar-2022

14 views

Category:

Documents


0 download

TRANSCRIPT

• Digital Power MeterDigital Power MeterDigital Power MeterDigital Power MeterDigital Power Meter

••••• Digital Power AnalyzerDigital Power AnalyzerDigital Power AnalyzerDigital Power AnalyzerDigital Power Analyzer

••••• Power Quality AnalyzerPower Quality AnalyzerPower Quality AnalyzerPower Quality AnalyzerPower Quality Analyzer

R-0

ED

CI-

000M

R-C

0-05

/01

INSTRUMENTS

Bridex Singapore Pte Ltd was founded in 1973 as a manufacturer of instruments transformer for

the Asian market. We are the first local electrical switchgear components manufacturer that

launches our own Asian identity – Rudolf.

Today we aim to become a knowledge-based, technology driven engineering organization,

with emphasis on providing solution for electrical distribution and control, in area of instruments,

distribution & protection and standard components. With our present headquarter in Singapore

and subsidiaries that are located in Philippines, China and Australia, we are well equipped to

service both local and Asia-Pacific countries.

Product Introduction

What are the reasons behind an increasing trend toward the use of power meter and power

analyzer? To replace the conventional metering using analogue meter? We take reasons better

than this. With just one product, we achieve consolidated measurement, energy metering,

alarm monitoring, possibility for remote communication, the possibility for control and command

and the possibility for data logging function via sole proprietor software. These possibilities

allow the user to obtain and manage information thereby providing the user with the capability

to control cost, improve power quality and participate in control system (BMS)

These functions can be achieved by your selection of any of RUDOLF:

R-DPM96 - Digital Power Meter

R-DPA96 - Digital Power Analyzer

R-PQA144 - Power Quality Analyzer

R-DPA96R-DPM96 R-PQA144

Corporate Introduction

1

Digital Power Meter - DPM96

2

Basic Features

OTHER FEATURES• Compact-size (96 x 96 mm), panel-mounting power meter.• True R.M.S. measuring system.• Instantaneous, maximum and minimum values of each measured parameter.• Energy measurement (indication through a lighting LED)• RS-485 type communication to a PC• Harmonic distortion measurement (THD-V & THD-A ).• Active & Reactive Metering.• Maximum 2 user-programmable pulse/alarm outputs are available in DPM 96 power meter to transmit active and reactive

energy information / user-defined threshold overshoots.• Energy Measurement - designed for energy management applications, the DPM 96 power meter can transmit all

information required for electricity billing such as load curves in active or reactive power, active and reactiveenergy to a computer.

• RS 485 or RS 232 Communication - The DPM 96 power meter can be equipped with an RS 485 output or RS 232 output(optional) ModBus RTU protocols to transmit all electrical information in digital form to a computer, PLC, or evena display repeater.

• Software - The DPM96 (model with RS 485 port / RS 232 port) can be used in conjunction with its proprietary software,Easycomm Plus for remote monitoring and display of its electrical parameters, remote modification of its setting, datalogging, to record its designated electrical parameter (programmable time interval, minimum 1 sec).

The DPM 96 is an instrument which measures, calculates and displays all the main electrical parameters atany electrical network (balanced or not). The measuring is true RMS value, through three a.c. voltage inputsand three a.c. current inputs (from Current Transformers .../ 5A).

It was designed according to EMC and electrical safety standards, and manufactured under the ISO 9001quality control. It is featured by its high measuring, its reduced size, an easy assembly mode and a yeteconomical price. It can be integrated into a communication network through its built-in-RS 485 type outputby just using ModBus standard protocol. Two relay outputs are also delivered by the power meter for alarmand /or energy pulses.

User Friendly Interfaces

Voltage (phase-neutral)Voltage (phase-phase)CurrentActive powerReactive power LReactive power CVoltage THDCurrent THDPower factorFrequencyPower demandkWhkvarhLkvarhC

VVAkWkvarLkvarC% THD- V% THD- APFHzPdenergyenergyenergy

Parameter Symbol L1 L2 L3 Average

The DPM 96 delivers the visualization of above listed parameters by means of three 4-digit LED type displays. Up to 3 parameters can be

simultaneously read in the screen. Up to 10 screens are available to visualize all 30 measured parameters.

Setup procedureby keyboard

Easy & fastmounting

Compact Size:96 x 96mm

Communication to remote sites

RS 232C RS 485

CommunicationConverterIBM PC 386 (or

compatible)or industrial PLC

ModemTelephone

Modem

ALARM

Max power demand alarm

Digital Power Meter - DPM96

3

Measurement CircuitsRated voltage

Frequency

Rated current

Permanent overload

Current input burden

Main Technical DataAuxiliary supply voltage 230 V a.c.

Voltage tolerance -10%/ +15%

Frequency 50...60 Hz

Burden 5VA

Operation temperature -10 to 50°C

AccuracyVoltage 0.5% of readout ± 2 digits

Current 0.5% of readout ± 2 digits

Powers 1.0% of readout ± 2 digits

Test conditions

• Errors due to C.T are not included and direct voltage measurement

• Temperature between + 5°C and + 45°C

• Power factor between 0.5 and 1

• Measured values between 5%... 100%

Mechanical CharacteristicsConnection Pluggable connection terminal

Case material Self-extinguishable, V0 plastic

Protection Assembled unit (frontal) : IP 54

Un-assembled unit (side and rear covers): IP 31

Dimensions 96x96mm -depth: 100mm

Weight 0.520 kg

Relays characteristics: according to modelMaximum switching load 2500 VA

Maximum switching voltage 400 V a.c

Maximum switching Current 10 A

Mechanical endurance 3 x 107 operations

Energy/alarms phases Max. 1 pulse/s

At full load: (250 V a.c./10A)

• Electrical endurance 1 x 105 operations

• Maximum operation 450 operations/hour

SafetyCategory III - 300 V a.c/520 a.c as per EN-61010

Protection against electric shock by class II double-isolation

StandardsIEC 664, VDE 0110, UL 94. IEC 801. IEC 348.

IEC 571-1, EN 50081-1, EN 50082-1, EN-61010-1

Specifications

Single Phase300V a.c.

45 to 65 Hz

In / 5A

1.2 In

0.75VA

3 Phase 300V a.c. Phase-to-Neutral /

520 V a.c. Phase-to phase

35 to 65 Hz

In / 5A

1.2 In

0.75VA

*Specification of RMD-DPM96-SDU-ITF+RS485 C2 on request.

3 Phase (VT) 100V a.c. Phase-to-Neutral /

177 V a.c. Phase-to phase

35 to 65 Hz

In / 5A

1.2 In

0.75VA

Digital Power Meter - DPM96

4

Selection Guide

Single-phase 50.....60Hz

Three-phase 50.....60Hz

Aux. supply 230 V a.c.

Supply & measure 110V

Programmable voltagetransformer ratio

Aux. supply 24-120V d.c.

True RMS value

LED Display

Isolated Current Inputs ITF

2 Quadrants

Energy

THD measurement (V, A)

Maximum demand

RS 232 Communication

RS 485 Communication

Relay outputs/Pulse Output

RMD-DPM96-ITF

RMD-DPM96-ITF+RS485 C2

RMD-DPM96-ITF+RS485 C2

(VT)

RMD-DPM96-SP

RMD-DPM96-ITF+RS232 C2

RMD-DPM96-SP-ITF+RS485 C2

RMD-DPM96-SDU-ITF+RS485 C2

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

2

X

X

X

X

X

X

X

X

X

X

2

X

X

X

X

X

X

X

X

X

X

X

2

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

2

X

X

X

X

X

X

X

X

X

2

Digital Power Analyzer - DPA96

5

Basic Features

The R-DPA96 is an instrument for measuring and metering electrical values for single, two and three-phase

LV/HV electrical networks. From the front panel (6 keys and LCD displays) you can programme and display

all the parameters and use the functions provided to carry out the following:

• measure electrical values on 4 quadrants

• hours run meter

• Compact DIN - 96 x 96 mm display and reduced depth of 60 mm (80 mm including plug-in options)

• instantaneous, average and maximum current over a programmable integration time (5 to 60 min),

• phase to neutral and phase to phase voltage,

• frequency,

• instantaneous, average and maximum active power P on 4 display quadrants (L/C/+/-) over a programmable

integration time (5 to 60 min),

• instantaneous, average and maximum reactive power Q on 4 display quadrants (L/C/+/-) over a programmable

integration time (5 to 60 min),

• instantaneous, average and maximum apparent power S over a programmable integration time (5 to 60 min),

• instantaneous and maximum power factor PF with L (inductive) and C (capacitive) indications,

• metering in 1/100th of an hour for operating time, with reset to zero,

• Optional plug-in modules (metering, harmonics, communication, analogue, alarms or control/command)

enable additional functions to be added to the base unit enabling initial performance vs cost to be optimised

whilst providing long term on-site flexibility for the end user,

• 6 direct access keys:

I: current,

U/F: Voltage and frequency,

PQS: active, reactive and apparent powers,

PF: power factor,

Max H: maximum demand, current and power,

/E: energy and hours run

• Large, clear, back-lit display is easy to read. Simultaneous display of measured parameter values in unit,

value and bar graph format. The self adjusting contrast enables the screen to be easily viewed in all environments

and from all positions.

Plug & display

Digital Power Analyzer - DPA96

6

Specification

Main Technical Data

Voltage (TRMS)

Direct measurement:

Measurement via PT:

• Primary

• Secondary

Display and resolution

Permanent overload:

Update period:

CaseDimensions:

Connection:

IP index:

Weight:

96 x 96 x 60mm

or 96 x 96 x 80 mm with all optional modules (DIN 43700)

via 2.5mm2 disconnectable terminals

(voltage and others) and 6mm2 fixed terminals (current)

IP54 (front panel) and IP20 (case)

400 g

DisplayType: High luminosity self adjusting LCD display

MeasurementsThree-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks

from 0 to 700 V AC (phase/phase)

from 0 to 404 V AC (phase/neutral)

up to 400 kV

60, 100, 110, 173 and 190 V AC

from 0 to 400.0 kV

760 V AC

1 second

Current (TRMS)

Via CT with:

• Primary

• Secondary

Input consumption:

Display:

Permanent overload:

Intermittent overload:

Update period:

Maximum ratio KI x KU:

up to 10000 A

1 or 5 A

0.1 VA

from 0 to 11 kA (1.1 times the primary value)

6 A

10 In / 1 second

1 second

2 000 000

Power

Per phase:

Total:

Update period:

0 to 1660 MW/Mvar/MVA

0 to 8000 MW/Mvar/MVA

1 second

Frequency

from 45.0 to 65.0 Hz

Update period: 1 second

Current:

Voltage:

Power:

Power factor:

Frequency:

Active energy metering:

Reactive energy metering:

Measurement Accuracy0.5% from 10 to 110% / In

0.5% from 140 to 700 V AC

1% of full scale (-90° - +90°)

1% for 0.5<FP<1

0.1Hz from 45 to 65Hz+/- 1% from 0.02 to 1.2 In with PF = 0.5 L or 0.8 C (class 1 IEC 61036)

+/- 2% from 0.1 to 1.2 In with sinϕ = 0.5 L or C (class 1 IEC 61268)

Digital Power Analyzer - DPA96

7

Specification (continue)

Auxiliary Supply110 to 440V AC

120 to 350V DC

Consumption:

Other version:

50/60 Hz +/- 10%

+/- 20%

10 VA

18 to 100 V DC (+/-10%)

Pulse outputsReed relays

No. of operations:

(100 V DC - 0.5 A - 10 VA)

<108

CommunicationRS 485:

Protocol:

Speed:

2 or 3 wires half duplex

JBUS/MODBUS protocol / RTU mode

2400 to 38400 Bauds

Galvanic insulation (AC insulation voltage)Auxiliary supply:

Voltage inputs:

Current inputs:

Serial link:

Pulse outputs:

4 kV

1.5 kV

1.5 kV

1.5 kV

1.5 kV

Operating conditionsOperating temperature:

Storage temperature:

Relative humidity:

-10° to +55°C (14° to 131°F)

-20° to +85°C (-4° to 158°F)

95%

StandardsMetering

CE-marking

Environment

IEC 61036 class 1

IEC 61268 class 2

IEC 61000-4/2-3-4-5-6-8-11

EN 50081-1

EN 50082-2

IEC 60068-2/6-11

Product code:R-DPA96 Basic model

R-Module-1 Plug in module for energy metering± kWh, ± kvarh and kVAh with two programmable pulse outputs

R-Module-2 Plug in module for energy metering + harmonicsI1, I2, I3, U12, U23, U31 and THD U/I up to harmonic no. 15

R-Module-3 Plug in module for communication RS 485 (JBUS/MODBUS protocol)2 or 3-wire RS485 with JBUS/MODBUS protocol, with transmission speed of up to38,400 bauds

R-Module-4 Plug in module for analogue outputs (0/4-20mA)Two configurable 0/4-20 mA analogue outputs

R-Module-5 Plug in module for alarms control/command (2 inputs/ 2 outputs)2 inputs for pulse metering or for input status. 2 outputs for alarm monitoring or outputcommand. The monitoring function allows upper and lower alarm thresholds to beprogrammed for the following parameters: 3I, 3U, In, ±∑P, F, PFL/C, THDI/U with timedelay and hysteresis options.

8

Basic Features

Power Quality Analyzer - PQA144

The PQA-144 is an instrument that can be used as a Power Quality Analyzerto support any network connection configuration, such as 3 and 4 Wire, Wye and

Delta, and single-phase. The connection is either direct (up to 347/600 VAC) or

using a Potential Transformer (PT). Minimum burden on the Current Transformers

(CTs) is achieved by connecting the CTs without a physical contact. Delta networks

use 2 or 3 CT’s and Wye networks use 3 or 4 CT’s.

When the system is configured as a Delta network, it displays the L-to-L current and

power, in additional to the line currents and total power. The system measures the

line current from the CTs and calculates the current and power inside the feeder

transformer (or generator). In completely balanced networks, the internal currents

are 1/√3 of the line currents. In many cases, the network is not balanced and the

internal currents are different from these expected.

The unique dual load model is advantageous when monitoring two loads (6 current channels) connected to the same feeder.

The analyzer displays each load separately, as well as their total or deduction.

Typical applications for the dual load model are:

Two Transformers

When two transformers are connected in parallel, the analyzer measures each transformer separately, add their output and

displays one joint measured network, as well as each transformer separately.

Large Loads

Loads on the transformer may include one large load (such as large motor, welder or other machines) and many relatively

small loads. In this situation it is advantagous to monitor the mains and the large load separately.

Connection of the mains to Load1 of the Power Analyzer and the large load to Load2 provides accurate measurements of the

mains, the large load and all other loads.

Typical connection of a single loadpower analyzer in a Wye network

9

Basic Features

Power Quality Analyzer - PQA144

Metered Values• True RMS measurements• Ultra rapid, real-time, cycle by cycle measurements, at 128 samples per cycle. Real-time values over 8 through 256

cycles for easy reading• Choice of models ranging from essential measurements only (Volts, currents, frequency and powers) to over 2000

electrical parameters• Min/Max values• Four quadrant readings (power, power factor)• Displays neutral voltage and current

Time-of-Use (TOU)• Time-of-Use information is automatically stored for each predefined period• PowerIQ software calculates electricity costs according to varying tariffs (based on time, season etc.)

Power Quality• Waveform display and capturing, at 128 samples per cycle• Harmonics analysis, up to 63rd harmonic (individual, THD, K and crest factors)• Sag/Swell recording (magnitude, duration and trigger events)

Compliance Monitoring• Compliance monitoring of international power quality standards• These monitoring operate on all product series

(e.g. the harmonics level is tested even if the meter doesn’t include harmonics display)

Logging & Recording• Up to 2048KB of flash memory• High speed data recording for short duration critical events• Logging of over 2000 parameters at scheduled intervals or by set-points• Min/Max recording of key parameters• Logging of setup changes, set-point and power quality events• Precise timestamp synchronized to external GPS (optional)

Input, Output & Relays• On board relay can be controlled automatically by internal set-points• Optional 4 digital inputs and 2 outputs for multiple purposes, such as synchronization to utility meter or to generate

energy pulsing (Wh, VArh and VAh)

Graphic Display & User Interface• Extra large graphic LCD screen• High visibility (FSTN technology)• Bright Backlight• Characters are displayed in varying sizes to enhance visibility from long distances• The user interface offers an easy to use, installation and configuration menu driven operation

Communication• Optional RS-485 or RS-232 communication port• Supported protocol: ElCom protocol - Rudolf’s unique ultra rapid communication protocol and ModBus RTU• Baud rate of up to 115200 BPS• Fully automated baud rate setup

Structure• Allows easy adaptation of the unit to current and future requirements• Easy upgrading of the firmwave (internal software)

Network Types• Supports any network connection configuration (3 and 4 Wire, Wye and Delta, single-phase etc.)• Feeder transformer (or local generator) current and power analysis (see Applications section)• Unique dual load model enables simultaneous analysis of two loads such as parallel-connected transformers, or mains

plus additional load (e.g., large motor, welder, capacitor bank)

Software• User-friendly PC software (PowerIQ)• Includes on-line help for easy use

10

Display Screens

Power Quality Analyzer - PQA144

Large Digit Screen

Permits simultaneoues display of 9 parameters: 3 measured values

plus 3 minimum and 3 maximum.

Parameters can be mixed, such as average voltage, current and

power factors. This unique feature allows analysis of the formost

parameters at a glance, without touching the unit. The PU% buttons

displays the values as a percentage from their nominal rating.

When using the dual load model, the readings are on all 3 loads .

Waveform Screen

This large graphic display allows easy monitoring of transients of

130/156µS (at 60/50Hz). The display includes detailed information

for each wave: the type and phase, THD, RMS, peak & bottom

values plus value at cursor position.

When using the dual load model, the readings are on all 3 loads .

Harmonics Screen

The graphic display enables inspection of the harmonics pollution

at a glance. The display includes detailed information for each

harmonic: type, phase, number of the harmonic, the value in

amperes/volts and in percent, the angle and the frequency.

When using the dual load model, the readings are on all 3 loads.

11

Detailed analysisof Time-Of-Use(TOU) can bedone using thePowerIQsoftware.

Display Screens

Power Quality Analyzer - PQA144

Mains Menu

Step-by-step installation assistant

Notes:* These detailed display screens are for single load unit with WYE

network configuration* Dual load unit has the same screens for all loads (two or three)* Other configurations have similar screens

Measurement Level1 2 3 4

The screens include automatic default and user-friendly help screen.

Info Screens

Additional event-specific information isdisplayed.

Detailed eventinformation is accessedusing PowerIQ software

12

Basic Features - PowerIQ Software

Power Quality Analyzer - PQA144

GeneralThis easy-to-use software displays the system’s status, as well as the measurement results on the numerous screens running

under Windows (95, 98, me, NT and 2000). PowerIQ integrates all Rudolf systems, allowing power quality analysis, cost

allocation, circuit optimization, demand & power factor monitoring. PowerIQ includes real-time measurements, as well as

comprehensive data logging and power quality analysis features. All screens allow customization, printing and exporting of

data. The network version enables complete intranet and internet operation, as well as modem access.

������������ �������

����������� ����������

����������� ����������

������� �������

������������ ����������� � !"��������� ������"�����

��#��

��#��

$��#�������������

$�%���&��"'(��)���� ������*�

$�%���&��"'(��)���� ������*�

$�%���&��"'(��)���� ������*

$�%���&��"'(��!+��#���*�

!"������"�'�����

13

Power Quality Analyzer - PQA144Basic Features - PowerIQ Software

Real-time MeasurementsProvides clearly visible real time values, with minimums and maximums.

Remote Control

Harmonics AnalysisDisplays the harmonics spectrum both as a graph and as atable, in addition to harmonics analysis parameters (THD,K-Factor and Crest-Factor). Compliance monitoring ofinternational power quality standards, such as IEEE-519,allows easy network analysis.

ScopeDisplays waves and their phase shifting, and enablesdetection of existing or potential power quality problems.

Data LoggingEnables comprehensive network analysis by logging over2000 parameters per record. It can be set to record dataeither on pre-defined intervals (from 1 cycle to 99 hours)or according to network events. The recording volumeand time is limited only by the size of the computer’shard disk.

Data MonitoringDisplays the recorded data in either on-line or off-linemode. The on-line mode displays the data whilesimultaneously recording it for maximum power analysiscontrol.

Report GeneratorCreates user-defined or preset reports (such as load profileand power quality) reports. The reports are easily definedusing a word processor (such as Microsoft Word).

Time-of-Use (TOU)Displays the Time-of-Use information stored in the analyzer,in addition to calculation of energy costs, according tovirtually any utility tariff structure.

EventsThe event screen is used for retrieving, monitoring andanalyzing the events information from the analyzer.

14

Power Quality Analyzer - PQA144Technical Specification

LCD Display Size : 94 x 76 mm

LCD Display Resolution : Graphic 160 x 128 pixies

LCD Display Type : FSTN, LED backlight

Overall Dimensions : 144 x 144 x 120 mm [HxWxD]

Panel Cutout : 138x138 mm

Weight : 1.4 kg

Ambient Temperature : -20°C -+55°C

Storage Temperature : -25°C -+65°C

Direct Voltage Measurement : 347/600 V AC Max.

Current Measurement : ../5A (1A)

Relay Alarm : Max. 2A 250VAC

EMC Compatibilty : EN61000-4-2/3/4/5, ENV50204, ENV50141

Safety Standards : EN61010-1, EN50439-1, UL508

Protection Class : IP40

Analog Channels : 7 or 10

4 x Voltage Channels

3 x Current Channels

3 x Current Channels (optional Load2)

Communication (optional) : ElCom (Rudolf’s protocol), ModBus RTU

Power Supply :110 or 230V, 50/60 Hz

Power Consumption :15 VA

Harmonics Analysis : 1 through 63rd

Selection Guide

Full InstrumentationWiring DiagnosticsANSI C12.1 Accuracy

FrequencyCurrent, per phaseCurrent, NeutralCurrent, L-to-L (Transformer)Volts, L-to-LVolts, L-to-NVolts, Neutral

Real Power (kW)Reactive Power (kVAr)Apparent Power (kVA)Power Factor

Time-of-Use (TOU):- Real Energy (kWh)- Reactive Energy (kVArh)- Energy Accumulation Modes: in, out, net, total

THD (Current, Volts, L-to-L and L-to-N)K-Factor (Current, Volts, L-to-L and L-to-N)Harmonics (Current, Volts, L-to-L and L-to-N)

Waveforms (Current, Volts, L-to-L and L-to-N)Min/Max ReadingsDual Load Measurement

Event loggingData LoggingData/ Time StampingFlash Memory (Kilo Bytes)Maximum Flash Memory (Kilo Bytes)

RS-422/485 Communication Port - Elcom ProtocolRS-422/485 Communication Port - ModBus/RTUOnboard Alarm

•••

•••••••

••••

°

•256256

°°•

OptionsOptionsOptionsOptionsOptionsPrPrPrPrProduct Seriesoduct Seriesoduct Seriesoduct Seriesoduct Series

R-PQA144-110-2R-PQA144-110-2R-PQA144-110-2R-PQA144-110-2R-PQA144-110-2 R-PQA144-210-2R-PQA144-210-2R-PQA144-210-2R-PQA144-210-2R-PQA144-210-2 R-PQA144-311-2R-PQA144-311-2R-PQA144-311-2R-PQA144-311-2R-PQA144-311-2 R-PQA144-411-2R-PQA144-411-2R-PQA144-411-2R-PQA144-411-2R-PQA144-411-2

•••

•••••••

••••

•••

••

°

•5121024

°°•

•••

•••••••

••••

•••

•••

••

°

•5121024

°°•

•••

•••••••

••••

•••

•••

••

°

•••

10242048

°°•

L1, L2, L3 AvgNL12, L23, L31, AvgL12, L23, L31, AvgL1, L2, L3, AvgN

L1, L2, L3, SumL1, L2, L3, SumL1, L2, L3, SumL1, L2, L3, Sum

SumSum

L1, L2, L3, Avg, NL1, L2, L3, Avg, NL1, L2, L3, N

L1, L2, L3, N

0.10.20.20.20.20.20.2

0.30.30.30.3

0.50.5

0.20.20.2

0.2

Displayed PhasesDisplayed PhasesDisplayed PhasesDisplayed PhasesDisplayed Phases AccurAccurAccurAccurAccur. (%). (%). (%). (%). (%)(FS) ±1 dgt(FS) ±1 dgt(FS) ±1 dgt(FS) ±1 dgt(FS) ±1 dgt

• - included ° − optional

An Overview

RUDOLFTM brandname is the registered trademark of Bridex Singapore Pte Ltd (a member of SMB United Group) in Singapore and other countries. Our company’s policy is one of continuousdevelopment and improvement and therefore, the products shown in this catalogue can be subject to change in appearance, characteristics, operation and utilisation. The details given are forguidance only and shall not bind us in any way.© Copyright SMB Group

No. 9 Senoko Drive Singapore 758197Tel: (65) 7560833Fax: (65) 7562007http://www.bridex.com.sge-mail: [email protected]

����������� ������������������� ������������ ��

RMD-DPM96-ITF

RMD-DPM96-ITF+RS232C2

RMD-DPM96-ITF+RS485C2

RMD-DPM96-ITF+RS485C2(VT)

RMD-DPM96-SP

RMD-DPM96-SP-ITF+RS485C2

RMD-DPM96-SDU-ITF+RS485C2

Voltage L1, L2, L3

Voltage L12, L23, L31

Current L1, L2, L3

Active Power L1, L2, L3, Avg

Reactive Power L L1, L2, L3, Avg

Reactive Power C L1, L2, L3, Avg

Voltage THD L1, L2, L3

Current THD L1, L2, L3

Power factor L1, L2, L3, Avg

Frequency L1

Power demand kW/VA Avg

Active energy Avg

Reactive energyL Avg

Reactive energyC Avg

Max & Min reading

Display ParameterModel Measuring Circuit

300VAC

Analogue Output

Optional

2 x 0/4-20mA maixmum

up to 4 x 0/4-20mA

Alarm Output

2 pulse/alarm relay

2 pulse/alarm relay

2 pulse/alarm relay

2 pulse/alarm relay

2 pulse/alarm relay

Communication

RS232

RS485

RS485

RS485

RS485

Digital Power Meter

DPM96

(96x96x100mm)

Power Quality AnalyzerPQA144

(144x144x120mm)

Digital Power AnalyzerDPA96

96x96x60mm (without option)96x96x80mm (with option)

347VAC L-N

600VAC L-L

404VAC L-N700VAC L-L

VT up to 400kVby 60,100,110,173

& 190V

Optional 2 I/P 2 O/P Optional RS485R-DPA96

+Current Avg

Neutral VoltageTime and date stamping

+energy accumulation modes: in, out, net total

K-factor for (A, V, L-L, L-N)

+Harmonics up to 63rd level for A, V, L-L & L-N

Waveform for (A, V, L-L, L-N)

+Event loggingData logging

+Neutral Current

Apparent power L1, L2, L3, AvgHarmonics odd & even up to 15th(optional)

Hour meter(without min reading)

1 C/O alarm relay

1 C/O alarm relay

1 C/O alarm relay

1 C/O alarm relay

Optional

Optional

RS 485

RS485

R-PQA144-110-2

R-PQA144-210-2

R-PQA144-311-2

R-PQA144-411-2

300VAC L-N

520VAC L-L

100V AC L-N177V AC L-L

VT up to 99kV by 110,300, 500V

300VAC L-N 520VAC L-Lwith aux supply 24-120VDC

7 or 10 channels

4x voltage channels

3x current channels

3x current channels

(optional Load2)

Nil