distance priciples_basic principles

64
> Distance Protection - January 2004 Distance Protection

Upload: ramesh-bakthavachalam

Post on 02-Dec-2014

107 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Distance Priciples_basic Principles

> Distance Protection - January 2004

Distance Protection

Page 2: Distance Priciples_basic Principles

> Distance Protection - January 2004

Distance Protection

Popular, widely used on Sub-Transmission and Transmission Systems

Virtually independent of Fault Current Level (ZS/ZL ratios)

Fast Discriminative Protection:- Zone 1 or ‘Aided’ Distance Scheme

Time Delayed Remote Back-Up:- Incorporated at little extra cost

Page 3: Distance Priciples_basic Principles

> Distance Protection - January 2004

Advantages of Distance Protection

Measures Z, X or R correctly irrespective of System Conditions

Compare this with Instantaneous OvercurrentProtection:-

Page 4: Distance Priciples_basic Principles

> Distance Protection - January 2004

Advantages of Distance Protection

F1

115kV 50

IF1ZS = 10 Ω

ZS = 10 Ω

ZL = 4 Ω

IF1 = 115kV/√3(5+4) = 7380A

∴ Is > 7380A

Page 5: Distance Priciples_basic Principles

> Distance Protection - January 2004

Advantages of Distance Protection

Consider with one source out of service:-

IF2 = 115kV/√3 x 10 = 6640A

∴ Is <6640A

>7380A - IMPRACTICAL

F2

50

IF2

ZS = 10 Ω

Page 6: Distance Priciples_basic Principles

> Distance Protection - January 2004

Basic Principle of Distance Protection

ZLZS

Generation

DistanceRelay

IR

21 VR

Page 7: Distance Priciples_basic Principles

> Distance Protection - January 2004

Impedance Seen By Measuring Element

jX

ZL

R

Page 8: Distance Priciples_basic Principles

> Distance Protection - January 2004

Basic Principle of Distance Protection

LOADLRR

R Z Z V Zmeasured Impedance +=Ι

=

RelayPT.

Normal Load

IR ZLZS

VRVSZLOAD

Page 9: Distance Priciples_basic Principles

> Distance Protection - January 2004

Basic Principle of Distance Protection

Fault

IRZS

VRVSZLOAD

ZL

ZF

Impedance Measured ZR = VR/IR = ZF

Relay Operates if ZF < Z where Z = setting

Increasing VR has a Restraining Effect ∴VR called Restraining Voltage

Increasing IR has an Operating Effect

Page 10: Distance Priciples_basic Principles

> Distance Protection - January 2004

Plain Impedance Characteristic

jX ZL

R

TRIP STABLE

Impedance Seen At Measuring Location For Line Faults

Page 11: Distance Priciples_basic Principles

> Distance Protection - January 2004

Impedance Characteristic Generation

Operate

IF

VF

Restrain

Spring

Trip

zF

Ampere Turns : VF IZ

Trip Conditions : VF < IFZ

jIX

IZ V1V2V3

IR

TRIP STABLE

Voltage to Relay = VCurrent to Relay = IReplica Impedance = Z

Trip Condition : S2 < S1

where : S1 = IZ ≈ Z

S2 = V ≈ ZF

Page 12: Distance Priciples_basic Principles

> Distance Protection - January 2004

Basic Principle of Distance Protection

IR

21 VR

I1/I2 ZP

V1V2

VFP

Relays are calibrated in secondary ohms :-

RATIOV.T.RATIO C.T. x Z Z

/VV/ x V

/ x /VVxV /V Z

PR

2121

FPFP

12FP12FP

RRR

=

ΙΙΙ

=ΙΙΙ

=Ι=

Page 13: Distance Priciples_basic Principles

> Distance Protection - January 2004

Example

ZP = 4Ω; V1/V2 = 115kV/115V; I1/I2 = 600/5A

ZR(5) = 4 x 600/5 x 115/115x103 = 0.48Ω -5A Relay

ZR(1) = 2.4 Ω - 1A Relay

C.T. RATIOZR = ZP x

V.T. RATIO

Page 14: Distance Priciples_basic Principles

> Distance Protection - January 2004

Input Quantities for ∅-∅ Faults

FAULT VRESTRAINT IOPERATE

A - B VA - VB IA - IB

B - C VB - VC IB - IC

C - A VC - VA IC - IA

VRESTRAINT & IOPERATE are selected inside the relay

No setting adjustments are required apart from Z1 = Phase Replica Impedance

Page 15: Distance Priciples_basic Principles

> Distance Protection - January 2004

Input Quantities for Phase to Earth Faults

FAULT VRESTRAINT IOPERATE

A - E VA ? IA ?

B - E

C - E

Page 16: Distance Priciples_basic Principles

> Distance Protection - January 2004

Neutral Impedance Replica Vectorial Compensation

Replica impedance circuit :-

Z1IRA

IRN

∑IZN

Z1

N

Z1

ZN

Z1 = Phase replica impedance

ZN = Neutral replica impedance

IRA passes through Z1

IRN passes through ZN

ZT = Z1 + ZN

Page 17: Distance Priciples_basic Principles

> Distance Protection - January 2004

Neutral Impedance Compensation

For a single phase to ground fault the total earth loop impedance is given by :- (Z1 + Z2 + Z0)/3 = ZT

ZT = (Z1 + Z2 + Z0)/3 = Z1 + ZN

ZN = (Z1 + Z2 + Z0)/3 - Z1

= (2Z1 + Z0)/3 - Z1

= - Z1 + Z0

= KN Z1

3 3

where KN = (Z0 - Z1) 3Z1

Page 18: Distance Priciples_basic Principles

> Distance Protection - January 2004

Neutral Impedance Vectorial Replica Compensation

Line CT’sA

ZPH

B

C

IAZPH

ZPH IBZPH

ZPH ICZPH

ZN INZN

Set Z PH = ZF1

Set Z N = (ZF0 - ZF1 )3

Usually ∠ ZN = ∠ ZPH for OHL’s

Page 19: Distance Priciples_basic Principles

> Distance Protection - January 2004

Neutral Impedance Replica Compensation

For cables ∠Z0 ≠ ∠Z1

∴ VECTORIAL COMPENSATION MUST BE USED

KN = Z0 - Z1 = KN ∠∅N

3Z1

Page 20: Distance Priciples_basic Principles

> Distance Protection - January 2004

Characteristics

Page 21: Distance Priciples_basic Principles

> Distance Protection - January 2004

Distance Characteristics

MHOR

Zn

jX

OFFSETMHO

jX

Zn′

Zn

R

IMPEDANCE

jX

ZnR

jX

R

Zs

Zn

CROSS-POLARISEDMHO

POLYGON

Zn

R

QUADRILATERAL

Zn

R

LENTICULAR

jX

ZnR

Page 22: Distance Priciples_basic Principles

> Distance Protection - January 2004

Self Polarised Mho Relays

Very popular characteristic

Simple

Less sensitive to power swings

Inherently directional

Operates for F1, but not for F2

Mho = 1/OHM

Settings :-

Z = reach settingϕ = characteristic angle

jX

F2

F1

Z

ϕ

OPERATE

RESTRAIN

R

Page 23: Distance Priciples_basic Principles

> Distance Protection - January 2004

Neutral Impedance Replica Vectorial Compensation

Vectorial compensation allows for ∠ZN ≠ ∠ZPH which is especially important for cable distance protection where ∠ZN < ∠ZPH and ∠ZN is sometimes negative.

ZE = Earth-loop impedance for ∅ - earth fault on a cable

jX

R

ZE

ZPHZN

Page 24: Distance Priciples_basic Principles

> Distance Protection - January 2004

Offset Mho Characteristic

Normally used as backup protection

Operates for zero faults (close up faults)

Generally time delayed (as not discriminative)

jX

R

Z

-Z’

Page 25: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mho Relays

Directional circular characteristic obtained by introducing VPOLARISING

VF → self polarisedVSOUND PHASE → fully cross-polarisedVF + xVS.F. → partially cross-polarisedVPRE-FAULT → ‘memory’ polarised

Purpose for this is to ensure operation for close up faults where measured fault voltage collapses

Page 26: Distance Priciples_basic Principles

> Distance Protection - January 2004

Quadrilateral Characteristic

Z

jX

ZR

RR

LoadL

1F

S

Page 27: Distance Priciples_basic Principles

> Distance Protection - January 2004

Lenticular Load Avoidance Characteristic

jIX

IR

ba

Lenticular characteristic created from two offset Mho comparators

Aspect ratio = a/b

Page 28: Distance Priciples_basic Principles

> Distance Protection - January 2004

Lenticular Characteristic

X

R

ab

Z3Aspect ratios a/b

0.410.671.00

Load impedance area

Z3 reverse

Page 29: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zones of Protection

Page 30: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zones of Protection

Z2A Z2C

Z3A Z3C

Time

T3

T2

Z1CZ1A

Z1B DCA

Z2B

T2

Z1A = 80% of ZAB

Z2A = 120% of ZABZ3A(FORWARD) = 120% of ZAB + ZCD

B

Page 31: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zones of Protection

RA

D

CB

Z1A

Z2A

Z3A

jX

Page 32: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 1

FAST OPERATIONTrips circuit breaker without delay as soon asfault within Zone 1 reach is detected.

REACH SETTINGCannot be set to 100% of protected line or mayoverreach into next section.Overreach caused by possible errors in :-

CTsVTsZLINE informationRelay Measurement

Page 33: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 1

PossibleOverreach

ZONE 1 = ZL

ZL

F

ZONE 1 = 0.8ZL

ZL

Possible incorrect tripping for fault at ‘F’

∴ Zone 1 set to ∼ 0.8ZL

Page 34: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 1 Settings for Direct Intertrip Schemes

Z1AReceiveSend

Trip ‘B’

Z1BReceive Send

Z1B

Z1A

ZLA

B

Page 35: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 1 Settings for Direct Intertrip Schemes

Effective Zone 1 reaches at A and B must overlap.Otherwise :- No trip for fault at ‘F’

∴ Effective Z1A and Z1B must be > 0.5ZL

Settings for Zone 1 > 0.8ZL are o.k.

Z1B

Z1A

F

A

B

Page 36: Distance Priciples_basic Principles

> Distance Protection - January 2004

Minimum Zone 1 Reach Setting

Dictated by :-

Minimum relay voltage for fault at Zone 1reach point to ensure accurate measurement.

Minimum voltage depends on relay design typically 1 → 3 volts.

Page 37: Distance Priciples_basic Principles

> Distance Protection - January 2004

System Impedance Ratio :- SIR

SIR = ZS/Zn

where :- ZS = Source impedance behind relayZn = Reach setting

VRPA = Minimum voltage for reach point accuracy

Can be expressed in terms of an equivalent value of SIRMAX

SIRMAX = ZS MAXZn MIN

∴ Zn MIN ≡ ZS MAXSIRMAX

Page 38: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 2

Covers last 20% of line not covered by Zone 1.Provides back-up protection for remote busbars.

To allow for errors :-Z2G > 1.2 ZGH

Zone 2 is time delayed to discriminate with Zone 1 on next section for faults in first 20% of next section.

Z1H

Z2G

TIMEZ1G

G H

F

Page 39: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 2

Overlap only occurs for faults in first 20% of following line.Faults at ‘F’ should result in operation of Z1H and tripping of circuit breaker ‘H’.

If ‘H’ fails to trip possible causes are :-Z1H operates but trip relays fail.

Z2H may operate but will not trip if followed by the same trip relays.Fault must be cleared at ‘G’ by Z2G.

Z1H and trip relays operate but circuit breaker fails to trip.

Zone 2 on adjacent line sections are not normally time graded with each other

Z1G Z1H

Z2G Z2H

‘H’‘G’F

Page 40: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 2

No advantage in time grading Z2G with Z2H

Unless Z2H + trip relays energise a 2nd circuit breaker trip coil.

Page 41: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 2Z1H fails to operate.

Results in race between breakers ‘G’ and ‘H’ if Z2H and Z2G have the same time setting.

Can only be overcome by time grading Z2G with Z2H.

Problem with this :-

Zone 2 time delays near source on systems with several line sections will be large.

End zone faults on lines nearest the infeed source point will be cleared very slowly.

Z1G Z1H

Z2G

Z2H

‘H’‘G’

Page 42: Distance Priciples_basic Principles

> Distance Protection - January 2004

Maximum Allowable Zone 2 Reach to Allow for Equal Zone 2 Time Settings

Z2A must not reach beyond Z1B

i.e. Z2A(EFF) MAX must not reach further than Z1B(EFF) MIN

Z1BSETTING = 0.8ZL2Z1B(EFF) MIN = 0.8 x 0.8ZL2 = 0.64ZL2

∴ Z2A(EFF) MAX < ZL1 + 0.64ZL2∴ 1.2 Z2ASETTING < ZL1 + 0.64ZL2

Z2ASETTING < 0.83ZL1 + 0.53ZL2

Z2A (EFF) MAX

Z1B (EFF) MIN

ZL2ZL1 BA

Page 43: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 2 Time Settings on Long Line Followed by Several Short Lines

Z3H

Z2G

Z3J

Z2HZ2J

Z1H Z1JZ1G

‘H’ ‘J’‘G’F

Z2G reaches into 3rd line section.

To limit remote back-up clearance for a fault at ‘F’, the time setting of Z2G must discriminate with Z3H.

Page 44: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone 3

Provides back-up for next adjacent line.Provides back-up protection for busbars (reverse offset).Actual Zone 3 settings will be scheme specified, i.e. permissive or blocking schemes.Many modern relays have more than 3 Zones to allow the use of three forward and an independent reverse zone.

HG K

Z1G Z1HZ2G

Z3G REV Z3G FWD

Time

Typical settings : Z3FWD > 1.2 x (ZGH + ZHK)Z3REV 0.1 to 0.25 of Z1G

Page 45: Distance Priciples_basic Principles

> Distance Protection - January 2004

Zone Time Coordination - Ideal Situation

Zone 1 :- tZ1 = instantaneous (typically 15 - 35mS)

Zone 2 :- tZ2 = tZ1(down) + CB(down) + Z2(reset) + Margine.g. tZ2 = 35 + 100 + 40 + 100 = 275mS

Zone 3 :- tZ3 = tZ2(down) + CB(down) + Z3(reset) + Margine.g. tZ3 = 275 + 100 + 40 + 100 = 515mS

Note: Where upper and lower zones overlap, e.g. Zone 2 up sees beyond Zone 1 down, the upper and lower zone time delays will need to be coordinated, e.g. tZ2(up) to exceed tZ2(down).

Page 46: Distance Priciples_basic Principles

> Distance Protection - January 2004

Under / Overreach

Page 47: Distance Priciples_basic Principles

> Distance Protection - January 2004

Under-Reach

Impedance presented > apparent impedance

%age Underreach = ZR - ZF x 100%ZR

where ZR = Reach settingZF = Effective reach

Page 48: Distance Priciples_basic Principles

> Distance Protection - January 2004

Underreaching Due to Busbar Infeed between Relay and Fault

IA IA+IB

Relay LocationIB

ZA ZB

VR = IAZA + (IA + IB) ZB

IR = IA

ZR = ZA + ZB + IB . ZB

IA

Page 49: Distance Priciples_basic Principles

> Distance Protection - January 2004

Underreaching Due to Busbar Infeed between Relay and Fault

∴ Relay with setting ZA + ZB will underreach withinfeed.

Relay with setting ZA + ZB + IB . ZB will measureIA

correctly with infeed present but if infeed is removed the relay will overreach.

Maximum allowable setting dictated by load impedance

Page 50: Distance Priciples_basic Principles

> Distance Protection - January 2004

Under-Reach

What relay reach setting is required to ensure fault at F is at boundary of operation ?

Impedance seen for fault at F= ZG + IG + IP . ZK

IGLimit of operation is when Impedance Seen = Reach Setting

∴ Reach setting required= ZG + IG + IP . ZK

IG

IP

ZK FIG+IP

ZG IG

RELAY

Page 51: Distance Priciples_basic Principles

> Distance Protection - January 2004

Over-Reach

Impedance seen < apparent impedance

%age Overreach = ZF - ZR x 100%ZR

where ZR = Reach settingZF = Effective reach

Page 52: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mutual Coupling

Page 53: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mutual Coupling

Mutual coupling causes distance relays to either underreach or overreach.

Positive and negative sequence has no impact.

Zero sequence mutual coupling can have a significant influence on the relay.

Only affects ground fault distance.

Page 54: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mutual Coupling Example Under Reach

Z2 ‘Boost’ G/F

Z2 PH

Zmo

Page 55: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mutual Coupling Example Over Reach

Z2 ‘reduced’ G/F

Z2 PH

Page 56: Distance Priciples_basic Principles

> Distance Protection - January 2004

Mutual Coupling Example Over Reach

Z1 G/F (optional)

Z1 G/F (normal)

Zmo

Page 57: Distance Priciples_basic Principles

> Distance Protection - January 2004

Ancilliary Functions

Page 58: Distance Priciples_basic Principles

> Distance Protection - January 2004

Switch on to Fault (SOTF)

XXX

Fast tripping for faults on line energisation, even where line VTsprovide no prefault voltage memory

Page 59: Distance Priciples_basic Principles

> Distance Protection - January 2004

Voltage Transformer Supervision

A VT fault and subsequent operation of VT fuses or MCB’s results in misrepresentation of primary voltagesRelay will remain stable as the current phase selector will not pick upSubsequent system fault may cause unwanted / incorrect trippingVTS operating from presence of V0 with no I0 or V2 with no I2 is used to block relay if required

Page 60: Distance Priciples_basic Principles

> Distance Protection - January 2004

VT Supervision

Under load conditionsLoss of 1 or 2 phase voltagesLoss of all 3 phase voltages

Upon line energisationLoss of 1 or 2 phase voltagesLoss of all 3 phase voltages

Digital input to monitor MCB

Set to block voltage dependent functions

Page 61: Distance Priciples_basic Principles

> Distance Protection - January 2004

Illustration of Basic Power Swing Blocking System

jX

Power Swing Locus

R

Z3

ZP

Page 62: Distance Priciples_basic Principles

> Distance Protection - January 2004

Power Swing BlockingA power swing will result in continuous change of current

Continuous output from the relay superimposed current element can be used to block for a power swing

Using this method the relay is able to operate for faults occurring during a power swingv

t

i, S

TS ~ 0.2 to 2 s

Load R

X

Page 63: Distance Priciples_basic Principles

> Distance Protection - January 2004

Directional Earth Fault Protection (DEF)

High resistance ground faults

Instantaneous or time delayed

IEC and IEEE curves

Single or shared signalling channel

Page 64: Distance Priciples_basic Principles

> Distance Protection - January 2004

21

67N

21

67N

R F

Independentsignalling channel

DEF