distribution overview ppt

Upload: abhijitwce

Post on 02-Jun-2018

249 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Distribution Overview PPT

    1/83

    1

    DISTRIBUTION PROTECTION OVERVIEW

    Kevin Damron & Mike Diedesch

    Avista Utilities

    Presented

    March 17th, 2014

    At the 31st Annual

    Hands-On Relay School

    Washington State University

    Pullman, Washington

  • 8/11/2019 Distribution Overview PPT

    2/83

    2

    Table of Contents

    System Overview .... 3

    Distribution (3-30MVA ) Transformer Protection ...... 14

    Relay Overcurrent Curves ... 22

    Symmetrical Components .... 8

    Distribution Fuse Protection .. 24

    Conductors ..... 28

    Electromechanical Relays used on Distribution Feeders.. 31Coordinating Time Intervals . 36

    Transformer Relay Settings using Electromechanical Relays . 48

    IEEE Device Designations ... 51

    Transformer & Feeder Protection using Microprocessor Relays . 52

    Transformer Differential Protection . 61

    Moscow 13.8kV Feeder Coordination Example . 64

  • 8/11/2019 Distribution Overview PPT

    3/83

    3

    System Overview - Distribution Protection

    Objective:

    Protect people (company personnel and the public) and equipment by the proper

    application of overcurrent protective devices.

    Devices include:

    Relays operating to trip (open) circuit breakers or circuit switchers, and/or fuses blowingfor the occurrence of electrical faults on the distribution system.

    Design tools used:

    1 Transformer and conductor damage curves,

    2 - Time-current coordination curves (TCCs), fuse curves, and relay overcurrent

    elements based on symmetrical components of fault current.

    Documentation:

    1 - One-line diagrams and Schematics with standardized device designations as defined

    by the IEEE (Institute of Electrical and Electronics Engineers) keeps everyone on the

    same page in understanding how the system works.

    2 - TCCs

  • 8/11/2019 Distribution Overview PPT

    4/83

    XFMR

    12/16/20

    MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kVFDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    4

    System Overview Inside the

    Substation Fence

    Transformer

    relays

    Feeder relay

  • 8/11/2019 Distribution Overview PPT

    5/83

    5

    XFMR

    12/16/20MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kV

    FDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    System Overview Outside the

    Substation Fence

    Midline

    recloser

    relay

  • 8/11/2019 Distribution Overview PPT

    6/83

    XFMR

    12/16/20 MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kVFDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECOND

    S

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCRFast: ME-341-B Mult=0.2

    Slow: ME-305-A Add=1000.Ia= 5665.9A T(Fast )= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.

    IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

    6

    System Overview Each device has at least one curve plotted with current and time values

    on the Time Coordination Curve.

  • 8/11/2019 Distribution Overview PPT

    7/83

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECOND

    S

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500

    CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCRFast: ME-341-B Mult=0.2

    Slow: ME-305-A Add=1000.Ia= 5665.9A T(Fast )= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.

    IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

    7

    System Overview

    Damage Curves:

    - transformer

    - conductor

    So, what curve goes where?

    What are the types of curves?

    Protective Curves:

    - relay

    - fuse

    Damage curves are at the top and to

    the right of the TCC.

    Protective curves lowest and to theleft on the TCC correspond to those

    devices farther from the substation

    where the fault current is less.

  • 8/11/2019 Distribution Overview PPT

    8/83

    8

    Transformer Protection - Damage Curve ANSI/IEEE C57.109-1985

    The main damage curve line shows only the thermal effect

    from transformer through-fault currents. It is graphed

    from data entered below (MVA, Base Amps, %Z ):10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. M1CTR=

    A

    A. T ransf. dam age curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.

    The dog leg on the curve is added to allow for additionalthermal and mechanical damage from (typically more

    than 5) through-faults over the life of a transformer

    serving overhead feeders.

    Dog leg curve - 10 times base current at 2 seconds.

    Main curve - 25 times base current at 2 seconds.

    Time at 50% of the maximum per-unit

    through fault current = 8 seconds.

    Avista has Category III size (5-30MVA) Distribution Transformers in service per the above standard.

  • 8/11/2019 Distribution Overview PPT

    9/83

    9

    Copper Conductor Damage Curves ACSR Conductor Damage Curves(2/0 damage at 1500A @ 100sec.) (2/0 damage at 900A @ 100sec.)

    Conductor Damage Curves

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @Voltage 13.8 kV By DLH

    For ACSR Conductor Damage Curves No.

    Comment Date 12/13/05

    1

    1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.ANo inst. TP@5=0.048s

    A

    A. Conductor damage curve. k=0.08620 A=355107.0 cmilsConductor ACSR336.4 ACSR

    B

    B. Conductor damage curve. k=0.08620 A=167800.0 cmilsConductor ACSR AWGSize 4/04/0 ACSR

    C

    C. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWGSize 2/02/0 ACSR

    D

    D. Conductor damage curve. k=0.08620 A=83690.0 cmilsConductor ACSR AWGSize 1/01/0 ACSR

    E

    E. Conductor damage curve. k=0.08620 A=52630.0 cmilsConductor ACSR AWGSize 2#2 ACSR

    FF. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWGSize 4#4 ACSR

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SEC

    ONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @Voltage 13.8 kV By DLH

    For Copper Conductor Damage Curves No.

    Comment Date 12/13/05

    1

    1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.ANo inst. TP@5=0.048s

    A

    A. Conductor damage curve. k=0.14040 A=105500.0 cmils

    Conductor Copper (bare) AWGSize 2/02/0 Copper

    B

    B. Conductor damage curve. k=0.14040 A=83690.0 cmilsConductor Copper (bare) AWGSize 1/01/0 Copper

    C

    C. Conductor damage curve. k=0.14040 A=52630.0 cmilsConductor Copper (bare) AWGSize 2#2 Copper

    D

    D. Conductor damage curve. k=0.14040 A=33100.0 cmilsConductor Copper (bare) AWGSize 4#4 Copper

    EE. Conductor damage curve. k=0.14040 A=20820.0 cmilsConductor Copper (bare) AWGSize 6#6 Copper

  • 8/11/2019 Distribution Overview PPT

    10/83

    10

    Conductor Rating556 730

    336.4 530

    4/0 340

    2/0 270

    1/0 230

    #2 180

    #4 140

    ACSR

    Ampacity Ratings

    Conductor Rating

    2/0 360

    1/0 310

    #2 230

    #4 170

    #6 120

    Copper

    Ampacity Ratings

    Conductor Ampacities

    Conductor at 25C ambient taken from the Westinghouse Transmission & Distribution book.

  • 8/11/2019 Distribution Overview PPT

    11/83

    11

    Comparing a 140T fuse versus a

    #4 ACSR Damage curve.

    The 140T wont protect the

    conductor below about

    550 amps where the curves cross.

    Conductor Protection Graph

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME- CURRENT CURVES @ Voltage 13.8 kV#4 ACSR & 140T By Protection

    For Aspen File: HORS M15 EXP.olr No.

    Comment Date 3/06

    1

    1. Moscow 515 Kear 140T Kearney 140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWG Size 4

  • 8/11/2019 Distribution Overview PPT

    12/83

    12

    Transformer Protection using

    115 kV Fuses

  • 8/11/2019 Distribution Overview PPT

    13/83

    13

    Transformer Protection using

    115 kV Fuses

    Used at smaller substations up to 7.5 MVA

    transformer due to low cost of protection.

    Other advantages are:

    - Low maintenance

    - Panel house & station battery not required

    There are also several disadvantages to

    using fuses however which are:

    Low interrupting rating from 1,200A (for

    some older models) up to 10,000A at 115 kV.By contrast a circuit switcher can have a rating

    of 25KAIC and our breakers have normally

    40KAIC.

    The fuses we generally use are rated to blowwithin 5 minutes at twice their nameplate

    rating. Thus, a 65 amp fuse will blow at 130

    amps. This compromises the amount of

    overload we can carry in an emergency and

    still provide good sensitivity for faults.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KVROK 451R2 By JDH

    For ROK FDR 451, BUS FAULTS: 3LG=3580A, SLG=3782A, L-L=3100A No.

    Comment ASPEN FILE: ROK NEW XFMR (2005 BASE).OLR Date 2-13-07

    STATION TRANSFORMER PROTECTION

    FEEDER VCR PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. LAT RP4211 50N CO-11 INST TD=1.000CTR=500/5 Pickup=2.A No inst. TP@5=0.048s

    2

    2. SMD-2B 65E VERY SLOW 176-19-065

    Minimum melt.H=8.33

    3

    3. LAT RP4211 50P CO-11 INST TD=1. 000CTR=500/5 Pickup=3.5A No inst. TP@5=0.048s

    4

    4. LAT RP4211 51P CO-11 CO-11 TD=2. 000CTR=500/5 Pickup=3.A No inst. TP@5=0.5043s

    5

    5. LAT RP4211 51N CO-11 CO-11 TD=4.000CTR=500/5 Pickup=2.A No inst. TP@5=1.0192s

    6

    6. LAT RP4211 FUSE S&C Link 65TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 7.3 percent.Rockford 13.8kV - ROCKFORD115 115.kV 1 T

  • 8/11/2019 Distribution Overview PPT

    14/83

    14

    The fuse time current characteristic (TCC) is fixed (although you can buy a standard, slowor very slow speed ratio which are different inverse curves).

    The sensitivity to detect lo-side SLG faults isnt as good as using a relay on a circuitswitcher or breaker. This is because we use DELTA/WYE connected transformers so the

    phase current on the 115 kV is reduced by the 3 as opposed to a three phase fault.

    Some fuses can be damaged and then blow later at some high load point.

    When only one 115 kV fuse blows, it subjects the customer to low distribution voltages.For example the phase to neutral distribution voltages on two phases on the 13.8 kV become

    50% of normal.

    No indication of faulted zone (transformer, bus or feeder).

    Transformer Protection using 115 kV Fuses - continued

    A

    B

    C

    a

    b

    c

    1.0 PU

    0.5 PU0.5 PU

  • 8/11/2019 Distribution Overview PPT

    15/83

    15

    Transformer Protection using a Circuit SwitcherShowing Avistas present standard using Microprocessor relays.

    13.8kV 115kV

  • 8/11/2019 Distribution Overview PPT

    16/83

    16

    Transformer Protection using a Circuit SwitcherShowing Avistas old standard using Electromechanical relays.

  • 8/11/2019 Distribution Overview PPT

    17/83

  • 8/11/2019 Distribution Overview PPT

    18/83

    18

    Transformer Protection using a Breaker

    This is very similar to using a circuit switcher with a couple of advantages such as: Higher interrupting 40kAIC for the one shown below. Somewhat faster tripping than a circuit switcher (3 cycles vs. 6 8 cycles).

    Possibly less maintenance than a circuit switcher. The CTs would be located on the breaker so it would interrupt faults on the bus section up to

    the transformer plus the transformer high side bushings.

  • 8/11/2019 Distribution Overview PPT

    19/83

    19

    SEL Various Relay Overcurrent Curves.Extremely Inverse steepest

    Very Inverse

    Inverse

    Moderately Inverse

    Short Time Inverse least steep

    The five curves shown here have the same

    pickup settings , but different time dial

    settings.

    These are basically the same as various E-Mrelays.

    Avista uses mostly extremely inverse on

    feeders to match the fuse curves.

    Relay Overcurrent Curves

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXTREMELY INVERSE SEL-EI TD=15.000

    CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

    2

    2. INVERSE SEL-I TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.8558s

    3

    3. MODERATELY INVERSE SEL-2xx-MI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.324s

    4

    4. SHORT TIME INVERSE SEL-STI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.1072s

    55. VERY INVERSE SEL-VI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.5478s

  • 8/11/2019 Distribution Overview PPT

    20/83

    20

    Time dial

    - at what time delay will the relay operate to

    trip the breaker

    - the larger time dial means more time delay

    - also known as lever from the

    electromechanical relay days- Instantaneous elements have a time dial

    of 1 and operate at 0.05 seconds.

    - Instantaneous curves are shown as a flat

    horizontal line starting at the left at the

    pickup value and plotted at 0.05 seconds.

    Relay Overcurrent Curves - Pickups & Time Dials

    Pickup- the current at which the relay will operate to trip the breaker.

    - also known as tap from the electromechanical relay days

    -expressed in terms of the ratio of the current transformer (CTR) that the relay is connected to,

    - e.g., a relay with a CTR of 120 and a pickup (or tap) of 4 will operate to trip the breaker at 480

    amps10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

    For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 251 PROTECTION

    MAXIMUM FEEDERFUSE

    HI-SIDE CT'S

    LO-SIDE CT'S

    MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sH=8.33

    2

    2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258sH=8.33

    3

    3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

    4

    4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401sH=8.33

    5

    5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    6

    6. IDR 251 50P 351S I NST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. IDR251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. 251 140T FUSE st n S&C Link140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

  • 8/11/2019 Distribution Overview PPT

    21/83

    21

    Same Time Dial = 9

    Right curve picks up at 960 Amps

    Left curve picks up at 320Amps

    Relay Overcurrent Curves - Example of Different Pickup & Time Dial Settings

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SE

    CONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXT INV 1 SEL-EI TD=15.000CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

    22. ~EXT INV 1 SEL-EI TD=12.000CTR=800/5 Pickup=6.A No inst. TP@5=3.2574s

    3

    3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

    4

    4. ~EXT INV 3 SEL-EI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.6287s

    5

    5. ~EXT INV 4 SEL-EI TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.5429s

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SE

    CONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME- CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXT INV 1 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

    2

    2. ~EXT INV 1 SEL-EI TD=9.000

    CTR=800/5 Pickup=5.A No inst. TP@5=2.4431s3

    3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=4.A No inst. TP@5=2.4431s

    4

    4. ~EXT INV 3 SEL-EI TD=9.000CTR=800/5 Pickup=3.A No inst. TP@5=2.4431s

    5

    5. ~EXT INV 4 SEL-EI TD=9.000

    CTR=800/5 Pickup=2.A No inst. TP@5=2.4431s

    Same Pickup = 960 Amps

    Top curve Time Dial = 15

    Bottom curve Time Dial = 2

  • 8/11/2019 Distribution Overview PPT

    22/83

    22

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVINT 12F1 By JDH

    For Indian Trail feeder 12F1 in INT 2007base.olr No.

    Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A Date 1-29-08

    TRANSFORMER PROTECTION

    STAT ION VCB 12F1 PROTECTION

    11. INT A-742 51P 351 SEL-VI TD=10.000CTR=600/5 Pickup=0.8A No inst. TP@5=2.5797sH=8.33

    2

    2. INT 12F1 51P 351S SEL-VI TD=1.800CTR=800/5 Pickup=3.A No inst. TP@5=0.4643s

    3

    3. INT 12F1 51G 351S SEL-VI TD=0.900CTR=800/5 Pickup=3.A No inst. TP@5=0.2322s

    4

    4. INT 12F1 51Q 351S SEL-VI TD=0.500CTR=800/5 Pickup=3.A No inst. TP@5=0.129s

    55. INT A-742 51G 351 SEL-VI TD=5.000

    CTR=600/5 Pickup=0.8A No inst. TP@5=1.2898sH=8.33

    6

    6. INT A-742 51Q 351 SEL-VI TD=3.000CTR=600/5 Pickup=0.8A No inst. TP@5=0.7739sH=8.33

    A

    A. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.4 percent.INDIAN TRAIL 12/16/20 MVA XFMR

    B

    B. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AAC556 kCMil AAC

    Microprocessor relays have different

    types of curves based on the type offault current being measured:

    51P phase time overcurrent

    51N or 51G ground time overcurrent

    51Q negative sequence time overcurrent

    Transformer relay curves

    Feeder relay curves

    51P phase time overcurrent

    51N or 51G ground time overcurrent

    51Q negative sequence time overcurrent

    This brings us to a brief discussion of:

  • 8/11/2019 Distribution Overview PPT

    23/83

    23

    Symmetrical Components

    Symmetrical Components for Power Systems Engineering,

    J. Lewis Blackburn,

    There are three sets of independent components in a three-phase

    system: positive, negative and zero for both current and voltage.

    Positive sequence voltages (Figure 1) are supplied by generators

    within the system and are always present. A second set of balanced

    phasors are also equal in magnitude and displaced 120 degrees

    apart, but display a counter-clockwise rotation sequence of A-C-B(Figure 2), which represents a negative sequence. The final set of

    balanced phasors is equal in magnitude and in phase with each

    other, however since there is no rotation sequence (Figure 3) this is

    known as a zero sequence.

  • 8/11/2019 Distribution Overview PPT

    24/83

    24

    Symmetrical Components

    Three phase (3LG) fault - Positive sequence currents for setting phase elements in relays.Phase -Phase (L-L) fault - Negative sequence currents for setting negative sequence elements in relays.

    Single phase (1LG or SLG) fault - Zero sequence currents for setting ground elements in relays.

    Symmetrical Components Notation:

    Positive Sequence current = I + = I1

    Negative Sequence current = I - = I2

    Zero Sequence current = I 0 = I0

    Phase Current notation:

    IA High side Amps

    Ia Low side Amps

    8.33= 115/13.8 = transformer Voltage (turns)ratioPhasor diagram from Fault-study Software.

    Examples of three 13.8kV faults showing the current distribution through aDelta-Wye high-lead-low transformer bank :

  • 8/11/2019 Distribution Overview PPT

    25/83

  • 8/11/2019 Distribution Overview PPT

    26/83

    26

    Symmetrical Components Negative Sequence, L-L 13.8 kV Fault

    115kV side sequence currents and voltages

    13.8kV side sequence currents and voltages

    A

    B

    C

    a

    b

    c

    RR

    IA = 309 -28 Ia = 0 0

    IB = 619 152 Ib = 4467 152

    IC = 309 -28 Ic = 4467 -28

    3LG 13.8kV fault = 5158A,

    Ib=Ic=4467 A, 4467/5158 = 86.6%=3/2IB3LG = IBLL = 619A

    IA & IC = IB or Ia & Ic = Ib

    I2 = the phase current/3 = 4467/3 = 2579

    Digital relays 50Q/51Q elements set using 3I2.

    3I2 = Ib x 3 = 4467 x 1.732 = 7737,

  • 8/11/2019 Distribution Overview PPT

    27/83

    27

    Symmetrical Components Zero Sequence, 1LG 13.8 kV Fault

    115kV side sequence currents and voltages

    A

    B

    C

    a

    b

    c

    RR

    3I0 is the sum of the 3 phase currents and since Ib & Ic

    = 0, then 3I0 = Ia. This means the phase and ground

    overcurrent relays on the feeder breaker see the same

    amount of current.

    5346/(8.33*3) = 370 amps. So the high side phasecurrent is the 3 less as compared to the 3 fault.

    Digital relays ground elements set using 3I0.13.8kV side sequence currents and voltages

    IA = 370 -118 Ia=3I0=5346 -118

    IB = 0 0 Ib = 0 0

    IC = 370 62 Ic = 0 0

    Ia = 3Va/(Z1 + Z2 + Z0)

  • 8/11/2019 Distribution Overview PPT

    28/83

    28

    Symmetrical Components - Summary of 13.8 kV Faults

    3LG positive sequence current

    SLG zero sequence current

    L-L negative sequence current

    IA = 619 Ia = 5158

    IB = 619 Ib = 5158IC = 619 Ic = 5158

    5158 / 8.33 = 619 Ia = 5158 = I1

    5346/(8.33x3) = 370 Ia = 5346 = 3I0

    If you have a Delta-Wye transformer bank, and you know the voltage ratio and secondary phase

    current values for 13.8kV 3LG (5158) and SLG (5346) faults, you can find the rest:

    IA = 309 Ia = 0

    IB = 619 Ib = 4467IC = 309 Ic = 4467

    5158 x 3/2 = 4467 Ib x 3 = 7737 = 3I2

    4467/(8.33x 3) = 309309 x 2 = 619

    IA = 370 Ia=5346IB = 0 Ib = 0

    IC = 370 Ic = 0

  • 8/11/2019 Distribution Overview PPT

    29/83

    29

    Symmetrical Components - Summary of 13.8 kV Faults

    Youve heard of a Line-to-Line fault, how about an Antler-to-Antler fault?

  • 8/11/2019 Distribution Overview PPT

    30/83

    30

    Electromechanical Relays

    used on Distribution Feeders

    Avistas standard distribution relay

    package (until the mid-1990s) included

    the following:

    3 phase 50/51 CO-11 relays,

    1 reclosing relay

    1 ground 50/51 CO-11 relay

    .

  • 8/11/2019 Distribution Overview PPT

    31/83

    31

    Objectives:

    Protect the feeder conductor

    Detect as low a fault current aspossible (PU = 50% EOL fault amps)

    Other than 51P, set pickup and timedial as low as possible and still haveminimum Coordinating Time Interval

    (CTI) to next device. CTI is minimum

    time between operation of adjacent

    devices.

    Carry normal maximum load (phaseovercurrent only).

    Pickup the feeder in a cold loadcondition ( 2 times maximum normalload) or pickup of the next feeder

    load

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KV By

    For No.

    Comment Date

    TRANSFORMER PROTECTION

    FEEDER VCB PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt.

    H=8.33

    2

    2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

    3

    3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

    4

    4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

    5

    5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

    6

    6. LAT421 FUSE S&C Link100TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

    B

    B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

    Electromechanical Relays

    used on Distribution Feeders

  • 8/11/2019 Distribution Overview PPT

    32/83

  • 8/11/2019 Distribution Overview PPT

    33/83

    33

    13 kV BUS

    FAULT at MIDLINE3LG = 2000 A1LG = 1000 A

    FEEDER SETTINGS51P = 2000 / 2 = 1000 A51N = 1000 / 2 = 500 A

    MIN FAULT at END OF LINE3LG = 1000 A

    1LG = 500 A

    MIDLINE SETTINGS51P = 1000 / 2 = 500 A51N = 500 / 2 = 250 A

    Electromechanical Relays

    used on Distribution Feeders

  • 8/11/2019 Distribution Overview PPT

    34/83

    34

    Electromechanical Relays

    used on Distribution Feeders

    13 kV BUS

    500A FEEDER SETTINGS51P = 960 A51N = 480 A

    SECTIONLOAD = 500 A

  • 8/11/2019 Distribution Overview PPT

    35/83

    35

    Electromechanical Relays

    used on Distribution Feeders

    13 kV BUS

    500A FEEDER SETTINGS51P = 960 A51N = 480 A N.O.

    SECTIONLOAD = 250 A

    SECTIONLOAD = 500 A

    SECTIONLOAD = 250 A

  • 8/11/2019 Distribution Overview PPT

    36/83

    36

    Most overhead feeders also use reclosing capability to automatically re-energize the feederfor temporary faults. Most distribution reclosing relays have the capability of providing up to three

    or four recloses.

    -- Avista uses either one fast or one fast and one time delayed reclose to lockout.

    The reclosing relay also provides a reset time generally adjustable from about 10 seconds tothree minutes. This means if we run through the reclosing sequence and trip again within the reset

    time, the reclosing relay will lockout and the breaker will have to be closed by manual means. Thetime to reset from the lockout position is 3 to 6 seconds for EM reclosing relays.

    -- Avista uses reset times ranging from 90 to 180 seconds.

    Lockout only for faults within the protected zone. That is; wont lockout for faults beyondfuses, line reclosers etc.

    Most distribution reclosing relays also have the capability of blocking instantaneous tripping.

    -- Avista normally blocks the INST tripping after the first trip to provide for a Fuse Protecting

    Scheme.

    Electromechanical Relays

    used on Distribution Feeders

    Reclosing

  • 8/11/2019 Distribution Overview PPT

    37/83

    37

    13 kV BUS

    RECLOSING SEQUENCE

    Closed

    Open

    0.5" 12" LOCKOUT

    RESET = 120"

    (INST Blocked during Reset Time)

    Electromechanical Relays

    used on Distribution Feeders

    Reclosing Sequence shown for a permanent fault

  • 8/11/2019 Distribution Overview PPT

    38/83

    38

    Distribution Fusing Fuse Protection/Saving Scheme

    Fault on fused lateral on an overhead feeder:

    - Station or midline 51 element back up fuse.

    - Station or midline 50 element protects fuse.

    During fault:

    Trip and clear the fault at the station (or linerecloser) by the instantaneous trip before the fuse

    is damaged for a lateral fault. Reclose the breaker. That way if the fault weretemporary the feeder is completely re-energized

    and back to normal.

    During the reclose the reclosing relay has to

    block the instantaneous trip from tripping again.

    That way, if the fault still exists you force thetime delay trip and the fuse will blow before you

    trip the feeder again thus isolating the fault and

    re-energizing most of the customers.

    Of course if the fault were on the main trunk

    the breaker will trip to lockout.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVM15 515 51N to 140T By Protection

    For Aspen File: HORS M15 EXP.olr No.

    Comment Date 3/06

    STATION FEEDER RELAYING

    MAXIMUM FEEDER FUSE

    1

    1. M15 515 GND TIME CO-11 TD=4.000CTR=160 Pickup=3.A No inst. TP@5=1.0192s

    2

    2. Moscow 515 Kear 140T Kearney 140TTotal clear.

    3

    3. M15 50N CO-11 INST TD=1.000CTR=160 Pickup=3.A No inst. TP@5=0.048s

  • 8/11/2019 Distribution Overview PPT

    39/83

    39

    Shows the maximum fault current for which

    S&C type T fuses can still be protected by a

    recloser/breaker instantaneous trip for

    temporary faults (minimum melt curve at 0.1

    seconds):

    6T 120 amps

    8T 160 amps10T 225 amps

    12T 300 amps

    15T 390 amps

    20T 500 amps

    25T 640 amps

    30T 800 amps40T 1040 amps

    50T 1300 amps

    65T 1650 amps

    80T 2050 amps

    100T 2650 amps

    140T 3500 amps

    200T 5500 amps

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. BR1 S&C 140T S&C Link140TMinimum melt.

    2

    2. ENDTAP S&C 40T S&C Link 40TMinimum melt.

    3

    3. M15 515 S&C 80T S&C Link 80TMinimum melt.

    Distribution Fusing Fuse Protection for Temporary Faults

  • 8/11/2019 Distribution Overview PPT

    40/83

    40

    NOTE: These values were taken from the S&C data bulletin 350-170 of March 28, 1988 based on nopreloading and then preloading of the source side fuse link. Preloading is defined as the source side

    fuse carrying load amps equal to its rating prior to the fault. This means there was prior heating of

    that fuse so it doesnt take as long to blow for a given fault.10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SE

    CONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME- CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. T FUSE S&C Link100TMinimum melt.

    2

    2. 251 140T FUSE stn S&C Link140TTotal clear.

    Distribution Fusing Fuse to Fuse Coordination

  • 8/11/2019 Distribution Overview PPT

    41/83

    41

    Typical continuous and 8 hour emergency rating of the S&C T rated silver fuse links plus the 140Tand 200T.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. BR1 S&C 140T S&C Link140TMinimum melt.

    Distribution Fusing S&C T-Fuse Current Ratings

    General Rule: Fuse Blows at 2X Rating in 5 Minutes

  • 8/11/2019 Distribution Overview PPT

    42/83

    42

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200

    CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1. 500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1. 000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140T

    Total clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCRFast: ME-341-B Mult=0.2

    Slow: ME-305-A Add=1000.Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z = 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

  • 8/11/2019 Distribution Overview PPT

    43/83

    43

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200

    CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1. 500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1. 000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCRFast: ME-341-B Mult=0.2

    Slow: ME-305-A Add=1000.Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z = 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

  • 8/11/2019 Distribution Overview PPT

    44/83

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 71000 1000

  • 8/11/2019 Distribution Overview PPT

    45/83

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

    For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 251 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    LO-SIDE CT'S

    MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sH=8.33

    2

    2. IDR A-777 51G 351 SEL-VI TD=1. 000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s

    H=8.33

    3

    3. IDR A-777 51N 351 SEL-EI TD=5. 700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

    4

    4. IDR A-777 51Q 351 SEL-EI TD=4. 200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401sH=8.33

    5

    5. IDR A-777 51Q 587 W2 SEL-EI TD=4. 300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    6

    6. IDR 251 50P 351S INST TD=1.000

    CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. IDR 251 51Q 351S SEL-EI TD=3. 500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. 251 140T FUSE stn S&C Link140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    45

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 71000 1000

  • 8/11/2019 Distribution Overview PPT

    46/83

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KV By

    For No.

    Comment Date

    TRANSFORMER PROTECTION

    FEEDER VCB PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt.

    H=8.33

    2

    2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

    3

    3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

    4

    4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

    5

    5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

    6

    6. LAT421 FUSE S&C Link100TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

    B

    B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

    46

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 71000 1000

    1

  • 8/11/2019 Distribution Overview PPT

    47/83

    47

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @Voltage 13.8 kV By DLH

    For M15 A-172 CS with fdr 515 with Kearney140T Fuse No.

    Comment Three Phase Fault Date 12/12/05

    1. Moscow515 Kear 140T Kearney140TMinimummelt.I= 5158.1A T= 0.10s

    2

    2. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5158.1A (32.2 sec A) T= 0.33s

    3

    3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 3LG

    3LG Fault Coordination

    Example:

    Top Ckt Swr w/ Phase E-M relay

    ----- 0.4 sec. ------

    Middle - E-M Phase relay for a 500

    Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 71000 1000

    1

  • 8/11/2019 Distribution Overview PPT

    48/83

    48

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @Voltage 13.8 kV By DLH

    For MoscowCS with fdr 515 with 140T fuses No.

    Comment Single Line to Ground Fault Date 12/12/05

    1. Moscow515 Kear 140T Kearney140TMinimummelt.I= 5346.4A T= 0.09s

    2

    2. M15 515 GND TIME CO-11 TD=4.000

    CTR=160 Pickup=3.A No inst. TP@5=1.0192sI= 5346.5A (33.4 sec A) T= 0.29s

    3

    3. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5346.4A (33.4 sec A) T= 0.31s

    4 4. M15 A-172 GND TIME CO-11 TD=4.000CTR=240 Pickup=4.A No inst. TP@5=1.0192sI= 5346.5A (22.3 sec A) T= 0.83s

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 1LG Type=A

    SLG Fault Coordination

    Example:

    Top Ckt Swr w/ E-M Phase relay

    ----- 0.4 sec. ------

    Middle - E-M relays (Phase &

    Ground) for a 500 Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 71000 1000

    1

  • 8/11/2019 Distribution Overview PPT

    49/83

    49

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @Voltage 13.8 kV By DLH

    For MoscowCS A-172 with fdr 515 with 140T Fuse No.

    Comment Line to Line Fault Date

    1. Moscow515 Kear 140T Kearney140TMinimummelt.I= 4467.0A T= 0.12s

    2

    2. M15-515 Phase Time CO-11 TD=1.500

    CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 4467.0A (27.9 sec A) T= 0.43s

    3

    3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L LL Type=B-C

    L-L Fault Coordination

    Example:

    Top Ckt Swr w/ E-M relay

    ----- 0.4 sec. ------

    Middle - E-M (Phase) relay for a 500

    Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

  • 8/11/2019 Distribution Overview PPT

    50/83

    IEEE Device Designations commonly used in Distribution Protection

  • 8/11/2019 Distribution Overview PPT

    51/83

    51

    2 Time delay relay.

    27 Undervoltage relay.

    43 Manual transfer or selective device.

    We use these for cutting in and outinstantaneous overcurrent relays,

    reclosing relays etc.

    50 (or 50P) Instantaneous overcurrent

    phase relay.

    50N (or 50G) Instantaneous overcurrent

    ground (or neutral) relay.

    50Q Instantaneous Negative Sequence

    overcurrent relay.

    51 (or 51P) Time delay overcurrent phase

    relay.

    51N (or 51G) Time delay overcurrentground (or neutral) relay.

    51Q Time delay Negative Sequence

    overcurrent relay.

    52 AC circuit breaker.

    Avista sometimes adds letters to these such as F for feeders, T for transformers, B for bus and BF for

    breaker failure.

    52/a Circuit breaker auxiliary switch closed

    when the breaker is closed.

    52/b Circuit breaker auxiliary switch closed

    when the breaker is open.

    59 Overvoltage relay.

    62 Time Delay relay

    63 Sudden pressure relay.

    79 AC Reclosing relay.

    81 Frequency relay.86 Lock out relay which has several contacts.

    Avista uses 86T for a transformer lockout,

    86B for a bus lockout etc.

    87 Differential relay.

    94 Auxiliary tripping relay.

  • 8/11/2019 Distribution Overview PPT

    52/83

    Mikes Turn

    52

    Distribution Transformer

  • 8/11/2019 Distribution Overview PPT

    53/83

    53

    Criteria (for outdoor bus arrangement, not switchgear)

    Protect the Transformer from thermal damage

    - Refer to Damage Curves

    Backup feeder protection (as much as possible)

    - Sensitivity is limited because load is higher

    Coordinate with downstream devices (feeder relays)

    Carry normal maximum load (phase only)

    Pick up Cold Load after outages

    Distribution TransformerElectromechanical Relays

    Distribution Transformer

  • 8/11/2019 Distribution Overview PPT

    54/83

    54

    Relays:

    3 High Side Phase Overcurrent (with time and instantaneous elements)

    1 Low Side Ground Overcurrent (with time and instantaneous elements)

    Sudden Pressure Relay

    Distribution Transformer

    Electromechanical Relays - Setting Criteria

    Distribution Transformer

    El t h i l R l S tti C it i

  • 8/11/2019 Distribution Overview PPT

    55/83

    55

    Phase Overcurrent Settings Current measured on 115kV side

    P Pickup (time overcurrent)

    Dont trip for load or cold load pickup (use 2.4 * highest MVA rating)

    Ends up being higher than the feeder phase element pickup

    Example: 12/16/20 MVA unit would use 2.4*20*5 = 240 amps (1940A low side)

    51P Time Lever (time dial)

    Coordinate with feeder relays for maximum fault (close in feeder fault)

    CTI is 0.4 seconds

    Worst coordination case: - on low side (discrepancy due to delta/wye conn.)

    Multiple feeder load can make the transformer relay operate faster

    50P Pickup (instantaneous overcurrent)

    Must not trip for feeder faults set at 170% of low side bus fault

    Accounts for DC offset

    Electromechanical Relays - Setting Criteria

    Distribution Transformer

    Electromechanical Relays - Setting Criteria

  • 8/11/2019 Distribution Overview PPT

    56/83

    56

    Ground Overcurrent Settings Current measured on 13.8 kV side

    N Pickup (time overcurrent)

    Set to same sensitivity as feeder phase relay (in case the feeder ground relay is failed)

    This setting is higher than the feeder ground, so we lose some sensitivity for backup

    51N Time Lever (time dial)

    Coordinate with feeder relays for ground faults

    CTI is 0.4 seconds

    50N Pickup (instantaneous overcurrent)

    DO NOT USE!!!!

    Electromechanical Relays Setting Criteria

    Distribution Transformer & Feeder Protection

  • 8/11/2019 Distribution Overview PPT

    57/83

    57

    with Microprocessor Relays

    Advantages:

    More precise TAP settings

    More Relay Elements

    Programmable Logic / Buttons

    Lower burden to CT

    Event Reports!!!!!!!!!

    Communications

    Coordinate with like elements

    (faster)

    More Settings

    Microprocessor

    Relay

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 8/11/2019 Distribution Overview PPT

    58/83

    58

    with Microprocessor Relays

    Elements We Set:

    51P

    50P

    50P2 (FTB)

    51G 50G (115kV)

    51N (13.8kV)

    50N1 (FTB)

    FTB = Fast Trip Block (feeder relays must be Microprocessor)

    Distribution Transformer & Feeder Protection

  • 8/11/2019 Distribution Overview PPT

    59/83

    59

    Transformer Phase Overcurrent Settings - Current measured on 115kV Side

    51P - Phase Time Overcurrent Pickup

    Set to 240% of nameplate (same as EM relay)

    51P Time Dial

    Set to coordinate with feeders fastest element for each fault

    CTI is still 0.4 seconds

    50P1 Phase instantaneous #1 Pickup

    Direct Trip

    Set to 130% of max 13.8 kV fault (vs. 170% with EM relay)

    50P2 Phase instantaneous pickup for Fast Trip Block scheme

    Set above transformer inrush

    4 Cycle time delay

    Blocked if any feeder overcurrent elements are picked up

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

  • 8/11/2019 Distribution Overview PPT

    60/83

    60

    Transformer Ground Overcurrent Settings - Current calculated from 115kV CTs

    51G - Ground Time Overcurrent Pickup

    Set very low (will not see low side ground faults due to transformer

    connection). Usually 120 Amps. 51GTime Dial

    Set very low

    50G1 Ground Instantaneous #1 Pickup

    Set very low. Usually 120 Amps.

    with Microprocessor Relays

    Symmetrical

    Components!

    Distribution Transformer & Feeder Protection

  • 8/11/2019 Distribution Overview PPT

    61/83

    61

    Transformer Neutral Overcurrent Settings - Current measured by neutral CT or

    calculated from 13.8kV CTs.

    51N - Ground Time Overcurrent Pickup

    Set slightly higher than feeder ground pickup (about 1.3 times)

    51NTime Dial

    Set to coordinate with feeder ground

    CTI is 0.4 seconds

    50N1 Ground Instantaneous for Fast Trip Block

    Set slightly above the feeder ground instantaneous pickup

    Time Delay by 4 cycles

    Blocked if Feeder overcurrent elements are picked up

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

    i i

  • 8/11/2019 Distribution Overview PPT

    62/83

    62

    Inrush The current seen when

    energizing a transformer.

    Need to account for inrush when usinginstantaneous elements (regular or FTB).

    Inrush can be approximately 8 times the

    nameplate of a transformer.

    Note that the microprocessor relay only responds to the 60 HZ fundamental and that this

    fundamental portion of inrush current is 60% of the total. So to calculate a setting, we could use

    the 8 times rule of thumb along with the 60% value. For a 12/16/20 MVA transformer, the

    expected inrush would be 8*12*5*0.6 = 288 amps. We set a little above this number (360 Amps).

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

    ith Mi R l

  • 8/11/2019 Distribution Overview PPT

    63/83

    63

    Transformer inrush UNFILTERED

    current. The peak current is about 1800

    amps.

    Transformer inrush FILTERED current

    (filtered by digital filters to show

    basically only 60 HZ). Peak is about700 amps.

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

    ith Mi R l

  • 8/11/2019 Distribution Overview PPT

    64/83

    64

    with Microprocessor Relays

    Microprocessor Feeder Relay

    Overcurrent

    Reclosing

    Fast Trip Block Output Breaker Failure Output

    Elements We Set:

    51P

    50P

    51G

    50G

    51Q

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 8/11/2019 Distribution Overview PPT

    65/83

    65

    Feeder Phase Overcurrent Settings

    51P - Phase Time Overcurrent Pickup

    Set above load and cold load (960 Amps for 500 Amp feeder)

    Same as EM pickup

    51P Time Dial

    Same as EM relay (coordinate with downstream protection with CTI)

    Select a curve

    50P Phase instantaneous Pickup

    Set the same as the 51P pickup (960 Amps)

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 8/11/2019 Distribution Overview PPT

    66/83

    66

    Feeder Ground Overcurrent Settings

    51G - Phase Time Overcurrent Pickup

    Same as EM pickup which is 480 Amps

    51G Time Dial

    Same as EM relay (coordinate with downstream protection)

    Select a curve

    50G Phase instantaneous Pickup

    Set the same as the 51G pickup

    with Microprocessor Relays

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 8/11/2019 Distribution Overview PPT

    67/83

    67

    Feeder Negative Sequence Overcurrent Settings

    51Q - Negative Sequence Time Overcurrent Pickup

    Set with equivalent sensitivity as the ground element (not affected by load)

    Coordinate with downstream protection

    51Q Time Dial

    Same as EM relay (coordinate with downstream protection)

    Select a curve

    50Q Negative Sequence instantaneous Pickup

    DONT USE!!!!!

    Contributions from motors during external faults could trip this

    with Microprocessor Relays

    Transformer Differential Protection

  • 8/11/2019 Distribution Overview PPT

    68/83

    68

    The differential relay is connected to both the high and low side transformer BCTs.

    EM Differential RelaySince the distribution transformer is connected delta wye the transformer CTs

    have to be set wye delta to compensate for the phase shift.

    Transformer Differential Protection External Fault

  • 8/11/2019 Distribution Overview PPT

    69/83

    69

    87R1

    87OP

    87R2

    PRI I

    PRI I

    SEC I

    SEC I

    EXTERNAL FAULTTHE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN THE SAME DIRECTION AND THENCIRCULATE BACK THROUGH THE CT'S. THEY DO NOTFLOW THROUGH THE OPERATE COIL

    CURRENT FLOW THROUGH AN E/M 87 DIFFERENTIALRELAY FOR AN INTERNAL AND EXTERNAL FAULT

    BCT'S

    BCT'S

    CT POLARITY MARK

    Transformer Differential Protection Internal Fault

  • 8/11/2019 Distribution Overview PPT

    70/83

    70

    87R1

    87

    OP

    87R2

    PRI I

    PRI I

    INTERNAL FAULT

    THE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN OPPOSITE DIRECTIONS, ADDAND THEN FLOW THROUGH THE OPERATE COIL ANDBACK TO THE RESPECTIVE CT'S

    SEC I

    SEC I

    BCT'S

    BCT'S

    CT POLARITY MARK

  • 8/11/2019 Distribution Overview PPT

    71/83

    71

    GRAB YOUR HANDOUT!MOSCOW FEEDER 515 PROTECTION EXAMPLE

    The Scenario

  • 8/11/2019 Distribution Overview PPT

    72/83

    72

    The Scenario

    A hydraulic midline recloser on a 13.8kV feeder in Moscow, ID is

    being replaced by a newer relayed recloser. The recloser is P584

    on feeder 515.

    The field engineer would like to replace the recloser in the existing

    location.

    Protection engineer must review the feeder protection and report

    back to the field engineer.

    NOTE: Avista designs for a fuse saving scheme with one

    instantaneous trip. The field engineers decide if they want to

    enable or disable the instantaneous tripping.

    MOSCOW FEEDER 515 PROTECTION EXAMPLE

  • 8/11/2019 Distribution Overview PPT

    73/83

    73

    MOSCOW FEEDER 515 PROTECTION EXAMPLE

    Where do we start the protection design?

    1) Gather Information:

    Feeder Rating (expected load) Protective devices (Breakers, line reclosers, fuses)

    Fault Duty (at each protective device)

    Conductors to be protected

    Project deadline (tomorrow?)

  • 8/11/2019 Distribution Overview PPT

    74/83

    74

    How do we proceed?

    At each coordination point

    Loading Coordination

    What will coordinate with the downstream device

    Are we above the fuse rating

    Conductor Protection minimum conductor that can be protected by the feeder settings or

    fuse

    Fault Detection Can we detect the fault by our 2:1 margin

    Fuse Saving for Temporary faults What can a fuse be protected up to?

  • 8/11/2019 Distribution Overview PPT

    75/83

    75

    Begin at the END

    POINT 8: This is a customers load and we are using 3-250 KVA

    transformers to serve the load. The full load of this size of bank is 31.4amps. The Avista transformer fusing standard says to use a 65T on this

    transformer so thats what well choose.

    FUSE - POINT 6B:

  • 8/11/2019 Distribution Overview PPT

    76/83

    76

    What we know: 3 lateral feeding to a 65T at the end #4 ACSR conductor

    Fuse Selection: Loading Assume the load is all downstream of point 8, so a 65T or higher will

    still suffice.

    Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

    100T or smaller fuse

    Fault Detection - Under the Relay Setting Criteria we want to detect the minimum

    line end fault with a 2:1 margin. The SLG is 463 so we calculate the max fuse as

    follows:

    463/2 (2:1 margin) = 231 amps. T fuses blow at twice their rating so divide

    by 2 again, with a result of 115. Fuse must be 100T or less.

    Coordination From Table 2, we see that we need an 80T or larger to coordinate

    with the downstream 65T fuse (at fault duties < 1400A w/preload)

    Fuse Saving - From Table 1 we see that an 80T fuse can be protected up to 2,050amps for temporary faults and the 3 fault is 1,907 amps so we could choose an

    80T or higher from that standpoint

  • 8/11/2019 Distribution Overview PPT

    77/83

    77

    Point 6B - So what fuse size should we use?

    POINT 5 Midline Recloser

  • 8/11/2019 Distribution Overview PPT

    78/83

    78

    What we know:

    Conductor to protect: #4 ACSR (can carry 140A load)

    Max fuse to coordinate with = 100T (FUTURE per distribution engineer)

    Maximum load (per engineer) = 84A

    Settings Considerations:

    Loading: Cold load would be 84*2 = 168 A, but the conductor can carry 140A max. Size for someload growth by setting at 2*conductor rating. 300 Amp phase pickup setting. NOTE: we dont design

    settings to protect for overload.

    Conductor Protection: From the table, Avistas 300A feeder settings can protect down to #2 ACSR, so300A pickup is still acceptable. Review curves to confirm.

    Fault Detection: detect the minimum fault with a 2:1 margin. Here the min fault is at point 6

    1. The - fault at point 6 is 0.866*1907 = 1,651 so our margin to detect that fault would be 1651/300= 5.5:1 so no problem with the 300 amps PU from that standpoint (used - because its the

    minimum multi phase fault)

    2. The SLG at point 6 is 1,492 so we could set the ground up to 1492/2 = 745 amps and still detect the

    fault. However, our criteria says to set as low as possible and still coordinate with the largest

    downstream device and from above were trying to use a 100T. Based on curves, this is 300 amps

    (same as phase, which is unusual). Coordination: Based on fault study, set the time dial to coordinate with a 100T fuse with 0.2 second

    CTI.

    Fuse Saving: The fault duty at the recloser is 3453 3PH and 2762 1LG. An instantaneous trip will

    protect the 80T fuse if the fault duty is less than 2050 Amps. Some fuse protection is compromised but

    there is nothing we can do about it.

    TRUNK FUSE - POINT 3C:

    What we know:

  • 8/11/2019 Distribution Overview PPT

    79/83

    79

    What we know: #4 ACSR 3 trunk

    Load is 84 Amps

    Downstream protection is the midline recloser

    Fuse Selection: Loading Assume the load is the same as at the midline recloser. We set that at

    300A, and a 200T can carry 295 A continuous.

    Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

    100T or smaller fuse.

    Fault Detection - Under the Relay Setting Criteria we want to detect the minimumline end fault with a 2:1 margin.

    SLG at midline is 2762 so even a 200T would provide enough sensitivity.

    Coordination PROBLEM! We have coordinated the midline with

    a 100T, so the upstream fuse must coordinate with that.

    Fuse Saving: As before, some fuse saving is compromised due to higher fault duty.

  • 8/11/2019 Distribution Overview PPT

    80/83

    80

    TRUNK FUSE Point 3C - Solutions?

  • 8/11/2019 Distribution Overview PPT

    81/83

    81

    TRUNK FUSE Point 3C - Solutions?

    Move Recloser

    Re-conductor

    FEEDER BREAKER - POINT 1:

  • 8/11/2019 Distribution Overview PPT

    82/83

    82

    What we know: This is a 500 amp feeder design. The load is 325 amps and cold load 650 per field engineer.

    Downstream protection is either the midline recloser or a 140T fuse.

    Settings Considerations: Loading: A standard 500 amp feeder phase pickup setting of 960 A will carry all normal

    load and pick up cold load. The ground pickup does not consider load and will be set at

    480A.

    Conductor Protection : The main trunk is 556 ACSR and from Table 7 a 500 amp feeder

    setting of 960 A can protect 1/0 ACSR or higher. Laterals with smaller conductor must be

    fused.

    Fault Detection:

    The - fault at point 5 is 0.866*3453 = 2990 so our margin to detect that fault would

    be 2990/960 = 3.1:1

    The SLG at point 5 is 2,762 so our margin to detect that fault is: 2762/480 = 5.7:1

    Coordination: Use fault study to calculate settings to achieve 0.2 second CTI to fuses and

    0.3 second CTI to the recloser.

    Fuse Saving We have decided that a 140T fuse is the maximum fuse we will use on the

    feeder even though it cant be saved by an instantaneous trip at the maximum fault duties.

  • 8/11/2019 Distribution Overview PPT

    83/83

    83

    Questions?