doc. n°: inverted bucket steam traps tiba - bluzac
TRANSCRIPT
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET – STEAM TRAPS
TIBA
Doc. n°: 11A261241 Rev.00
Pag.1/3
SIZES GENERAL NOTE – STEAM TRAPS PRODUCTION
ORIENTATION
Vertical connection
See data sheet n° 11A261530
Horizontal connection
CONNECTION
BW or NPT or BSP
Flanged
GENERAL NOTE – STEAM TRAPS STANDARD PRODUCTION
SIZES
from 1/2” to 6”
The inverted bucket type of steam trap is created for standard and special applications, designed to the customer’s specifications, welded body. Steam traps suitable for high pressures and capacities, usable for all applications. how it works: 1- The bucket is placed on the base, the shutter is opened; in the steam trap there is no fluid of any kind. 2- Start-up: when the condensate begins to circulate, the bucket is prevented from floating and the steam trap eliminates the excess condensate. 3- As the system heats up, the condensate reduces and steam starts to arrive, accumulating inside the vessel, trapped under the inverted bucket, which allows it to float on the condensate and keep the shutter closed. 4- As the steam condenses, the bucket sinks, returning to the base of the vessel where it opens the escape valve, permitting the internal pressure to discharge the accumulated condensate. All of Blu Zac products have been designed to satisfy the requests and specific requirements of the customer, including high pressure applications.
CONNECTIONS Buttweld BW ANSI B16.25
Flanged FLG ANSI B16.5 Socket
Welding SW ANSI B16.11
Screwed NPT BSP
ANSI B1.20.1 ANSI BS21
Reduced dimension and weight simple and reliable. It discharges air. It withstands water hammer. Condensate discharge is intermittent. Some loss of live steam.
� Steam mains � Tracing lines � Turbines � Marine applications � Presses
MAIN FEATURES
APPLICATION
LIMITING CONDITIONS ( according to ISO 6552 )
Steam Trap rating 600 Max Working Differential Pressure TIBA Dp10 bar TIBA Dp20 bar TIBA Dp40 bar TIBA Dp60 bar Min Working Differential Pressure 0,1 bar PMOB: max working back pressure 80%
Body and Cover Material A105 A350 LF2
A182 F304 A182 F316
A182 F304L A182 F316L
A182 F11 Cl.2 A182 F22 Cl.3
A182 F91
A182 F321 A182 F347
A182 F44 A182 F51 A182 F53
PMA: Max allowable pressure 103bar at 280°C 99bar at 425°C 82bar at 260°C 103bar at 450°C 99bar at 425°C 103bar at 450°C TMA: max allowable temperature 400°C at 70bar 530°C at 74bar 425°C at 55bar 530°C at 75bar 530°C at 74bar 530°C at 75bar PMO: max working pressure 103bar at 280°C 99bar at 425°C 82bar at 260°C 103bar at 450°C 99bar at 425°C 103bar at 450°C TMO: max working temperature 400°C at 70bar 530°C at 74bar 425°C at 55bar 530°C at 75bar 530°C at 74bar 530°C at 75bar
DISCARGE CAPACITY
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET – STEAM TRAPS
TIBA
Doc. n°: 11A261241 Rev.00
Pag.2/3
DIMENSION TOLLERANCE
SIZE
DIMENSION*
S SF & A F
1/2" to 2.1/2" ± 1 ± 1
3" to 4" ± 2 ± 2
*S, SF, A, H and H1 are in millimeters (mm)
Size 1/2" 3/4" 1" 1.1/4" 1.1/2" 2" 2.1/2" 3" A (mm) 258 258 258 258 258 258 258 258
F (mm) 47 47 47 47 47 47 47 47
S(mm) 382 382 382 400 400 400 420 420
SF (mm)
150RF 460 470 480 490 505 505 300RF 470 480 490 505 515 515 600RF 485 495 515 515 525 525
Wt (Kg)
150# 47 47 49 51 53 53 300# 47 47 49 52 56 56 600# 47 48 51 53 59 59
Hold phase
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET – STEAM TRAPS
TIBA
Doc. n°: 11A261241 Rev.00
Pag.3/3
ORDER CODE i.e. TIBA 2” 150RF A105 TIBAS 2” 150RF A105
POS DESCRIPTION MATERIALS MATERIALS MATERIALS MATERIALS SPARES
1 Body ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 2 Cover ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 3 Bucket AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X 4 Lever AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
5 Gasket SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-GraphiteW-316 X
6 Pivot AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
7 Support lever AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
8 Seat AISI 410 AISI 410 AISI 410 AISI 410 X 9 Nuts ASTM A193 B7 ASTM A320 L7 ASTM A193 B8 ASTM A193 B8
10 Studs ASTM A194 Gr.2H ASTM A194 Gr.4 ASTM A194 Gr.8 ASTM A194 Gr.8 11 Screwed Stainless Steel Stainless Steel Stainless Steel Stainless Steel X
Note 1: Other Materials and Dimensions on Request
HOW TO INSTALL: Vertical installation with vertical connection. Due to gravity, the condensate tends to go down, so the trap should be installed vertically below the point of the system condensate drainage .In this way, the inlet connection, located below the trap, maintain the bucket immersed in water. Recommended: - Install a filter upstream of the trap. - Install a check valve upstream from the trap when you have loads of very low condensate or superheated steam. - Check that the trap is properly sized to the plant before starting the installation. HOW TO MAINTENANCE: 1. Before starting, wear the required safety equipment and follow all plant safety procedures. 2. Stop the main line to make sure that no residues of dangerous waste fluid could be emitted. 3. Unscrew cover studs(10) and nuts(9), then remove the blind flange(2) and gasket(5). 4. Pick up the bucket (3) from lever (4). 5. Unscrew the lever guides. 6. Unscrew the valve seat (8) from the cover. 7. Screw a new seat to the cover. 8. Replace the guides, the lever and assemble the bucket (3). 9. Reposition the cover (2), then screw the studs(10) and nuts(9). 10. Slowly start the plant and check if there are any line losses. 11. Apply a label to the trap with the maintenance date.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBAO
Doc. n°: 11A261530 Rev.00
Pag.1/3
SIZES GENERAL NOTE – STEAM TRAPS PRODUCTION
ORIENTATION See data sheet n°
11A261530
Vertical connection
Horizontal connection
CONNECTION
BW or NPT or BSP
Flanged
GENERAL NOTE – STEAM TRAPS STANDARD PRODUCTION
SIZES
from 1/2” to 2”
CONNECTIONS Buttweld BW ANSI B16.25
Flanged FLG ANSI B16.5 Socket
Welding SW ANSI B16.11
Screwed NPT BSP
ANSI B1.20.1 ANSI BS21
Reduced dimension and weight simple and reliable. It discharges air. It withstands water hammer. Condensate discharge is intermittent. Some loss of live steam.
� Steam mains � Tracing lines � Turbines � Marine applications � Presses
MAIN FEATURES
APPLICATION
LIMITING CONDITIONS ( according to ISO 6552 )
Steam Trap rating 600 Max Working Differential Pressure TIBA Dp10 bar TIBA Dp20 bar TIBA Dp40 bar TIBA Dp60 bar Min Working Differential Pressure 0,1 bar PMOB: max working back pressure 80%
Body and Cover Material A105 A350 LF2
A182 F304 A182 F316
A182 F304L A182 F316L
A182 F11 Cl.2 A182 F22 Cl.3
A182 F91
A182 F321 A182 F347
A182 F44 A182 F51 A182 F53
PMA: Max allowable pressure 103bar at 280°C 99bar at 425°C 82bar at 260°C 103bar at 480°C 99bar at 425°C 103bar at 480°C TMA: max allowable temperature 400°C at 85bar 530°C at 73bar 425°C at 54bar 530°C at 78bar 530°C at 73bar 530°C at 75bar PMO: max working pressure 103bar at 280°C 99bar at 425°C 82bar at 260°C 103bar at 480°C 99bar at 425°C 103bar at 480°C TMO: max working temperature 400°C at 85bar 530°C at 73bar 425°C at 54bar 530°C at 78bar 530°C at 73bar 530°C at 75bar
DISCARGE CAPACITY
The inverted bucket type of steam trap is created for standard and special applications, designed to the customer’s specifications, welded body. Steam traps suitable for high pressures and capacities, usable for all applications. how it works: 1- The bucket is placed on the base, the shutter is opened; in the steam trap there is no fluid of any kind. 2- Start-up: when the condensate begins to circulate, the bucket is prevented from floating and the steam trap eliminates the excess condensate. 3- As the system heats up, the condensate reduces and steam starts to arrive, accumulating inside the vessel, trapped under the inverted bucket, which allows it to float on the condensate and keep the shutter closed. 4- As the steam condenses, the bucket sinks, returning to the base of the vessel where it opens the escape valve, permitting the internal pressure to discharge the accumulated condensate. All of Blu Zac products have been designed to satisfy the requests and specific requirements of the customer, including high pressure applications.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBAO
Doc. n°: 11A261530 Rev.00
Pag.2/3
DIMENSION TOLLERANCE
SIZE
DIMENSION*
S SF & A B
1/2" to 2.1/2" ± 1 ± 1
3" to 4" ± 2 ± 2
*S, SF, A, H and H1 are in millimeters (mm)
Size 1/2" 3/4" 1" 1.1/4" 1.1/2" 2"
A (mm) 436 436 436 452 452 460 S(mm) 310 310 310 330 330 340
B (mm) 600RF 431 447 450 470 480 495
SF (mm)
600RF 410 415 425 455 460 470 600RJ 410 415 425 455 460 475
Wt (Kg) 600# 86 87 88 92 96 122
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBAO
Doc. n°: 11A261530 Rev.00
Pag.3/3
ORDER CODE i.e. TIBAO10 2” 150RF A105 TIBAO10S 2” 150RF A105
POS DESCRIPTION MATERIALS MATERIALS MATERIALS MATERIALS SPARES
1 Body ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 2 Cover ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 3 Bucket AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X 4 Lever AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
5 Gasket SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-GraphiteW-316 X
6 Pivot AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
7 Support lever AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 AISI 304 or 316 X
8 Seat AISI 410 AISI 410 AISI 410 AISI 410 X 9 Nuts ASTM A193 B7 ASTM A320 L7 ASTM A193 B8 ASTM A193 B8
10 Studs ASTM A194 Gr.2H ASTM A194 Gr.4 ASTM A194 Gr.8 ASTM A194 Gr.8 11 Screwed Stainless Steel Stainless Steel Stainless Steel Stainless Steel X 12 Inner Pipe ASTM A312 TP316 ASTM A312 TP316 ASTM A312 TP316 ASTM A312 TP316 14 Plug Stainless Steel Stainless Steel Stainless Steel Stainless Steel
Note 1: Other Materials and Dimensions on Request
HOW TO INSTALL: Vertical installation with horizontal connection. Due to gravity, the condensate tends to go down, so the trap should be installed vertically below the point of the system condensate drainage .In this way, the inlet connection, located below the trap, maintain the bucket immersed in water. Recommended: - Install a filter upstream of the trap. - Install a check valve upstream from the trap when you have loads of very low condensate or superheated steam. - Check that the trap is properly sized to the plant before starting the installation. HOW TO MAINTENANCE: 1. Before starting, wear the required safety equipment and follow all plant safety procedures. 2. Stop the main line to make sure that no residues of dangerous waste fluid could be emitted. 3. Unscrew cover studs(10) and nuts(9), then remove the blind flange(2) and gasket(5). 4.Unscrew cover studs(10) and nuts(9), remove the blind flange(2) and gasket(5). 5.Pick up the bucket (3) from lever (4). 6.Unscrew the lever guides. 7.Unscrew the valve seat (8) from the cover. 8.Screw a new seat to the cover. 9.Replace the guides, the lever and assemble the bucket (3). 10.Reposition the cover (3), then screw the studs(10) and nuts(9). 11. Slowly start the plant and check if there are any line losses. 12. Apply a label to the trap with the maintenance date.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBDO
Doc. n°: 11G130917 Rev.00
Pag.1/3
SIZES GENERAL NOTE – STEAM TRAPS PRODUCTION
ORIENTATION Not possible
Vertical connection
Horizontal connection
CONNECTION
BW or NPT or BSP
Flanged
GENERAL NOTE – STEAM TRAPS STANDARD PRODUCTION
SIZES
from 1/2” to 2”
CONNECTIONS Buttweld BW ANSI B16.25
Flanged FLG ANSI B16.5 Socket
Welding SW ANSI B16.11
Screwed NPT BSP
ANSI B1.20.1 ANSI BS21
Reduced dimension and weight simple and reliable. It discharges air. It withstands water hammer. Condensate discharge is intermittent. Some loss of live steam.
� Steam mains � Tracing lines � Turbines � Marine applications � Presses
MAIN FEATURES
APPLICATION
LIMITING CONDITIONS ( according to ISO 6552 )
Steam Trap rating 300 Max Working Differential Pressure TIBDO Dp5 bar TIBDO Dp10 bar TIBDO Dp20 bar TIBDO Dp30 bar TIBDO Dp40 bar Min Working Differential Pressure 0,1 bar PMOB: max working back pressure 80%
Body and Cover Material A105 A350 LF2
A182 F304 A182 F316
A182 F304L A182 F316L
A182 F11 Cl.2 A182 F22 Cl.3
A182 F91
A182 F321 A182 F347
A182 F44 A182 F51 A182 F53
PMA: Max allowable pressure 51bar at 315°C 50bar at 425°C 42bar at 260°C 52bar at 480°C 50bar at 425°C 52bar at 480°C TMA: max allowable temperature 400°C at 45bar 530°C at 48bar 425°C at 40bar 530°C at 50bar 530°C at 48bar 530°C at 50bar PMO: max working pressure 51bar at 315°C 50bar at 425°C 42bar at 260°C 52bar at 480°C 50bar at 425°C 52bar at 480°C TMO: max working temperature 400°C at 45bar 530°C at 48bar 425°C at 40bar 530°C at 50bar 530°C at 48bar 530°C at 50bar
DISCARGE CAPACITY
The inverted bucket type of steam trap is created for standard and special applications, designed to the customer’s specifications, welded body. Steam traps suitable for high pressures and capacities, usable for all applications. how it works: 1- The bucket is placed on the base, the shutter is opened; in the steam trap there is no fluid of any kind. 2- Start-up: when the condensate begins to circulate, the bucket is prevented from floating and the steam trap eliminates the excess condensate. 3- As the system heats up, the condensate reduces and steam starts to arrive, accumulating inside the vessel, trapped under the inverted bucket, which allows it to float on the condensate and keep the shutter closed. 4- As the steam condenses, the bucket sinks, returning to the base of the vessel where it opens the escape valve, permitting the internal pressure to discharge the accumulated condensate. All of Blu Zac products have been designed to satisfy the requests and specific requirements of the customer, including high pressure applications.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBDO
Doc. n°: 11G130917 Rev.00
Pag.2/3
DIMENSION TOLLERANCE
SIZE
DIMENSION*
S SF & A B
1/2" to 2.1/2" ± 1 ± 1
3" to 4" ± 2 ± 2
*S, SF, A, H and H1 are in millimeters (mm)
Size 1/2" 3/4" 1" 1.1/4" 1.1/2" 2"
A (mm) 160 160 160 B (mm) 106 106 106 S (mm) 120 120 120
SF (mm)
150RF 300RF 225
Wt (Kg)
150# 300# 6,9
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBDO
Doc. n°: 11G130917 Rev.00
Pag.3/3
ORDER CODE i.e. TIBDO5 2” 150RF A105 TIBDO5S 2” 150RF A105
POS DESCRIPTION MATERIALS MATERIALS MATERIALS MATERIALS SPARES
1 Body ASTM A105 + ASTM A240 F316/316L
ASTM A350 LF2 + ASTM A240 F316/316L
ASTM A182 F304 + ASTM A240 F316/316L
ASTM A182 F316 + ASTM A240 F316/316L
2 Cover ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 3 Bucket AISI-316L AISI-316L AISI-316L AISI-316L X 4 Lever AISI-316L AISI-316L AISI-316L AISI-316L X
5 Gasket SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-Graphite W-316
SPW: F-GraphiteW-316 X
6 Pivot AISI-316L AISI-316L AISI-316L AISI-316L X
7 Support lever AISI-316L AISI-316L AISI-316L AISI-316L X
8 Seat AISI 410 AISI 410 AISI 410 AISI 410 X 9 Nuts ASTM A193 B7 ASTM A320 L7 ASTM A193 B8 ASTM A193 B8
10 Studs ASTM A194 Gr.2H ASTM A194 Gr.4 ASTM A194 Gr.8 ASTM A194 Gr.8 11 Nut Seat Stainless Steel Stainless Steel Stainless Steel Stainless Steel X 12 Inner Pipe ASTM A312 TP316L ASTM A312 TP316L ASTM A312 TP316L ASTM A312 TP316L 13 Washer Stainless Steel Stainless Steel Stainless Steel Stainless Steel X 14 Plug Stainless Steel Stainless Steel Stainless Steel Stainless Steel X
Note 1: Other Materials and Dimensions on Request
HOW TO INSTALL: Vertical installation with horizontal connection. Due to gravity, the condensate tends to go down, so the trap should be installed vertically below the point of the system condensate drainage .In this way, the inlet connection, located below the trap, maintain the bucket immersed in water. Recommended: - Install a filter upstream of the trap. - Install a check valve upstream from the trap when you have loads of very low condensate or superheated steam. - Check that the trap is properly sized to the plant before starting the installation. HOW TO MAINTENANCE: 1. Before starting, wear the required safety equipment and follow all plant safety procedures. 2. Stop the main line to make sure that no residues of dangerous waste fluid could be emitted. 3. Unscrew cover studs(10) and nuts(9), then remove the blind flange(2) and gasket(5). 4.Unscrew cover studs(10) and nuts(9), remove the blind flange(2) and gasket(5). 5.Pick up the bucket (3) from lever (4). 6.Unscrew the lever guides. 7.Unscrew the valve seat (8) from the cover. 8.Screw a new seat to the cover. 9.Replace the guides, the lever and assemble the bucket (3). 10.Reposition the cover (3), then screw the studs(10) and nuts(9). 11. Slowly start the plant and check if there are any line losses. 12. Apply a label to the trap with the maintenance date.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBEO
Doc. n°: 11G211025 Rev.00
Pag.1/3
SIZES GENERAL NOTE – STEAM TRAPS PRODUCTION
ORIENTATION See 12F131201
Vertical connection
Horizontal connection
CONNECTION
BW or NPT or BSP
Flanged
GENERAL NOTE – STEAM TRAPS STANDARD PRODUCTION
SIZES
from 1/2” to 2”
CONNECTIONS Buttweld BW ANSI B16.25
Flanged FLG ANSI B16.5 Socket
Welding SW ANSI B16.11
Screwed NPT BSP
ANSI B1.20.1 ANSI BS21
Reduced dimension and weight simple and reliable. It discharges air. It withstands water hammer. Condensate discharge is intermittent. Some loss of live steam.
� Steam mains � Tracing lines � Turbines � Marine applications � Presses
MAIN FEATURES
APPLICATION
LIMITING CONDITIONS ( according to ISO 6552 )
Steam Trap rating 300 Max Working Differential Pressure TIBEO Dp5 bar TIBEO Dp10 bar TIBEO Dp20 bar TIBEO Dp30 bar TIBEO Dp40 bar Min Working Differential Pressure 0,1 bar PMOB: max working back pressure 80%
Body and Cover Material A105 A350 LF2
A182 F304 A182 F316
A182 F304L A182 F316L
A182 F11 Cl.2 A182 F22 Cl.3
A182 F91
A182 F321 A182 F347
A182 F44 A182 F51 A182 F53
PMA: Max allowable pressure 51bar at 315°C 50bar at 425°C 42bar at 260°C 52bar at 480°C 50bar at 425°C 52bar at 480°C TMA: max allowable temperature 400°C at 45bar 530°C at 48bar 425°C at 40bar 530°C at 50bar 530°C at 48bar 530°C at 50bar PMO: max working pressure 51bar at 315°C 50bar at 425°C 42bar at 260°C 52bar at 480°C 50bar at 425°C 52bar at 480°C TMO: max working temperature 400°C at 45bar 530°C at 48bar 425°C at 40bar 530°C at 50bar 530°C at 48bar 530°C at 50bar
DISCARGE CAPACITY
The inverted bucket type of steam trap is created for standard and special applications, designed to the customer’s specifications, welded body. Steam traps suitable for high pressures and capacities, usable for all applications. how it works: 1- The bucket is placed on the base, the shutter is opened; in the steam trap there is no fluid of any kind. 2- Start-up: when the condensate begins to circulate, the bucket is prevented from floating and the steam trap eliminates the excess condensate. 3- As the system heats up, the condensate reduces and steam starts to arrive, accumulating inside the vessel, trapped under the inverted bucket, which allows it to float on the condensate and keep the shutter closed. 4- As the steam condenses, the bucket sinks, returning to the base of the vessel where it opens the escape valve, permitting the internal pressure to discharge the accumulated condensate. All of Blu Zac products have been designed to satisfy the requests and specific requirements of the customer, including high pressure applications.
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBEO
Doc. n°: 11G211025 Rev.00
Pag.2/3
DIMENSION TOLLERANCE
SIZE
DIMENSION*
S SF & A B
1/2" to 2.1/2" ± 1 ± 1
3" to 4" ± 2 ± 2
*S, SF, A, H and H1 are in millimeters (mm)
Size 1/2" 3/4" 1" 1.1/4" 1.1/2" 2"
A (mm) 150 150 155 155 155 155 B (mm) 85 85 85 85 85 85 S (mm) 100 100 100 100 100 100
SF (mm)
150RF 300RF 195
Wt (Kg)
150# 300#
[Digitare il testo]
Blu Zac reserves the right to carry-out any necessary modification without prior notice
INVERTED BUCKET– STEAM TRAPS
TIBEO
Doc. n°: 11G211025 Rev.00
Pag.3/3
ORDER CODE i.e. TIBEO5 1/2” 150RF A105
POS DESCRIPTION MATERIALS MATERIALS MATERIALS MATERIALS SPARES
1 Body ASTM A240 Gr.316/316L ASTM A240 Gr.316/316L ASTM A240 Gr.316/316L ASTM A240 Gr.316/316L 2 Cover ASTM A105 ASTM A350 LF2 ASTM A182 F304 ASTM A182 F316 3 Bucket AISI-316L AISI-316L AISI-316L AISI-316L 4 Lever AISI-316L AISI-316L AISI-316L AISI-316L 6 Pivot AISI-316L AISI-316L AISI-316L AISI-316L
7 Support lever AISI-316L AISI-316L AISI-316L AISI-316L
8 Seat AISI 410 AISI 410 AISI 410 AISI 410 11 Nuts Seat Stainless Steel Stainless Steel Stainless Steel Stainless Steel 12 Inner Pipe ASTM A312 TP316L ASTM A312 TP316L ASTM A312 TP316L ASTM A312 TP316L 13 Washer Stainless Steel Stainless Steel Stainless Steel Stainless Steel 14 Plug Stainless Steel Stainless Steel Stainless Steel Stainless Steel
Note 1: Other Materials and Dimensions on Request ASSEMBLING PRE-WELD
HOW TO INSTALL: Vertical installation with horizontal connection. Due to gravity, the condensate tends to go down, so the trap should be installed vertically below the point of the system condensate drainage .In this way, the inlet connection, located below the trap, maintain the bucket immersed in water. Recommended: - Install a filter upstream of the trap. - Install a check valve upstream from the trap when you have loads of very low condensate or superheated steam. - Check that the trap is properly sized to the plant before starting the installation. HOW TO MAINTENANCE: The inverted bucket TIBEO doesn’t allowed any kind of maintenance because body and cover are welded.
ASSEMBLING AFTER-WELD