A typical Lockout Relay would have two positions "TRIP - RESET". Under normal
condition, the handle would be turned to "RESET" position and would remain mechanicallylatched at this position. The Lockout Relay contact LR which is in series with the LockoutRelay coil would be closed at the 'RESET" position only. The fault contact FC makes onlywhen there is a fault in the circuit.
When the Lockout Relay coil LR is energise, it would released the mechanical latchholding the handle at 'RESET" position and the handle would spring return to 'TRIP"
position. So long as FC remains at close contact condition ( due tothe presence of a faultin the circuit ) the handle will not latched at "RESET" position but would always spring
return to "TRIP "
Fig. 1
Fig. 3
Fig. 2
L
FC
D1LR
LRD2
N
L
FC
D1LR
LRD2
N
L
FCD1
LR
LRD2
N
a. No Fault Condition - Fig. 1
Handle at "TRIP" position LR contact open circuit because handle is at "TRIP" position. FC contact open circuit because there is no fault condition
b. No Fault Condition - Fig. 2 Handle turn to "RESET " position
LR contact close circuit because handle at "TRIP" position. FC contact open circuit because there is no fault condition.
c. Fault Condition - Fig. 3
FC contact close circuit to energise Lockout Relay coil LR via the Lockout Relaycontact LR.
" 86 " LOCKOUT RELAY
46
APPLICATION
The Lockout Relay is a high speed Automatic Trip/Manual Reset auxiliary relay permit-
ting simultaneous operations of up to 48 contacts from 10A to 80A for AC and 10A to 63A
for DC.Lockout Relays are normally connected to the fault sensing contacts of the circuit
breakers. If a fault should occur, the Lockout Relays ensure that all the critical circuits areisolated and would remain isolated so long as the fault is not cleared. It's positive tripaction ensures that all the contacts would perform as to requirements and it multi-contact
arrangement eliminates the need for several control relays contacts.
PRINCIPLE OF OPERATION
TRIP RESET
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
2/52
KRAUS & NAIMER BLUE LINE RC/02/2004
b. Lockout Relay without manual release. Testing of the switching system can becarried out by energising the coil.
50
48
TRIP RESET
Switch Type CA10L CA20L CA25L A11L A14L C26L
CHR10L CHR16L
Ratings
Ith2 current (A) 20 25 32 20 25 40
Number of Contacts
- 60 deg. switching 24 24 24 43 48 21
- 90 deg. switching 24 24 24 38 48 18
Fig. 4b - Contact Ratings
When coil LR is energise, the mechanical latch holding the handle is release, and
the handle spring returns to "TRIP" position. Contact LR opens to isolate the coil from
the power supply to prevent overheating of the coil.
TYPES OF LOCKOUT RELAY
Two types of Lockout Relays are available:
a. Lockout Relay with Manual Release to allow testing of the of the switching system.
TRIP RESET
6450
4 max.
48
48
Switch Type CA10M CA20M CA25M A11M A14M C26M
CHR10M CHR16M
Ratings
Ith2 current (A) 20 25 32 20 25 40
Number of Contacts- 60 deg. switching 24 24 24 43 48 21
- 90 deg. switching 24 24 24 38 48 18
Fig. 4a - Contact Ratings
" 86 " LOCKOUT RELAY
47
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
3/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
4/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Typical Requirement
1. Lockout Relay with manual reset
2. Contact rating 40A
3. Contact requirement 4NO + 4 NC4. Coil voltage 110VDC
5. Engraving "TRIP-CLOSE"6. Trip Indicator required.
HOW TO ORDER
When ordering the Lockout Relay, the following datas are to be provided:1. Type of Lockout Relay required
Without Manual Release ( Type C26Letc.)
With Manual release (Type C26M etc )Manual Release type have a pushbutton which manually trips the Lockout Relay for
circuit testing of the contacts. The location of the pushbutton on the front of the unitmakes it unnecessary for the operator to go inside a live panel in order to mechanically
trip the device from behind the switch.
2. Contact Ratings required - refer Fig. 4
3. Contact Configuration required
Specify contact arrangements as follows; Number of contacts making at "TRIP" position and if required the terminal number.
Number of contacts making at "RESET" position and if required, the terminalnumber.
4. Coil voltage required.
5. Engraving on plate
For example, "TRIP-RESET"
6. Optional Extras
- Trip Indictor
" 86 " LOCKOUT RELAY
49
Ordering Code of Standard Switch
C26 M A723 / D 110
Contact Rating
Type M - With manual reset
L - Without manual reset
Contact Configuration
Frequency A - 50hz B - 60hz
D - DC
Coil Voltage
024 - 24v to 28v 038 - 32v to 40v 048 - 42v to 50v 060 - 60v 110 - 110v to 125v 220 - 220v to 240v 380 - 380v to 440v
The ordering code to be as follows:
Item Code Description
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
5/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
6/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
7/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
8/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
9/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
10/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
11/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
12/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
13/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Ammeter Switch 20A CHR10 A021/SGZ877*EG - S1/PR
4 positions 25A CHR16 A021/SGZ877*EG - S1/PR
2 CT 40A C26 A021/SGZ877E - S1/PR
Monitor phase current 6A CAD11 A021/SGZ877*EG - S1/PR
Ammeter Switch 20A CHR10 A048/SGZ878*EG - S1/PR
4 positions 25A CHR16 A048/SGZ878*EG - S1/PR 3 CT 40A C26 A048/SGZ878E - S1/PR
Monitor phase current 6A CAD11 A048/SGZ878*EG - S1/PR
Ammeter Switch 20A CHR10 SGZ879EG SIS0001 S1/PR
4 positions 25A CHR16 SGZ879EG SIS0001 S1/PR
3 CT 40A C26 SGZ879E SIS0001 S1/PR
Monitor phase current 6A CAD11 SGZ879EG SIS0001 S1/PR
Ammeter Switch 20A CHR10 SGZ880EG SIS0001 S1/PR
5 positions 25A CHR16 SGZ880EG SIS0001 S1/PR
3 CT 40A C26 SGZ880E SIS0001 S1/PR
Monitor phase & 6A CAD11 SGZ880EG SIS0001 S1/PR
neutral current
Ammeter Switch 20A CHR10 SGZ881EG SIS0001 S1/PR
5 positions 25A CHR16 SGZ881EG SIS0001 S1/PR
40A C26 SGZ881E SIS0001 S1/PR
6A CAD11 SGZ881EG SIS0001 S1/PR
"AS" Ammeter Switch
58
OFF
AMMETER
64
79
RT
S
OFF
AMMETER
64
79
R
T
S
OFF
AMMETER
64
79
R
T
S
N
2
4
6
8
OFF R S TR T
1
3
5
7
A
2
4
6
8
1
3
5
7
OFF 1 2 3R T
10
12
9
11
S
A
2
4
6
8
OFF R S T
10
12
1
3
5
7
9
11
N
14
16
13
15
+
-
R
S
T
N
A
2
4
68
1
3
57
OFF R S TR T
10
12
9
11
S
A
2
4
6
8
OFF R S TR T
10
12
1
3
5
7
9
11
S N
A
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
14/52
KRAUS & NAIMER BLUE LINE RC/02/200459
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Ammeter Switch 20A CHR10 SGZ891EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ891EG SIS0001 S1/PE
2 CT
3 phase 3 wire
Ammeter Switch 20A CHR10 SGZ892EG SIS0001 S1/PE 4 positions 25A CHR16 SGZ892EG SIS0001 S1/PE
2 CT with transducer 3 phase 3 wire
Ammeter Switch 20A CHR10 SGZ893EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ893EG SIS0001 S1/PE
3 CT
3 phase 3 wire
Ammeter Switch 20A CHR10 SGZ894EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ894EG SIS0001 S1/PE
3 CT with transducer
3 phase 3 wire
"AS" Ammeter Switch
64
OFF
RS
T
AMMETER
79
OFF
AMMETER
64
79
RT
S
1
3
5
7
2
4
6
8
OFF R S TR S T
A
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
OFF R S T
RT
R S TA
1
3
5
7
9
11
2
4
6
8
10
12
OFF R S TR S T
A
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
OFF R S T
A
RST
R S T
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
15/52
KRAUS & NAIMER BLUE LINE RC/02/200460
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Ammeter Switch 20A CHR10 SGZ895EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ895EG SIS0001 S1/PE
3 CT
3 phase 3 wire
Ammeter Switch 20A CHR10 SGZ896EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ896EG SIS0001 S1/PE
3 CT
3 phase 4 wire
"AS" Ammeter Switch
OFF
R
S
T
AMMETER
79
64
OFF
R
S
T
OFF
AMMETER
79
64
ROFF S T
1
3
5
7
4
6
8
2
R S T
9
11
10
12
A
N
ROFF S T
1
3
5
7
4
6
8
2
R S T
9
11
10
12
A
OFF
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
16/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Voltmeter Switch 20A CHR10 SGZ882EG SIS0001 S1/PR
4 positions 25A CHR16 SGZ882EG SIS0001 S1/PR
Phase to phase voltage 40A C26 SGZ882E SIS0001 S1/PR
Voltmeter Switch 20A CHR10 SGZ884EG SIS0001 S1/PR
7 positions 25A CHR16 SGZ884EG SIS0001 S1/PR
Phase to phase and 40A C26 SGZ884E SIS0001 S1/PRphase to neutral voltage
Voltmeter Switch 20A CHR10 SGZ885EG SIS0001 S1/PR
8 positions 25A CHR16 SGZ885EG SIS0001 S1/PR
Phase to phase and 6A CAD11 SGZ885EG SIS0001 S1/PR
phase to neutral voltage 40A C26 SGZ885E SIS0001 S1/PRthrough transducers
" VS " Voltmeter Switch
61
OFF
VOLTMETER
64
79
RSTR
ST
OFF
VOLTMETER
64
79
SNST
TR
RS RN
TN
OFF
VOLTMETER
64
79
SNST
TR
RS RN
TN
OFF
1
3
5
7
9
11
13
15
17
19
21
23
2
4
6
8
10
12
14
16
18
20
22
24
OFFRS
STTR
OFFTN
SNRN
V
+-
RS
+-
+-
+-
+-
+-
ST
TR
TN
SN
RN
OFF RS ST TR
R
T
S
1
3
5
7
V
2
4
6
8
1
3
5
7
TR ST RSOFF
V
R
S
T
9
11
2
4
6
8
10
12
RN SN TN
N
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
17/52
KRAUS & NAIMER BLUE LINE RC/02/200462
" VS " Voltmeter Switch
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Voltmeter Switch 20A CHR10 SGZ886EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ886EG SIS0001 S1/PE
Phase to phase voltage
via 2 PT 3 phase 3 wire system
Voltmeter Switch 20A CHR10 SGZ887EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ887EG SIS0001 S1/PE Phase to phase voltage
via 3 PT 3 phase 3 wire system
Voltmeter Switch 20A CHR10 SGZ888EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ888EG SIS0001 S1/PE
Phase to neutral voltage
via 3 PT
3 phase 4 wire system
Voltmeter Switch 20A CHR10 SGZ889EG SIS0001 S1/PE
5 positions 25A CHR16 SGZ889EG SIS0001 S1/PE
Phase tophase voltage
via 3 PT 3 phase 3 wire system
Voltmeter Switch 20A CHR10 A007/SGZ890*EG - S1/PE
7 positions 25A CHR16 A007/SGZ890*EG - S1/PE
Phase tophase and
Phase to neutral voltage
3 phase 4 wire system
RSOFF ST TR
2
6
8
4V
R S T
1
3
5
7
RSOFF ST TRR T
1
3
5
7
S
2
6
8
4V
RNOFF SN TN
2
6
8
4
R T
1
3
5
7
S N
V
RSOFF ST TRR T
1
3
5
7
S
2
6
8
4 V
OFF
OFF
RSST
TR
VOLTMETER
79
64
OFF
RS
ST
TR
OFF
VOLTMETER
79
64
OFF
VOLTMETER
64
79
SNST
TR
RS RN
TN
RNOFF SN TN
R T NTR ST RS
2
4
6
8
10
12
S
1
3
5
7
9
11
V
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
18/52
KRAUS & NAIMER BLUE LINE RC/02/2004
" VS + AS " Voltmeter /Ammeter Switch
Plate Type of Electrical Rating Switch SIS Handle Dimension
Engraving Metering Switch Diagram Ith2 Reference Code (Black) (Refer Pg. 2)
Voltmeter/Ammeter 20A CHR10 SGZ890EG SIS0001 S1/PE
4 positions 25A CHR16 SGZ890EG SIS0001 S1/PE
Phase to phase voltage
via 3 PT
3 CT
3 phase 3 wire system
63
64
64
OFF
RR-S
SS-T
TT-R
RS ST TR
A
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
R TS
19 20
ROFF
S T
CT
PT
V
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
19/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
20/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH
65
A
AB
EEB
Push
-inLev
el
Norm
alLe
vel
Fig. 2 - Handle movement
1. FEATURES OF DISCREPANCY SWITCH
a. Ratings available:
Size S00 - 10A Size S0 - 16A to 32A AC21 Size S1 - 20A to 63A AC21.
b. The lighting system is placed directly behind a translucent handle and consist of lamps
connected in series/parallel network as follows:
Size S00 consist of a single lamp Size S0 consist of 4 lamps with rating of 1.2W each. Size S1 consist of 6 lamps with rating of 1.2W each.
The advantage of having more than one lamp is that should one lamp fails, the other
lamps connected in the parallel network still operates but with reduced illumination in casea discrepancy condition occurs.
c. Auxiliary push-button contacts can be operated which operates when the handle isPush-in ( S0 AND S1 only )
d. Residual or slip-clutch contact can be incorporated on request ( S0 and S1 only ).
2. TYPES OF DISCREPANCY SWITCH
Kraus & Naimer discrepancy switch are available in the following sizes:a. Size S00 - for switch rating up to 10A. These switches are commonly used inmimic and mosaic panels. Low voltage switches of gold contact ( Type CA4-1 ) areavailable for electronics and thermocouple circuits.
b. Size S0 - for switch rating from 16A to 32A/AC21. These switches are commonlyused in mimic and mosaic panels. Low voltage switches of silver H- Bridge contact ( typeCAD12 ) or gold H-Bridge contact ( type CAD11) are available for electronics andthermocouple circuits.
c. Size S1 - for switch rating of 20A to 63A AC21. These switches are especiallysuitable for switching highly inductive loads e.g. circuit breaker coils etc.
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
21/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH FOR MOSIAC Mounting - Size S00
66
Lampterminals
Lock nut
Adaptor Lampholder
Lamp
Mosiac Grid
25
25
Fig. 4c- Rear mounting Fig. 4d- Front mounting by lock nut/adaptor on mosaic grid
Mosiactile
12 Translucenthandle
Fig . 4e- Ti le mounti ng ho le Fi g. 4f - Handle moun ted on til e.
b. Switch Ratings
The switch contacts operate when the handle is turn. The switches are suitable forboth AC and DC switching . Type CA4-1 with gold contacts are specially suitable for : Low voltage switching of electronics and thermocouple circuits due to it's lowcontact resistance.
Corrosive environment where the gold contact prevent oxidation of the contactsurface which can increases contact resistance.
In selecting the switch model for DC switching, the selection of appropriate switchdepends on: The DC supply voltage
The DC load current The type of load - resistive/inductive
In selecting the switch model for low voltage switching, the Dry Circuit Ratingshould not be exceeded. The Dry Circuit Rating refers to the relationship between thesupply voltage and load current. If the value exceeds, arcing may occur which would
remove the layer of gold on the contact.
3. DISCREPANCY SWITCH for Mosaic Panel Mounting - Size S00
Fig. 4a - M24/M25 Mounting
a. General in fo rmat ion .Type M 24 and M25 mountings are designed for used on mosaic panel with
24 x 24mm tiles - Type M24 25 x 25mm tiles - Type M25
The switch is slot in between the grids of the mosaic panel and mounted on thegrids and clamp on to the grids by means of the hexagonal nut from the front. Access to
the lamp is by removing the illuminated handle.
Handle
Mosiactile
Mosiac aluminium grid
Lamp
Switch
Lamp terminals
Cast alumnium casingmounted on grid
L2
L1
Fig. 4b- Constru ctional details of M24 and M25 mountin g
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
22/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for MOSIAC Mounting - Size S00
67
AC Swit ching Capacity
Switch Type CG4
Nominal Voltage V 500
Nominal Current
AC21 A 10 AC23/415V kW 2.2
Fig. 6d- AC Switching Capacity
DC Switching Capacity DC1 T = 1 mS ResistiveLoad
Number .of Series Contact1 2 3 4 CG424V 48V 95V 120V 10A
48V 95V 140V 190V 6A60V 120V 180V 240V 2.5A
Fig. 6e - DC Switching Capacity - resistive load
DC Switch ing Capacity T = 50 mS Induct ive Load
Number of Series Contact1 2 3 4 CG424V 48V 95V 120V 6A
48V 95V 140V 190V 3A60V 120V 180V 240V 1A
Fig. 6f - DC Switching Capacity - inductive load
Dry Circuit Rat ing CG4-1
1V 6V 12V 24V 48V 60V 120VAC1 1A 0.6A 0.45A 0.3A 0.22A 0.2A 0.15A
Fig. 6g - Dry Circuit Rating
Maximum Number of Contacts Possible
Switch Type Maximum Contacts Maximum StagesCG4 8 4
c. Light ing System for mounting Type M24 and M25
A single lamp is mounted directly below the translucent handle. The lamp used may beeither filament lamp ( Type T5.5K ) or LED which is available in red, yellow and green
colour. Maximum voltage possible is 60V for filament and 24V for LED.
i. Filamen t L amp
Supply Voltage Lamp Rating Lamp Reference
6V 0.75 W 999 T5.5K/6V
12V 0.75 W 999 T5.5K/12V24V 0.75 W 999 T5.5K/24V36V 0.75 W 999 T5.5K/36V48V 0.75 W 999 T5.5K/48V
60V 0.75 W 999 T5.5K/60V
i i. LED Lamp
Supply Voltage Yellow LED Red LED Green LED
24V LE-6-T5.5Y LE-6-T5.5R LE-6-T5.5G
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
23/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for MOSIAC Mounting - SIZE S0
68
4. DISCREPANCY SWITCH for Mosaic Mounting - Size S0
a. General Information
The Type M50 mounting is design for mounting Size S0 discrepancy switch on mosaictiles with the following dimensions:
50 x 50mm 75 x 75mmThe switch is screwed on the to the aluminium grid of the mosaic panel from the rear as
well as well as held by two screws from the front via the mosaic tile and clamp ring ( Refer
Fig. 9). Thetranslucent handle is screwed on to the aluminium shaft which operates theauxiliary contacts when the handle is Push-in and the switch contacts when the handle isturned. Removal of the handle from the shaft allows access to the lamps from the front ofthe panel.
Residual Contact( Optional )
Switch Contacts -Turn to Operate
Push to OperateInterlock & Auxillary
Contacts
LampHolder
Lamps
ClampingDisk
EscutcheonPlate
TranslucentHandle
SwitchShaft
Fig 6 - Type M50 Mounting
50
50
75
75
Fig. 7 Mounting on 50x50mm mosaic tile Fig. 8 - Mounting on 75x75 mosaic tile
Mosiac aluminium grid
Mosiac tile
Fig. 9 - Type M50 mounting method
30.5
Clamp Disk screwedto mosiac tile
ClampDisk Translucent
Handle
MosiacTile
Fig. 10a - Mounting hole Fig. 10b - Switch front Fig10c - Final mounting
on mosaic tile by two screws on mosaic tile.
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
24/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for MOSIAC Mounting - Size S0
69
LampsLampholder
Switchshaft
Fig. 11a - M50 Front Mounting Fig. 11b- M50 Front mounting
Fig 12a - Type M50 - lamp holder Fig. 12b - Type M50 rear mounting
b. Lighting System
110VDC
60V/1.2W 60V/1.2W
Fig. 7- Size S0 Lighting System
The Size S0 lighting system consist of a lamp holder with four socket outlets to
accommodate 4 telephone bulbs type T6.8K Voltages available for the lamps are 6V, 12V,24V, 30V, 36V, 42V, 48V and 60V of rating 1.2 watts per lamp. Depending on the control
voltage, the lamps can be connected in series/parallel circuit. ( Fig. 7 ) The advantage of
this arrangement is that should any of the lamps fails, other lamps in the parallel circuit will
still lights up to indicate discrepancy reducing the danger of not knowing that there is adiscrepancy fault due to lamp failures.
In addition, high bright LED lamps type LE6.5B are available in T6.8K. Ratingsavailable for LED/T6.8K are 12VDC/35mA and 24VDC/15mA and available in Red, Yellow
and Green Colour.
c. Lamps for S0 Discrepancy Switch
42-44mm6-6.5mm
Fig. 13a - Filament lamp type T6.8K
i. Filament Lamp
Supply Lamp Lamp
Voltage Rating Reference
6V 1.2W 999 T6.8K/612V 1.2W 999 T6.8K/1224V 1.4W 999 T6.8K/2436V 1.4W 999 T6.8K/36
42V 1.4W 999 T6.8K/4260V 1.5W 999 T6.8K/60
Fig. 13b - Types of filament lamp
ii. LED Lamp
Voltage Yellow LED Red LED Green LED
12V LE-6.5B-2Y LE-6.5B-2R LE-6.5B-2G24V LE-6.5B-4Y LE-6.5B-4R LE-6.5B-4G
Fig. 13c - Types of LED
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
25/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for MOSIAC Mounting - SIZE S0
70
D. Coding of Lamp holders Q100
S0 Q100 / RKD004
e. Push To Turn Interlocks and Auxiliary Contacts
The auxiliary contacts are rated at 10A and operates when the handle is Push-in. Up to amaximum of 8 auxiliary contacts are available.
S0 V130 / F 11 / 6 A - EL
Number of Auxillary ContactsNO NC Contacts0 0 without contacts1 0 1 contact0 1 1 contact1 1 2 contact2 0 2 contact0 2 2 contact2 2 4 contact3 1 4 contact
1 3 4 contact4 0 4 contact0 4 4 contact3 3 6 contact4 2 6 contact6 0 6 contact4 4 8 contact6 2 8 contact8 0 8 contact
Fig. 14 - Auxiliary contacts combination
e. Switch Ratings
Kraus & Naimer switches are design for both AC and DC switching. For DC switching,the selection of suitable switch type depends on:
The DC Voltage The DC Load Current
The type of Load - resistive or inductive. For rating on DC switching capacity,please refer to the information on "DC Switching Capacity" for C, CA and A switchesrespectively.
It is possible to add residual contacts to give a self-holding effect by adding the
optional extra M200
AC Swit chi ng Capacity
Switch Size Type Rating/Ith2S0 CHR10 20AS0 CHR16 25A
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
26/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for PANEL Mounting - SIZE S0
5. DISCREPANCY SWITCH FOR PANEL MOUNTING - SIZE S0
Fig. 15a - Type FT1 Panel Mounting for switch Size S0
Fig. 15b - Type FT2 Panel Mounting for switch Size S0
Translucenthandle
Lamp LampTerminal
AuxillaryContacts
SwitchContacts
Dismantling Tool SOE Q110 09( To remove Q110 switch body from handle)
Fig. 15c - Type FT1/FT2 Mounting for Size S0 switch constructional details
a. Size S0 Discrepancy switches for mounting on panels and mimic are available forswitch of ratings up to 32A and are suitable for:
Low voltage switches of silver contact ( Type CAD12 ) or gold contact ( TypeCAD11) for electronics and thermocouple circuits.
For power switching of highly inductive loads e.g. circuit breaker coils .
The types of mounting available are:
D
D = 37.5mm
Fig. 16a - FT1 Mounting
i. Type FT1Mounting ( Fig. 15a and Fig 16a. )The front escutcheon is a black ring . A black escutcheon plate can be provided
on request.
A
A
Fig 16b - FT2 Mounting
ii. Type FT2 Mounting ( Fig. 15b and Fig. 16b )
A square escutcheon plate 48 x 48 mm is provided which allows engravings.
71
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
27/52
KRAUS & NAIMER BLUE LINE RC/02/2004
DISCREPANCY SWITCH for PANEL Mounting - SIZE S0
iii. Type FH3 Mounting ( Fig. 16b )
Similar to Type FT2 except the escutcheon plate size is 64 x 64mm.
b. Handle
The translucent handle is screwed on to the aluminium shaft which operates the auxiliarycontacts when the handle is Push-in and the switch contacts when the handle is turned.Removal of the handle from the shaft allows access to the lamps from the front of the panel
c. Mounting System
The switch is mounted on to the panel by means of a single hole mounting 30mm with
locking nut.( Fig. 15c )
d. Lighting System
The Size S0 lighting system consist of a lamp holder with a socket outlets to accom-modate one lamp of Type BA9 base Voltages available for the lamps are 6V, 12V, 24V,30V
and 130VIn addition, high bright LED lamps type are available . Ratings available for LED are
6V, 12V, 24V, 110V and 220VDC.
e. Auxiliary ContactsThe auxiliary contacts are rated at 10A and operates when the handle is Push-in. Up to a
maximum of 2 auxiliary contacts are available. The type of contacts available are: Standard silver contacts Gold contacts for corrosive environments Gold H-Bridge contacts for low voltage application
f. Dismantling Tool SOE Q110 09
To separate the switch body ( consisting of the switch stage, auxillary contacts and thelighting system) from the handle/mounting system, a dismantling tool is available. This tool isespecially suitable :
When mounting the switch body to the mounting system.
When removing the switch body from the mounting system for the purpose ofremoving/changing the lamp from the lamp holder.
g. LampRemover 999 LZ8
This tool allow easy removal of the lamp from the lamp holder
h. Switch Ratings
Kraus & Naimer switches are design for both AC and DC switching. For DCswitching, the selection of suitable switch type depends on:
The DC Voltage The DC Load Current The type of Load - resistive or inductive. For rating on DC switching capacity,
please refer to the information on "DC Switching Capacity" for C, CA and Aswitches respectively.
It is possible to add residual contacts to give a self-holding effect by
adding the slip clutch optional extra M200
i. AC Switching Capaci ty
Switch Size Type Rating/Ith2S0 CA10 20A
S0 CA20 25AS0 CA25 32AS0 CHR10 20AS0 CHR16 25A
72
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
28/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
29/52
KRAUS & NAIMER BLUE LINE RC/02/2004
are 6V, 12V, 24V, 30V, 36V, 42V, 48V and 60V of rating 1.2 watts per lamp. Depending onthe control voltage, the lamps can be connected in series/parallel circuit. ( Fig. 19b ) The
advantage of this arrangement is that should any of the lamps fails, other lamps in theparallel circuit will still lights up to indicate discrepancy reducing the danger of not knowingthat there is a discrepancy fault due to lamp failures.
In addition, high bright LED lamps type LE6.5B are available in T6.8K. Ratingsavailable for LED/T6.8K are 12VDC/35mA and 24VDC/15mA and available in Red, Yellowand Green Colour.
e. Coding of Lamp holders Q100
S0 Q100 / RKD001
f. Push to Turn Interlock and Auxiliary ContactsThe auxiliary contacts are rated at 10A and operates when the handle is Push-in. Up to a
maximum of 8 auxiliary contacts are available.
S0 V130 / F 11 / 6 A - EL
Number of Auxillary ContactsNO NC Contacts0 0 without contacts1 0 1 contact0 1 1 contact1 1 2 contact2 0 2 contact0 2 2 contact2 2 4 contact3 1 4 contact1 3 4 contact4 0 4 contact0 4 4 contact3 3 6 contact
4 2 6 contact6 0 6 contact4 4 8 contact6 2 8 contact8 0 8 contact
e. Switch Ratings
Kraus & Naimer switches are design for both AC and DC switching. For DC switching,the selection of suitable switch type depends on:
The DC Voltage
The DC Load Current
The type of Load - resistive or inductive. For rating on DC switching capacity, please
refer to the information on "DC Switching Capacity" for C, CA and A switches respectively.It is possible to add residual contacts to give a self-holding effect by adding the
optional extra M200
i. AC Switching Capaci ty
Switch Size Type Rating/Ith2 Maximum Number of StagesS0 CA10 20A 5S0 CA20 25A 4S0 CHR10 20A 4
S0 CHR16 25A 4
DISCREPANCY SWITCH for PANEL Mounting - SIZE S0/S1
74
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
30/52
KRAUS & NAIMER BLUE LINE RC/02/2004
7. DISCREPANCY SWITCH FOR PANEL MOUNTING - SIZE S1
D
D = 50mm
Fig. 20a - Type EL Panel Mounting for switch Size
1
ClampingDisk Front
Plate
TranslucentHandle
Residual Contact( Optional )
Switch Contacts -Turn to Operate
Push to Operate Interlock& Auxillary Contacts
LampHolder
Fig. 20b - Type EL Mounting for Size S1 switch constructional details
a. Size S1 Discrepancy switches for mounting on panels and mimic are available for switchof ratings up to 80A and suitable for power switching of highly inductive loads e.g. circuit
breaker coils etc.
b. HandleThe translucent handle is screwed on to the aluminium shaft which operates the auxiliary
contacts when the handle is Push-in and the switch contacts when the handle is turned.
Removal of the handle from the shaft allows access to the lamps from the front of the panel
c. Clamping System
Fig. 21 - Handle and clamping system
The switch is mounted on to the panel by means of a clamping system which consist of
the clamping disk, pressing ring and the lamp-holder. Mounting and tightening of the switch tothe panel is by means of the four screws fitted on the lamp holder ( Fig. 17) .
d. Lighting System
42-44mm6-6.5mm
110VDC
42V/1.2W 42V/1.2W 42V/1.2W
Fig. 22a - Filament lamp type T6.8K Fig. 22b- Size S1 Lighting System
The Size S1 lighting system consist of a lamp holder with six socket outlets to
accommodate 6 telephone bulbs type T6.8K( Fig. 22a ) Voltages available for the lamps are6V, 12V, 24V, 30V, 36V, 42V, 48V and 60V of rating 1.2 watts per lamp. Depending on thecontrol voltage, the lamps can be connected in series/parallel circuit. ( Fig. 22b ) The advan-tage of this arrangement is that should any of the lamps fails, other lamps in the parallel
circuit will still lights up to indicate discrepancy reducing the danger of not knowing that thereis a discrepancy fault due to lamp failures.
In addition, high bright LED lamps type LE6.5B are available in T6.8K. Ratingsavailable for LED/T6.8K are 12VDC/35mA and 24VDC/15mA and available in Red, Yellow
DISCREPANCY SWITCH for PANEL Mounting - SIZE S1
75
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
31/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
32/52
KRAUS & NAIMER BLUE LINE RC/02/2004
8. ORDERING PROCEDURE
P
N
R
OALARM
Fig. 21 - Typical Discrepancy Switch Circuit
a. Typical Specifications
When the handle of a discrepancy swi tch is turn 90 degrees, the mimic diagram ofthe control panel will immediately indicate any circuit interruptions . The handle of thediscrepancy switch will be illuminated to indicate a discrepancy between the conditionas indicated in the mimic panel and the actual condi tion of the circui t breaker. Forexample, if the circuit breaker and the discrepancy switch handle is in the is in the"CLOSED" positi on, the handle will not be illuminated because there is no discrepancy
between what is shown in the mimic panel and the actual condition of the circui tbreaker.
If the circu it breaker TRIP due to a fault condi tion, the handle of the discrepancyswitch will be ill uminated because a discrepancy arise i.e. the handle is still in the
CLOSE condition. The lamp wil l cut of f only when the handle is turn to the TRIPposition . This removes the discrepancy between the mimic diagram and the true
position of the breaker.Pushing-in and Turning the discrepancy switch handle at the TRIP position will
activates the tripping circuit of the breakerPush-in and Turning the handle at the 'CLOSE" posi tion wi ll activates the
closing circuit of the breaker.The switching conf iguration required is as shown in Fig. 22. Contact rating
required is 25A. Auxili ary contact required is 1 NO + 1 NC . Voltage of the lighting
system is 110V
EEB A AB
1 2
3
5
7
4
6
8
13 14
15 16
Closed contact
Continous contact
Residual contact
Fig. 22 - Required contact configuration
9. HOW TO ORDER - Size S0
When ordering a Discrepancy Switch, the following are to be provided:a. Switch Typeselected according to the control voltage, load current and the type of
load. In this case CHR16 would be suitable
b. The Switching Configurationrequired ( refer Fig. 22 ). The switch can be given a
special switch reference :
CHR16 SGxxx1
c. The number ofAux il iary contacts required. In this case 1 NO + 1 NC auxiliary
contact are required. As no engravings are required on the escutcheon plate, FT1
DISCREPANCY SWITCH for PANEL Mounting
77
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
33/52
KRAUS & NAIMER BLUE LINE RC/02/200478
mounting type of lamp holder would be suitable.Hence the coding for the Control & Indicator
Device with TURNING/PUSHING facility Iis as follows:
S0 Q110/F11A1
d. The Ordering Code as follows:Reference DescriptionCHR16 SGxxx1 Switch
S0 Q110/F11A1 Control & Indicator device with single hole FT! mountingOperation by TURNING/PUSHING
999 BA9/130V 130V Filament Lamp
10. HOW TO ORDER - Size S0/S1
When ordering a Discrepancy Switch, the following are to be provided:a. Switch Typeselected according to the control voltage, load current and the type of
load. In this case CHR16 would be suitable
b. The Switching Configurationrequired ( refer Fig. 22 ). The switch can be given a
special switch reference :
CHR16 SGxxx2
c. The number ofAux il iary contacts required. In this case 1 NO + 1NC auxiliary contact
are required. Hence the coding for the Push to Turn Interlock Device which housed the
auxiliary contacts is:
S0 V130/F11/6A-EL
d. EL mounting type of lamp holder would be suitable. Hence the coding for the lamp holder
is:
S0 Q100/RKD001
e. The Ordering Code as follows:
Reference DescriptionCHR16 SGxxx2 SwitchS0 V130/F11/6A-EL Push to Turn Interlock Device & 1 N0+ 1NC aux. contact4 x 999 T6.8K/60 Filament Lamps
S0 Q100/RKD001 Lamp holder
11. HOW TO ORDER - Size S1
When ordering a Discrepancy Switch, the following are to be provided:a. Switch Typeselected according to the control voltage, load current and the type ofload
In this case CHR16B would be suitable
b. The Switching Configurationrequired. The switch can be given a special switch
reference :
CHR16B SGxxx3
c. The number ofAux il iary contacts required. In this case 1 NO + 1 NC auxiliary
contact are required. Hence the coding for the Push to Turn Interlock Device whichhoused the auxiliary contacts is:
S1 V130/F11/6A-EL
d. EL mounting type of lamp holder would be suitable. Hence the coding for the lamp
holder is:
S1 Q100/A2/B
e. The Ordering Code as follows:Reference Description
CHR16 SGxxx3 SwitchS0 V130/F11/6A-EL Push to Turn Interlock Device & 1 N0 + 1 NC aux.
contact 6 x 999 T6.8K/60 Filament LampsS1 Q100/A2/B Lamp holder
DISCREPANCY SWITCH for PANEL Mounting
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
34/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Discrepancy Switch w ith Key Lock Device
Fitted with separate drive key lock device Type V760 which willallow operation of thediscrepancy switch only by authorised personnels.
Key lock device available with differnt types of locks
Available in Size S0 and S1.
Discrepancy Switch with key lock Size S0 Discrepancy Switch with key lock Size S1
Switch Lamp holder
Key Lock Device
DISCREPANCY SWITCH for PANEL Mounting - Other Versions
79
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
35/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Mounting Electrical Rating Switch SIS Switch Handle Mounting
Type Drawing Ith2 Reference Code Depth Size Hole
20A CHR10 SGC081*EL SIS0001 120 S0 30.5
25A CHR16 SGC081*EL SIS0001 120 S0 30.5
Discrepancy Switch - Size S0 Panel Mount
80
Size S0 handle without plate
38
Size S0 handle with plate
2
4
6
8
1
3
5
7
A B
Auxillarycontacts
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
36/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Mounting Electrical Rating Switch SIS Switch Handle Mounting
Type Drawing Ith2 Reference Code Depth Size Hole
20A CHR10 RK8201*EL SIS0001 S1 46
25A CHR16 RK8201*EL SIS0001 S1 46
40A C26 RK8201*EL SIS0001 S1 46
Size S1 handle without plate
20A CHR10 RK8202*EL SIS0001 S1 46
25A CHR16 RK8202*EL SIS0001 S1 46
40A C26 RK8202*EL SIS0001 S1 46
Size S1 handle with plate 20A CHR10 RK8203*EL SIS0001 S1 46
25A CHR16 RK8203*EL SIS0001 S1 46
40A C26 RK8203*EL SIS0001 S1 46
20A CHR10 RK8204*EL SIS0001 S1 46
25A CHR16 RK8204*EL SIS0001 S0 46
40A C26 RK8204*EL SIS0001 S1 46
20A CHR10 RK8205*EL SIS0001 S1 46
25A CHR16 RK8205*EL SIS0001 S1 46
40A C26 RK8205*EL SIS0001 S1 46
2
4
6
8
1
3
5
7
OPEN CLOSE
9
11
10
12
2
4
6
8
1
3
5
7
OPEN CLOSE
9
11
10
12
2
4
6
8
1
3
5
7
OPEN CLOSE
9
11
10
12
2
4
6
8
1
3
5
7
OPEN CLOSE
9
11
10
12
2
4
6
8
1
3
5
7
OPEN CLOSE
Discrepancy Switch - Size S1 Panel Mount
81
50
52
52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
37/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
38/52
KRAUS & NAIMER BLUE LINE RC/02/2004
1. APPLICATION
Key operated switches are extensively used in situations : To prevent inadvertent operation of the electrical circuits. To provide security against unauthorised operations of the electrical circuits.
To ensure that the key operational personals are in attendance before the criticalelectrical circuits can be operated.
2. TYPES OF KEY LOCKS
To prevent inadvertent operations, the handle of the critical switch can :a. Be replaced by a key which can be removed at selected positions using theKraus &
Naimer key lock device type V750/V750D. To prevent unauthorised duplication of keys orhave master key lock system, high security KABA key locks can be used.b. Be locked the handle in selected positions by means of a separate key lock deviceusing theKraus & Naimer safety key lock device type V760.c. Be replaced with a removable "handle" type key using theKraus & Naimer key handledevice type V900 in which the standardKraus & Naimer handle can be fitted to the key
device. Master key lock systems are available.
3. FEATURES OF KEY LOCK DEVICE V750/V750D
The device replace the normal switch handle by a key. Features of the V750/V750D keylock device are:a. It has several locking programs which allows the key to be removed up to a maximum of12 positions.b. It has several different types of locks/keys. In critical installations, key personals must bepresent before operating the electrical circuits. This can be done by issuing different keys
to operate different key switches to the key personals. Hence all the key personals must bepresent to switch on all the key switches fitted with different locks before the installation canfinally be switched on. Master key lock systems are available.c. It is available with single hole mounting of
22/25/30 mm for S0 switch (20-32A AC21) 40 mm for S1 switch ( 32-63A/AC21)
4. FEATURES
Kraus & Naimer is able to offer a wide range of key operated switches where:a. Standard switches are used but the key locks can be programmed for safety/security
applications.b. Non-standard switches are required with standard programs.c. Non-standard switches are required with special programs.
In ordering key switches, the following information are required:
Switch Rating Types of Mounting Types of Key Locks Types of Locking Programs
a. Switch Rating Fig. 4a
Rating Ith2 SwitchType Switch Size
20A CHR10 S025A CHR16 S020A CHR10B S125A CHR16B S140A C26 S1
63A C32 S180A C42 S1
83
KEY SWITCH
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
39/52
KRAUS & NAIMER BLUE LINE RC/02/200484
b. Types of MountingVarious types of mountings are available depending on the requirement:
i. Single hole mountings ( Fig 2 )
Switch of Size S0 can have a basic mounting hole of 22.5mm ( for mounting type FT1/FT2/FH3) . Adaptors can be supplied for 25mmand 30.5mm mounting holes. 40mm diameter ( for mounting EL2 )
FT1 Mounting
FT2 Mounting
25 Adaptor
30.5 Adaptor
FH3 Mounting
Fig. 4b - Single hole mounting for key switch
Switch Escutcheon Mounting Mounting Hole RequiredType Plate Size Type Dimension Adaptor CHR10/CHR16 - FT1 22.5 -
25.0 S0E T160 1130.5 S0E T160 01
CHR10/CHR16 - EL 1) 25.0 -
Switch Escutcheon Mounting Mounting Hole Required
Type Plate Size Type Dimension Adaptor
CHR10/CHR16 48 x 48 FT2 22.5 -25.0 S0E T160 1130.5 S0E T160 01
CHR10/CHR16 64 x 64 FH3 22.5 -25.0 S0E T160 1130.5 S0E T160 01
C26/C32/C42 64 x 64 EL2 1) 40 -
1) Use high security KABA key lock
ii. Four screws mounting
The key switch is mounted to the panel by four screws
Switch Escutcheon MountingType Plate Size Type
CHR10/CHR16 48 x 48 E
CHR10/CHR16 64 x 64 EG
c . Types o f Locking Program
The Locking Program refers to the position at which the key can be removed from the
lock. a mark on the circle shown in the figure below indicates the position/s at which the keycan be removed from the locking device. For example in Program C, the key can beremoved at 6 and 12 o'clock positions whereas in Program G, the key can be removed at 3,6, 9 and 12 o'clock positions.
A
B
E
F
C
D
G H
J
K L
R
Fig. 4c - Type of Locking Program
KEY SWITCH V750
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
40/52
KRAUS & NAIMER BLUE LINE RC/02/2004
d. Types of Key Locks
The types of locks refer to the type of keys and lock drives available.
i. Key Locks for Normal Application
STREBOR Key lock devices are suitable for use withKraus & Naimer switches for
normal applications. It has 10 different key lock drives available. This feature isespecially useful in installation where certain personnal are authorised to operate importantcircuits only. Having different types of locs ensures that only authorised personals are
allowed to operate the crtical circuits.
Switch Type Mounting Type Types of Key Lock AvailableCHR10/CHR16 FT1/FT2/FH3 SF101*/SF105/SF121/SF137
SF191/SF200/SF201/SF203SF204/SF205
Fig. 4d - STREBOR Key lock device
* Unless specified, key lock SF101 will be provided as standard.
S0 V750D / 3 H / 1 1
Key Locking Program Key removable at
Type of Mounting 1 ..... *FT1 (round front ring) 2 ..... *FT2 (square 48x48mm plate)
7 ..... *FH3 (square 64x64mm plate)
L
H
J
A C E G
B D F
K
Fig. 4e - Coding of STREBOR Key Lock Device
85
KEY SWITCH V750
Fig. 4f - FT1 Mounting Fig. 4g- FT2 Mounting Fig. 4h- FH3 Mounting
ii. Key Locks for High Security and Master Key Lock SystemKABA Key lock devices are suitable for use with Kraus & Naimer switches for highsecurity and master key lock system.
Switch Mounting Types of Number of Locking
Type Type Key Lock Key Locks ProgramCHR10/CHR16 E/EG KABA 8 1036 A, B, C, D, E, F, G
( Short cylinder )
CHR10/CHR16 E/EG KABA 8 1036 G, H, J, K, L
( Long cylinder )
CHR10/CHR16 E/EG KABA 20 20,000 A, B, C, D, E, F, G( Short cylinder )
CHR10/CHR16 E/EG KABA 20 20,000 G, H, J, K, L( Long cylinder )
CHR10/CHR16 EL KABA 8 1036 A, B, C, D, E, F, G( Short cylinder )
CHR10/CHR16 EL KABA 8 1036 G, H, J, K, L( Long cylinder )
CHR10B/CHR16B EL2 KABA 8 1036 A
( Centric drive )
CHR10B/CHR16B EL2 KABA 20 20,000 A( Centric drive )
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
41/52
KRAUS & NAIMER BLUE LINE RC/02/2004
24
32
25
22
34
22
KABA8/ KABA 20 KABA8/ KABA 20 KABA8/ KABA 20
Centric Drive Short Cyclinder Long Cyclinder
Fig. 4i- Coding of KABA High Security Key Lock Device for E and EG Mounting
Escutcheon plateA ... SquareB ... Rectangular
Type of Lock1 ... KABA 8 ( program A - G)2 ... KABA 8 ( program G - L )3 ... KABA 20 ( program A - G )
4 ... KABA 20 ( program G - L )
Locking Program
MountingBlank ... E1 ... EG
S0 V750D / A 1 A / 1 1
A
B
E
F
C
D
G H
J
K L
Fig. 4j KABA Key Lock Device
Type of Lock1 ... KABA 8 ( program A - G)2 ... KABA 8 ( program G - L )3 ... KABA 20 ( program A - G )
4 ... KABA 20 ( program G - L )
Locking Program
Mounting1 ... *EL ( 25mm )
S0 V750D / 1 A 1
A
B
E
F
C
D
G H
J
K L
Fig. 4j- Coding of KABA High Security Key Lock Device for E L Mounting
86
KEY SWITCH V750
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
42/52
KRAUS & NAIMER BLUE LINE RC/02/2004
Function Number 39 Round 48x48 Square Switch
of Mounting plate Mounting plate Lengthpoles Type FT1 Type FT2 (mm)
1 CHR10 A200 *FT1 CHR10 A200-620*FT2 522 CHR10 A201 *FT1 CHR10 A201-620*FT2 52
3 CHR10 A202 *FT1 CHR10 A202-620*FT2 624 CHR10 A203 *FT1 CHR10 A203-620*FT2 62
1 CHR10 A290 *FT1 CHR10 A290-620*FT2 522 CHR10 A291 *FT1 CHR10 A291-620*FT2 523 CHR10 A292 *FT1 CHR10 A292-620*FT2 624 CHR10 A293 *FT1 CHR10 A293-620*FT2 62
1 CHR10 A210 *FT1 CHR10 A210-620*FT2 522 CHR10 A211 *FT1 CHR10 A211-620*FT2 623 CHR10 A212 *FT1 CHR10 A212-620*FT2 71
4 CHR10 A213 *FT1 CHR10 A213-620*FT2 81
1 CHR10 A210 *FT1 CHR10 A210-623*FT2 52
2 CHR10 A211 *FT1 CHR10 A211-623*FT2 623 CHR10 A212 *FT1 CHR10 A212-623*FT2 714 CHR10 A213 *FT1 CHR10 A213-623*FT2 81
ORDERING PROCEDURE
ii. Non-standard Switch
Typical Specification
A synchronising mode selector switch is to be key operated to prevent unauthorisedoperation. It shall consist of three positions "MANUAL - NORMAL MANUAL - MANUAL
OVERRIDE" which shall be 90 degrees apart. The key shall be removable at every switchingposition. Contact rating shall be 20A/AC21 at 690VAC. The required configuration is as
shown in Fig. 5a
OFFON
OFF
ON
OFF21
OFF
AUTOMAN
Locking Program
- key remove at
Type of Lock1 ... KABA 8
6 ... KABA 20
Type of MountingA ... EL1 ( without escutcheon plate )B... EL2 ( escutcheon plate 64 x 64mm )
Type of VersionBlank ... for same switch size1 ... for next smaller switxh size
S1 V750 / A 1 / A 1 1
A
Fig. 4k - Coding of KABA High Security Key Lock Device for E L Mounting
5. ORDERING PROCEDURE
a. Normal Key Lock Device
i. Standard Switch
20A/AC21 rating
Single hole mounting 22/25/30 mm Escutcheon plate size 48 x 48 mm Strebor key lock SF101 with key removable at 12 o'clock position only.
87
KEY SWITCH V750
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
43/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
44/52
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
45/52
KEY SWITCH V750
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
46/52
KRAUS & NAIMER BLUE LINE RC/02/200491
KEY SWITCH V750
9. GROUP MASTER KEY LOCK SYSTEM WITH DUST COVER( Key remove at several positions)
The examples provided in items (1) to (4) allows key to be remove only at one position i.e.
at 12 o'clock position. Where key need to be removed at more than one positions, the orderingcode shall be:
A. Ordering Code of GROUP Master Key Swtch KGM - key remove at several positions(1o'clock, 2 o'clock .... to 12 o'clock )
Item Description Referencei. Switch CHR10 A211-620 *E
ii. Key Lock device S0 V750D/AZ0/1
S0D V756 GZST%NUMBER LA 3291/KGM
S0D V750 34
iii. Dust Cover S0D V750 ST
B Ordering Code of MASTER Key Swtch KMA/KMB - key remove at several positions( 1o'clock, 2 o'clock .... to 12 o'clock )
Item Description Reference
i. Switch CHR10 A211-620 *Eii. Key Lock device S0 V750D/AZ0/1
S0D V756 GZST%NUMBER LA 3291/KMA%NUMBER LA 3291/KMB
S0D V750 34iii. Dust Cover S0D V750 ST
C Ordering Code of Key Swtch KA1, KA2, KA3, KB1, KB2, KB3 - key remove at severalpositions ( 1o'clock, 2 o'clock .... to 12 o'clock )
Item Description Reference
i. Switch CHR10 A211-620 *Eii. Key Lock device S0 V750D/AZ0/1
S0D V756 GZST%NUMBER LA 3291/KA1%NUMBER LA 3291/KA2
%NUMBER LA 3291/KA3%NUMBER LA 3291/KB1
%NUMBER LA 3291/KB2%NUMBER LA 3291/KB3S0D V750 34
iii. Dust Cover S0D V750 ST
A. Ordering code of Key Swtch S1
Item Description Referencei. Switch CHR10 A293-622 *Eii. Key Lock device S0 V750D/A20
S0D V751 ZZS0D V750 34
% SPERRE LA3251/1
B. Ordering code of Key Swtch S2
Item Description Referencei. Switch CHR10 A293-622 *E
ii. Key Lock device S0 V750D/A20S0D V751 ZZS0D V750 34
% SPERRE LA3251/2
C. Ordering code of Key Swtch SZ
Item Description Reference
i. Switch CHR10 A293-622 *EII. Key Lock Device S0 V750D/A20
S0D V751 ZZ
S0D V750 34% SPHERE LA3251/Z
8. KEY LOCK WITH DUST PROTECTION COVER
Dust protection covers are available on KABA key lock device to prevent entry of dustand moisture into the metal key lock cylinder which may caused jamming. The key to beremove only at "OFF" position only.
A. Ordering code of Key Switch with Dust Cover
i.e of Key Swtch with dust cover
Item Description Referencei. Switch CHR10 A293-622 *E
ii. Key Lock device S0 V750D/AZ0/1S0D V751 ZZST%LA .....................
iii. Dust Cover SOD V750 ST
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
47/52
KRAUS & NAIMER BLUE LINE RC/02/200492
Group Master Key
Switch KGM
Master Key Switch
KMA
Key Switch
KA1Key Switch
KA2Key Switch
KA3
Master KeySwitch KMB
Key Switch
KB1
Key Switch
KB2Key Switch
KB3
KEY SWITCH V760
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
48/52
KRAUS & NAIMER BLUE LINE RC/02/2004
10. V760/V765 SAFETY KEY LOCK DEVICE with separate drive
The Safety Key Lock device type V760 allows the switching operation
to be done by the switch handle. With the V760, it is possible to lock thehandle at selected positions by means of a separate key lock device.The V760 is available from size S0 to S3 and can be use with tandemdrive M300 and door interlock M280D.
The following information are required when ordering either a stand-ard switch/special switch which is to be fitted with a separate key lockdevice.
a. Switch Ratings
b. Type of Escutcheon Plate Square Rectangular
c. Key Program required.The key program refers to the position/s at which the key is to be removed from the lock
which can occur when: Key is to be removed at both LOCKED and UNLOCKED positions. LOCKED position
refers to the position where it is not possible to turn the handle of the switch because it islocked at that particular position by the separate key lock device. Key is to be removed only at the LOCKED position.
d. Type of LockVarious types of locks are available namely ZEISS, BKS, STREBOR and RONIS for
general application and KABA 8 locks for high security/master key lock system.When using STREBOR locks for S0 and S1 switches, type SF101 key lock will be
provided unless specified.
e. Locking Programs
Various standard locking programs are available. For non-standard programs, thefollowing information are required:
The number of positions to be locked The position/s to be locked.
S1 V760 / B 1 E 2 / 90 1
Plate FrameA ... SquareB ... Rectangular
Key Program1 ... Key removable at
Lock/Unlock positions
2 ... Key removable atLock position only
Type of LockB ... ZeissC ... BKSD ... KABA 8E ... StreborG ... KABA 20
H ... Ronis
Locking Program1 ... 1 position (0) to be lockedall other positions not to be locked2 ... All positions to be locked3 ... 1 position not to be lockedall other positions to be locked
9 ... Special locking program - specify
Angular disp lacement20 ... 20 deg. switching angle30 ... 30 deg. switching angle45 ... 45 deg. switching angle60 ... 60 deg. switching angle90 ... 90 deg. switching angle
Fig. 10a - Ordering Code
93
KEY SWITCH V760
V765 key lock device
KEY SWITCH V760
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
49/52
KRAUS & NAIMER BLUE LINE RC/02/2004
11. ORDERING PROCEDURE
a. Typical Specifications
A manual override selector switch is to be fitted with a separate key lock device forsecurity reasons. The selector switch shall have three switching positions "MANUAL-NOR-MAL-MANUAL OVERRIDE ". The switching angle shall be 90 degrees. The contact rating
shall be 25A/AC21 660VAC.The separate key lock device should be able to lock the selector switch at all positions.
The key should be able to be remove at both LOCKED and UNLOCKED situation.The selector switch handle and escutcheon plate shall be big enough for easy operation
by the operator.
The contact configuration required is as follows:
MANUAL NORMAL MANUAL
OVERRIDE
1
3
5
7
2
4
6
8
Fig. 11a - Required contact configuration
b. How To Order
When ordering a switch to be fitted with a separate key lock device V760, the followinginformations are require:i. Switch Type
Switch type is selected according to the ratings and application ( AC21, AC23 etc.) In this
case 25A AC21 is required and hence switch CHR16B can be used.
ii Contact configuration - refer Fig. 11.
iii. Key Program.
In this case, the key is to be remove at both LOCKED and UNLOCKED positions.
iv. Type of Lock.
Unless specified, STREBOR SF101 lock device will be provided.
Coding of required Safety Key Lock
The required coding is:
S1 V760 / B 1 E 2 / 90 1
Plate FrameA ... SquareB ... Rectangular
Key Program1 ... Key removable at
Lock/Unlock positions2 ... Key removable at
Lock position only
Type of LockB ... ZeissC ... BKSD ... KABA 8E ... StreborG ... KABA 20
H ... Ronis
Locking Program1 ... 1 position (0) to be lockedall other positions not to be locked2 ... All positions to be locked3 ... 1 position not to be lockedall other positions to be locked
9 ... Special locking program - specify
Angular disp lacement20 ... 20 deg. switching angle
30 ... 30 deg. switching angle45 ... 45 deg. switching angle60 ... 60 deg. switching angle90 ... 90 deg. switching angle
94
KEY SWITCH V760
KEY SWITCH V760
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
50/52
KRAUS & NAIMER BLUE LINE RC/02/2004
0
90
180
270
45
135225
315
NORMAL
MANUAL
MANUALOVE
RRIDE
1
3
5
7
2
4
6
8
270 o 300 o 330 o 0 o 30 o 60 o 90 o
NORMALMANUAL MANUAL OVERRIDE
Fig. 11b - Special switch diagram
With the information provided , a switch drawing can be prepared as according to require-
ment. A special switch drawing number CHR16B SG9996 can be allocated by theKraus &Naimer's representative - refer Fig. 11b
95
KEY SWITCH V760
KEY SWITCH V900
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
51/52
KRAUS & NAIMER BLUE LINE RC/02/200496
Program For Key Angular Key Removable
Number Profile Movement Locations
014 A, C, D, E, F, H, K, M, N, P 45
015 L, R, B 30/45/60/90
B
L R
016 A, C, D, E, F, H, K, M, N, P 30/45/60/90
c The Locking ProfileThe locking profile refers to the type of key lock selected which would make it suitable for
master group key lock system, group key lock system or individual key lock.
P N M K H F E D C A
P N M K H F E D C A
G
d. The type of keyed handle device required. Flat key Key equipped with a standardKraus & NaimerSize S1 handle. Unless specified,
type S1 G001 handle will be provided as standard.
12. V900 - KEYED HANDLE DEVICE
The V900 basically resembles the features of acylinder lock. Therefore, it provides a number of featureswhich are usually found on cylinder locks such as: Variety of locking arrangement Removal of the key in predetermined positions. Master key lock system.
It can be operated by a flat key ( V902 ) or a keyequipped with a Kraus & Naimer Size S1 handle whichgives it the feature of a "removable handle " controlswitch.
The following information are required
when orderinga standard switch/special switch which is tobe fitted with a V900.
a. Switch RatingsSwitch Type Rating AC21 VoltageCHR10B 20A 690V ACCHR16B 25A 690V AC
C26 32A 690V ACC32 40A 690V AC
C42 63A 690V AC
b. Locking Program
The locking program refers
The key removable positions. The type of key profile suitableProgram For Key Angular Key RemovableNumber Profile Movement Locations
011 A, C, D, E, F, H, K, M, N, P 30/45/60/90
012 A, C, D, E, F, H, K, M, N, P 30/60/90
013 A, C, D, E, F, H, K, M, N, P 30/60/90
KEY SWITCH V900
-
8/10/2019 78_1375264594_142606_lockout relay Catalogue-
52/52
KRAUS & NAIMER BLUE LINE RC/02/2004
14. SPECIAL PROFILES FOR KEYED HANDLE DEVICE
If pratical requirements exceed the number of standard locking profiles , cipher identifica-
tion instead of lettering allows expansion of available number of ( non-interchangeable )locking profiles:
Series 1 - Key numerals 01-16 with master key G0 ( identical with G )
Series 2 - Key numerals 21 - 36, master key G2
Series 4 - Key numerals 41 - 56 , master key G4
ORDERING CODE KEY V901/902
a. Special Profile
S1B V901 / Z G4
Type of Keyed
Handle DeviceV901 ... Flat key
V902 ... Key with switch handle
Special Lock ing Number
01 ..... Locking profile 01
16 ..... Locking profile 16
G0 ..... Master key for locking profile 01 - 16
21 ..... Locking profile 01
36 ..... Locking profile 16G2 ..... Master key for locking profile 21 - 36
41 ..... Locking profile 41
56 ..... Locking profile 56G4 ..... Master key for locking profile 41 - 56
97
13. SPECIAL LOCK - KEY Combination
Keyed handle device V900 with locking program 015 provides a special arrangement asfollows: When use with key V901/B ( or V902/B) , the key can be turn in both clockwise andanti-clockwise direction. When use with key V901/L ( or V902/L), the key can be turn in the anti-clowise direction
When use with key V901/R ( or V902/R), the key can be turn in the anti-clowise direction
a. Ordering Code Key Lock V900
S1 V900 / C A
Locking ProgramA ..... Program 015C ..... Program 011D ..... Program 016K ..... Program 014L ..... Program 013S ..... Program 012
Locking ProfileA, B, C, D, E, F, H,K, L, M, N, P, R
b. Ordering Code key V901/902 - Standard Profile
S1 V901 / A
Type of Keyed
Handle DeviceV901 ... Flat keyV902 ... Key with switch handle