Download - Ac Current Transducer
-
8/3/2019 Ac Current Transducer
1/2
AC CURRENT TRANSDUCER
n Dual Aux. Power 110/220V AC
o on High Accuracy 0.2% RO at 23 C 5 C
n High Dielectric Strength 2.6KV AC/Min,Between Input / Output/ Power Case
n ABS Plastic Case, DIN Rail or Wall Mounting
ORDERING :
1
FEATURES
TDATDA3TDARTDAR3
1 Unit avg. to rms conversion3 Unit avg. to rms conversion1 Unit True RMS conversion3 Unit True RMS conversion
Input Voltage Output Aux. Power
A
B
C
Y
0 ~ 1A AC
0 ~ 5A AC
0 ~ 10A AC
Other
ABCDEFY
0 ~ 10mA DC0 ~ 20mA DC4 ~ 20mA DC0 ~ 5V DC1 ~ 5V DC0 ~ 10V DCOther
A
CDENY
AC 110/220V(Dual Power)
DC 24VDC 110VDC 125V* Self-Power ModeOther
STANDARD :
TDA-S INPUT: 0 ~ 5A AC, OUTPUT : 4 ~ 20mA DC, POWER : 110/220V ACSPECIFICATION
::::
::::
:::::::::::
::
:
o o o o0.2% RO at 23 C 5 C (Self-Power Mode 0.25% RO at 23 C 5 C).0.3VA / 60Hz, Self-Power Mode 3VA / 60Hz.45 ~ 70Hz or 400Hz.Normal AC 5A, Current Over 15A Continuous; 50A 10Sec / Hour;400A 0.5 Sec / Hour.DC Current Mode : 10V DC Maximum, DC Voltage Mode : 10mA DC Maximum.Without Damage for Output Open or Short Circuit.2.6KV AC / 1 Min, between Input / Power / Case.
5KV (1.2X50mS), ANSI C37. 90a / 1983. DIN, IEC 255 - 4, IEC 688-19922.5KV - 0.25mS / 1MHz IEC 801-3 (Ring WAVE).
> 120db, 50 / 60Hz.< 0.2% / Year.SPAN and ZERO 10%.
400mS. 0 ~ 99%; 0.5% P-P (STD) or Option.
DIN - IEE 688 0.005% Change 10" Center 100A- Turn.o o o o
100ppm / C from 0 ~ 60 C; 50ppm / 23 C 3 Co o
-10 C ~ + 65 C, 20 ~ 95% RH Non - Condensed.o o
-40 C ~ + 75 C, 20 ~ 95% RH Non - Condensed.
AC or DC 20%, 50 / 60Hz 1f 3VA / AC : 3f 3VA / AC.< 0.01% / V. ABS Plastic, Self-Extinguishing to UL Subject 94 Class V-O. Case IP 50Snap Mounting On DIN EN 50022-35 Or Surface Mounting. Compliance
With IEC 529, BS 5490, Din 40054. Protection Touch-Proof Terminals and
Enclosure Meeting Requirements Of VBG 4 & VDE 0106 oart 100(Germany).DIN Rail or Wall Mounting.
W H L W H L1 f [ 50 X 115 X 73.4 mm ] ; 3f [ 120 X 115 X 73.4 mm ].
Effective Range 5 ~ 150%, Output 0~XmA DC.
AccuracyInput BurdenFrequencyInput Over
Output LoadOutput ProtectionDielectric StrengthImpulse
Common Mode RejectionStabilityCalibrationResponse Time & Ripple(p-p)Magnetic EffectTemperature CoefficientOperating ConditionStorage ConditionPower SupplyAux. Power EffectHousing Material
MountingSize
*Self-Power Mode
TD SERIES0.2% Class
*Specifications subject to change without prior notice.
-
8/3/2019 Ac Current Transducer
2/2
2
Outline Dimension : (Unit : mm)
Model : TDA, TDAR
115
60
M5M4
40
Model : TDA3, TDAR3
60
M5M4
110
6 7 8 9 10
1 2 3 4 5
I/P
+ -
+ - + -
Aux Power
DC
O/P 110V-
220V
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
I/P I/P I/P
A B C
+ - + - + -
+ - + - + - + -
Aux Power
DC
O/P O/P O/P 110V-220V
A B C
Model : TDA, TDARTerminal Connection :
Model : TDA3, TDAR3
115
73.4
70
8.0
1.6
50
73.4
70
8.6
2
120
*Specifications subject to change without prior notice.