Download - AccuMax Single Point Injection
AccuMaxAccuMaxSingle Point InjectionSingle Point Injection
OperationOperation(See Installation and Operation Manual for detailed instructions)
2
WaterTank
Check Valves
WaterPump
MultipleDischarges
Flowmeter
FoamTank
Line Strainer
Digital Display Control
AccuMax Single Point InjectionAccuMax Single Point Injection
3
• Digital display reads “Hypro” upon initial power-up
• System then enters flow mode in standby– Operates as flowmeter
Digital Display OperationDigital Display Operation
4
• Push red “FOAM” button to arm system– “ON” light illuminates
• Open foam discharge– Displays solution volume– “ON” light blinks when foam
pump runs
Digital Display OperationDigital Display Operation
5
• Water flow display
• Push “SELECT” button and total volume of water discharged is displayed– Gallons, liters, imperial
gallons
Digital Display OperationDigital Display Operation
6
• Push “SELECT” button to enter “%” mode– Displays default injection
percentage– “PA” Single tank system
– “PC” Remote start/stop
(“UP” or “DOWN” button will override default setting)
Digital Display OperationDigital Display Operation
7
Digital Display OperationDigital Display Operation
• Push “SELECT” button to enter “TOTAL FOAM”– Displays total concentrate
injected
• Dual-tank mode– Totals for each tank– Display corresponds to tank
chosen by dual-tank valve
8
Digital Display OperationDigital Display Operation
• Enter “INJECTION PERCENTAGE” from any mode– Press either “UP” or “DOWN”
button momentarily to display current percentage setting
– Hold either button for two seconds to change setting accordingly
9
Operating Instructions Operating Instructions System ResetSystem Reset
Total Water %(Percent) Total Foam
• Reset these modes to 0 or % to default setting• Push both the up and down buttons in desired mode
10
Size Max Accuracy Max OperatingTee Flow Range Flow Range1-1/2x1" 5 - 110 gpm 3 - 145 gpm
1-1/2" 10 - 320 gpm 3 - 380 gpm
2" 15 - 520 gpm 5 - 625 gpm
2-1/2" 20 - 750 gpm 8 - 900 gpm
3" 30 - 1150 gpm 12 -1380 gpm
4" 55 - 1980 gpm 20 - 2380 gpm6" ** 70 - 2800 gpm 30 - 3300 gpm8" ** 120 - 4800 gpm 50 - 5600 gpm ** Electromagnetic flowmeter
FlowmeterFlowmeter
No Flow Restrictions
Safety FeaturesSafety Features
12
• When Lo con is Displayed
– Selected foam concentrate tank is getting low
– If foam concentrate is added within 2 minutes Lo con goes out
– If no foam concentrate is added within 2 minutes no con is displayed
• When no con is Displayed
– Foam concentrate pump will not run
– Add foam concentrate until no con display goes out then push Red Foam button to start the foam pump
Low Foam DisplayLow Foam Display
13
Exceeding Foam Injection RateExceeding Foam Injection Rate
• Hi Flo display– Occurs when the water flow and
selected foam concentrate injection percentage exceeds the foam pump capabilities
– Informs pump operator when this situation occurs
– Lower the foam concentrate injection percentage or water flow to stop the flashing Hi Flo display
14
Motor DriverMotor Driver
• Module controls pump motor
• Totally enclosed environmentally sealed
• Incorporates system circuit breaker
15
Digital Display OperationDigital Display Operation
• Simulated flow– While in “FLOW” mode, push
both lower buttons simultaneously
– Three bars on left indicate manual mode
– Pushing red “FOAM” button will turn foam pump on/off
– Pump injects to simulated flow default setting
16
System Air PurgeSystem Air Purge
• Enter “SIMULATED FLOW”
• Turn injection valve from “INJECT” to “CAL/FLUSH”
• Push red “FOAM” button on display to start foam pump
17
System Air Purge System Air Purge (cont.)(cont.)
• Run until concentrate flows steady out of dump line
• Push red “FOAM” button to stop pump
• Turn injection valve to “INJECT”
• Exit “SIMULATED FLOW”
System MaintenanceSystem Maintenance
19
AccuMaxAccuMaxSingle Point Foam PumpSingle Point Foam Pump
• Hydraulic pump• Housing incorporates
speed sensor• Positive displacement
plunger pump– Components made of
corrosion resistant materials
– Max operating pressure is 400 psi
20
System MaintenanceSystem Maintenance
• Clean strainer(s) regularly– Purge pump to remove
air pockets afterwards
• Check oil level– Dip stick reading
or– Sight glass
Concentrate Management SystemsConcentrate Management Systems(Only Available on AccuMax Single Point Models 3020 and 3040)
22
Foam TankA
Foam TankB
Manual CMSManual CMS
23
Foam TankB
Electronic CMSElectronic CMS
Foam TankA
24
Digital Display OperationDigital Display Operation
• Dual-tank function– Dual-tank valve in “A”– Displays “PA” and default
setting
– Dual-tank valve in “B”– Displays “Pb” and default
setting
• Default settings from 0.1 to 6.0%
25
Dual Foam Concentrate Tank (CMS)Dual Foam Concentrate Tank (CMS)
26
Dual-Tank FlushDual-Tank Flush
• Flush after using Class B foam– Flow water and engage
foam system– Turn manual valve to
“FLUSH” or electric valve to “OFF”
(“Off” position is a constant flush)
MultiFlo InterfaceMultiFlo Interface
28
MultiFlo InterfaceMultiFlo Interface
Std. Controller or AFC
MultiFloDisplay
ControlCable
FlowmeterCable
Flowmeter
Flowmeter
Flowmeter
Flowmeter