accumax single point injection

28
AccuMax AccuMax Single Point Injection Single Point Injection Operation Operation (See Installation and Operation Manual for detailed instructions)

Upload: kay-foreman

Post on 30-Dec-2015

42 views

Category:

Documents


0 download

DESCRIPTION

AccuMax Single Point Injection Operation (See Installation and Operation Manual for detailed instructions). AccuMax Single Point Injection. Digital Display Control. Foam Tank. Line Strainer. Water Tank. Check Valves. Flowmeter. Multiple Discharges. Water Pump. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: AccuMax Single Point Injection

AccuMaxAccuMaxSingle Point InjectionSingle Point Injection

OperationOperation(See Installation and Operation Manual for detailed instructions)

Page 2: AccuMax Single Point Injection

2

WaterTank

Check Valves

WaterPump

MultipleDischarges

Flowmeter

FoamTank

Line Strainer

Digital Display Control

AccuMax Single Point InjectionAccuMax Single Point Injection

Page 3: AccuMax Single Point Injection

3

• Digital display reads “Hypro” upon initial power-up

• System then enters flow mode in standby– Operates as flowmeter

Digital Display OperationDigital Display Operation

Page 4: AccuMax Single Point Injection

4

• Push red “FOAM” button to arm system– “ON” light illuminates

• Open foam discharge– Displays solution volume– “ON” light blinks when foam

pump runs

Digital Display OperationDigital Display Operation

Page 5: AccuMax Single Point Injection

5

• Water flow display

• Push “SELECT” button and total volume of water discharged is displayed– Gallons, liters, imperial

gallons

Digital Display OperationDigital Display Operation

Page 6: AccuMax Single Point Injection

6

• Push “SELECT” button to enter “%” mode– Displays default injection

percentage– “PA” Single tank system

– “PC” Remote start/stop

(“UP” or “DOWN” button will override default setting)

Digital Display OperationDigital Display Operation

Page 7: AccuMax Single Point Injection

7

Digital Display OperationDigital Display Operation

• Push “SELECT” button to enter “TOTAL FOAM”– Displays total concentrate

injected

• Dual-tank mode– Totals for each tank– Display corresponds to tank

chosen by dual-tank valve

Page 8: AccuMax Single Point Injection

8

Digital Display OperationDigital Display Operation

• Enter “INJECTION PERCENTAGE” from any mode– Press either “UP” or “DOWN”

button momentarily to display current percentage setting

– Hold either button for two seconds to change setting accordingly

Page 9: AccuMax Single Point Injection

9

Operating Instructions Operating Instructions System ResetSystem Reset

Total Water %(Percent) Total Foam

• Reset these modes to 0 or % to default setting• Push both the up and down buttons in desired mode

Page 10: AccuMax Single Point Injection

10

Size Max Accuracy Max OperatingTee Flow Range Flow Range1-1/2x1" 5 - 110 gpm 3 - 145 gpm

1-1/2" 10 - 320 gpm 3 - 380 gpm

2" 15 - 520 gpm 5 - 625 gpm

2-1/2" 20 - 750 gpm 8 - 900 gpm

3" 30 - 1150 gpm 12 -1380 gpm

4" 55 - 1980 gpm 20 - 2380 gpm6" ** 70 - 2800 gpm 30 - 3300 gpm8" ** 120 - 4800 gpm 50 - 5600 gpm ** Electromagnetic flowmeter

FlowmeterFlowmeter

No Flow Restrictions

Page 11: AccuMax Single Point Injection

Safety FeaturesSafety Features

Page 12: AccuMax Single Point Injection

12

• When Lo con is Displayed

– Selected foam concentrate tank is getting low

– If foam concentrate is added within 2 minutes Lo con goes out

– If no foam concentrate is added within 2 minutes no con is displayed

• When no con is Displayed

– Foam concentrate pump will not run

– Add foam concentrate until no con display goes out then push Red Foam button to start the foam pump

Low Foam DisplayLow Foam Display

Page 13: AccuMax Single Point Injection

13

Exceeding Foam Injection RateExceeding Foam Injection Rate

• Hi Flo display– Occurs when the water flow and

selected foam concentrate injection percentage exceeds the foam pump capabilities

– Informs pump operator when this situation occurs

– Lower the foam concentrate injection percentage or water flow to stop the flashing Hi Flo display

Page 14: AccuMax Single Point Injection

14

Motor DriverMotor Driver

• Module controls pump motor

• Totally enclosed environmentally sealed

• Incorporates system circuit breaker

Page 15: AccuMax Single Point Injection

15

Digital Display OperationDigital Display Operation

• Simulated flow– While in “FLOW” mode, push

both lower buttons simultaneously

– Three bars on left indicate manual mode

– Pushing red “FOAM” button will turn foam pump on/off

– Pump injects to simulated flow default setting

Page 16: AccuMax Single Point Injection

16

System Air PurgeSystem Air Purge

• Enter “SIMULATED FLOW”

• Turn injection valve from “INJECT” to “CAL/FLUSH”

• Push red “FOAM” button on display to start foam pump

Page 17: AccuMax Single Point Injection

17

System Air Purge System Air Purge (cont.)(cont.)

• Run until concentrate flows steady out of dump line

• Push red “FOAM” button to stop pump

• Turn injection valve to “INJECT”

• Exit “SIMULATED FLOW”

Page 18: AccuMax Single Point Injection

System MaintenanceSystem Maintenance

Page 19: AccuMax Single Point Injection

19

AccuMaxAccuMaxSingle Point Foam PumpSingle Point Foam Pump

• Hydraulic pump• Housing incorporates

speed sensor• Positive displacement

plunger pump– Components made of

corrosion resistant materials

– Max operating pressure is 400 psi

Page 20: AccuMax Single Point Injection

20

System MaintenanceSystem Maintenance

• Clean strainer(s) regularly– Purge pump to remove

air pockets afterwards

• Check oil level– Dip stick reading

or– Sight glass

Page 21: AccuMax Single Point Injection

Concentrate Management SystemsConcentrate Management Systems(Only Available on AccuMax Single Point Models 3020 and 3040)

Page 22: AccuMax Single Point Injection

22

Foam TankA

Foam TankB

Manual CMSManual CMS

Page 23: AccuMax Single Point Injection

23

Foam TankB

Electronic CMSElectronic CMS

Foam TankA

Page 24: AccuMax Single Point Injection

24

Digital Display OperationDigital Display Operation

• Dual-tank function– Dual-tank valve in “A”– Displays “PA” and default

setting

– Dual-tank valve in “B”– Displays “Pb” and default

setting

• Default settings from 0.1 to 6.0%

Page 25: AccuMax Single Point Injection

25

Dual Foam Concentrate Tank (CMS)Dual Foam Concentrate Tank (CMS)

Page 26: AccuMax Single Point Injection

26

Dual-Tank FlushDual-Tank Flush

• Flush after using Class B foam– Flow water and engage

foam system– Turn manual valve to

“FLUSH” or electric valve to “OFF”

(“Off” position is a constant flush)

Page 27: AccuMax Single Point Injection

MultiFlo InterfaceMultiFlo Interface

Page 28: AccuMax Single Point Injection

28

MultiFlo InterfaceMultiFlo Interface

Std. Controller or AFC

MultiFloDisplay

ControlCable

FlowmeterCable

Flowmeter

Flowmeter

Flowmeter

Flowmeter