Performance-Based Design of Structural Fire Resistance
Morgan J. Hurley, P.E.Society of Fire Protection Engineers
Brian Y. Lattimer, Ph.D.Hughes Associates, Inc.
![Page 2: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/2.jpg)
Presentation Overview
• Historical perspective• Elements of performance-based design
approach• Calculation of fire boundary conditions
– Enclosure fires– Localized fires
![Page 3: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/3.jpg)
Historical Perspective
• Fire resistance specified based on ASTM E-119 “standard fire”
• ASTM E-119 specifies furnace temperature and thermal endpoint criteria
• Codes specify required “ratings”
![Page 4: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/4.jpg)
ASTM E-119 Endpoint Criteria
• Must maintain applied load or• Average of measured temperatures must not
exceed specified limits
![Page 5: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/5.jpg)
Basis for Code Requirements
![Page 6: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/6.jpg)
Application
• Select an assembly that has been tested• Use engineering calculations, e.g.,
ASCE/SFPE 29-99
![Page 7: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/7.jpg)
Limitations• “Standard” fire does not consider all of the factors
that would influence fire severity• Single elements tested in isolation, without
considering structural performance• Air temperature in furnace measured
– Radiation from walls dominant mode of heat transfer
• Ratings based on mass per unit area in typical occupancies– Mass not necessarily indicative of severity
![Page 8: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/8.jpg)
Limitations
• Convection
• Radiation
( )sg TThq −=′′&
( )44sTTq −=′′ σ&
![Page 9: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/9.jpg)
Performance-Based Design Approach
• Estimate fire exposures• Perform heat transfer analysis to determine
thermal response• Perform structural analysis
![Page 10: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/10.jpg)
Why Performance-Based Design?
• Better knowledge of fire safety provided by a design
• Apply best available science• Tailor safety to building use and
characteristics
![Page 11: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/11.jpg)
Scenarios Considered
![Page 12: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/12.jpg)
Heat Transfer
• Generally use finite element or finite difference approach
• Conservatively assume ε = 1 (ε expected to vary between 0.65 for small enclosures to 0.95 for realistic fires.)
• hc ≈ 10 – 30 W/m2K• For insulated members – assume surface
temperature = fire temperature
![Page 13: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/13.jpg)
Compartment Fires
Time
Tem
pera
ture
Dev
elop
men
t
Flas
hove
r
Fully Developed
Cooling Phase
Significant effect on structure
Time
Tem
pera
ture
Dev
elop
men
t
Flas
hove
r
Fully Developed
Cooling Phase
Significant effect on structure
![Page 14: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/14.jpg)
Compartment Fires
Ao
C.V.
T
fm&
δ k, ρ, c
Ho
m&
om&
ρ0, T0
![Page 15: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/15.jpg)
Factors
• Fuel Load (mf)• Ventilation (Ao, Ho)• Enclosure thermal properties (k, ρ, C, A)
![Page 16: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/16.jpg)
Compartment Fire Modeling
• Several predictive methods available – most are algebraic correlations
• Assumptions– Fuel distributed uniformly over floor– Vents in walls– Natural ventilation only– Large fires– Uniform conditions throughout enclosure
![Page 17: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/17.jpg)
Compartment Fire Models
• Most models based on wood cribs, which may be conservative for enclosure fires
• Long, narrow, ventilation controlled enclosures – assumption of uniform conditions breaks down
• FDS holds some promise – CFD modeling + heat transfer and combustion
![Page 18: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/18.jpg)
Eurocode Parametric Method
( )*** 197.12.0 472.0204.0324.011325 ttt eeeT −−− −−−=
![Page 19: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/19.jpg)
Lie’s Parametric Method
5.0
1236.0/1.0 600)]1(4)1()1(3[)10(250
23.0
⎟⎟⎠
⎞⎜⎜⎝
⎛+−+−−−= −−−⎟
⎟⎠
⎞⎜⎜⎝
⎛−⎟
⎟⎠
⎞⎜⎜⎝
⎛
oo
tttt
AHA
AHA
oo
HAACeeee
AHA
Toooo
![Page 20: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/20.jpg)
Tanaka
31
0000
32
0000
6.1
−
∞∞
∞
∞⎟⎟⎠
⎞⎜⎜⎝
⎛⎟⎟⎠
⎞⎜⎜⎝
⎛=⎟⎟
⎠
⎞⎜⎜⎝
⎛ −=
∆HAcg
AhHATcg
QT
TTT
T k
ρρ
&
![Page 21: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/21.jpg)
Magnusson and ThelanderssonCurves
![Page 22: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/22.jpg)
Harmathy
( ) ( ) ( ) ( )⎥⎦⎤
⎢⎣⎡ −−−+−∆+∆= 4
04
0 368.0932.01 TT
ATTcmmHHm
Aq o
focvfE σζβ &&&
41
42
1
0 2⎪⎭
⎪⎬⎫
⎪⎩
⎪⎨⎧
⎥⎥⎦
⎤
⎢⎢⎣
⎡⎟⎠⎞
⎜⎝⎛++≈
πκτ
ση kq
Tq
T EE
![Page 23: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/23.jpg)
Babrauskas
54321 *****)1452( θθθθθoo TTT −+=
• θ1 - Stoiciometry• θ2 – Steady-state heat loss to walls• θ3 – Transient wall losses• θ4 – Radiation loss through vent• θ5 – Combustion efficiency
![Page 24: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/24.jpg)
Ma and Mäkeläinen
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Time Ratio (t / tm)
Tem
pera
ture
Rat
io (T
g / T
gm)
δ = 0.5, 1.0
δ = 0.8, 1.6
![Page 25: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/25.jpg)
CIB – Temperature
0
200
400
600
800
1000
1200
0 10 20 30 40 50A/AoHo1/2 (m-1/2)
T (°
C)
CIB Data
CIB Curve
![Page 26: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/26.jpg)
CIB – Burning Rate
0
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0.16
0.18
0 10 20 30 40 50 60
A/AoHo (m^-1/2)
R/A
oHo(
D/W
)^1/
2 (k
g/s-
m^5
/2)
121
221
211
441
Curve Fit
![Page 27: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/27.jpg)
Law
⎟⎟⎟⎟⎟
⎠
⎞
⎜⎜⎜⎜⎜
⎝
⎛
−=
−
oo
HAA
gm
HAA
eToo
1.0
16000
( )Ψ−−= 05.01 eTT gm
![Page 28: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/28.jpg)
Evaluation
• Use CIB temperature and burning rate data to evaluate methods
![Page 29: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/29.jpg)
Cardington
23 m
Closed end
Cribs distributed on floor
Thermocouple locations
2.7 m
5.5 m
![Page 30: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/30.jpg)
Findings – Law
0
200
400
600
800
1000
1200
1400
0 10 20 30 40 50
( ) )(m / -1/2oo HAA
![Page 31: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/31.jpg)
Findings – Law
0
0.05
0.1
0.15
0.2
0.25
0 10 20 30 40 50 60
A/AoHo (m^-1/2)
R/A
oHo(
D/W
)^1/
2 (k
g/s-
m^5
/2)
121
221
211
441
Law X 1.4
![Page 32: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/32.jpg)
Findings – Law
0200400600800
100012001400
0 0.5 1
Time (h)
Tem
pera
ture
(C)
Measured
Law withoutreduction factorLaw
![Page 33: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/33.jpg)
Findings – Law
Cardington Test #1
0200400600800
100012001400
0 1 2
Time (h)
Tem
pera
ture
(C)
MeasuredLaw Adusted
21
18−
= mHA
A
oo
![Page 34: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/34.jpg)
Findings – Magnusson and Thelandersson
0
200
400
600
800
1000
1200
1400
0 0.5 1 1.5 2 2.5 3 3.5 4
Time (h)
Tem
pera
ture
(C)
Measured
Magnusson (Type C)
21
45−
= mHA
A
oo
![Page 35: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/35.jpg)
Findings - Lie
0
100
200
300
400
500
600
700
800
900
0 1 2 3 4 5 6 7 8
Time (h)
Tem
pera
ture
(C)
Measured
Lie
21
45−
= mHA
A
oo
![Page 36: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/36.jpg)
Are Correlations Based on Burning Wood Cribs OK?
![Page 37: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/37.jpg)
Limitations
• Uncertainty in model inputs, e.g., fire load• Intervention, e.g. sprinklers or fire brigade• Designing for extreme events
![Page 38: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/38.jpg)
Localized Fires
• Heat transfer from fire plume in contact with a structural element
• May be more severe than hot gas layer exposure– Large enclosures– Open parking garages– Bridges and overpasses– Tunnels
![Page 39: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/39.jpg)
Heat Flux Boundary Condition
( ) ( )44∞∞ −−−−′′=′′ TTTThqq ssshfgnet σε
Ts General boundary condition ( ) 44
sssfffsnet TTThTqdxdTk σεσεε −−+=′′=−h(Tf –Ts)
Determined from heat flux gaugeεf εsσTf4
q”net
εsσTs4
![Page 40: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/40.jpg)
Fire Types
• Bounding fires– Items immersed in large fires
• Specific geometries– Fire against vertical walls– Fire in a corner with a ceiling– Fire impinging on unbounded flat ceiling– Fire impinging on I-beam mounted below ceiling– Others in SFPE Handbook of Fire Protection
Engineering, 3rd Edition
![Page 41: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/41.jpg)
Immersed Objects
• Peak in most tests– 150-170 kW/m2
• Highest in tests– 220 kW/m2
– appears exceptional
TEST POOL SIZE FUEL peakq ′′
(kW/m2) AEA Winfrith [1] 1.6 ft x 31 ft Kerosene 150
US DOT [1] Not listed. Kerosene 138 USCG [1] Not listed. Kerosene 110-142
US DOT [1] Not listed. Kerosene 136-159 Sandia [1] Not listed. Kerosene 113-150
HSE Buxton [1] Not listed. Kerosene 130 Shell Research [1] 13 ft x 23 ft Kerosene 94-112 Large cylinder [2] 30 ft x 60 ft JP-4 100-150 Small cylinder [2] 30 ft x 60 ft JP-4 150-220
Ref. [3] 8 ft x 16 ft JP-5 144 1. Cowley (1991). 2. Gregory, Mata, and Keltner (1987). 3. Russel and Canfield (1973).
![Page 42: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/42.jpg)
Specific Geometries
• Empirical correlations– Heat flux gauge measurements
• Required input data– Heat release rate– Fuel diameter– Location relative to top of fuel package
![Page 43: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/43.jpg)
General Calculation Approach
• Calculate flame height• Calculate virtual source origin (if required)• Calculate location of element relative to fire
centerline and top surface of fuel• Use correlations to determine heat flux
![Page 44: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/44.jpg)
Vertical Wall
Heat Release Rate [kW]
0 100 200 300 400 500 600
Peak
Hea
t Flu
x, q
" peak
[kW
/m2 ]
0
20
40
60
80
100
120
140
Aspect Ratio ~1Aspect Ratio ~2Aspect Ratio ~3
![Page 45: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/45.jpg)
Vertical Wall
z/Lf
0.01 0.1 1 10
Cen
terli
ne H
eat F
lux,
q" c
l [kW
/m2 ]
1
10
100
1000
Q ≈ 59 kWQ ≈ 121 kWQ ≈ 212 kWQ = 313 kWQ = 523 kWCorrelation for Q=59 kWCorrelation for Q=523 kW
Vertical on Centerline Horizontally off Centerline
![Page 46: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/46.jpg)
Vertical Wall - Limitations
• Wall is vertical• Flames are luminous• No heating from upper-layer of gases • Fire assumed in contact with wall• Data developed for specific size fires
– Heat release rate up to 520 kW– Diameter up to 0.70 m
![Page 47: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/47.jpg)
Corner with Ceiling
Regions for Correlations
![Page 48: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/48.jpg)
Corner with Ceiling
Length of Area Burner Side, D [m]0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Pea
k H
eat F
lux,
q" p
eak
[kW
/m2 ]
0
10
20
30
40
50
60
70
80
90
100
110
120
z/Lf,tip
0.01 0.1 1 10
Max
imum
Hea
t Flu
x in
Cor
ner,
q"m
ax (k
W/m
2 )
1
10
100
1000
Along Height in CornerPeak in Corner
![Page 49: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/49.jpg)
Corner with Ceiling
(x+H) / Lf,tip
0.1 1 10
Max
imum
Hea
t Flu
x, q
" max
[kW
/m2 ]
1
10
100
1000
(r+H)/Lf,tip
0.1 1 10
Hea
t Flu
x to
Cei
ling
[kW
/m2 ]
0.1
1
10
100
1000
Along Top of Walls Along Ceiling
![Page 50: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/50.jpg)
Corner with Ceiling - Limitations
• Walls are vertical and at a 90o angle• Ceiling is horizontal and at a 90o angle with walls• Flames are luminous• No heating from upper-layer of gases• Fire assumed in contact with wall• Data developed for specific size fires
– Heat release rate up to 300 kW– Diameter up to 0.50 m
![Page 51: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/51.jpg)
Unbounded Ceiling
![Page 52: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/52.jpg)
Unbounded Ceiling
At Stagnation Point
![Page 53: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/53.jpg)
Unbounded Ceiling
w = (r+H+z')/(LH+H+z')
0.1 1 10H
eat F
lux,
q" [
kW/m
2 ]1
10
100
1000
Along Ceiling Radially out from Impingment Point
![Page 54: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/54.jpg)
Unbounded Ceiling - Limitations
• Ceiling is flat with no pockets or beams• Flames are luminous• No heating from upper-layer of gases• Data developed for specific size fires
– Heat release rate up to 400 kW– Diameter up to 1.0 m
![Page 55: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/55.jpg)
I-Beam Beneath Ceiling
![Page 56: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/56.jpg)
I-Beam Beneath Ceiling
• Fires <1,000 kW– Within band of
unbounded ceiling data
• Depends on location on I-beam– Highest on lower
flange face
![Page 57: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/57.jpg)
I-Beam Beneath Ceiling
w (- -)
0.1 1 10
Hea
t Flu
x, q
", (k
W/m
2 )
0.1
1
10
100
1000• Fires 500-3,600 kW– Data close to bounding
fit
• Large fires >2,000 kW– All faces of I-beam
exposed to similar heat flux
– Close to bounding fit
![Page 58: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/58.jpg)
I-Beam Beneath Ceiling -Limitations
• Only one I-beam tested– Web
• 150 mm high and 5mm thick– Flanges
• 75 mm wide and 6 mm thick• Fire impinges on I-beam lower flange face• Flames are luminous• No heating from upper-layer of gases• Data developed for specific size fires
– Heat release rate up to 3,600 kW– Diameter up to 1.6 m
![Page 59: Apresentação NFPA SFP](https://reader034.vdocument.in/reader034/viewer/2022042616/55cf97e6550346d033944d1a/html5/thumbnails/59.jpg)
Summary
• Performance-based design of structural fire resistance requires three steps– Estimation of thermal boundary conditions– Estimation of heat transfer– Estimation of structural response at elevated
temperatures• SFPE Guide provides information needed to
estimate thermal boundary conditions