Download - Autopilot Teory
-
8/9/2019 Autopilot Teory
1/70
Publication No. 1-0485-009
March 1999 Rev L
AutoPILOT
CONTROL DOCUMENT
AND ENTITY PARAMETERS
9303 W. Sam Houston Parkway South, Houston, TX 77099-5296 PH:(713)272-0404 FAX:(713)272-2272
Please contact the manufacturer if the informationpresented in the manual does not match your unit.
-
8/9/2019 Autopilot Teory
2/70
Document 1-0485-009 Rev Li
AutoPILOT
CONTROL DOCUMENT
AND ENTITY PARAMETERS
CONTENTS
1.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 THE AutoPILOT LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 CONCEPT OF ENTITY APPROVAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 BARRIER INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 WIRING INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 AutoPILOT SYSTEM LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 POWER INPUT SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.1 Internal Power Source with External Solar Panel . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 ISCOM 3-0474-004 (Intrinsically-Safe Power and Communications) . . . . . . . . . . 62.1.3 6V ISCOM (Intrinsically-Safe Power and Communications) . . . . . . . . . . . . . . . . 10
2.2 LOCAL RS-232 (CHIT) SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3 ANALOG INPUT SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4 AutoMITTER SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5 RTD INPUT SYSTEM CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.6 AutoPULSE INPUT SYSTEM CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.0 AutoPILOT ENTITY LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1 LOCAL RS-232 PORT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.1.1 Application #1 - Local Communication Port to IS Apparatus . . . . . . . . . . . . . . . 24
3.2 ANALOG INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2.1 Application #1 - Analog Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . 26
3.2.2 Application #2 - Analog Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . 27
3.3 DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.3.1 Application #1 - Discrete Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . 29
3.3.2 Application #2 - Discrete Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . 30
3.4 MEB 2DI/DO DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . 31
3.4.1 Application #1 - MEB 2DI/DO Discrete Input to Non IS Apparatus . . . . . . . . . . 32
3.4.2 Application #2 - MEB 2DI/DO Discrete Input to IS/Simple Apparatus . . . . . . . . 33
3.5 MEB 4 DI DISCRETE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . 34
3.5.1 Application #1 - MEB 4 DI Discrete Input to Non IS Apparatus . . . . . . . . . . . . . 35
3.5.2 Application #2 - MEB 4 DI Discrete Input to IS/Simple Apparatus . . . . . . . . . . 36
3.6 DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.1 Application #1 - Discrete Output to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . 38
3.6.2 Application #2 - Discrete Output to IS Apparatus . . . . . . . . . . . . . . . . . . . . . . . . 39
Click on the contents line to go to the desired section.Click on the table of contents button to return.
-
8/9/2019 Autopilot Teory
3/70
Document 1-0485-009 Rev Lii
3.7 MEB 2DI/DO DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . 40
3.7.1 Application #1 - MEB 2DI/DO Discrete Output to Non IS Apparatus . . . . . . . . 41
3.7.2 Application #2 - MEB 2DI/DO Discrete Output to IS Apparatus . . . . . . . . . . . . 42
3.8 MEB 4 DO DISCRETE OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . 43
3.8.1 Application #1 - MEB 4 DO Discrete Output to Non IS Apparatus . . . . . . . . . . . 44
3.8.2 Application #2 - MEB 4 DO Discrete Output to IS Apparatus . . . . . . . . . . . . . . 45
3.9 PULSE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463.9.1 Application #1 - Pulse Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . . . . . . . 47
3.9.2 Application #2 - Pulse Input to IS Apparatus/Simple Apparatus . . . . . . . . . . . . . 48
3.10 MEB PULSE INPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.10.1 Application #1 - MEB Pulse Input to Non IS Apparatus . . . . . . . . . . . . . . . . . . 50
3.10.2 Application #2 - MEB Pulse Input to IS Apparatus/Simple Apparatus . . . . . . . 51
3.11 ANALOG OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3.11.1 Application #1 - Analog Output to Non-IS Apparatus . . . . . . . . . . . . . . . . . . . . 53
3.11.2 Application #2 - Analog Output to IS Apparatus/Simple Apparatus . . . . . . . . . 54
3.12 DUAL ANALOG OUTPUT ENTITY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . 55
3.12.1 Application #1 - MEB 2D/A Analog Output to Non-IS Apparatus . . . . . . . . . . 563.12.2 Application #2 - MEB 2D/A Analog Output to IS/Simple Apparatus . . . . . . . . 57
-
8/9/2019 Autopilot Teory
4/70
Document 1-0485-009 Rev L1
AutoPILOT
CONTROL DOCUMENT
AND ENTITY PARAMETERS
1.0 GENERAL INFORMATION
1.1 THE AutoPILOT LISTING
The AutoPILOT is UL-Listed for use in Class I Division 1, Groups C and D hazardous locations for
United States installations, and C-UL listed for Class I Division 1, Groups C and D hazardous
locations for Canadian installations. It is intrinsically safe when connected according to this control
document. The AutoPILOT has an Operating Temperature Code of T3C. WARNING:
Substitution of components may impair the intrinsic safety of the AutoPILOT.
The listing includes connections for a System Approval and Entity Approval. The AutoPILOTlisting includes the following maximum number and type of electrical connections:
• One Power Input (System Listing)
• Three Host Ports (RS-232 port; System Listing for use with ISCOM 3-0474-004 or 6V
ISCOM 3-0474-016 or 3-0474-025)
• One CHIT Port (Local RS-232 port; System Listing for use with CHIT, or with Entity
Parameters)
• Analog Inputs (Three with System Listing for use with specified transducers, or One with
Entity Parameters)
• One Comm 3 Terminator IS connection to up to four AutoMITTERs (System Listing)
• One RTD Input (System Listing)
• Up to ten Discrete Inputs (with Entity Parameters)
• Up to ten Discrete Outputs (with Entity Parameters)
• Up to four Pulse Inputs (System Listing with AutoPULSE, or with Entity Parameters)
• Up to four 4-20 mA Analog Outputs with +24V Loop Power Inputs (with Entity Parameters)
Power Systems available with System Listing include the following options. ISCOM model
numbers must be verified to ensure safety.
• Internal +6VDC/12 AH, rechargeable battery with an external 2-watt solar panel
• ISCOM 3-0474-004 (UL Listed Associated Apparatus)
• 6V ISCOM 3-0474-016 (UL Listed Associated Apparatus)
• 6V ISCOM 3-0474-025 (UL and C-UL Listed Associated Apparatus)
-
8/9/2019 Autopilot Teory
5/70
Document 1-0485-009 Rev L2
1.2 CONCEPT OF ENTITY APPROVAL
The concept of an Entity Approval allows connection of intrinsically-safe apparatus and intrinsically-
safe associated apparatus, including barriers, that have not been specifically approved as a system.
Refer to Article 504 of the National Electrical Code, NFPA 70, for acceptable wiring methods,
sealing methods, and separation of intrinsically-safe and non-intrinsically safe wiring for United
States installations, or Section 18 of the Canadian Electrical Code for wiring, sealing and separationrequirements for Canadian installations.
Under Entity Approval, connection between an intrinsically-safe apparatus and an intrinsically-safe
associated apparatus is limited as follows:
1. The approvedMaximum Open-Circuit Voltage (Voc) of the associated apparatus must be less
than or equal to the Maximum Safe Input Voltage (Vmax) of the intrinsically-safe apparatus.
(Voc Vmax)
2. The approved Maximum Short-Circuit Current (Isc) of the associated apparatus must be lessthan or equal to the Maximum Safe Input Current (Imax) of the intrinsically-safe apparatus.
(Isc Imax)
3. The approved Maximum Allowable Capacitance (Ca) of the associated apparatus must be
greater than or equal to the sum of the Internal Capacitance (Ci) of the intrinsically-safe
apparatus and the Wiring Capacitance (Cw). (Ca Ci + Cw)
4. The approved Maximum Allowable Inductance (La) of the associated apparatus must be
greater than or equal to the sum of the Internal Inductance (Li) of the intrinsically-safe
apparatus and the Wiring Inductance (Lw). (La Li + Lw)
Note
If the wiring parameters (capacitance and inductance) are not known, use the following
parameters:
• Wiring Capacitance of 60 pF per foot
• Wiring Inductance of 0.2 H per foot
A 100-foot cable has a Cw of 6000 pF (0.006 F) and a Lw of 20 H.
When two intrinsically-safe devices are connected and installed in the hazardous location, the same
four entity approval concepts apply. However, they must be applied from both directions: first with
the AutoPILOT as the intrinsically-safe apparatus connected to an intrinsically-safe associated
apparatus (such as a pressure transmitter), then the AutoPILOT as the intrinsically-safe associated
apparatus connected to the intrinsically-safe apparatus (pressure transmitter).
-
8/9/2019 Autopilot Teory
6/70
Document 1-0485-009 Rev L3
1.3 BARRIER INFORMATION
When the device connected to the AutoPILOT is not an approved intrinsically-safe device for use
in the hazardous location, it must be installed in an non-hazardous area, and an intrinsically-safe
barrier must be wired between the AutoPILOT and the device. The general requirements of the
selected barrier are as follows:
The barrier output must be limited by a resistor such that the output voltage verses current plot
is a straight line between Voc and Isc.
The barrier must be approved for the installation location and hazardous area, and be installed
as instructed by the barrier manufacturer.
The barrier ground must be connected to the Earth Ground.
Typical Single-Channel, Shunt-Diode, Resistive Barrier
Typical Dual-Channel, Shut-Diode, Resistive & Diode Barrier
for 4-20mA Applications
-
8/9/2019 Autopilot Teory
7/70
Document 1-0485-009 Rev L4
1.4 WIRING INFORMATION
When installed in the United States in a Class I Division 1 hazardous location, all customer wiring
to the AutoPILOT connections with entity parameters must be made according to Article 504
(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing
methods. For Canadian Class I Division 1 installations, all customer wiring to the AutoPILOT
connections with entity parameters must be made according to Section 18-066 of the CanadianElectrical Code. Multiple circuits that run in the same multiple-conductor cable must have a
minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor.
-
8/9/2019 Autopilot Teory
8/70
Document 1-0485-009 Rev L5
2.0 AutoPILOT SYSTEM LISTING
The System Listing of the AutoPILOT includes power systems, RS-232 communication ports,
connections to a standard suite of analog/digital transmitters, connection to up to four
AutoMITTERs, one dedicated external RTD input, and connections to the AutoPULSE Indexer. The
System listing provides two power options: an internal battery with external solar panel, or one of
the Intrinsically Safe COMmunication interfaces (ISCOM). The communication ports included inthe system listing are the Local Port (used with the CHIT) and up to three Host Ports (used with an
ISCOM). The AutoPILOT Main Board provides system termination for three analog inputs from
a suite of optional low-power transmitters, for the optional Rosemount 205 Digital Combo
Transmitter, or for the optional Honeywell MXA145 or MXG170 combination transmitters. The
Comm 3 Terminator option provides an intrinsically safe power and communication connection to
up to four AutoMITTERs wired in parallel, with each AutoMITTER having one temperature input
which can be system wired to one of the Flow Automation RTD Temperature Probe assemblies. The
RTD1 input at TB5 connects to one of the Flow Automation RTD Temperature Probe assemblies.
For positive displacement (PD) meters, a system connection may be made between the AutoPULSE
Indexer and the AutoPILOT or MEB Pulse Input Board(s).
2.1 POWER INPUT SYSTEM CONNECTION
The AutoPILOT is powered by one of two power systems: an internal rechargeable battery with an
external solar panel, or an Intrinsically Safe Communication System (ISCOM 3-0474-004 or 6V
ISCOM 3-0474-016 or 3-0474-025). ISCOM model numbers must be verified to ensure safety.
2.1.1 Internal Power Source with External Solar Panel
The intrinsically safe battery assembly consists of a +6 Vdc, 12 AH rechargeable battery with
associated protective components. The battery assembly charge is maintained with a 2-watt solar
panel. The battery assembly mounts inside the enclosure internal chassis on the backpanel, and may
be shipped outside the unit to avoid shipping damage. To install the battery assembly, lift the battery
assembly above the bracket retaining lip, and lower the battery assembly into the bracket. The power
leads from the battery assembly connect to the flow computer at the power distribution terminal
block TB1 mounted on the equipment panel at positions 1-3 (POS) and 4-6 (NEG).
Mount the solar panel assembly to the pole, route the solar panel wiring through the bottom of the
flow computer enclosure, then connect it to the two-position Molex connector of the battery
assembly.
When the battery needs to be changed, the entire battery assembly must be replaced. Order the
replacement Division 1 battery assembly from Flow Automation (PN# 3-0485-026).
-
8/9/2019 Autopilot Teory
9/70
Document 1-0485-009 Rev L6
2.1.2 ISCOM 3-0474-004 (Intrinsically-Safe Power and Communications)
The ISCOM 3-0474-004 provides the AutoPILOT with an intrinsically safe +6 Vdc input power, and
an RS-232 link with a Host communication port. ISCOM model numbers must be verified to ensure
safety. This option is not available for Canadian installations. When installed in a Class I Division
1 hazardous location in the United States, all customer wiring to the AutoPILOT must be made
according to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70,including wiring and sealing methods. Multiple circuits that run in the same multiple-conductor
cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer
to the ISCOM Installation and Wiring Manual (PN# 1-0446-004) for proper installation guidelines
of the ISCOM 3-0474-004.
ISCOM 3-0474-004 Non Intrinsically-Safe Connections
The non intrinsically-safe connections of the ISCOM 3-0474-004 are made to a power source (+8
Vdc to +16 Vdc) and an RS-232 communication device. When installed in the nonhazardousarea, the power source and the communication device are not part of the Listed System and
shall not use or generate more than 250 Volts. The ISCOM 3-0474-004 when mounted inside the
AutoLINK may be installed in a Division 2 or nonhazardous area. Refer to the ISCOM Installation
and Wiring Manual (Flow Automation Part Number 1-0446-004) for proper connection of these
devices to the ISCOM 3-0474-004.
ISCOM 3-0474-004 to AutoPILOT Intrinsically-Safe Connections
The connection between the ISCOM 3-0474-004 and AutoPILOT is an intrinsically-safe connection.
The cable length between the ISCOM 3-0474-004 and the AutoPILOT shall not exceed 200 feet.
Because the AutoPILOT with Div I Comm Expansion Board option provides up to three RS-232
ports, three ISCOMs 3-0474-004 can be connected to the AutoPILOT in non-hazardous area
installations, while the AutoLINK provides only one ISCOM 3-0474-004. Only the primary
ISCOM connected to the AutoPILOT Main Board can supply power to the flow computer.
The IS Power Outputs of a secondary or tertiary ISCOM 3-0474-004 must not be connected.
Refer to Figure 2-1-1 or Figure 2-1-2 for typical System Connection wiring between the ISCOM 3-
0474-004 and AutoPILOT.
-
8/9/2019 Autopilot Teory
10/70
Document 1-0485-009 Rev L7
Connection of the ISCOM 3-0474-004 to the AutoPILOT is as follows:
Primary
ISCOM
3-0474-004 Power Distribution AutoPILOT
IS Output Terminal Block Main Board
PWR (1) TB1 position 1-3 (POS) No connection
GND (2) TB1 position 4-6 (NEG) No connection
SBAT (3) No connection +5 (TB2-9)
HRTS (4) No connection RTS (TB2-4)
HTX (5) No connection TX (TB2-3)
HDCD (6) No connection DCD (TB2-5)
HCTS (7) No connection CTS (TB2- 2)
HRX (8) No connection RX (TB2-1)
2nd or 3rd
ISCOM Div I Div I
3-0474-004 Comm Expansion Bd. Comm Expansion Bd.
IS Output Comm 4 Comm 5
PWR (1) No Connection No connection
GND (2) GND (TB1-8) GND (TB2-8)
SBAT (3) No Connection No connection
HRTS (4) RTS (TB1-4) RTS (TB2-4)
HTX (5) TXD(TB1-3) TXD(TB2-3)
HDCD (6) DCD (TB1-5) DCD (TB2-5)
HCTS (7) CTS (TB1- 2) CTS (TB2- 2)HRX (8) RXD (TB1-1) RXD (TB2-1)
-
8/9/2019 Autopilot Teory
11/70
Document 1-0485-009 Rev L8
Figure 2-1-1: Typical Nonhazardous ISCOM 3-0474-004 to AutoPILOT Connection
Notes:
1. Not part of Listed System. Shall not use or generate more than 250 Volts.
2. Maximum cable length between ISCOM 3-0474-004 and AutoPILOT is 200 Feet.
3. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,
for proper sealing between hazardous and nonhazardous areas, and separation between
intrinsically-safe and non intrinsically-safe wiring.
4. Refer to Installation Manual 1-0446-004 for ISCOM 3-0474-004 installation and wiring
instructions.
-
8/9/2019 Autopilot Teory
12/70
Document 1-0485-009 Rev L9
Figure 2-1-2: Typical AutoLINK ISCOM 3-0474-004 to AutoPILOT Connection
Notes:
1. Maximum cable length between ISCOM 3-0474-004 and AutoPILOT is 200 Feet.
2. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,
for proper sealing between hazardous and nonhazardous areas, and separation between
intrinsically-safe and non intrinsically-safe wiring.
3. Refer to Installation Manual 1-0446-004 for ISCOM 3-0474-004 installation and wiring
instructions. Refer to AutoLINK manual 1-0488-001 for AutoLINK installations.
-
8/9/2019 Autopilot Teory
13/70
Document 1-0485-009 Rev L10
2.1.3 6V ISCOM (Intrinsically-Safe Power and Communications)
The 6V ISCOM provides the AutoPILOT with an intrinsically safe +6 Vdc input power, and an RS-
232 link with a Host communication port. 6V ISCOM 3-0474-016 is Listed for United States
installations, while the 6V ISCOM 3-0474-025 is Listed for United States or Canadian installations.
ISCOM model number must be verified to ensure safety. When installed in a Class I Division 1
hazardous location in the United States, all customer wiring to the AutoPILOT must be madeaccording to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70,
including wiring and sealing methods. For Canadian installations, all customer wiring to the
AutoPILOT installed in a Class I Division 1 hazardous location must be made according to Section
18-066 of the Canadian Electrical Code. Multiple circuits that run in the same multiple-conductor
cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer
to the 6V ISCOM Installation and Wiring Manual (PN# 1-0474-004) for proper installation
guidelines of the 6V ISCOM 3-0474-016 or 3-0474-025.
6V ISCOM 3-0474-016 or 3-0474-025 Non Intrinsically-Safe Connections
The non intrinsically-safe connections of the 6V ISCOM 3-0474-016 or 3-0474-025 are made to a
power source (+8 Vdc to +16 Vdc) and an RS-232 communication device. When installed in the
nonhazardous area, the power source and the communication device are not part of the Listed
System and shall not use or generate more than 125 Volts. The 6V ISCOM 3-0474-016 or 3-
0474-025 when mounted inside the AutoLINK may be installed in a Division 2 or nonhazardous
area. Refer to the 6V ISCOM Installation and Wiring Manual (PN# 1-0474-004) for proper
connection of these devices to the 6V ISCOM 3-0474-016 or 3-0474-025.
6V ISCOM 3-0474-016 or 3-0474-025 to AutoPILOT Intrinsically-Safe Connections
The connection between the 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is an
intrinsically-safe connection. The cable length between the 6V ISCOM 3-0474-016 or 3-0474-025
and the AutoPILOT shall not exceed 200 feet. Because the AutoPILOT with Div I Comm Expansion
Board option provides up to three RS-232 ports, three 6V ISCOMs 3-0474-016 or 3-0474-025 can
be connected to the AutoPILOT in non-hazardous area installations, while the AutoLINK provides
only one 6V ISCOM 3-0474-016 or 3-0474-025. Only the primary ISCOM connected to the
AutoPILOT Main Board can supply power to the flow computer. The IS Power Outputs of
a secondary or tertiary 6V ISCOM 3-0474-016 or 3-0474-025 must not be connected. Refer to
Figures 2-1-3 and 2-1-4 for typical System Connection wiring between the 6V ISCOM 3-0474-016
or 3-0474-025 and AutoPILOT.
-
8/9/2019 Autopilot Teory
14/70
Document 1-0485-009 Rev L11
Connection of the 6V ISCOM 3-0474-016 or 3-0474-025 to the AutoPILOT is as follows:
Primary 6V ISCOM
3-0474-016 or 3-0474-025 Power Distribution AutoPILOT
IS Output Terminal Block Main Board
VSAFE (TB2-6) TB1 position 1-3 (POS) No connection
GND (TB2-7) TB1 position 4-6 (NEG) No connectionRTS-IN (TB2-5) No connection RTS (TB2-4)
TX-IN (TB2-4) No connection TX (TB2-3)
DCD-OUT (TB2-3) No connection DCD (TB2-5)
CTS-OUT (TB2-2) No connection CTS (TB2- 2)
RX-OUT (TB2-1) No connection RX (TB2-1)
2nd or 3rd 6V ISCOM Div I Div I
3-0474-016 or 3-0474-025 Comm Expansion Bd. Comm Expansion Bd.
IS Output Comm 4 Comm 5
VSAFE (TB2-6) No Connection No connection
GND (TB2-7) GND (TB1-8) GND (TB2-8)
RTS-IN (TB2-5) RTS (TB1-4) RTS (TB2-4)
TX-IN (TB2-4) TXD(TB1-3) TXD(TB2-3)
DCD-OUT (TB2-3) DCD (TB1-5) DCD (TB2-5)
CTS-OUT (TB2-2) CTS (TB1- 2) CTS (TB2- 2)
RX-OUT (TB2-1) RXD (TB1-1) RXD (TB2-1)
-
8/9/2019 Autopilot Teory
15/70
Document 1-0485-009 Rev L12
Figure 2-1-3: 6V ISCOM 3-0474-016 or 3-0474-025 to AutoPILOT Connection
Notes:
1. Not part of Listed System. Shall not use or generate more than 125 Volts.
2. Maximum cable length between 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is 200
Feet.
3. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,
for proper sealing between hazardous and nonhazardous areas, and separation between
intrinsically-safe and non intrinsically-safe wiring. For Canadian installations, refer to Section
18-066 and 18-106 of the Canadian Electrical Code for separation and sealing requirements.
4. Refer to Installation Manual 1-0474-004 for 6V ISCOM 3-0474-016 or 3-0474-025 installation
and wiring instructions.
-
8/9/2019 Autopilot Teory
16/70
Document 1-0485-009 Rev L13
Figure 2-1-4: 6V ISCOM 3-0474-016 or 3-0474-025 AutoLINK to AutoPILOT Connection
Notes:
1. Maximum cable length between 6V ISCOM 3-0474-016 or 3-0474-025 and AutoPILOT is 200
Feet.
2. For United States installations, refer to Article 504 of the National Electrical Code, NFPA 70,
for proper sealing between hazardous and nonhazardous areas, and separation between
intrinsically-safe and non intrinsically-safe wiring. For Canadian installations, refer to Section
18-066 and 18-106 of the Canadian Electrical Code for separation and sealing requirements.
3. Refer to Installation Manual 1-0474-004 for 6V ISCOM 3-0474-016 or 3-0474-025 installation
and wiring instructions. Refer to AutoLINK manual 1-0488-001 for AutoLINK
interconnections.
-
8/9/2019 Autopilot Teory
17/70
Document 1-0485-009 Rev L14
2.2 LOCAL RS-232 (CHIT) SYSTEM CONNECTION
The AutoPILOT provides an RS-232 compatible Local communication port for software
configuration and calibration of the flow computer. Connection to the port is made using the six-
position LEMO connector located on the bottom of the flow computer enclosure. The interface to
the port is made only to the Class I Division 1 CHIT with a coiled cable (PN# 3-0330-014) or a 25-
foot cable (PN# 3-0330-071).
-
8/9/2019 Autopilot Teory
18/70
Document 1-0485-009 Rev L15
2.3 ANALOG INPUT SYSTEM CONNECTIONS
The AutoPILOT System listing includes connections to direct mounted combination transmitters,
remote mounted AutoMITTERs, and/or three analog inputs for use with low power single analog
transmitters (differential pressure, static pressure, and temperature). Refer to Section 2.4 for
AutoMITTER connections. The following single transmitters are included under the System Listing:
• Druck Static Pressure Transmitter Model PDCR143-8003 (25 to 3000 psi range)
• Rosemount Static Pressure Transmitter Model 3051C Low Power (3626 psi maximum range)
• Rosemount Differential Pressure Transmitter Model 2024 (2000 psi maximum range)
• Rosemount Differential Pressure Transmitter Model 3051C Low Power (3626 psi maximum
range)
• Flow Automation RTD Temperature Transmitter Model 465A
The standard low-power transmitters may be factory wired to the AutoPILOT Main Board with a
maximum cable length of 25 feet or less between the AutoPILOT and the transmitters. See Figure
2-3-1 for typical wiring of the Analog Input System Connection (Direct Wired). The AutoPILOTMain Board Analog Input Direct Wired connections are as follows:
CHANNEL SIG AGND XPWR
AI1 TB4-1 TB4-2 TB4-3
AI2 TB4-4 TB4-5 TB4-6
AI3 TB4-7 TB4-8 TB4-9
The single transmitters may also be wired to one of six junction box assemblies included in the
system listing. The 3-0485-158, 3-0485-195 or 3-0485-255 assembly is used for transducers whichcannot power cycle (typically Rosemount 3051's), and has XPWR connected to the power input at
TB1 position 1-3 (POS) on the internal chassis power distribution terminal block. The 3-0485-156,
3-0485-194 or 3-0485-254 assembly is used with power cycling transducers, and has XPWR
connected to the AutoPILOT Main Board at TB4-3. Cabling from the junction box assembly to the
transmitters is limited to 25 feet maximum cable length. See Figure 2-3-2 for typical wiring of the
Analog Input System Connection (Junction Box) assembly.
-
8/9/2019 Autopilot Teory
19/70
Document 1-0485-009 Rev L16
The connections to any analog input junction box assembly are as follows:
JB TB1 SIG
1 AGND
2 XPWR
3 AI1
4 AI2
5 AI3
Figure 2-3-1: Typical Analog Input System Connection (Direct Wired)
Figure 2-3-2: Typical Analog Input System Connection (Junction Box)
-
8/9/2019 Autopilot Teory
20/70
Document 1-0485-009 Rev L17
The Rosemount Model 205 Digital Combo Transmitter (0-250" DP, maximum 3626 psi) is also a
system connection to the AutoPILOT. The 205 transmitter provides digital, temperature
compensated, differential and static pressure signals. The digital combo transmitter mounts directly
to the bottom of the AutoPILOT enclosure and connects to the AutoPILOT Main Board through the
205 Interface Board.
The Honeywell combination transmitter MXA145 (0-400" DP, maximum 1500 psia) or MXG170(0-400" DP, maximum 3000 psig) are also system connections to the AutoPILOT, mount directly
to the bottom of the AutoPILOT enclosure, and connect to the AutoPILOT Main Board through the
Honeywell transducer interface board. The Honeywell transducer interface board has station ID
jumpers which may need to be user configured. If the flow computer software version was initially
developed to use the Rosemount 205, then jumpers J1 through J4 on the Honeywell interface board
must be installed. If the software version was developed to use a Honeywell combination transducer,
then J1 is removed, and J2 through J4 installed on the interface board.
2.4 AutoMITTER SYSTEM CONNECTIONS
The AutoPILOT provides an optional system connection through the Comm 3 Terminator board to
up to four remote mounted AutoMITTER transducers. Comm 3 Terminator assembly 3-0485-333
is used for 6V input power systems as described in Section 2.1 for use with the Division 1
AutoPILOT for United States and Canadian installations. Each AutoMITTER uses one of the
Honeywell combination transmitters to provide differential and static pressure measurements, and
an optional temperature input. All AutoMITTERs are wired in parallel to the Comm 3 Terminator
intrinsically safe output, which provides a +6V power and RS-485 communication buss to and from
the AutoMITTERs, with a total cable length of 2250 feet or less. Each AutoMITTER also has an
optional RTD input, which may be system wired to the 3-0465-029 or 3-0465-033 Temperature
Probe assembly using up to 25 feet of cable. When installed in a Class I Division 1 hazardous
location in the United States, all wiring to and from the AutoMITTER is intrinsically safe wiring,
and must be made according to Article 504 (Intrinsically Safe Systems) of the National Electrical
Code, NFPA 70. For Canadian installations, all wiring to and from the AutoMITTER is intrinsically
safe wiring, and must be made according to Sections 18-066 and 18-106 of the Canadian Electrical
Code. Multiple circuits that run in the same multiple-conductor cable must have a minimum
insulation thickness of 0.01 inch (0.25 mm) on each conductor.
-
8/9/2019 Autopilot Teory
21/70
Document 1-0485-009 Rev L18
AutoPILOT to AutoMITTER Intrinsically Safe Connections
The connection between the Comm 3 Terminator and the AutoMITTER(s) is intrinsically safe
wiring, and must be installed according to Article 504 (Intrinsically Safe Systems) of the National
Electrical Code, NFPA 70, for United States installations, or according to Sections 18-066 and 18-
106 of the Canadian Electrical Code for Canadian installations. The total cable length between the
AutoPILOT and all AutoMITTERs must not exceed 2250 feet. Refer to Figure 2-4 for typicalsystem connection wiring between the AutoPILOT and AutoMITTERs.
WARNING:
REPLACE THE WIRING SEPARATOR AFTER MAKING
CONNECTIONS TO THE AutoMITTER.
Connections between the AutoPILOT Comm 3 Terminator and each AutoMITTER are as follows:
Comm 3
IS OUTPUT AutoMITTER
TX+ (TB2-5) RX+ (TB1-1)
TX- (TB2-4) RX- (TB1-2)
RX- (TB2-2) TX- (TB1-3)
RX+ (TB2-1) TX+ (TB1-4)
GND (TB2-6) GND (TB1-5)
+6V (TB2-7) BAT (TB1-6)
Shielded cable is recommended for use between the Comm 3 Terminator and the AutoMITTER(s),
with the drain wire connected to the Comm 3 Terminator at TB2-3.
-
8/9/2019 Autopilot Teory
22/70
Document 1-0485-009 Rev L19
Figure 2-4: AutoPILOT to AutoMITTER System Connections
Notes:
1. Up to four AutoMITTERs may be connected in parallel to one Comm 3 Terminator output.
2. Maximum total cable length connected to the Comm 3 Terminator intrinsically safe output and
all AutoMITTERs is 2250 feet.
3. Maximum cable length for each AutoMITTER system Temperature Probe assembly connection
is 25 feet.
4. For United States installations, all wiring to and from the AutoMITTER is intrinsically safe and
must be installed according to Article 504 of the National Electrical Code, NFPA 70. For
Canadian installations, all wiring to and from the AutoMITTER is intrinsically safe and must be
installed according to Sections 18-066 and 18-106 of the Canadian Electrical Code.
-
8/9/2019 Autopilot Teory
23/70
Document 1-0485-009 Rev L20
2.5 RTD INPUT SYSTEM CONNECTIONS
The AutoPILOT provides process temperature measurement using the standard Model 465A
Temperature Transmitter into an Analog Input, or the 3-0465-029 or 3-0465-033 Temperature Probe
assembly factory wired to RTD1, with a maximum cable length of 25 feet. Each AutoMITTER may
also use one of the Temperature Probe assemblies. All connections to and from the AutoMITTER
are intrinsically safe wiring, and must be installed according to Article 504 of the National ElectricalCode, NFPA 70, for United States installations, or according to Sections 18-066 and 18-106 of the
Canadian Electrical Code for Canadian installations. The Temperature Probe assemblies differ in
the condulet housing only, and come standard with the Stark composite-body RTD probe or the
optional stainless-steel body RTD probe. Both probe elements are 100-ohm, platinum RTD sensors.
The Main Board RTD2 connections are not used for an external input, and are terminated with a
100-ohm resistor.
-
8/9/2019 Autopilot Teory
24/70
Document 1-0485-009 Rev L21
2.6 AutoPULSE INPUT SYSTEM CONNECTION
For flow corrector applications, the AutoPILOT provides a system connection to the AutoPULSE
Indexer. The AutoPULSE mounts directly to the bottom of the AutoPILOT enclosure for the System
listing, and connects to the AutoPILOT Main Board through the AutoPILOT or MEB Pulse Input
Board(s). The AutoPULSE also connects directly to the top of a standard turbine or positive
displacement (PD) meter. Up to two Pulse Input Boards may be installed in each unit, with twoindexer inputs per board. Either Pulse Input Board has a 7-position DIP configuration for each input,
with PL1 configured with switch SW2 and PL2 configured with SW1. The AutoPULSE is
configured as a contact closure type input, with switch positions 2, 4, 6, and 7 typically set to the
"ON" position on the Pulse Input Board. A unique address which determines the software
configuration must be set using jumpers JP4 and JP2 for each AutoPILOT Pulse Input board
installed in the unit, or JP1 and JP2 for the MEB Pulse Input Board.. The Pulse Input address
jumpers are configured as follows:
Jumper JP1 (MEB)
Jumper JP4 (AP) Jumper JP2 BOARD NO.
Not Installed Not Installed 1
Not Installed Installed 2
-
8/9/2019 Autopilot Teory
25/70
Document 1-0485-009 Rev L22
3.0 AutoPILOT ENTITY LISTING
The Entity Listing of the AutoPILOT includes the following connections:
One RS-232 Communication Port (AutoPILOT Main Board - Local Port)
The following connections to the optional Digital I/O Board are included in the Entity Listing:
One Analog Input Two Discrete Inputs
Two Discrete Outputs
The following buttsplice connections to the optional MEB 2DI/DO Board(s) are included in the
Entity Listing:
Up to four Discrete Inputs
Up to four Discrete Outputs
The following buttsplice connections to the optional MEB 4 DI Board(s) are included in the Entity
Listing: Up to eight Discrete Inputs
The following buttsplice connections to the optional MEB 4 DO Board(s) are included in the Entity
Listing:
Up to eight Discrete Outputs
The following buttsplice connections to the optional AutoPILOT or MEB Pulse Input Board(s) are
included in the Entity Listing:
Up to four Pulse Inputs
The following buttsplice connections to the optional Digital/Analog (D/A) or 2D/A Board(s) are
included in the Entity Listing:
Up to two +24V power inputs
Up to four Analog Outputs
-
8/9/2019 Autopilot Teory
26/70
Document 1-0485-009 Rev L23
3.1 LOCAL RS-232 PORT ENTITY CONNECTIONS
The Local RS-232 port has entity parameters for connection to an intrinsically-safe handheld or PC
device other than the UL and C-UL-listed Flow Automation CHIT. The port provides serial
communication for software configuration and calibration of the AutoPILOT. Connection is made
using the six-position LEMO connector mounted in the bottom of the AutoPILOT’s enclosure.
When installed in a Class I Division 1 hazardous location, all customer wiring to the AutoPILOTmust be made according to Article 504 (Intrinsically Safe Systems) of the National Electrical Code,
NFPA 70, including wiring and sealing methods for United States installations, or according to
Section 18-066 of the Canadian Electrical Code for Canadian installations. Multiple circuits that run
in the same multiple-conductor cable must have a minimum insulation thickness of 0.01 inch (0.25
mm) on each conductor. Refer to Section 1.4, Wiring Information, for proper connection to the
AutoPILOT.
The LEMO provides the following connections:
SIGNAL LEMO Connection
CRX Position #6
CTX Position #3
CEN* Position #4
GND Position #2,5
The CEN* signal must be connected to ground in the plug mating to the LEMO connector on the
AutoPILOT. The AutoPILOT uses the CEN* input to activate the Local RS-232 port when a
connection is made.
-
8/9/2019 Autopilot Teory
27/70
Document 1-0485-009 Rev L24
3.1.1 Application #1 - Local Communication Port to IS Apparatus
Typical AutoPILOT Local RS-232 IS Connection to IS Apparatus
ENTITY PARAMETERS
AutoPILOT AutoPILOT
CTX-GND CRX-GND
Voc = 9.23 Vdc Voc = 9.23 Vdc
Isc = 84 mA Isc = 84 mA
Vmax = 16 Vdc Vmax = 16 Vdc
Imax = 250 mA Imax = 250 mACi = 0 Ci = 0
Li = 0 Li = 0
Ca = 2 F Ca = 2 F
La = 1 mH La = 1 mH
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.3. Terminals CRX-GND and CTX-GND have not been evaluated for parallel connection.
4. LEMO Mating Plug can be ordered under Flow Automation Part Number 5-3521-801.
-
8/9/2019 Autopilot Teory
28/70
Document 1-0485-009 Rev L25
3.2 ANALOG INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes one analog input on the optional AutoPILOT Digital I/O
Board for use with a single 0-5 Vdc maximum range analog transmitter (differential pressure, static
pressure, or temperature). Transducers with voltage output ranges such as 0.8-3.2 Vdc or 1-5 Vdc
units may be used with software scaling provided the 0-volt minimum and 5-volt maximum limits
are not exceeded. The transmitter is wired to TB2 of the Digital I/O Bd. When installed in a ClassI Division 1 hazardous location, all customer wiring to the AutoPILOT must be made according to
Article 504 (Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring
and sealing methods for United States installations, or according to Section 18-066 of the Canadian
Electrical Code for Canadian installations. Multiple circuits that run in the same multiple-conductor
cable must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer
to the Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection
to the AutoPILOT.
The AutoPILOT Digital I/O Board Analog Input connections are identified as follows:
CHANNEL IN AGND
AI3 TB2-9 TB2-10
-
8/9/2019 Autopilot Teory
29/70
Document 1-0485-009 Rev L26
3.2.1 Application #1 - Analog Input to Non IS Apparatus
Typical Analog Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
AutoPILOT
IN-AGND
Vmax = 12 VDC
Imax = 250 mACi = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
30/70
Document 1-0485-009 Rev L27
3.2.2 Application #2 - Analog Input to IS Apparatus/Simple Apparatus
Typical Analog Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
AutoPILOT
IN-AGND
Voc = 9.23 Vdc
Isc = 0.266 mA
Vmax = 12 VdcImax = 250 mA
Ci = 0
Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.3. Simple Apparatus is a non-energy storing device that will not store or generate more than:
• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
31/70
Document 1-0485-009 Rev L28
3.3 DISCRETE INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two discrete inputs on the optional Digital I/O Board and
up to eight discrete inputs on optional MEB 2DI/DO or MEB 4 DI board(s). The inputs are wired
to TB2 of the Digital I/O Bd. Refer to Section 3.4 for MEB 2DI/DO discrete input connections or
Section 3.5 for MEB 4 DI connections. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum)
is provided by the flow computer for each input. When installed in a Class I Division 1 hazardouslocation, all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically
Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for
United States installations, or according to Section 18-066 of the Canadian Electrical Code for
Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have
a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,
Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.
The Digital I/O Board Discrete Input connections are identified as follows:
INPUT SIG GND
DI1 TB2-5 TB2-6
DI2 TB2-7 TB2-8
-
8/9/2019 Autopilot Teory
32/70
Document 1-0485-009 Rev L29
3.3.1 Application #1 - Discrete Input to Non IS Apparatus
Typical Discrete Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Vmax = 12 Vdc
Imax = 250 mACi = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
33/70
Document 1-0485-009 Rev L30
3.3.2 Application #2 - Discrete Input to IS Apparatus/Simple Apparatus
Typical Discrete Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Voc = 8.44 Vdc
Isc = 0.853 mA
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
34/70
Document 1-0485-009 Rev L31
3.4 MEB 2DI/DO DISCRETE INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two discrete inputs on each optional MEB 2DI/DO board.
Up to two boards may be installed in a unit. The inputs are wired to TB2 of the 2 DI/DO Board
using cabling and numbered buttsplices. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum)
is provided by the flow computer for each input. When installed in a Class I Division 1 hazardous
location, all customer wiring to the AutoPILOT must be made according to Article 504 (IntrinsicallySafe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for
United States installations, or according to Section 18-066 of the Canadian Electrical Code for
Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have
a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,
Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.
The 2 DI/DO Board Discrete Input connections are identified as follows:
BOARD NO. INPUT SIG GND CABLE NO.
1 DI1 141 142 Cable 17
1 DI2 143 144 Cable 17
2 DI1 149 150 Cable 18
2 DI2 151 152 Cable 18
A unique address which determines the software configuration must be set using jumpers J1 through
J3 for each 2 DI/DO board installed in the unit. The address jumpers are configured as follows:
Jumper J3 Jumper J2 Jumper J1 BOARD NO.
Not Installed Not Installed Not Installed 1
Not Installed Not Installed Installed 2
-
8/9/2019 Autopilot Teory
35/70
Document 1-0485-009 Rev L32
3.4.1 Application #1 - MEB 2DI/DO Discrete Input to Non IS Apparatus
Typical MEB 2DI/DO Discrete Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
2 DI/DO
SIG-GND
Vmax = 12 Vdc
Imax = 250 mACi = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
36/70
Document 1-0485-009 Rev L33
3.4.2 Application #2 - MEB 2DI/DO Discrete Input to IS/Simple Apparatus
Typical MEB 2DI/DO Discrete Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
2 DI/DO
SIG-GND
Voc = 8.44 Vdc
Isc = 0.853 mA
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0
Li = 0Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
3. Simple Apparatus is a non-energy storing device that will not store or generate more than:
• 1.2 Volts• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
37/70
Document 1-0485-009 Rev L34
3.5 MEB 4 DI DISCRETE INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes four discrete inputs on each optional MEB 4 DI board. Up
to two boards may be installed in a unit. The inputs are wired to TB2 of the MEB 4 DI Board using
cabling and numbered buttsplices. A wetting voltage (nominally +5 Vdc at 0.1 mA maximum) is
provided by the flow computer for each input. When installed in a Class I Division 1 hazardous
location, all customer wiring to the AutoPILOT must be made according to Article 504 (IntrinsicallySafe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for
United States installations, or according to Section 18-066 of the Canadian Electrical Code for
Canadian installations. Multiple circuits that run in the same multiple-conductor cable must have
a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3,
Barrier Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.
The MEB 4 DI Board Discrete Input connections are identified as follows:
BOARD NO. INPUT SIG GND CABLE NO.
1 DI1 205 206 Cable 25
1 DI2 207 208 Cable 25
1 DI3 209 210 Cable 25
1 DI4 211 212 Cable 25
2 DI1 213 214 Cable 26
2 DI2 215 216 Cable 26
2 DI3 217 218 Cable 26
2 DI4 219 220 Cable 26
A unique address which determines the software configuration must be set using jumpers J1 through
J3 for each MEB 4 DI board installed in the unit. The address jumpers are configured as follows:
Jumper J3 Jumper J2 Jumper J1 BOARD NO.
Not Installed Not Installed Not Installed 1
Not Installed Not Installed Installed 2
-
8/9/2019 Autopilot Teory
38/70
Document 1-0485-009 Rev L35
3.5.1 Application #1 - MEB 4 DI Discrete Input to Non IS Apparatus
Typical MEB 4 DI Discrete Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
MEB 4 DI
SIG-GND
Vmax = 12 VdcImax = 250 mA
Ci = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
39/70
Document 1-0485-009 Rev L36
3.5.2 Application #2 - MEB 4 DI Discrete Input to IS/Simple Apparatus
Typical MEB 4 DI Discrete Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
MEB 4 DI
SIG-GND
Voc = 8.44 Vdc
Isc = 0.853 mA
Vmax = 12 Vdc
Imax = 250 mACi = 0
Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
40/70
Document 1-0485-009 Rev L37
3.6 DISCRETE OUTPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two discrete outputs on the optional Digital I/O Board and
up to eight discrete outputs on the optional MEB 2DI/DO or MEB 4 DO board(s). The outputs are
wired to TB2 of the Digital I/O Board. Refer to Section 3.7 for MEB 2DI/DO discrete output
connections or Section 3.8 for MEB 4 DO connections. When installed in a Class I, Division 1,
hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing
methods for United States installations, or according to Section 18-066 of the Canadian Electrical
Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable
must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the
Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the
AutoPILOT.
The Digital I/O Board Discrete Output connections are identified as follows:
OUTPUT SIG GND
DO1 TB2-1 TB2-2
DO2 TB2-3 TB2-4
The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as
current sinks to be detected as a level signal. Since they are active devices, each output requires an
external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s
input power, although a common ground between the flow computer and external power source must
be provided.
-
8/9/2019 Autopilot Teory
41/70
Document 1-0485-009 Rev L38
3.6.1 Application #1 - Discrete Output to Non IS Apparatus
Typical Discrete Output IS Connection to Non IS Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
42/70
Document 1-0485-009 Rev L39
3.6.2 Application #2 - Discrete Output to IS Apparatus
Typical Discrete Output IS Connection to IS Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Voc = 8.44 Vdc
Isc = 12.77 mA
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
43/70
Document 1-0485-009 Rev L40
3.7 MEB 2DI/DO DISCRETE OUTPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two discrete outputs on each optional MEB 2DI/DO board.
Up to two boards may be installed in a unit. The outputs are wired to TB2 of the 2 DI/DO Board
using cabling and numbered buttsplices. When installed in a Class I Division 1 hazardous location,
all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically Safe
Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for UnitedStates installations, or according to Section 18-066 of the Canadian Electrical Code for Canadian
installations. Multiple circuits that run in the same multiple-conductor cable must have a minimum
insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3, Barrier
Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.
The 2 DI/DO Board Discrete Output connections are identified as follows:
BOARD NO. OUTPUT SIG GND CABLE NO.
1 DO1 145 146 Cable 17
1 DO2 147 148 Cable 17
2 DO1 153 154 Cable 18
2 DO2 155 156 Cable 18
The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as
current sinks to be detected as a level signal. Since they are active devices, each output requires an
external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s
input power, although a common ground between the flow computer and external power source mustbe provided.
A unique address which determines the software configuration must be set using jumpers J1 through
J3 for each 2 DI/DO board installed in the unit. The address jumpers are configured as follows:
Jumper J3 Jumper J2 Jumper J1 BOARD NO.
Not Installed Not Installed Not Installed 1
Not Installed Not Installed Installed 2
-
8/9/2019 Autopilot Teory
44/70
Document 1-0485-009 Rev L41
3.7.1 Application #1 - MEB 2DI/DO Discrete Output to Non IS Apparatus
Typical MEB 2DI/DO Discrete Output IS Connection to Non IS Apparatus
ENTITY PARAMETERS
2 DI/DO
SIG-GND
Vmax = 12 Vdc
Imax = 250 mACi = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
45/70
Document 1-0485-009 Rev L42
3.7.2 Application #2 - MEB 2DI/DO Discrete Output to IS Apparatus
Typical MEB 2DI/DO Discrete Output IS Connection to IS Apparatus
ENTITY PARAMETERS
2 DI/DO
SIG-GND
Voc = 8.44 Vdc
Isc = 12.77 mA
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
46/70
Document 1-0485-009 Rev L43
3.8 MEB 4 DO DISCRETE OUTPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes four discrete outputs on each optional MEB 4 DO board.
Up to two boards may be installed in a unit. The outputs are wired to TB2 of the MEB 4 DO Board
using cabling and numbered buttsplices. When installed in a Class I Division 1 hazardous location,
all customer wiring to the AutoPILOT must be made according to Article 504 (Intrinsically Safe
Systems) of the National Electrical Code, NFPA 70, including wiring and sealing methods for UnitedStates installations, or according to Section 18-066 of the Canadian Electrical Code for Canadian
installations. Multiple circuits that run in the same multiple-conductor cable must have a minimum
insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to Section 1.3, Barrier
Information, and Section 1.4, Wiring Information, for proper connection to the AutoPILOT.
The MEB 4 DO Board Discrete Output connections are identified as follows:
BOARD NO. OUTPUT SIG GND CABLE NO.
1 DO1 269 270 Cable 33
1 DO2 271 272 Cable 33
1 DO3 273 274 Cable 33
1 DO4 275 276 Cable 33
2 DO1 277 278 Cable 34
2 DO2 279 280 Cable 34
2 DO3 281 282 Cable 34
2 DO4 283 284 Cable 34
The outputs are not mechanical-contact devices (relays), but are open drain FETs functioning as
current sinks to be detected as a level signal. Since they are active devices, each output requires an
external power source (12 Vdc maximum) which is not necessarily connected to the flow computer’s
input power, although a common ground between the flow computer and external power source must
be provided.
A unique address which determines the software configuration must be set using jumpers J1 through
J3 for each MEB 4 DO board installed in the unit. The address jumpers are configured as follows:
Jumper J3 Jumper J2 Jumper J1 BOARD NO.Not Installed Not Installed Not Installed 1
Not Installed Not Installed Installed 2
-
8/9/2019 Autopilot Teory
47/70
Document 1-0485-009 Rev L44
3.8.1 Application #1 - MEB 4 DO Discrete Output to Non IS Apparatus
Typical MEB 4 DO Discrete Output IS Connection to Non IS Apparatus
ENTITY PARAMETERS
MEB 4 DO
SIG-GND
Vmax = 12 Vdc
Imax = 250 mA
Ci = 0Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
48/70
Document 1-0485-009 Rev L45
3.8.2 Application #2 - MEB 4 DO Discrete Output to IS Apparatus
Typical MEB 4 DO Discrete Output IS Connection to IS Apparatus
ENTITY PARAMETERS
MEB 4 DO
SIG-GND
Voc = 8.44 Vdc
Isc = 12.77 mA
Vmax = 12 VdcImax = 250 mA
Ci = 0
Li = 0
Ca = 1 F
La = 10 H
Notes:
1. Refer to Section 1.4 for Wiring Information.2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
49/70
Document 1-0485-009 Rev L46
3.9 PULSE INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two pulse inputs on each optional AutoPILOT or MEB
Pulse Input Board, and up to two AutoPILOT Pulse Input Boards may be installed in each unit. The
inputs are wired to TB3 of the AutoPILOT Pulse Input Board(s) using cabling and buttsplices. Refer
to Section 3.10 for MEB Pulse Input Board connections. When installed in a Class I, Division 1
hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504
(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing
methods for United States installations, or according to Section 18-066 of the Canadian Electrical
Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable
must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the
Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the
AutoPILOT.
The Pulse Input Board cabling is identified as follows:
BOARD NO. INPUT SIG GND CABLE NO.
1 PL1 1 2 Cable 11 PL2 3 4 Cable 1
2 PL1 5 6 Cable 2
2 PL2 6 8 Cable 2
Each input can be configured for use with different pulse input devices, including a slot sensor, a
dry-contact switch, or a magnetic pulse input. Use switch SW2 (seven-position DIP switch) to
configure PL1 and switch SW1 to configure PL2 on each board. Set the configuration switches
determined by the input type as follows:
INPUT TYPE SWITCH(S) ON
Slot Sensor 2, 3* or 4* and 6
Magnetic 1 and 5
Contact Closure 2, 3* or 4*, 6 and 7
* Positions #3 and #4 provide a nominal +5 Vdc wetting voltage. Position #3 has a nominal
current output of 2.5 mA, with position #4 providing 100 A. Select the desired current
output necessary for the application.
A unique address which determines the software configuration must be set using jumpers JP4 and
JP2 for each Pulse Input board installed in the unit. The Pulse Input address jumpers are configuredas follows:
Jumper JP4 Jumper JP2 BOARD NO.
Not Installed Not Installed 1
Not Installed Installed 2
-
8/9/2019 Autopilot Teory
50/70
Document 1-0485-009 Rev L47
3.9.1 Application #1 - Pulse Input to Non IS Apparatus
Typical Pulse Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Vmax = 16 Vdc
Imax = 250 mA
Ci = 0Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
51/70
Document 1-0485-009 Rev L48
3.9.2 Application #2 - Pulse Input to IS Apparatus/Simple Apparatus
Typical Pulse Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
AutoPILOT
SIG-GND
Voc = 8.44 Vdc
Isc = 5 mA
Vmax = 16 Vdc
Imax = 250 mA
Ci = 0Li = 0
Ca = 1 F
La = 2 mH
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
3. Simple Apparatus is a non-energy storing device that will not store or generate more than:• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
52/70
Document 1-0485-009 Rev L49
3.10 MEB PULSE INPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes two pulse inputs on each optional MEB Pulse Input Board.
Up to two MEB Pulse Input Boards may be installed in each unit. The inputs are wired to TB3 of
the MEB Pulse Input Board(s) using cabling and buttsplices. When installed in a Class I, Division
1 hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504
(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing
methods for United States installations, or according to Section 18-066 of the Canadian Electrical
Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable
must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the
Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the
AutoPILOT.
The MEB Pulse Input Board cabling is identified as follows:
BOARD NO. INPUT SIG GND CABLE NO.
1 PL1 101 102 Cable 5
1 PL2 103 104 Cable 5
2 PL1 105 106 Cable 6
2 PL2 107 108 Cable 6
Each input can be configured for use with different pulse input devices, including a slot sensor, a
dry-contact switch, or a magnetic pulse input. Use switch SW2 (seven-position DIP switch) to
configure PL1 and switch SW1 to configure PL2 on each board. Set the configuration switches
determined by the input type as follows:
INPUT TYPE SWITCH(S) ON
Slot Sensor 2, 3* or 4* and 6
Magnetic 1 and 5
Contact Closure 2, 3* or 4*, 6 and 7
* Positions #3 and #4 provide a nominal +5 Vdc wetting voltage. Position #3 has a nominal
current output of 2.5 mA, with position #4 providing 100 A. Select the desired current output
necessary for the application.
A unique address which determines the software configuration must be set using jumpers JP1 and
JP2 for each MEB Pulse Input board installed in the unit. The address jumpers are configured as
follows:
Jumper JP1 Jumper JP2 BOARD NO.
Not Installed Not Installed 1
Not Installed Installed 2
-
8/9/2019 Autopilot Teory
53/70
Document 1-0485-009 Rev L50
3.10.1 Application #1 - MEB Pulse Input to Non IS Apparatus
Typical MEB Pulse Input IS Connection to Non IS Apparatus
ENTITY PARAMETERS
MEB PI
SIG-GND
Vmax = 16 Vdc
Imax = 250 mACi = 0
Li = 0
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for UnitedStates installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
54/70
Document 1-0485-009 Rev L51
3.10.2 Application #2 - MEB Pulse Input to IS Apparatus/Simple Apparatus
Typical MEB Pulse Input IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
MEB PI
SIG-GND
Voc = 8.44 Vdc
Isc = 5 mA
Vmax = 16 Vdc
Imax = 250 mA
Ci = 0Li = 0
Ca = 1 F
La = 2 mH
Notes:
1. Refer to Section 1.4 for Wiring Information.
2. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
3. Simple Apparatus is a non-energy storing device that will not store or generate more than:
• 1.2 Volts• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
55/70
Document 1-0485-009 Rev L52
3.11 ANALOG OUTPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes connections for the +24 Vdc Input Power and 4-20 mA
Analog Output of the optional Digital/Analog (D/A) Board or 2D/A Board. Power for the D/A
Board must be provided from an external +24 Vdc source through a barrier. Up to two D/A boards
may be installed in each unit. The Input Power is wired to TB1 and the Analog Output is wired to
TB3 of the D/A Board(s) using cabling and buttsplices. Refer to Section 3.12 for 2D/A Boardconnections. When installed in a Class I Division 1 hazardous location, all customer wiring to the
AutoPILOT must be made according to Article 504 (Intrinsically Safe Systems) of the National
Electrical Code, NFPA 70, including wiring and sealing methods for United States installations, or
according to Section 18-066 of the Canadian Electrical Code for Canadian installations. Multiple
circuits that run in the same multiple-conductor cable must have a minimum insulation thickness of
0.01 inch (0.25 mm) on each conductor. Refer to the Section 1.3, Barrier Information, and Section
1.4, Wiring Information, for proper connection to the AutoPILOT.
The Analog Output is configured for +24 Vdc output operation only, which is recommended for
driving total loop resistance of 250 to 750 ohms (including any barrier resistance). The associatedapparatus connected across to the current output must have a 250-ohm minimum resistance to analog
ground.
The D/A Board Analog Output cabling is identified as follows:
SIGNAL AOI GND CABLE NO.
AO1 9 10 Cable 3
Connect the external +24V input power to the D/A Board cabling as follows:
SIGNAL +VIN GND CABLE NO.
EXT PWR 11 12 Cable 3
If a second D/A Board is installed, the cabling is identified as follows:
SIGNAL AOI GND CABLE NO.
AO2 13 14 Cable 4
SIGNAL +VIN GND CABLE NO.
EXT PWR 15 16 Cable 4
A unique address which determines the software configuration must be set using jumpers J4 and J3for each D/A board installed in the unit. The D/A address jumpers are configured as follows:
Jumper J4 Jumper J3 BOARD NO.
Not Installed Not Installed 1
Not Installed Installed 2
-
8/9/2019 Autopilot Teory
56/70
Document 1-0485-009 Rev L53
3.11.1 Application #1 - Analog Output to Non-IS Apparatus
Typical 4-20 mA Analog Output IS Connection to Non IS Apparatus
ENTITY PARAMETERS
AutoPILOT AutoPILOT
+VIN-GND AOI-GND
Vmax = 28 Vdc Vmax = 28 Vdc
Imax = 150 mA Imax = 150 mA
Ci = 0 Ci = 0.1 F
Li = 0 Li = 0
Notes:
1. Power Sources must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
57/70
Document 1-0485-009 Rev L54
3.11.2 Application #2 - Analog Output to IS Apparatus/Simple Apparatus
Typical Analog Output IS Connection to IS Apparatus/Simple Apparatus
ENTITY PARAMETERS
D/A BOARD D/A BOARD
+VIN-GND AOI-GND
Vmax = 28 Vdc Voc = 28 Vdc
Imax = 150 mA Isc = 150 mA
Ci = 0 Vmax = 28 Vdc
Li = 0 Imax = 150 mA
Ci = 0.1 FLi = 0
Ca = 0.3 F
La = 1 mH
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.6. Simple Apparatus is a non-energy storing device that will not store or generate more than:
• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
58/70
Document 1-0485-009 Rev L55
3.12 DUAL ANALOG OUTPUT ENTITY CONNECTIONS
The AutoPILOT’s Entity Listing includes connections for the +24 Vdc Input Power and dual 4-20
mA Analog Outputs of the optional MEB 2 Digital/Analog (2D/A) Board. Power for the 2D/A
Board must be provided from an external +24 Vdc source through a barrier. Up to two 2D/A boards
may be installed in each unit. The Input Power is wired to TB1 and the Analog Outputs are wired
to TB3 of the 2D/A Board(s) using cabling and buttsplices. When installed in a Class I Division 1hazardous location, all customer wiring to the AutoPILOT must be made according to Article 504
(Intrinsically Safe Systems) of the National Electrical Code, NFPA 70, including wiring and sealing
methods for United States installations, or according to Section 18-066 of the Canadian Electrical
Code for Canadian installations. Multiple circuits that run in the same multiple-conductor cable
must have a minimum insulation thickness of 0.01 inch (0.25 mm) on each conductor. Refer to the
Section 1.3, Barrier Information, and Section 1.4, Wiring Information, for proper connection to the
AutoPILOT.
The Analog Outputs are configured for +24 Vdc output operation only, which is recommended for
driving total loop resistance of 250 to 750 ohms (including any barrier resistance). The associatedapparatus connected across each current output must have a 250-ohm minimum resistance to analog
ground. The 2D/A Board Analog Output cabling is identified as follows:
BOARD NO. NAME SIGNAL GND CABLE NO.
1 AOI1 117 118 Cable 9
1 AOI2 119 120 Cable 9
1 +VIN 121 122 Cable 10
2 AOI1 123 124 Cable 112 AOI2 125 126 Cable 11
2 +VIN 127 128 Cable 12
A unique address which determines the software configuration must be set using jumpers J6 and J7
for each 2D/A board installed in the unit. The 2D/A address jumpers are configured as follows:
Jumper J7 Jumper J6 BOARD NO.
Not Installed Not Installed 1
Not Installed Installed 2
-
8/9/2019 Autopilot Teory
59/70
Document 1-0485-009 Rev L56
3.12.1 Application #1 - MEB 2D/A Analog Output to Non-IS Apparatus
Typical MEB 2D/A 4-20 mA Analog Output IS Connection to Non IS Apparatus
ENTITY PARAMETERS
2D/A BOARD 2D/A BOARD
+VIN-GND AOI-GND
Vmax = 28 Vdc Vmax = 28 Vdc
Imax = 150 mA Imax = 150 mA
Ci = 0 Ci = 0.1 F
Li = 0 Li = 0
Notes:
1. Power Sources must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.
-
8/9/2019 Autopilot Teory
60/70
Document 1-0485-009 Rev L57
3.12.2 Application #2 - MEB 2D/A Analog Output to IS/Simple Apparatus
Typical MEB 2D/A Analog Output IS Connection to IS/Simple Apparatus
ENTITY PARAMETERS
2D/A BOARD 2D/A BOARD
+VIN-GND AOI-GND
Vmax = 28 Vdc Voc = 28 Vdc
Imax = 150 mA Isc = 150 mA
Ci = 0 Vmax = 28 Vdc
Li = 0 Imax = 150 mA
Ci = 0.1 FLi = 0
Ca = 0.3 F
La = 1 mH
Notes:
1. Power Source must not generate or use more than 250 Vrms with respect to earth ground.
2. All circuits connected to both sides of the barrier must be segregated from all other wiring.
3. Refer to Section 1.3 for Barrier Information.
4. Refer to Section 1.4 for Wiring Information.
5. Refer to Article 504 (Intrinsically Safe Systems) of the National Electrical Code, for United
States installations, or Section 18 of the Canadian Electrical Code for Canadian installations.6. Simple Apparatus is a non-energy storing device that will not store or generate more than:
• 1.2 Volts
• 100 mA
• 25 mW
• 20 microjoules
-
8/9/2019 Autopilot Teory
61/70
FLOW COMPUTER INSTALLATION
GROUNDING GUIDELINES
ADDENDUM - A
-
8/9/2019 Autopilot Teory
62/70
A-1
GROUNDING PROCEDURES FOR FLOW COMPUTER INSTALLATIONS
A proper ground connection between the flow computer and an earth-ground connection protects the
meter run and the flow computer from natural and man-made electrical transients that may be present
on the system. Several factors determine the grounding configuration of the meter-run installation,
especially the flow-computer mounting and cathodic protection of the pipeline. The flow computermay be mounted to a 2-inch vertical stand-pipe, using two 2-inch pipe clamps or U-bolts and saddle
brackets supplied with the system. The stand-pipe can be mounted directly on the pipeline using a
saddle, or be mounted in the ground. The selected method of mounting the flow computer and the
cathodic protection of the pipeline determines the grounding method to be used.
In all installations, the flow computer system must be grounded to a suitable earth-ground. The flow
computer provides a chassis ground lug located on the lower left side of the flow computer
enclosure. The lug is marked with the ground symbol. The chassis-ground wire must be a minimum
of an 12-AWG stranded wire and as short as possible. The DC resistance from the lug to earth
ground should measure less than one ohm. Install the earth ground as outlined in Articles 250
(Grounding) and 501 (Class I Locations) of the National Electrical Code for United Statesinstallations. For Canadian installations, install the earth ground as outlined in Sections 10 and 18
of the Canadian Electrical Code.
This guideline deals with the following three installation configurations:
Meter runs without cathodic protection
Meter runs with cathodic protection using isolating flanges
Meter runs with cathodic protection using isolating fittings
-
8/9/2019 Autopilot Teory
63/70
A-2
Meter Runs without Cathodic Protection
Flow computer installation on meter runs without cathodic protection can be mounted directly on
the pipeline or on a stand-alone vertical stand-pipe. Refer to Exhibit 1. The ground conductor
connects between the flow computer and the earth ground. The Flow Automation Temperature
Transducer may be grounded through the pipeline. If any pressure/pulse transducers orAutoMITTERS are remotely mounted, connect the chassis ground of these transducers to the
pipeline or earth ground.
Exhibit 1: Meter-Run Installation without Cathodic Protection
-
8/9/2019 Autopilot Teory
64/70
A-3
Meter Runs with Cathodic Protection Using Isolating Flanges
Isolating flanges can be used to electrically isolate the meter run (including the flow-computer
system, the orifice/turbine meters, and AutoMITTERs) from the pipeline with cathodic protection.
The flow computer can be mounted directly on the isolated section of pipeline or on a stand-alone
vertical stand-pipe. Refer to Exhibit 2. The ground conductor connects between the flow computerand the earth ground. Mount a ground strap to the isolated meter-run section and connect it to the
earth ground to protect the Temperature Transducer and any remotely mounted pressure/pulse
transducers. Connect any AutoMITTER grounds directly to earth ground.
Exhibit 2: Meter Run Installation with Isolating Flanges
-
8/9/2019 Autopilot Teory
65/70
A-4
Meter Runs with Cathodic Protection Using Isolating Fittings
Isolating fittings can be used to electrically isolate the meter run from the pipeline with cathodic
protection. Refer to Exhibit 3. Install an isolated fitting or gasket between the following
connections:
all metallic tubing runs between the orifice meter and pressure transducers/manifolds (includingremotely mounted units or AutoMITTERs)
all metallic connections or tubing runs between the flow computer and turbine meter/pulse
transducers
any Temperature Transducer and its pipe-mount, including those connected to AutoMITTERs
Mount the flow computer on a stand-alone vertical stand-pipe. The ground conductor connects
between the flow computer and the earth ground. Connect the cases of the Temperature Transducers,
any remotely mounted pressure transducer cases, or AutoMITTER chassis grounds, to the earth
ground.
Exhibit 3: Meter Run Installation with Isolating Fittings
-
8/9/2019 Autopilot Teory
66/70
RTD PROBE CUTTING
AND WIRING PROCEDURES
ADDENDUM - B
-
8/9/2019 Autopilot Teory
67/70
B-1
1.0 CUTTING THE TEMPERATURE PROBE TO LENGTH
Flow Automation recommends the temperature probe length be measured from the inside bottom
surface of the RTD Housing to the desired depth in the thermowell. This measurement takes into
consideration the combined lengths of the thermowell and mounting hardware when the temperature
probe is installed on the pipeline. When installed in the thermowell, the tip of the probe must notcontact the bottom of the thermowell, to electrically isolate the probe from transient currents. Cut
the temperature probe as follows:
1. Measure or calculate the desired length of the temperature probe.
2. Remove the heat shrink from the top of the temperature probe.
3. Carefully, remove the small plastic sleeve from the top of the temperature probe. Caution: Do
not discard the small plastic sleeve. It protects the wires from the edge of the probe.
4. Measure and mark the body of the temperature probe to the desired length, measuring from thetip of the temperature probe.
5. When using the standard Stark temperature probe, the composite-probe body is pre-scored.
Hand break the probe body at the desired score, then pull the portion to be removed from the
tr