CIRCUIT BREAKER FIRST TRIP TESTING
Michael McCraney
![Page 2: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/2.jpg)
Nameplate
capacity of
12,222
Megawatts
24 generating facilities
4,527 breakers 1,581 substations
![Page 3: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/3.jpg)
Southern Company Transmission System
![Page 4: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/4.jpg)
Some pics to use
![Page 5: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/5.jpg)
What is first trip testing?
Identifying lubrication problems in the mechanism.Identifying mechanical wear.
Identifying control circuit malfunctions.
![Page 6: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/6.jpg)
How does it work?
• The breaker is in service while the load is transferred.• It captures:
– Contact part / make time– DC supply current– DC supply voltage
![Page 7: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/7.jpg)
Test Equipment
![Page 8: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/8.jpg)
Typical Trip Shot
Trip coil plunger strikes latch
Auxiliary contact interrupts DC supply Voltage curve
Trip Coil Current curve
Main contact time
![Page 9: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/9.jpg)
General Times & Measurements
Main Contacts (Trip): < 50 ms or 3 cycle Main Contacts (Close): <200 ms or 12 cycle Voltage Drop: <10% Trip Latch: <5 ms between first & second shots Auxiliary Contacts: <5 ms between first & second shots
![Page 10: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/10.jpg)
What to look for…• Latch
– Increased latch time increases pole separation time.• Aux. contact interruption time
– Any delay in Acon time extends coil energizing time.• Maximum current
– High current could indicate wrong coil size or low current could show increased coil resistance.
• Voltage – Might indicate failing DC supply, insufficient wiring, or loose fuses.
• Main contact times– Could indicate worn mechanism or incorrect electrical wipe.
![Page 11: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/11.jpg)
Past Trip
Present Trip
Latch time difference
ACon
Increased Trip Latch Friction: FK-121-43000-5
![Page 12: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/12.jpg)
Decreased Operating Speed: HVB-121-40000
Second Trip
First Trip
![Page 13: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/13.jpg)
Defective Battery Bank: GM6A
Present First TripPast First Trip
![Page 14: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/14.jpg)
Faulty Auxiliary Contacts: 100-SFMT-40E
Close
Trip
![Page 15: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/15.jpg)
Close Coil Fire:72-PM-31-20
![Page 16: CIRCUIT BREAKER FIRST TRIP TESTING Michael McCraney](https://reader035.vdocument.in/reader035/viewer/2022062313/56649ca65503460f94968bdd/html5/thumbnails/16.jpg)