Download - d07515701_00000000_0en
-
8/9/2019 d07515701_00000000_0en
1/2
751-5701
Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 •D-32385 Minden Tel.: +49(0)571/887-0 E-Mail: [email protected]
10.09.2008 Hansastr. 27 •D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
AS-Interface Slaves IP 20Digital IO Module 4 IN / 4 OUT 24 V / 2 A Single
W751-57014IN/4OUT 24V/2A Single
O4 O3 O2 O1AUX
S-7.F.E
I4 I3 I2 I1ASIFLT
X8 X6
X1 X3X2 X4
X7 X5
NTERFACETERF CE
< _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 9 2 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ >
The 751-5701 AS-Interface Module allows standard sensors and actuators tobe controlled as slave devices on an AS-Interface network.It is an economical solution for the fieldbus-independent and flexibleconnection of sensors and actuators in the field and/or the switchgearcabinet.One module accepts 4 24VDC digital inputs and 4 24VDC digital outputs(2A).All connections to the module, including the AS-Interface connection, theactuator supply connection, and connections to the I/O, are made via sepa-rate WAGO MULTI CONNECTION (MCS) pluggable terminal blocks.
The module provides a shor t circuit proof sensor supply, and a separateactuator supply via the AUX contacts.
Short circuit and overload conditions are reported via LED and over theAS-Interface bus.An onboard programming socket serves for slave configuration.The 751-5701 AS-Interface Module is designed in accordance with theAS-Interface specification V.3.0.
Description Item no. Pack.unit
AS-Interface Module 4IN/4OUT 24V/2A
Single
751-5701 1
Accessories Item no. Pack.unit
Female connector 3-pole 734-103 200
Female connector 4-pole 734-104 100
Self-adhesive marker strips 210-332/350-202 1 card
Height of marker strip 3 mm, 1-16 (240x)
Self-adhesive marker strips 210-332/350-204 1 card
Height of marker strip 3 mm, 17-32 (240x)
Approvals
AS-Interface certificate ZU 72801
r UL 508
Technical Data
Operating voltage (AS-I) 26.5V ... 31.6V
Current consumption (typ.) 35 mA
Isolation of Outputs 500 V system/supply
Current consumption (max.) 50 mA (start-up),
280 mA incl. sensor supply
AS-Interface version 3.0
AS-Interface profile S-7.F.E
Extended address mode no
ID code 7.F.F.E
Operation indicators
Operation LED yellowError LED red
Function LED (ASI /AUX) green
Assignment of data bits
D0 bidirectional I-1/O-1
D1 bidirectional I-2/O-2
D2 bidirectional I-3/O-3
D3 bidirectional I-4/O-4
-
8/9/2019 d07515701_00000000_0en
2/2
AUX+
AUX–
AUX+
AUX–
Load
ASI
FLT
IN+
IN1IN–
IN1
NTERFACETERF CE
OUT1/3
OUT2/4
IN+
IN3IN–
IN3
IN+IN2
IN–
IN2
IN+IN4
IN–
IN4
OUT1OUT–
OUT1
OUT3OUT–
OUT3
OUT2OUT–
OUT2
OUT4OUT–
OUT4
IN+ IN2 IN–
IN+ IN1 IN–
IN+ IN4 IN–
IN+ IN3 IN–
AUX+ AUX+ AUX– AUX–
X1
X2
X3
X4
X5
X6
X7
X8
X5 X7
X6 X8
X3
X4
AS-i –
AS-i +
AUX+
AUX–
ASI+ ASI+ ASI– ASI– OUT3 OUT– OUT1 OUT–
OUT4 OUT– OUT2 OUT–751-5701
Sensor +
Sensor –
for 3-wire sensors
Input configuration:4 x 3 wire inputs
Output configuration:4 x 2 wire outputs2 x AUX, 2 x ASI
Technical Data
Inputs
Sensor supply from AS-Interface
control voltage max. 200 mA, short-circuit proof
Current limitation for all inputs 200 mA
Rated voltage 18 V ... 31V PELV from AS-Interface
Input types IEC 61131 type 1,+ active 7mA current sink (type 2)
Outputs
Output type Electronic outputs PNP
Isolation ASI /AUX
Short-term overload acc. to EN 61131
Watchdog integrated yes
Current carrying capacity per output 2 A*
* inductive loads Utilization category DC 13
Current carrying capacity per module 8 A; 6 A at 55 °C
(derating see manual)
External power supply (AUX) acc. to PELV
Rated voltage 24 V (-15 % ... +20 %)
General Specifications
Operating temperature -25 °C ... +70 °C
Wire connection MULTI CONNECTION SYSTEM male
connectors, WAGO Series 734
Dimensions (mm) W x H x L 42,5 x 55 x 92
Height from upper-edge of DIN 35 rail
Weight 112 gStorage temperature -25 °C ... +85 °C
Relative air humidity (no condensation) 95 % (storage/operation)
Vibration resistance acc. to IEC 60068-2-6
Shock resistance acc. to IEC 60068-2-27
Degree of protection IP20
EMC1-Immunity to inter ference acc. to EN 61000-6-2
EMC1-Emission of inter ference acc. to EN 61000-6-3