48"
MA
X
18" MIN
CEILING
SWITCH, FIRE ALARM PULL STATION, WASHER ANDDRYER RECEPTACLE, INTERCOM, THERMOSTATOR COMMUNICATIONS OUTLET
ABOVE COUNTER RECEPTACLE
RECEPTACLES, TELEPHONE ORDATA OUTLET
COUNTER
FINISHED FLOOR
UNDER COUNTER RECEPTACLE
CO
OR
DIN
AT
EW
/CO
UN
TE
R
108"
SECURITY CAMERA
OR
AS
PR
AC
TIC
AL
TVS
S
S
S
S
S
S
N
N
N
N
N
S
SP
SP
C
N
PC
J
S
FAAP
FB
FACP
DH
H
D
S
FS
TS
RS
B
E
DS
M
CB
X
C
CR
ES
EL
ML
DE
PS
M
3
4
DM
K
MC
L
TO
P
FB
OB
P
T
CB
OS
VC
WAP
E N
L
K
ELECTRICAL SYMBOLS LEGENDRECEPTACLES
COMMUNICATIONS
POWER
NURSE CALL
LIGHTING
FIRE ALARM
SECURITY
GENERAL ELECTRICAL NOTES
SWITCHING
ELECTRICAL ABBREVIATIONSONE LINE DIAGRAM
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
SINGLE-PLEX RECEPTACLE
TELEPHONE
TELEPHONE/DATA
PANEL BOARD
DISCONNECT
FUSED DISCONNECT SWITCH
J-BOX
QUADPLEX RECEPTACLE
TAMPER RESISTANT RECEPTACLE
FLOOR BOX
MOTOR CONNECTION
CEILING FAN
UTILITY METER
QUADPLEX FLOORBOX
CEILING MOUNTED SPEAKER
20A, 120/277V SPST SWITCH
20A, 120/277V 3-WAY SWITCH
20A, 120/277V 4-WAY SWITCH
CABLE TRAY RUN
DIMMER SWITCH
DATA ONLY
TROFFER STYLE RECESSED FIXTURE,
SURFACE MTD FIXTURE
COMBO EMERGENCY/EXIT LIGHT
EMERGENCY FIXTURE
RECESSED/DOWNLIGHT FIXTURE
CLG MTD EMERGENCY FIXTURE
EXIT SIGN (ARROWS INDICATED AS SHOWN)
WALL MOUNTED FIXTURE
PENDANT/SURFACE MTD UP/DOWN LIGHT
SINGLE HEAD FIXTURE/POLE
TWIN HEAD FIXTURE/POLE
BOLLARD/SIDEWALK LIGHT
FLOOD LIGHT
STRIP LIGHT / SUSPENDED DIRECT/INDIRECT
KEY OPERATED SWITCH
MOMENTARY CONTACT SWITCH
LOW VOLTAGE SWITCH
CEILING MTD OCC. SENSOR
PHOTOCELL
CARD READER
TELEVISION OUTLET
NURSECALL - PATIENT
ACCENT FIXTURE
OVERHEAD BOX
PUSH BUTTON STATION AS NOTED
- (1 SWITCHED & 1 UNSWITCHED)
- (ARROW INDICATES DIRECTION)- (SHADING INDICATES # OF FACES)
- (SHADING INDICATES # OF FACES)
BEDSIDE STATION
NURSECALL - EMERGENCYSTATION W/ PULL CORD
NURSECALL - CORRIDOR LIGHT
NURSECALL - DUTY STATION
NURSECALL - MAIN CONTROLLER
NURSECALL - CODE BLUE
FIXTURE ON EMERGENCY POWER
20A, 120V, 2P, 3W GROUNDING
THERMAL OVERLOAD SWITCH
PULL BOX, SIZE AS NOTEDOR AS REQUIRED BY CODE
EMERGENCY FUSEDDISCONNECT SWITCH
WALL MOUNTED SPEAKER
CLOSED CIRCUIT CAMERA (CCC)
MOTOR STARTER/CONTACTOR
TRANSFORMER
COMBINATION MOTOR STARTER
DISTRIBUTION PANEL BOARD
SEPARATE CIRCUIT BREAKER
SPECIAL RECEPTACLE
SURFACE MOUNTED RACEWAYWITH DEVICES AS NOTED
HOME RUN TO PANEL BOARD
abA
FIXTURE TYPE PER SCHEDULE
SWITCH OR RELAY LEGS
1. THIS IS AN OFFICE STANDARD SYMBOL LIST. ALL SYMBOLS DO NOT NECESSARILY
APPEAR IN THIS PROJECT.
2. ALL WORK SHALL BE IN CONFORMANCE WITH NATIONAL, STATE, AND LOCAL
CODES AND/OR ORDINANCES.
3. ELECTRICAL CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER
CONTRACTORS & OWNER-DESIGNATED PERSONNEL.
4. SEE ARCHITECTURAL, MECHANICAL, & PLUMBING DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
5. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. THEY ARE INTENDED TO GIVE
APPROXIMATE LOCATIONS AND OVERALL DESIGN INTENT. THE ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR PRODUCTS, MATERIALS, AND
ELECTRICAL METHODS WHICH HAVE NOT BEEN SHOWN OR INDICATED BUT ARE
REQUIRED FOR A COMPLETE SYSTEM TO THE STANDARDS OF THE INDUSTRY.
6. UPON COMPLETION OF THE ELECTRICAL WORK, THE INSTALLATION SHALL BE
TESTED FOR CONTINUITY, GROUNDS, AND SHORT CIRCUITS. THE ELECTRICAL
CONTRACTOR SHALL DEMONSTRATE PROPER PERFORMANCE OF ALL SYSTEMS.
ALL DEFECTIVE WORK OR MATERIALS SHALL BE REPLACED OR REPAIRED AS
NECESSARY AND RETESTED.
7. ELECTRICAL RACEWAYS THAT PENETRATE FIRE RATED ASSEMBLIES SHALL BE
SLEEVED AND SEALED AS PER THE LOCAL BUILDING CODE.
8. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TEMPORARY ELECTRICAL
SYSTEM FOR THE PROJECT. AT LEAST ONE 120 VOLT SINGLE PHASE RECEPTACLE
SHALL BE PROVIDED FOR EACH 500 SQUARE FEET OF FLOOR SPACE. SUFFICIENT
TEMPORARY LIGHTING SHALL BE PROVIDED TO ALLOW ALL CONTRACTORS TO
COMPLETE THEIR WORK. TEMPORARY ELECTRICAL CIRCUITS SHALL BE
EQUIPPED WITH COMBINATION GROUND FAULT INTERRUPTER AND CIRCUIT
BREAKER PER NEC. TEMPORARY ELECTRICAL SYSTEM SHALL BE INCLUDED IN
THIS BID. USAGE CHARGES SHALL BE PAID FOR BY THE GENERAL CONTRACTOR.
9. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ASSOCIATED COSTS
AND SCHEDULING OF REQUIRED ELECTRICAL INSPECTIONS.
10. MULTIWIRE BRANCH CIRCUITS SHALL NOT BE USED. ALL 120V CIRCUITS SHALL
HAVE A SEPARATE NEUTRAL CONDUCTOR.
11. 20 AMP CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP PER CIRCUIT OVERALL
LENGTH AS FOLLOWS:
TRACK LIGHTING
SPEAKER VOLUME CONTROL
COMMUNICATION DEVICE MTD. 6"ABOVE COUNTER OR HGT SHOWN
COUNTER OR HGT SHOWNRECEPTACLE MTD. 6" ABOVE
GFCI RECEPTACLE
WEATHER-PROOF GFCI RECEPTACLE
PILOT LIGHT
A AMPERES
AB ABOVE COUNTERTOP
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AIC AMPS INTERUPTING CURRENT
ANNC ANNUNICIATOR
ARCH ARCHITECT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
BATT BATTERY
BD BOARD
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CC CONTROLS CONTRACTOR
CKT CIRCUIT
CLG CEILING
COMB COMBINATION STARTER
CONN CONNECT
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
DET DETAIL
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DWG DRAWINGS
EA EACH
EC ELECTRICAL CONTRACTOR
EM EMERGENCY
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EX EXISTING
EXP EXPLOSION PROOF
EXR EXISTING RELOCATED
F FUSE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FT FEET
FUT FUTURE
G , GND GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPT
HORZ HORIZONTAL
HORIZ HORIZONTAL
HP HORSEPOWER
HR HOUR
HTG HEATING
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
IG ISOLATED GROUND
IN INCH
JB JUNCTION BOX
k KILO
LTG LIGHTING
LV LOW VOLTAGE
m MILI
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MFG MANUFACTURER
MH MANHOLE
MIC MICROWAVE OVER
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MTD MOUNTED
MT EMPTY
MTR MOTOR
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NF NON-FUSED
NL NIGHT LIGHT
NO NORMALLY OPENED
OCC OCCUPANCY
OH OVERHEAD
PB PULL BOX
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH PHASE
PNL PANEL
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PWR POWER
REC RECEPTACLE
REF REFRIGERATOR
RM ROOM
SC SPACE
SEC SECONDARY
SHT SHEET
SP SPARE
SPD SURGE PROTECTIVE DEVICE
SPST SINGLE POLE SINGLE THROW
SURF SURFACE
SW SWITCH
TEL TELEPHONE
TERM TERMINAL
TV TELEVISION
TYP TYPICAL
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
V VOLTS
VA VOLT-AMPERES
VAR VOLT-AMPERES REACTIVE
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHER PROOF
W/ WITH
XFMR TRANSFORMER
20A 20 AMP
3W 3 WIRE
20/1 20 AMP, SINGLE PHASE
WIRELESS ACCESS POINT
ELECTRIC STRIKE
ELECTRIC LATCH
MAGNETIC LOCK
DELAYED EGRESS(TIED TO INFANT ABDUCTION SYSTEM OR
DOOR SECURITY POWER SUPPLY(CONNECT TO AUTO OPERATOR CIRCUIT)
ED LOCK DOWN PUSH BUTTON)
SMOKE DETECTOR
HEAT DETECTOR
DUCT DETECTOR
MANUAL PULL STATION 46" A.F.F. CENTER
WALL MTD. AUDIO/VISUAL NOTIFICATION
FIRE ALARM CONTROL PANEL
SPRINKLER FLOW SWITCH
MAGNETIC DOOR HOLD
TAMPER FLOW SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE BARRIER CONNECTION
CEILING MTD. VISUAL NOTIFICATION
CEILING MTD. AUDIO NOTIFICATION
CEILING MTD. AUDIO/VISUAL NOTIFICATION
FIRE ALARM RELAY
82" A.F.F. TO CENTER
WALL MTD. VISUAL ONLY NOTIFICATION82" A.F.F. TO CENTER
WALL MTD. AUDIO ONLY NOTIFICATION82" A.F.F. TO CENTER
120 VOLT 277 VOLT
LENGTH AWG LENGTH AWG
<85' #12 <170' #12
85'-140' #10 170'-280' #10
140'-215' #8 280'-420' #8
>215' #6 >420' #6
FUSED SWITCH
METER
CIRCUIT BREAKER
AUTOMATIC TRANSFER SWITCH
TRANSFORMER
KIRK KEY INTERLOCK
ELECTRICAL EQUIPMENT:PANELBOARD, DISTRIBUTION PANEL,SWITCHBOARD
TYPE AS NOTED
#CIRCUIT NUMBER
SQUARE RECESSED/DOWNLIGHT FIXTURE
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:55
:49
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E000
ELECTRICAL TITLESHEET
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
ELECTRICAL SHEET INDEX
E000 ELECTRICAL TITLE SHEET
E001 SITE LIGHTING PLAN
E101 LEARNING CENTER LIGHTING PLAN
E102 LEARNING CENTER POWER PLAN
E103 LEARNING CENTER FIRE DETECTION PLAN
E104 LEARNING CENTER ROOF AND BELOW GRADE POWER PLAN
E111 GREENHOUSE LIGHTING PLAN
E112 GREENHOUSE POWER PLAN
E113 GREENHOUSE FIRE DETECTION PLAN
E400 ONE-LINE DIAGRAM AND SCHEDULES
E410 ELECTRICAL GREENHOUSE SCHEDULES
E500 ELECTRICAL DETAILS
ED110 GREENHOUSE ELECTRICAL DEMOLITION PLAN
12" = 1'-0"
TYPICAL MOUNTING DETAILS1
NOT FOR BIDDING
E-5.2
1
GREENHOUSE TO BE DEMOLISHED. DEMOLISH ALL RACEWAYS, CONDUIT, RECEPTACLES, LIGHT FIXTURES, CONTROL WIRING WITH RACEWAY, MOTORS, ETC. REMOVE RACEWAY AND CIRCUIT BACK TO SOURCE. ALL LIGHT FIXTURES TO SALVAGED AND OFFERED TO OWNER.
KEYED NOTES
1
A. SEE SHEET E000 FOR SYMBOLS, ABBREVIATIONS, AND PROJECT GENERAL NOTES THAT APPLY.
B. SEE ARCHITECTURAL, MECHANICAL AND GREENHOUSE DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING EQUIPMENT LOCATIONS.
C. THIS DEMOLITION PLAN HAS BEEN PREPARED TO ASSIST THE CONTRACTOR IN DETERMINING THE SCOPE OF DEMOLITION WORK TO BE INCLUDED IN THIS PROJECT. DUE TO CONDITIONS BEYOND OUR CONTROL, THIS DRAWING IS NOT INTENDED TO BE A COMPLETE INDICATION OF ALL DEMOLITION WORK REQUIRED TO COMPLETE THE PROJECT. THE CONTRACTOR SHOULD REVIEW ALL DRAWING AND SPECIFICATIONS, INCLUDING DEMOLITION SHOWN FOR OTHER TRADES, AND BECOME FAMILIAR WITH EXISTING CONDITIONS, IN ORDER TO DETERMINE THE SCOPE OF DEMOLITION WORK..
D. ALL ITEMS REMOVED AND NOT RELOCATED SHALL BE OFFERED TO THE OWNER PRIOR TO DISPOSAL. ITEMS ACCEPTED BY THE OWNER SHALL BE CLEANED PRIOR TO THE OWNER TAKING POSSESSION. ITEMS NOT ACCEPTED BY THE OWNER SHALL BE DISPOSED.
E. ALL ITEMS SHOWN AS REMOVED SHALL HAVE THE ITEM AND CIRCUIT REMOVED BACK TO THE PANELBOARD OR THE LAST ACTIVE DEVICE REMAINING.
F. NO ITEM THAT IS INTENDED TO REMAIN SHALL BE LEFT WITH LOSS OF POWER OR COMMUNICATIONS DUE TO REMOVAL OF OTHER ITEMS CONNECTED TO THE SAME CIRCUIT. EXTEND ALL EXISTING CIRCUITS TO EQUIPMENT/DEVICES THAT ARE TO REMAIN.
GENERAL DEMOLITION NOTES
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/3
0/2
01
8 1
0:0
8:4
0 A
MC
:\U
sers
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
ED110
GREENHOUSEELECTRICAL
DEMOLITION PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET 1/8" = 1'-0"
GREENHOUSE ELECTRICAL DEMOLITION PLAN1
NOT FOR BIDDING
EF
EF
EF
EF
EF
EF
EF
EF
EF
EF
EF
EF
EF
MS
MS
MS
A
B
C
D
E
F
G
H
J
1
2
3
4
5
25'-6
"
25'-6
"
10'-0
"
25'-6
"
25'-6
"
112'
-0"
11'-1
07_
8"
95'-93_
4"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
11'-1
07_
8"
605±
SQFT
(COOL
ZONE)
ORCHID
S%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
PAR
TITIO
N
PARTIT
ION
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
~~~~
~~~```G
UTT
ER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
`T̀RU
SS
PAR
TITIO
N
1840
± SQ
FT
(WAR
M Z
ONE)
ORCHID
S
PARTIT
ION
4'-0
" x 7
'-0"
DOOR (T
YP)
12'-0
"
7'-67_
8"
20'-11_
8"
A6B
B6B
MAN
UALL
Y OPER
ABLE
CURTAIN
PARTIT
ION
INSU
LATE
D M
OTO
RIZ
ED
DAM
PER
S (TYP)
INSU
LATE
D M
OTO
RIZ
ED
SHUTTE
R (T
YP) O
PTIO
N
WIT
H H
INGES
FOG S
YSTEM &
NO
ZZLE (T
YP)
16 x 1
8 ALU
M.
SCREEN
BOX
MS
DS
DS
DS
DS
WS
EF1
EF
EF
EF
EF
EF
EF
EF
EF1
EF
EF
A
B
C
D
E
F
G
H
J
11'-1
07_
8"
95'-93_
4"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
11'-1
07_
8"
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
PAR
TITIO
N
PARTIT
ION
%%
130`
``GUTTER
%%
130`
`T̀RU
SS
PAR
TITIO
N
PARTIT
ION
1
2
3
4
5
25'-6
"
25'-6
"
10'-0
"
25'-6
"
25'-6
"
112'
-0"
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
26'-37_
8"
26'-0
"
F/O C
URB T
O F
/O W
ALL
GREEN
HOUSE
PRODUCTI
ON
SIN
GLE
HANGIN
G
RAIL
DOUBLE
HANGIN
G R
AIL
SIN
GLE
HANGIN
G
RAIL
CORREC
T PARTIT
ION W
ALL
LOCATIO
N T
O A
CCOM
ODATE
CHANG
E IN
PAR
TITIO
N G
LAZI
NG.
DS
DS
DS
DS
EF1
EF
EF
EF
EF
EF
EF
EF
EF
EF
EF1
MS2
MS2
MS2
MS2
MS2
MS2
MS2
MS2
A
B
C
D
E
F
G
H
J
1
2
3
4
5
25'-6
"
25'-6
"
10'-0
"
25'-6
"
25'-6
"
112'
-0"
11'-1
07_
8"
95'-93_
4"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
12'-0
"
11'-1
07_
8"
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
%%
130`
`T̀RU
SS
PAR
TITIO
N
PARTIT
ION
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
``GUTTER
%%
130`
`T̀RU
SS
PAR
TITIO
N
%%
130`
` RID
GE
PARTIT
ION
4'-0
" x 7
'-0"
DOOR (T
YP)
26'-37_
8"
A6B
MAN
UALL
Y OPER
ABLE
CURTAIN
PARTIT
ION
INSU
LATE
D M
OTO
RIZ
ED
DAM
PER
S (TYP)
INSU
LATE
D M
OTO
RIZ
ED
SHUTTE
R (T
YP) O
PTIO
N
WIT
H H
INGES
FOG S
YSTEM &
NO
ZZLE (T
YP)
16 x 1
8 ALU
M.
SCREEN
BOX
26'-0
"
F/O C
URB T
O F
/O W
ALL
48" S
LIDIN
G
DOOR
(INTER
MED
IATE
ZONE)
ORCHID
S
(COOL
ZONE)
ORCHID
S
FERTIL
IZER IN
JECTO
R
(LOCATI
ON T
BD)
CORREC
T PARTIT
ION W
ALL
LOCATIO
N T
O A
CCOM
ODATE
CHANG
E IN
PAR
TITIO
N G
LAZI
NG.
DS
DS
DS
DS
WS
OS OS
OS
OS
L
LL
L
LL
OS
OS
D
OS
LLL LL
LL
LL LL
LL
OS
OS
OS
OS
OS
OS
PSPS PS
OS OS OS
OS
L
L
PS OS
PS
OS
OS
OS
OS
OSLLLL
LL
OS
OS
PS
J1
J1 B2
B2
B2
B2
B2
B2
B2
B2
J2J2
J1
N1 N1 N1
2
1
25
25
4
3
2
INDICATED LIGHTS ON CONTROLS TO BE SWITCHED OFF BETWEEN HOURS OF 11 PM AND 7 AM. ASTRONOMICAL TIME CLOCK TO BE LOCATED IN MECHANICAL ROOM 120. SEE DETAIL ON SHEET E500.
EXISITNG OUTDOOR PHOTOCELL FOR EXTERIOR LIGHTING SHALL CONTROL SWITCHING OF EXTERIOR LIGHT FIXTURES.
STEP LIGHTS, TYPE L, TO BE INSTALLED IN TREADS OF OUTDOOR STAIRWELL.
EXTERIOR LIGHTS FOR SECOND LEVEL SHOWN ON E101 LEARNING CENTER LIGHTING PLAN.
DOWNLIGHTS MOUNTED UNDER OVERHANG OF EAVES.
KEYED NOTES
1
2
3
4
5
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:55
:54
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E001
SITE LIGHTINGPLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/16" = 1'-0"
SITE LIGHTING1
2
TYPE DESCRIPTION Mounting MANUFACTURER MODEL LAMP VOLTS NOTES
B2 4" Square LED Downlight,Black Housing, Wet/Outdoor
Rated
Recessed Indy SDSQ4BBD 3500K, 90 CRI,1250 LM
120 V
J1 Exterior Rectangular WallPack, Black
Wall Surface BEGA 33 242 3000k, 85+ CRI, 120 V
J2 Exterior Rectangular WallPack, Black
Wall Surface BEGA 22 380 3000k, 85+ CRI, 120 V
N1 IN-GROUND FLOOD W.GRILL AND GLARE BEZEL
Recessed (Ground) AURORALIGHT HWL11LIGHTHAUS
2700K, flood 120 V ADJUST ANGLE TO SHINE HIGH ONWATER FEATURE
LIGHT FIXTURE SCHEDULE
NOT FOR BIDDING
OS OS
OS
OS
L
LL
L
LL
OS
LL
L LL
LL
LL
LL L
L
OS
OS
OS
PSPS PS
OS OS OS
OS
OS
L LL L
LL
PS
gb
b g l l
1 1 1
E13
M
N
1 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
33
3
3
33 3
B2 B2
B2 B2
B2 B2
B2 B2
B2 B2
B1 B1 B1
B1
B1
B1
B1 B1 B1
A48
A48
A48
A48E
B1 B1 B1
B1
B1
B1
B1 B1 B1
A48
A48
A48
A48
A48
A48
B1
B1
B1
B1 B1 B1
A48
A48
A48
B1 B1 B1
A48 A48E A48 A48 A48 A48 A48 A48
A48
A48
A48
B1 B1 B1
B1
B1
B1
B1 B1 B1
A48
A48
A48
A48
A48
A48
B1 B1 B1
A48
A48E
A48
B1 B1 B1 B1 B1 B1
A48
A48
A48
B1
B1
B1
B1 B1 B1
A48
A48
A48
A48E A48 A48 A48 A48 A48
A48
A48
A48
B1 B1 B1
A48
A48
A48
B1
B1
B1
B1 B1 B1
A48
A48
A48
A48
B1 B1 B1
A48
A48E
A48
B1
B1
B1
B1 B1 B1
A48 A48E
B1
B1 B1 B1
A48
B1
A48
A48
B1
A48
B1 B1 B1F1 F1
F1 F1
F1
B1
B1
B1
B1
B1
EM1 EM1
G1 G1F1
F1
F1
F1
F1
D1
D1E
D1
D1
B1
B1
B1
A48
A42 A42
A42 A42
E1
E1
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
2 22222222222222222
2 2
2 2
111111
a,b,c
A48
A48
2
A48
A48
A48
n,oi,jd,e
f,g,h k,l,m
a ca c f h f h k m k m
a
a
ab b
c,d
c,d
c,e
c,e c,e c,e c,e c,e c,e c,e c,e
a a a aac,e c,e
a
a
c,d
c,d
b b b
a
a
a
a
a
a
a
a
c,d
c,d
h,j
h,j
b b b g g g g g g g g g
h,i
h,i h,i h,i h,i h,i h,i h,i h,i h,i
h,j
h,j
h,j
h,j
f
f
f
h,i h,if
f
f
f
f
f
f
f
f
f
f
f
f
f
f
k
k
k l l l l l l l l l
A48 A48
k
k
k
k
k
jk
k
k
k
k
k
k
k
k
k
m,n m,n m,n
m,n
m,n m,n
m,n
m,n m,n
m,n
F1
J1
J1
F1
44
4JC
101
DATA
102
FURNITURE STORAGE
103
LINK
100
CIRCULATION
110
CIRCULATION
110
CLASSROOM 3
123
CLASSROOM 2
122
CLASSROOM 1
121
MECH
120
FP
106
TOILET
105
TOILET
104
OUTDOOR CLASSROOM
124
STORAGE
125STORAGE
114
STORAGE
112
STORAGE
116
?
?
B2
5
EM1
A48
A48
A48
a
a
a
B2
B2
B2
B1
A48
B3B3B3B3B3B3B3B3B3B3
C1
C1
C1
B1
m,o
m,o m,o
m,om,o
m,o
4
p
p
p
p,w
p,w
p,w
p,w
qqq
qp,qr r r r r r r r r r r r r r r r r rsssssssss
r,s
F2F2F2
B2
t
t
t
t
u
t
t
t
tt
t
t
t
uu
t uv
A48O
A48O
A48OA48O
A46O A46O
A48O A48O
A48OA48O
A46O A46O
vv
v v
v v v v
v v
v v
6
w
7
OFFICE / WORKROOM
210
DIRECTOR'S OFFICE
213
STORAGE
211
LOBBY
201
TOILET
202
E131 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
BA66
A68
A68
E1
A66
A68
A68
I1
A66
A68
A68
A66
A68
A68
A66
A68
A68
A66
A68
A68
A66
A68
A68
A66
A68
A68
A68A68
A66
A66
A66
A66 A66 A66
F1
F1
EM1
G1
H1
H1
H1
H1
H1 H1
H1H1
E1
E1
n
o
p
p
q
p
qqqqppppppo,p
o,p
n,p n,p n,p n,p n,p n,p n,p n,p
ppppppo,p
J1
J1
8
6
F1
M1E
M1E M1E
M1E
o,p
M1E
A. SEE ARCHITECTURE DRAWINGS FOR LUMINAIRE SCHEDULE AND INSTALLATION DETAILS.
B. INSTALL IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. PROVIDE SUPPORTING DEVICES FOR ADEQUATE SUPPORT OF LUMINAIRES FROM THE STRUCTURE.
C. PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH CIRCUIT, MULTIWIRE BRANCH CIRCUITS SHALL NOT BE UTILIZED.
D. SWITCHES/LIGHTING CONROL DEVICES SHOWN ADJACENT TO EACH OTHER SHALL BE MOUNTED UNDER A COMMON FACEPLATE, UNLESS NOTED OTHERWISE.
E. LUMINAIRES THAT DO NOT INCLUDE A SWITCH LEG OR OTHER CONTROL DESIGNATION SHALL BE CONTROLLED FROM THE SWITCH/LIGHTING CONTROL DEVICE SHOWN WITHIN THE ROOM INCLUDING THE LUMINAIRE.
GENERAL LIGHTING NOTES
INDICATED LIGHTING SHALL BE IN DAYLIGHTING ZONES WITH DIMMABLE CONTROLS ROUTED THROUGH LOW VOLTAGE SWITCH ON WALL - LIGHT FIXTURES IN EACH ZONE AS NOTED BY PHOTOSENSOR SWITCH TAG. SEE DETAIL 1 ON SHEET E500.
LED SLOT LIGHTS (A) TO BE MOUNTED IN COVE NEXT TO GLULAM BEAM WITH BOTTOM OF FIXTURE AT 11' 2" AFF.
BATTERY BACK-UP POWER EMERGENCY LIGHT FIXTURE.
CLASSROOM SENSORS SHALL BE VACANCY TYPE.
OUTDOOR CLASSROOM LIGHT SWITCHES LOCATED HERE, CONTROLLING FIXTURES AS INDICATED BY TAGS.
MOUNT OUTDOOR SLOT FIXTURES TO EITHER SIDE OF GLULAM BEAMS.
COORDINATE MOUNTING HEIGHT OF STRIP LIGHT FIXTURES WITH DUCTWORK AND PIPING.
INDIVIDUAL TASK LIGHTING, INCORPORATED INTO THE OFFICE FURNITURE, SHALL BE LOCATED AT EACH WORKSTATION.
KEYED NOTES
1
2
3
4
5
6
7
8
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:01
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E101
LEARNING CENTERLIGHTING PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
LEARNING CENTER LIGHTING PLAN LEVEL 11
1/8" = 1'-0"
LEARNING CENTER LIGHTING PLAN - LEVEL 22
TYPE DESCRIPTION Mounting EXAMPLE MFR. MODEL LAMP VOLTS NOTES
A42 4" LED Recessed Slot 2' Long,Flush Clear Diffuser
Recessed (Cove) Litecontrol 15L-CC 3500K, 90 CRI, 400LM/FT
120 V
A46O 4" LED Surface Slot 6' Long,Outdoor Rated, Flush Clear
Diffuser
Surface 3500K, 90CRI,400LM/ft
120 V
A48 4" LED Recessed Slot 8'Long,Flush Clear Diffuser
Recessed (Cove) Litecontrol 15L-CC 3500K, 90 CRI, 400LM/FT
120 V
A48E 4" LED Recessed Slot 8' Long,Battery Backup, Flush Clear
Diffuser
Recessed (Cove) Litecontrol 15L-CC 3500K, 90 CRI, 400LM/FT
120 V
A48O 4" LED Surface Slot 8' Long,Outdoor Rated, Flush Clear
Diffuser
Surface 3500K, 90 CRI, 400LM/FT
120 V
A66 6" LED Recessed Slot 6' Long,Flush Clear Diffuser
Recessed Acuity BrandsLighting
SLOT 6 3500K, 90 CRI, 400LM/FT
120 V
A68 6" LED Recessed Slot 8' Long,Flush Clear Diffuser
Recessed Acuity BrandsLighting
SLOT 6 3500K, 90 CRI, 400LM/FT
120 V
B1 4" Square LED Downlight,Black Housing, Clear Reflector
Recessed Indy SDSQ4BBD 3500K, 90 CRI,1250 LM
120 V
B2 4" Square LED Downlight,Black Housing, Wet/Outdoor
Rated
Recessed Indy SDSQ4BBD 3500K, 90 CRI,1250 LM
120 V
B3 4" square LED Downlight,Black Housing, Wall Wash,
Clear Reflector
Recessed Indy SD4SQ 3500K, 90 CRI,1500 LM
120 V
C1 3" Gimbal LED Downlight,White Housing, adjustable
Recessed Lithonia Lighting 3iG 4000K, 90 CRI, 600LM
120 V
D1 2' x 4' LED Troffer, ClearDiffuser
Recessed Lithonia Lighting ALL 3500K, 80 CRI,4000 LM
120 V
D1E 2' x 4' LED Troffer, BatteryBackup, Clear Diffuser
Recessed Lithonia Lighting ALL 3500K, 80 CRI,4000 LM
120 V Integral Battery
E1 1-Sided EXIT Light, LED,Battery Backup
Recessed Lithonia Lighting LRP LED 120 V Battery Backup
EM1 Emergency Lighting Unit,Battery Backup
Wall Surface Lithonia Lighting ELM2 LED 120 V Battery Backup
F1 4' LED Strip Light Surface Lithonia Lighting ZL SERIES 3500K, 5000 LM 120 V
F2 4' LED Surface Basket Light Surface Lithonia Lighting LBL4 3500K, 80 CRI,4000 LM
120 V
G1 LED Wall-MountedRectangular Sconce, Black
Wall Surface BEGA STUDIO LINE 3500K, 80+ CRI, 120 V
I1 4' LED Under Cabinet StripLight w. Integrated Power
Cord
Under CabinetSurface
Lithonia Lighting UCLD 3500K, 80+ CRI,740 LM
120 V Power Cord andIntegral Switch
J1 Exterior Rectangular WallPack, Black
Wall Surface BEGA 33 242 3000k, 85+ CRI, 120 V
J2 Exterior Rectangular WallPack, Black
Wall Surface BEGA 22 380 3000k, 85+ CRI, 120 V
M1E LED Surface, Asymmetric Surface 120 V Integral Battery
LIGHT FIXTURE SCHEDULE
NOT FOR BIDDING
REF
J
J J
J
J
J
J
J
J J J J J
J
J J
J J
OFFICE / WORKROOM
210
STORAGE
211
DIRECTOR'S OFFICE
213LOBBY
201
PATIO
402
RFC-1
RFC-1
RFC-1 RFC-1 RFC-1RFC-1
RFC-1
RFC-1
E131 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
12
4
TOILET
202
5
13
15
MECH
120
CLASSROOM 1
121
FURNITURE STORAGE
103 LINK
100
TOILET
104
TOILET
105
CLASSROOM 2
122
CLASSROOM 3
123OUTDOOR CLASSROOM
124
STORAGE
125
DATA
102
JC
101
CIRCULATION
110
LC-1
RFC-1RFC-1RFC-1RFC-1RFC-1RFC-1RFC-1RFC-1RFC-1
UH-1
EF-1EF-2
E13
M
N
1 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
MS-1
MS-1 MS-1 MS-1 MS-1 MS-1 MS-1 MS-1 MS-1 MS-1
EF-3
2
DR-1
3 3 3
FP
106
UH-2
4
4 4
3
P-4A P-4B
P-5A
5 5
AHU-1
1 11 1
1 1
6
6
5 5
7
88 8 8 8 8 9
9
55
11
10
P-5B
8 8
LC-2
1212
12
A. SEE SHEET E000 FOR SYMBOLS, ABBREVIATIONS, AND PROJECT GENERAL NOTES.
B. SEE ARCHITECTURAL, MECHANICAL AND GREENHOUSE DRAWINGS FOR ADDITIONAL INFORMATION ON EQUIPMENT LOCATIONS.
C. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR CONNECITON INFORMATION. COORDINATE THE LOCATION OF EQUIPMENT CONNECTIONS AND DISCONNECTING MEANS WITH THE EQUIPMENT SUPPLIER.
D. VERIFY ROUGH-IN REQUIREMENTS OF ALL OWNER FURNISHED EQUIPMENT PRIOR TO INSTALLATION.
E. GFCI PROTECTED RECEPTACLES SHALL BE PROVIDED WHERE THE RECEPTACLE IS LOCATED WITHIN 6' OF A SINK AND IN ANY WET LOCATION.
F. MINIMUM HOME RUN CONDUIT SIZE SHALL BE 3/4".
G. PANEL CIRCUIT DESIGNATIONS PROVIDED FOR DESIGN INTENT. EC SHALL VERIFY AND DOCUMENT EXACT CIRCUIT NUMBERS AS CIRCUITED IN THE FIELD.
GENERAL POWER NOTES
PROVIDE INDICATED FLOOR BOX WITH (2) DUPLEX RECEPTACLES, (2) DATA OUTLETS, AND (1) HDMI CONNECTION.
PROVIDE NEMA L-20R TWIST LOCK RECEPTACLES ON WALL FOR TECHNOLOGY RACKS. SEE T200 FOR RACK DETAILS.
MOUNT DUPLEX RECEPETACLES AT 78" FOR A/V MONITORS.
CONTROL SWITCHING FOR THE EXHAUST FANS THROUGH BAS.
CONNECTION FOR MOTION-SENSOR ACTIVATED FAUCET ROUGHED IN UNDER SINK IN CABINET.
RECEPTACLE MOUNTED NEXT TO LIGHT SWITCH AT SAME HEIGHT.
PROVIDE POWER FOR ELECTRONIC LOCK AND DOOR STRIKE FOR CONTROLLED DOOR. SEE TECHNOLOGY DRAWING T300 FOR CONTROLLED DOOR DETAIL.
PROVIDE JUNCTION BOX FOR POWER FOR DOOR ASSIST MOTOR AT HINGE. SEE DOOR ASSIST MANUFACTURER INSTALLATION INSTRUCTIONS FOR WIRING.
PROVIDE JUNCTION BOX FOR POWER FOR ELECTRONIC LATCH AND STRIKE ASSOCIATED WITH CARD READER ACCESS. SEE DETAIL # ON SHEET E500.
PROVIDE JUNCTION BOXES FOR DISCONNECT TO SUMP MOTOR AND SENSOR CONTROLS IN STORMWATER ACCESS HATCH. CONNECT TO CIRCUIT AND CONTROL WIRING RUNS TO SKID IN ROOM 42 - SEE SHEET E112.
PROVIDE 40A CIRCUIT TO CONTROL PANEL FOR LIFT STATION MOTOR. MOTOR LOCATED BELOW GRADE FOR LIFT STATION. SEE CIVIL DRAWINGS FOR DETAILS.
RECEPTACLE TO INCLUDE DUAL USB CHARGING PORTS.
RACEWAYS TO DESK FURNITURE IN OFFICE AREA TO BE RUN BELOW RAISED FLOOR. COORDINATE RECEPTACLE PLACEMENT WITH OFFICE MODULAR FURNITURE.
QUAD RECEPTACLES MOUNTED ON SIDES OF ISLAND AT XX" AFF. COORDINATE BOX PLACEMENT AND CONDUIT ROUTING WITH ARCHITECTURAL DETAIL FOR ISLAND.
LOCATION OF AC DISCONNECT SWITCH FOR PV ARRAY ON ROOF. MOUNT ON WALL AT 48" AFF.
KEYED NOTES
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:05
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E102
LEARNING CENTERPOWER PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
LEARNING CENTER POWER PLAN LEVEL 22
1/8" = 1'-0"
LEARNING CENTER POWER PLAN LEVEL 11
NOT FOR BIDDING
REF
MECH
120
FURNITURE STORAGE
103 LINK
100
TOILET
104
TOILET
105
CLASSROOM 3
123
OUTDOOR CLASSROOM
124
STORAGE
125
DATA
102
JC
101
?
?
CIRCULATION
110
CLASSROOM 2
122
CLASSROOM 1
121
E13
M
N
1 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
OFFICE / WORKROOM
210
STORAGE
211
DIRECTOR'S OFFICE
213
LOBBY
201
E131 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
1. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION DURING CONSTRUCTION. ALL NEW DEVICES SHALL BE ADDED INTO THE EXISTING SYSTEM.
GENERAL FIRE ALARM NOTES
-
-
KEYED NOTES
1
2
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:08
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E103
LEARNING CENTERFIRE DETECTION
PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
LEARNING CENTER FIRE DETECTION PLAN LEVEL 11
1/8" = 1'-0"
LEARNING CENTER FIRE DETECTION PLAN LEVEL 22
NOT FOR BIDDING
1
E131 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
3
2
A. SEE SHEET E000 FOR SYMBOLS, ABBREVIATIONS, AND PROJECT GENERAL NOTES.
B. SEE ARCHITECTURAL, MECHANICAL AND GREENHOUSE DRAWINGS FOR ADDITIONAL INFORMATION ON EQUIPMENT LOCATIONS.
C. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR CONNECITON INFORMATION. COORDINATE THE LOCATION OF EQUIPMENT CONNECTIONS AND DISCONNECTING MEANS WITH THE EQUIPMENT SUPPLIER.
D. VERIFY ROUGH-IN REQUIREMENTS OF ALL OWNER FURNISHED EQUIPMENT PRIOR TO INSTALLATION.
E. GFCI PROTECTED RECEPTACLES SHALL BE PROVIDED WHERE THE RECEPTACLE IS LOCATED WITHIN 6' OF A SINK AND IN ANY WET LOCATION.
F. MINIMUM HOME RUN CONDUIT SIZE SHALL BE 3/4".
G. PANEL CIRCUIT DESIGNATIONS PROVIDED FOR DESIGN INTENT. EC SHALL VERIFY AND DOCUMENT EXACT CIRCUIT NUMBERS AS CIRCUITED IN THE FIELD.
GENERAL POWER NOTES
PHOTOVOLTAIC ARRAY BASIS OF DESIGN: MODULES W. PANEL ARRAYS ON FIXED, NON-BALLASTED RACKING, DC STRING COMBINERS, INVERTERS TO 208 VOLT 3-PHASE. SEE DETAIL ON E500.
MOUNT DC STRING COMBINER, DC DISCONNECT, AND AC INVERTER TO WALL IN THIS LOCATION. SEE ONE LINE ON SHEET E500.
STEP LIGHTS, TYPE L, TO BE INSTALLED IN TREADS OF OUTDOOR STAIRWELL.
CONTROLS FOR SUMP PUMPS MOUNTED ON WALL IN MECH ROOM 120. SEE SHEET P301 FOR SUMP PUMP DETAIL.
MOUNT LIGHT FIXTURE AND SWITCH ON WALL AND GFCI RECEPTACLE IN ELEVATOR PIT.
RAIN WATER CISTERN SUMP PUMP. SEE NOTES ON SHEETS E102 AND E112.
LIFT STATION MOTOR. SEE NOTE ON SHEET E102.
KEYED NOTES
1
2
3
4
5
6
7
M
N
1 2 3 4 5 6 7 8 9 10 11 12 13
D
14
A
F
B
SP-1
SP-2
4
5
6
7
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:09
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E104
LEARNING CENTERROOF AND BELOW
GRADE POWERPLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
LEARNING CENTER ELECTRICAL ROOF PLAN1
LOCATION FOR PHOTOVOLTAIC ARRAY
1/8" = 1'-0"
LEARNING CENTER ELECTRICAL PLAN - BELOW GRADE2
NOT FOR BIDDING
OPENIN
G DIAGRAM
OS
OS OS
?
?
E4 E5 E6E1
G.3
G.4
G.5
G.6
G.2
G.1
G.JG.HG.GG.FG.EG.DG.CG.BG.A
E-5.2
J1
EM1 EM1EM1
EM1 EM1 EM1
K2K2 K2 K2
E1
E1
E1
E1
E1
E1
F1
F1
F1
F1
F1
F1
F1F1
F1F1 F1 F1 F1 F1 F1
1 2
1 2
1 2
1 2
K2 K2K2 K2
K2K2K2K2K2K2K2K2
K2 K2 K2 K2 K2 K2 K2 K2
K2K2K2K2K2K2K2K2
F1
K1
K1
1 3
1 3
1 3
1 3
TROPICAL ZONE
GH02
ORCHIDS (INT. ZONE)
GH03
ORCHIDS (COOL ZONE)
GH04
PRODUCTION ZONE
GH05
CORRIDOR
GH01
HEADHOUSE
31
A. SEE ARCHITECTURE DRAWINGS FOR LUMINAIRE SCHEDULE AND INSTALLATION DETAILS.
B. INSTALL IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. PROVIDE SUPPORTING DEVICES FOR ADEQUATE SUPPORT OF LUMINAIRES FROM THE STRUCTURE.
C. PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH CIRCUIT, MULTIWIRE BRANCH CIRCUITS SHALL NOT BE UTILIZED.
D. SWITCHES/LIGHTING CONROL DEVICES SHOWN ADJACENT TO EACH OTHER SHALL BE MOUNTED UNDER A COMMON FACEPLATE, UNLESS NOTED OTHERWISE.
E. LUMINAIRES THAT DO NOT INCLUDE A SWITCH LEG OR OTHER CONTROL DESIGNATION SHALL BE CONTROLLED FROM THE SWITCH/LIGHTING CONTROL DEVICE SHOWN WITHIN THE ROOM INCLUDING THE LUMINAIRE.
GENERAL LIGHTING NOTES
GROW LIGHTING IN GREENHOUSE SHALL BE POWERED BY POWER CORDS ON ELEVATED RAILS.
GROW LIGHTING IN TROPICAL AND ORCHID AREAS SHALL BE MOUNTED SUSPENDED AT 9'0" AFF.
GROW LIGHTING STRIPS IN PRODUCTION AREA SHALL BE MOUNTED SUSPENDED AT 6'0" AFF.-
KEYED NOTES
1
2
3
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:11
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E111
GREENHOUSELIGHTING PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
GREENHOUSE LIGHTING PLAN1
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION Mounting MANUFACTURER MODEL LAMP VOLTS NOTES
E1 1-Sided EXIT Light, LED,Battery Backup
Recessed Lithonia Lighting LRP LED 120 V Battery Backup
EM1 Emergency Lighting Unit,Battery Backup
Wall Surface Lithonia Lighting ELM2 LED 120 V Battery Backup
F1 4' LED Strip Light Surface Lithonia Lighting ZL SERIES 3500K, 5000 LM 120 V
K1 LED Plant Growth Strip Light,150 cm, 150 deg. distt.
Suspended PL LIGHT HORTILED MULTISERIES
RBFR HBFR198umols/s
120 V
K2 HPS Plant Growth Light Suspended PL LIGHT PLX SERIES HPS, 400W,53000L,
705umols/s
120 V
NOT FOR BIDDING
EF1EF EFEF
EF
EF
EF
EF
EF1EFEF
OPEN
ING DIAGRAM
CORRECT PARTITION WALL LOCATION TO ACCOMODATE CHANGE IN PARTITION GLAZING.
OUTSIDE/KEYSIDE
OUTSIDE/KEYSIDE
OUTSIDE/KEYSIDE
OUTSIDE/KEYSIDE
OPEN
ING DIAGRAM
J
J
GH-PN GH-C
EF-G EF-G EF-G EF-G EF-G EF-G1 EF-G1
HAF
HAFHAF
HAF
HAF
HAF
HAF
HAF
HAF
HAF
HAFHAF
HAF HAFHAF
EF-G
EF-G
EF-G
EF-G
HAF
HAF
HAF
HAF
HAF
HAF
HAF
HAF
HAF
RVM
RVMRVM2
RVM2RVM2
RVM2
RVM
RVM
RVM2
RVM2
RVM2
RVM2
RVM
RVM
RVM
RVM
RVM
RVM
RVM
RVM
EP-1EP-2 EP-3
MS-G MS-G MS-G MS-GMS-G
MS-G
MS-G
MS-G2
MS-G2
MS-G2
MS-G2
MS-G2
MS-G2
MS-G2
MS-G2
MS-G2
MS-G
MS-G
MS-G
MS-G
SM
SM
SM
SM
SM
SM
SM
SM
1
1
1
11
1
1 1
1 1
11
1 1
1
1
E4 E5 E6E1
G.3
G.4
G.5
G.6
G.2
G.1
G.JG.HG.GG.FG.EG.DG.CG.BG.A
CH-1
P-3A
P-3B
WH-2
4
HAF
HAF
DO-G1
FOG PUMP ROOM
38
SIGNS
39
CHEMICAL
40
COOLER
-
HEADHOUSE
31
2
5
4
4
4
TROPICAL ZONE
GH02
ORCHIDS (INT. ZONE)
GH03 ORCHIDS (COOL ZONE)
GH04
CORRIDOR
GH01
PRODUCTION ZONE
GH05
HEADHOUSE
31
BOILER
30
STORAGE
42
GH-T GH-OI GH-OC GH-PS
BM
FP
BMV
BMV
BMV
BMV
EP-4
GH-1
MTS-GH GDS-GH6
P-6
A. SEE SHEET E000 FOR SYMBOLS, ABBREVIATIONS, AND PROJECT GENERAL NOTES.
B. SEE ARCHITECTURAL, MECHANICAL AND GREENHOUSE DRAWINGS FOR ADDITIONAL INFORMATION ON EQUIPMENT LOCATIONS.
C. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR CONNECITON INFORMATION. COORDINATE THE LOCATION OF EQUIPMENT CONNECTIONS AND DISCONNECTING MEANS WITH THE EQUIPMENT SUPPLIER.
D. VERIFY ROUGH-IN REQUIREMENTS OF ALL OWNER FURNISHED EQUIPMENT PRIOR TO INSTALLATION.
E. GFCI PROTECTED RECEPTACLES SHALL BE PROVIDED WHERE THE RECEPTACLE IS LOCATED WITHIN 6' OF A SINK AND IN ANY WET LOCATION.
F. MINIMUM HOME RUN CONDUIT SIZE SHALL BE 3/4".
G. PANEL CIRCUIT DESIGNATIONS PROVIDED FOR DESIGN INTENT. EC SHALL VERIFY AND DOCUMENT EXACT CIRCUIT NUMBERS AS CIRCUITED IN THE FIELD.
GENERAL POWER NOTES
WEATHER-PROOF SWITCHED DUPLEX RECEPTACLES SHALL BE MOUNTED ON OVERHEAD RAILS AT 9' AFF (RECEPTACLES LOCATED FOR GROW LIGHTS).
EC SHALL BE PROVIDE CONDUIT AND WIRE FOR ALL CONTROL WIRING FOR GREENHOUSE CONTROL PANELS. SEE GREENHOUSE DRAWINGS GH6 FOR EQUIPMENT SCHEDULE, GH6-3, GH6-4, GH6-5, AND GH6-6 FOR POWER DIAGRAMS AND CONTROL WIRING DETAILS.
PROVIDE POWER FOR ELECTRONIC LOCK AND DOOR STRIKE FOR CONTROLLED DOOR. SEE TECHNOLOGY DRAWING T300 FOR CONTROLLED DOOR DETAIL.
PROVIDE POWER FOR MOTORIZED DOOR AUTOMATIC OPERATOR AND PUSH BUTTON PADS. SEE DETAIL # ON SHEET E501 AND DOOR DETAILS ON SHEET GH10.
PROVIDE 40A CIRCUIT FOR CONTROL PANEL OF SKID. SEE SKID DETAIL ON XXX SHEET. RUN 1"C. FOR POWER AND 3/4" C. FOR SENSOR WIRING TO ACCESS HATCH FOR STORMWATER IN MECHANICAL ROOM - SEE SHEET E102.
PROVIDE 208V,3PH., 400A MANUAL TRANSFER SWITCH AND GENERATOR DOCKING STATION MOUNTED ON EXTERIOR OF CONNECTING CORRIDOR TO GREENHOUSE AND CONNECTED PER ONE-LINE DIAGRAM.
KEYED NOTES
1
2
3
4
5
6
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:13
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E112
GREENHOUSEPOWER PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
GREENHOUSE POWER PLAN1
NOT FOR BIDDING
?
?
?
?
E4 E5 E6
K
E-A
E-B
E-C
E-D
E1
G.3
G.4
G.5
G.6
G.2
G.1
G.JG.HG.GG.FG.EG.DG.CG.BG.A
E-D.6
E.1
E-D.4
E2E3
E-5.2
1. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION DURING CONSTRUCTION. ALL NEW DEVICES SHALL BE ADDED INTO THE EXISTING SYSTEM.
GENERAL FIRE ALARM NOTES
-
-
KEYED NOTES
1
2
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:14
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E113
GREENHOUSE FIREDETECTION PLAN
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
1/8" = 1'-0"
GREENHOUSE FIRE DETECTION PLAN1
NOT FOR BIDDING
EXISTINGMAINSWITCHBOARD,1200A,208/120V
GH-C120/208V100A, 3PH.,4W
GH-1120/208V400A, 3PH,4W
3#3/0, 1#3 GEA. IN (2) 2" C.
LC-1120/208V225A, 3PH.,4W
3#4/0, 1#4 GIN2-1/2" C.
PV ARRAYINVERTERSAND A/CCOMBINER208V, 3PH.
AC 3-POLEDISCONNECTNEMA 3
ELEV-1120/208V100A, 3PH.,4W
ELEVATOR
DR-1120/208V100A, 3PH.,4W
GH-PS120/208V100A, 3PH.,4W
GH-PN120/208V100A, 3PH.,4W
GH-OC120/208V100A, 3PH.,4W
GH-OI120/208V100A, 3PH.,4W
GH-T120/208V100A, 3PH.,4W
3#3/0, 1#3 GEA. IN (2) 2" C.
L
N E
MTS-1208Y/120V400A, 3PH.NEMA 3RGENERATORDOCKINGSTATION
208V,400A, 3PHNEMA-3R
LC-2120/208V100A, 3PH.,4W
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:15
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E400
ONE-LINE DIAGRAMAND SCHEDULES
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
12" = 1'-0"
ELECTRICAL ONE LINE1
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 LC-2 20 A 3 0 VA 0 VA 3 20 A DR-1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 225 A
Location: MECH 120 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: LC-1
MOTOR SCHEDULE
EQUIPMENTNO. EQUIPMENT DESCRIPTION L
OC
AT
ION
VO
LT
AG
E
PH
AS
E
HP
FL
A CONDUIT & WIRESIZE S
TA
RT
ER
BY
ST
AR
TE
R
DIS
CO
NN
EC
T B
Y
DIS
CO
NN
EC
T T
YP
E
PA
NE
L
NOTE
AHU-1 Air Handler Unit Mech Room 332 208 V 3 59.6 1-1/4" C., (3) #3, (1) #8G.
BM Blackout Motor Greenhouse 208 V 3 1 3/4" C., (3) #12, (1) #12G.
BMV Blackout Motor Vertical Greenhouse 120 V 1 3/8 2.3 3/4" C., (2) #12, (1)#12G.
CH-1 Chiller Outside Greenhouse 208 V 3 51 1-1/4' C., (3) #4, (1) #8G.
DO-1 Door Opener various doors 120 V 1 3/4" C., (3) #12
DO-G1 Door Opener - Greenhouse Greenhouse 120 V 1 3/4" C., (3) #12
EF-1 Exhaust Fan Restroom Toilet 105 120 V 1 3/4" C., (3) #12
EF-2 Exhaust Fan Restroom Toilet 104 120 V 1 3/4" C., (3) #12
EF-3 Exhaust Fan Janitor Closet 101 120 V 1 3/4" C., (3) #12
EF-4 Exhaust Fan Restroom Toilet 202 120 V 1 3/4" C., (3) #12
EF-G Exhaust Fan Greenhouse Greenhouse 208 V 3 1-1/2 6 3/4" C., (3) #12
EF-G1 Exhaust Fan Greenhouse Small Greenhouse 208 V 3 3/4 3.3 3/4" C., (3) #12
EP Evaporative Pad Pump Greenhouse 120 V 1 13 3/4" C., (3) #12
EP-1 Evaporative Pad Pump Small Greenhouse 120 V 1 13 3/4" C., (3) #12
FP Fog Pump ROOM 38 208 V 3 1.5 5.2 3/4" C., (3) #12
HAF Greenhouse Fan Greenhouse 120 V 1 1.3 3/4" C., (2) #12, (1)#12G.
MS-1 Shade Motor Classroom Classrooms 101, 102, 103 120 V 1 3/4" C., (3) #12
MS-G Motor Shutters Greenhouse Greenhouse 120 V 1 3/4" C., (3) #12
MS-G2 Motor Shutters Grenhouse Type2
Greenhouse 120 V 1 3/4" C., (3) #12
P-3 Mechanical Pumps Head House & Mech Room 332 208 V 3 1/2 2 3/4" C., (3) #12
P-4,5 Mechanical Pumps Mech Room 120 208 V 3 2 6.8 3/4" C., (3) #12
P-6 Mechanical Pumps ROOM 38 120 V 1 3/4" C., (3) #12
RFC-1 Recessed Fan Coil Classrooms 101,2,3 & 2nd LvlOffices
24 V 1 3/4" C., (2) #12
RVM Roof Vent Motor Greenhouse 280 V 3 1.7 3/4" C., (3) #12
RVM2 Roof Vent Motor Small Greenhouse 208 V 3 0.9 3/4" C., (3) #12
SM Shade Motor Greenhouse Roof Greenhouse 208 V 3 3/4" C., (3) #12, (1) #12G.
SP-1 Sump Pump Mech Room 332 Sump Basket 120 V 1 3/4" C., (3) #12
SP-2 Sump Pump Mech Room 332 Sump Basket 120 V 1 3/4" C., (3) #12
UH-1 Unit Heater Mech Room 332 120 V 1 3/4" C., (3) #12
UH-2 Unit Heater Mech Room 332 120 V 1 3/4" C., (3) #12
WH-2 Water Heater ROOM 38
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: Wires: 4
Supply From: LC-1 Phases: 3 Mains:
Location: DATA 102 Volts: 120/208 Wye A.I.C. Rating: 10K AIC
Branch Panel: DR-1
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: Wires: 4
Supply From: LC-1 Phases: 3 Mains: 225 A
Location: MECH 120 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: LC-2
NOT FOR BIDDING
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:16
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E410
ELECTRICALGREENHOUSESCHEDULES
RAJMJG
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000 AIC
Branch Panel: GH-OI
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: Not Computed
Total Conn. Current: Not Computed
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps:
Total Load: 0 VA 0 VA 0 VA
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: Surface Wires: Not Computed
Supply From: Phases: Not Computed Mains: 400 A
Location: Volts: A.I.C. Rating: 22K AIC
Branch Panel: GH-1
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: GH-C
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: GH-PN
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000 AIC
Branch Panel: GH-PS
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000 AIC
Branch Panel: GH-T
Notes:
Total Est. Demand - NC: 0 A
Non-Coincident... 0 A
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Top/Bottom Feed
Mounting: SURFACE Wires: 4
Supply From: Phases: 3 Mains: 100 A
Location: CORRIDOR GH01 Volts: 120/208 Wye A.I.C. Rating: 22000 AIC
Branch Panel: GH-OC
NOT FOR BIDDING
S2C-1
DCSTRINGCOMBINER
24 PV MODULES, 7.2 kW2 STRINGS AT 440VDC, 8.18A EA.
DCDISCONNECT
INVERTER9kVA, 208/120V, 3 PHTO BAS
INVERTER AC OUTPUT26.0kVA, 208V, 3 PH
AC DISCONNECT LOCATED ONBUILDING EXTERIOR, 100A/3 POLE
S2C-2
S2C-3
S2C-4
S2B-1
S2B-2
S2B-3
S2B-4
S2A-1
S2A-2
S2A-3
S2A-4
S1C-1
S1C-2
S1C-3
S1C-4
S1B-1
S1B-2
S1B-3
S1B-4
S1A-1
S1A-2
S1A-3
S1A-4
POWER OPTIMIZERTYP. OF 12
OCCUPANCY SENSOR AND 0-10V DIMMING, SINGLE SWITCH LEG
ROOM CONTROLLERLMRC-220
120/277
L - BLACK
N - WHITE
LMDM-101
(a)
'a' RAISE/
'a' LOWER
LIGHTINGLOAD(a)
LIGHTINGLOAD(b)
OCCUPANCY SENSOR, DAYLIGHTING PHOTOCELL, AND 0-10VDIMMING, MULTIPLE SWITCH LEGS
CATEGORY 5E CABLE
ADDITIONAL SENSORSHALL BE DAISY CHAINCONNECTED WITH CAT6 CABLE
OCCUPANCY SENSOR
CATEGORY 5E CABLE
LMDM-101
(b)
'b' RAISE/
'b' LOWER
LOAD
CLASS 2 0-10V CONTROL
CLASS 2 0-10V CONTROL
CATEGORY 5E CABLE
OCCUPANCY CONTROL WITH OVERRIDE OFF SWITCH
POWER PACKN
HOT LOADSWITCH
LIGHTINGLOAD
+24VDC
CONTROL RETURN
CONTROL OUTPUT 24VDC
ADDITIONAL SENSORSHALL BE DAISY CHAINCONNECTED WITH CAT6 CABLE
CONTROL MODE: OCCUPANCY CONTROL
CONTROL MODE: VACANCY CONTROL
CONTROL MODE: VACANCY CONTROL
ADDITIONAL CONTROLLERMAY BE INTERCONNECTEDFOR ADDITIONAL SWITCHLEGS, SEE PLANS.
LOAD
N
HOT
TIME CLOCKCONTROLLER
WITHASTRONOMICAL
TIME CLOCK
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
LIGHTING LOAD
SEE PLANS FOR THEQUANTITY OF LOADS.TIME CLOCK SHALL BEPOWERED FROMCIRCUIT #1. TIMECLOCK SHALL HAVE AMINIMUM OF 4 OUTPUTCIRCUITS.
OUTDOOR LIGHTING CONTROLCONTROL MODE: ASTRONOMICAL TIME CLOCK
POWER PACKN
HOT LOAD
LIGHTINGLOAD
+24VDC
CONTROL RETURN
CONTROL OUTPUT 24VDC
ADDITIONAL SENSORSHALL BE DAISY CHAINCONNECTED WITH CAT6 CABLE
PHOTOSENSOR
0 - 10VDIMMER
0 - 10V
DETAIL NOTES
1. ALL LIGHTING CONTROL CABLING SHALL BE PROVIDED IN ACCORDANCE WITH
SPECIFICATION DIVISION 27.
2. BASIS OF DESIGN IS WATTSTOPPER DLM SERIES DIGITAL LIGHTING CONTROL.
3. SEE FLOOR PLANS FOR OCCUPANCY SENSOR TYPES.
4. SEE PLANS FOR QUANTITY AND LOCATION OF OCCUPANCY SENSORS.
5. CATEGORY COMMUNICATIONS CABLE SHALL BE COMPLETE WITH RJ45
CONNECTORS ON EACH END.
6. FOR SPACES WITH MORE THAN TWO SWITCH LEGS ADDITIONAL ROOM
CONTROLLERS SHALL BE ADDED AND DAISY CHAINED WITH CATEGORY
COMMUNICATIONS CABLE.
11'-0"
6 ROWS OF 4 PANELS TOTAL
ROOF
PV MODULE,TYPICAL
PV RACKING,TYPICAL
TYPICAL
PV MODULE AT 30DEG TILT
POWEROPTIMIZER,
TYPICAL
1. INSTALLING CONTRACTOR SHALL PROVIDE SUBMITTALS OF ALL EQUIPMENT INSTALLED WITHIN THE COMPLETED SYSTEM. SUBMITTALS SHALL INCLUDE PHYSICAL LAYOUT DRAWINGS AND INTERCONNECTION DIAGRAMS.
2. THE PV SYSTEM SHALL INCLUDE RAPID SHUTDOWN MEETING THE 2017 NEC REQUIREMENTS AT A MINIMUM.
3. THE PV SYSTEM SHALL INCLUDE LABELING AS REQUIRED WITHIN THE NEC. LABELING SHALL INCLUDE A PLACARD AT THE ELECTRICAL SERVICE IDENTIFYING THE LOCATION OF INVERTERS AND RAPID SHUTDOWN DEVICES.
4. COORDINATE INSTALLATION OF THE PV SYSTEM WITH THE UTILITY. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, APPLICATIONS, INSPECTIONS, AND ADDITIONAL REQUIREMENTS THE UTILITY MAY HAVE FOR A UTILITY INTERACTIVE SYSTEM.
5. DC AND AC COMBINERS SHALL INCLUDE DISCONNECTING MEANS AND FUSE PROTECTION.
6. SEE ARCHITECTURAL SHEET A105 AND ELECTRICAL ROOF PLAN E104 FOR FURTHER INFORMATION ON PHYSICAL LAYOUT.
GENERAL NOTES
BASIS OF DESIGN:MODULES: SEE SPECIFICATION FOR MANUFACTURERS & MODELS MAX POWER: 285 - 300W OPEN CKT VOLTAGE: 40.1V MAX SHORT CIRCUIT CURRENT: 10.23A MAX MAXIMUM POWER POINT CURRENT: 9.57A DIMENSIONS: 37.8" X65.9" X 1.3"INVERTER: SOLAREDGE 3 PHASE INVERTER 120/2080V GRID, SE9KUS INPUT MAX DC POWER: 12.15kW MAX INPUT VOLTAGE DC+ TO DC-: 500VDC NOMINAL INPUT VOLTAGE DC+ TO DC-: 400VDC MAXIMUM INPUT CURRENT: 26.5ADC OUTPUT RATED AC OUTPUT: 9kVA AC OUTPUT VOLTAGE NOMINAL (L-N/L-L): 120/208V AC FREQUENCY (NOMINAL): 60 HZ MAX CONTINUOUS OUTPUT CURRENT (PER PHASE): 25 RAPID SHUTDOWN : ADD ON KIT COMMUNICATES WITH OPTIMIZERS.POWER OPTIMIZER: SOLAREDGE P320 MPPT OPERATING RANGE: 8-48VDC MAXIMUM DC INPUT CURRENT: 13.75ADC MAXIMUM OUTPUT CURRENT: 15ADC MAX OUTPUT VOLTAGE: 60VDCRACK: SEE SPECIFICATION.
PV ARRAY BASIS OF DESIGN
DRAWN BY: CHECKED BY:
PROJECT NO.
PROJECT PHASE
Dra
win
g 2
016
Co
pyrig
ht
Meyer,
Sch
ere
r &
Ro
ca
stl
e,
Ltd
.
Drawing 2016 Copyright Meyer, Scherer & Rockcastle, Ltd.
ISSUE
DATEMARK DESCRIPTION
NO
T F
OR
C
ON
ST
RU
CT
ION
3/2
9/2
01
8 5
:56
:17
PM
C:\
Users
\Matt
hew
G\D
ocu
me
nts
\M1
0.1
7.0
4-O
BG
E-C
EN
TR
AL
-ME
P.R
17
_m
att
he
wg
.rvt
E500
ELECTRICALDETAILS
CheckerAuthor
70% CONSTRUCTION DOCUMENTS
2017016
Civil Engineer
Vierbicher Associates, Inc.
999 Fourier Drive, Suite 201Madison, WI 53717
608.826.0532 tel
Landscape Architect
Ken Saiki Design, Inc.
303 South Paterson Street, Suite 1Madison, WI 53703
608.251.3600 tel
Structural Engineer, Technology and A/V
IMEG Corp.
1800 Deming Way, Suite 200Middleton, WI 53562
608.223.9600 tel
MEP Engineer
MEP Associates, LLC
860 Blue Gentian Road, Suite 175Eagan, MN 55121
651.379.9120 tel
Olb
rich B
ota
nic
al G
ard
ens
Expansio
n P
hase 1
BP
W P
roje
ct #8162
3330 A
twood A
venue
Madis
on, W
I 53704
Fire Protection Engineer and Code Consultant
Summit Fire Consulting
575 Minnehaha Ave WestSt. Paul, MN 55103
651.251.1880 tel
Greenhouse Design
Rough Brothers, Inc.
5513 Vine StreetCincinnati, OH 45217
513.242.0310 tel
09.09.2017 SCHEMATIC DESIGN SUBMISSION
01.10.2018 DESIGN DEVELOPMENT SUBMISSION
01.17.2018 UDC SUBMISSION
03.31.2018 70% CD PRICING ISSUE
12.08.2017 DD PRICING SET
NTS
PV ARRAY ONE LINE2
NTS
LIGHTING CONTROLS1
NTS
PV SECTION3
NOT FOR BIDDING