Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 1 11.08.10
Energi Savr NodeTM 0-10 V/Softswitch®
The Energi Savr Node family is a group of modular prod-ucts for the control of lighting and other loads. This document describes the following products:
Energi Savr Node unit for 0-10 V (model QSN-4T16-S — 0-10 V Control / Softswitch)
Softswitch Energi Savr Node unit (model QSN-4S16-S — Softswitch)
Features
Energi Savr Node unit.
lights in 4 zones.
levels based on the amount of natural light entering through the windows.
®
Softswitch -time.
® System.
System Example
LUTRON
R
LUTRON
R
120-277 V
120-277 V
4 0-10 V
Channels
(QSN-4T16-S only)
Contact
Closure
Contact
Closure
(16 A Softswitch
120-277 V )
Wireless
Communication
Sensors (up to 4)2
Wired
Sensors
(up to 4)
Sensors (up to 4)
Wired
Sensors
(up to 4)1
Wired Wallstation
Wired
Wallstation
(up to 4)1
® Class 2/
Switch (up to 4)
(by others)
Notes:
1 Up to 4 wired sensors total (of any type).
2 The maximum number of daylight sensors (wired and wireless) that an
Energi Savr Node unit can support is four (1 per zone).
QSMseeTouch® QS
Wallstation
TM
Sensor (up to 10 per QSM)
TM
(up to 10 per QSM)2
® Wireless Controller (up to 10 per QSM)
1
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 2 11.08.10
Specifications
Energi Savr NodeTM
Power
; 220-240 V ; 277 V 50/60 Hz
62.41-1991. Can withstand voltage surges of up to 6000 V and current surges of up to 3000 A
prior to power interruption
when control power feed is lost
Standards
®
Environment
®
used for environmental air”
Terminal Wiring
(2.5 mm2 2)
2 2)2 2)
2 2) — maximum wire run length to each input not to
exceed 150 ft (46 m)2 2)
2 2)
Physical Design and Mounting
Load Types (relay ratings)
Input Default Associations
Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4
Gro
up
1
X
X
X
Switch X
Gro
up
2
X
X
X
Switch X
Gro
up
3
X
X
X
Switch X
Gro
up
4
X
X
X
Switch X
X X X X
X X X X
Softswitch®
(120 V - 277 V )
Softswitch relay is rated for 16 A continuous use
Softswitch circuit eliminates arcing at
mechanical contacts when loads are switched.
-
tive sources.
0–10 V Product Ratings
(QSN-4T16-S only)
supply).
NEC
2
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 3 11.08.10
Specifications (continued)
Occupancy Sensors
®
one or more zones.Lutron occupancy sensors in vacancy mode to au-
tomatically turn the lights off in an area after it becomes vacant.Lutron occupancy sensors can be programmed to auto-matically turn the lights on in area when it becomes oc-cupied and turn the lights off in an area after it becomes vacant.
Lutron occupant sensor.
be programmed independently.Lutron
TM
assigned when associated with a QS Sensor Module (QSM) with manual programming.
Energi Savr Node unit when programming with an Apple
iPod touch or iPhonesection for details.
seeTouch® QS Controls
seeTouchEnergi Savr Node unit scenes or zones.
one or more zones on any Energi Savr Node unit con-
more Energi Savr Node
Table 1: seeTouch QS Wallstation Configurations
# Buttons
Wallstation Function 1 2 3 5 7Zone Toggle ü ü ü ü ü
Scene(toggle)
N/A
IR Wallstation or Receiver Input
control of lighting zones can be connected di-rectly to the Energi Savr Node unit
Lutron -stations to control one or more zones.
Lutron mount sensors to control one or more zones.
receivers can be assigned when associated with a QS Sensor Module (QSM).
with Energi Savr Node unit when programming
with an Apple iPod touch or iPhone
Daylight Sensors
Lutron daylight sensors allow daylight harvesting with programmable effect on light output.
to the Energi Savr Node unit.Lutron
more zones.Lutron Wired
TM
Sensors) can be assigned when associated with a QS Sensor Module (QSM).
Lutron daylight sensors
unit or indirectly (associated with a QSM) cannot exceed four.
with Energi Savr Node unit when programming
with an Apple iPod touch or iPhone
Contact Closure Input (CCI) Default behavior:
Activate scenes using momentary or maintained closures from an external device such as a time-
closure.
closure or solid-state output.-
ly-Closed (NC) operation.
.
other countries.
3
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 4 11.08.10
Specifications (continued)
Emergency Contact Closure Input
to full output when emergency state is detected.
closed (NC). The Energi Savr Node unit is
output and ignore control inputs.
signal is cleared.
closure or solid-state output..
Energi Savr
Node units.
Functionality with GRAFIK Eye® QS
Energi Savr Node unit follows GRAFIK Eye QS
scene activations when associated with the
GRAFIK Eye QS.
Energi Savr Node unit responds to commands
initiated by the GRAFIK Eye QS astronomic time
GRAFIK Eye QS.
Energi Savr Node unit operates in afterhours
mode when associated with a GRAFIK Eye QS
that is in afterhours mode.
Functionality with QSE-IO
Energi Savr Node unit responds to scene com-
switches have been set to either scene selection
-
cupancy sensor mode.
Functionality with QSE-CI-NWK-E
Energi Savr Node unit with touch-
systems and devices.
NEC® Class 2/PELV Dry Contact Switches
NEC
switches can be assigned to turn on and off one
or more zones.
-
tion.
QS Link Limits
Energi Savr Node unit can provide up to 14
zones.
Energi Savr Node unit counts as 1 device
towards the 100 device limit.
Energi Savr Node unit counts as 4 zones
towards the 100 zone limit.
QSM (QS Sensor Module)
TM
Radio Powr Savr
® Wireless Controllers to
control zones on the Energi Savr Node unit.
Energi Savr Node unit with
manual programming.
Energi Savr Node
unit with Apple iPod touch or iPhone program-
Radio Powr Savr
sensors per Energi Savr Node unit via QSM.
Radio Powr Savr
per Energi Savr Node unit via QSM.
Pico Wireless Controllers per
Energi Savr Node unit via QSM.
Pico Wireless Controllers
associated with the QSM should be mounted
information.
other countries.
4
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 5 11.08.10
QS System Limits
maximums for zones and devices.
Softswitch or 0-10 V Energi Savr Node unit can supply 14
power draw units.
Table 2: QS System Limits
QS Device
Description
Zone
Count
Device
Count
Power
Draw Units
(supplied)
Power
Draw Units
(consumed)
Softswitch Energi Savr Node unit (QSN-4S16-S) 4 1 14 0
Energi Savr Node unit for 0-10 V/Softswitch (QSN-4T16-S) 4 1 14 0
EcoSystem Energi Savr Node up to 100 1 30 0
Energi Savr Node 0 1 0 2
0 1 0 3
® 0 0 0 2
Lutron 0 0 0 0.5
Lutron 0 0 0 0.5
® QS 3 1 3 0
4-zone GRAFIK Eye QS 4 1 3 0
6-zone GRAFIK Eye QS 6 1 3 0
6-zone GRAFIK Eye ® 6 1 3 0
8-zone GRAFIK Eye QS with EcoSystem 8 1 3 0
16-zone GRAFIK Eye QS with EcoSystem 16 1 3 0
seeTouch® QS 0 1 0 1
QS contact closure interface up to 5 1 0 3
0 1 0 2
0 0 8 0
*Note:
connected directly to the Energi Savr Node unit.
5
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 6 11.08.10
Programming Options
Manual Programming:
Use buttons on the front of the Energi Savr Node unit.
Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module
HHD Programming
Apple iPod touch or iPhone mobile digital device.
Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple
Energi Savr Node
Apple iPod touch or iPhone.
Energi Savr Node
Energi Savr Node
Lutron recommends that an Energi Savr Node Energi Savr Node -
router.
Apple iPod touch or iPhone can program all Energi Savr Node QS units connected to an Energi Savr Node
® system).
Energi Savr Node Apple iTunes Store
QSM QSM QSM
Energi Savr
Node
Unit
Apple iPod touch or iPhone mobile digital device
Wireless
(by others)
Energi Savr Node
Connection for Energi Savr Node
units
Energi Savr
Node
Unit
Energi Savr
Node
Unit
registered in the U.S. and other countries.
2 Note: Energi Savr Node units are not designed to exist on an open
6
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 7 11.08.10
Programming Options and Features
Manual Programming
HHD Programming:
Apple iPod touch or iPhone mobile
Energi Savr Node units (ESNs)
Connected to 1 QS Link
Not more than 1 Multiple—100 QS devices and 100 zone limits apply
QS Sensor Modules (QSMs)
Connected to 1 QS link
Not more than 1 Multiple—100 QS devices limit applies
Wired Occupancy Sensors
System Limits 4 connected directly to ESN unit
Up to 4 wired to QSM
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wireless Occupancy Sensors
System Limits Associate 10 occupancy sensors to QSM
to control zones on the ESN unit
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wired Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
4 connect directly to the ESN unit
Additional daylight sensors can connect to
the QSM
Maximum of 2 daylight sensors per zone
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
Wireless Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
Associate wireless daylight sensors to the
QSM
Maximum of 2 daylight sensors per zone
Associate up to 10 wireless daylight sensors per QSM
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
7
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 8 11.08.10
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Apple iPod touch or iPhone mobile
Pico® Wireless Controllers
System Limits Associate 10 Pico wireless controllers to
QSM to control zones on the ESN unit
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
IR Receivers and Wallstations
System Limits 4 connect directly to the ESN unit
Up to 4 wired to the QSM
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
NEC® dry contact Switches Inputs
Can be assigned to… Any zone(s) on the connected ESN Any zone(s) on the connected ESN
Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones
Functions
Afterhours Con!guration afterhours timeout- 15 minutes
blink-warn timeout- 5 minutes
Afterhours timeout and blink-warn
timeouts are con!gurable
Emergency Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN zones
Emergency Light level Con!gurable Con!gurable
8
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 9 11.08.10
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Apple iPod touch or iPhone mobile
seeTouch® QS wallstations
Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Scene + off keypads assigned
to…
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Zone toggle keypad buttons
assigned to…
Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link
Change Keypad to Scene or
Zone
Yes Yes
Changing keypads to shade,
panic, !ne tune
No Yes
Zone Configuration Parameters
Load type 0-10, 10-0, or switched 0-10, 10-0, or switched
High-end trim Adjustable Adjustable
Low-end trim Adjustable Adjustable
Absolute minimum level Adjustable Adjustable
Scenes
Available scenes Scenes 1-16 Scenes 1-16
GRAFIK Eye® QS Share scenes, timeclock events, or
afterhours events to ESN units on QS Link
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy
QSE-CI-NWK-E Yes Yes
9
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 10 11.08.10
Mechanical Dimensions
All dimensions shown as inches (mm)
11.25 (285.75)
0.20 (5.16) dia.
1.00 (25.40)
1.22 (30.99)
1.66 (42.16)
1.31 (33.27)
0.88 (22.35)
9.25 (234.95)
7.50 (190.50)
3.16 (80.26)
13.25 (336.55)
use side
Line Voltage Shield
10
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 11 11.08.10
Wiring: QS Link
Terminal 2 NEVER connected
between devices that supply PDUs
Terminal 2 (+24 V)
COM
+24 V
MUX
MUX
COM
MUX
MUX
Energi Savr Node QS unit
Energi Savr Node QS unit
QS
Output
Interface
Wired
QS
Keypad
QSM
QSMQSMWired
QS
Keypad
Wired
QS
Keypad
Wired
QS
Keypad
QS
Output
Interface
QS
Link
power
supply
all 4 terminals
no t
erm
inal 2
no t
erm
inal 2
all 4 terminals
all 4 terminals
Terminal 2 (+24 V)
Terminal 2 (+24 V)
**
QS Link Wiring Rules
*
**
for the specific power supply model being used.
11
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 12 11.08.10
Wiring: NEC® Class 2/PELV Inputs
Sensor
Transmitter
Transmitter
Note: Maximum wire run length to each input not to exceed 150 ft (46 m).
or Wired NEC Class 2/
Switch
Yello
w
NEC
LUTRON
LUTRON
R
(0.5 mm2 to 4.0 mm2)
m)
same inputs as shown in the diagram below.
* Note:
versa.
**
20V
LUTRON
R
12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 13 11.08.10
Wiring: Contact Closure Inputs (CCI and Emerg)
(0.5 mm2 to 4.0 mm2)
m)
13
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 14 11.08.10
Wiring Diagram: Example A – 4 circuits, multiple feeds
Sw
itche
d H
ot (1
B)
Hot
Fee
d (1
A)
Hot
Fee
d (2
A)
Hot
Fee
d (3
A)
Hot
Fee
d (4
A)
Sw
itche
d H
ot (2
B)
Sw
itche
d H
ot (3
B)
Sw
itche
d H
ot (4
B)
Ground Bar
Hot
Hot
Hot
Hot
Neutral
Neutral
Neutral
Neutral
Neutral
Ground
Hot
Neutral
Neutral Wires
Distribution Panel
LOAD
LOAD
LOAD
LOAD
0-10 V Wiring(QSN-4T16-S only)
0-10 V Zones:
(QSN-4T16-S only)
Zone Switching:
120-277 V
0-10 V Wiring (QSN-4T16-S only)2 2)
®
NEC
14
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers
369-241d 15 11.08.10
Wiring Diagram: Example B – 4 circuits, single feed
Zone Switching:
120-277 V
0-10 V Zones:
(QSN-4T16-S only)
Hot
Neutral
Ground
Ground Bar
Neutral Wires
Distribution Panel A
LOAD
LOAD
LOAD
LOAD
0-10 V Wiring(QSN-4T16-S only)
Sw
itche
d H
ot (1
B)
Hot
Fee
d (1
A)
Sw
itche
d H
ot (2
B)
Sw
itche
d H
ot (3
B)
Sw
itche
d H
ot (4
B)
Hot
Neutral
Ground
Distribution Panel B
0-10 V Wiring (QSN-4T16-S only)2 2)
®
NEC
15