CAPEX-efficient Integration of FF-devices into Modbus Architectures ▪ Parallelsupportofupto4FF-H1channels,eachformax.16fielddevices ▪ Fastaccesstoprocessdata ▪ Suitableforuseinhazardousareas ▪ EasyCommissioning:

• OptionalsupportofR.STAHLbus-CarrierSeries 9419andFieldbusPowerSupply9412products (cablingreducedtoaminimum)• Modbusdataimporttowebserverreducing mappingefforts

Device Redundancy ▪ Redundancylinkenablingdeviceredundancy(D-3accordingtoFF-593) ▪ Automaticmirroringofconfigurationdata ▪ Veryfastredundancyswitch-over

Prepared for Plant Asset Management tasks ▪ Visitormodeavoidinginterferencewithnetworkbehavior ▪ Enablingassetmanagementsystems(e.g.Emerson’sAMS)andFieldDeviceTool(FDT)frameapplications(e.g.SMARTVISION,FieldMate,FieldDeviceManager,FieldCare,orPACTware)

All Necessary Tools Included ▪ FFConfigurationToolforconfigurationofdevicesandcycliccommunication ▪ PACTwarefordeviceconfigurationandbasicassetmanagementtasks

FFNetworkIntegrationviaModbusIncludingRedundancy

  ▪ Implementation of FF advantages in Modbus host systems  ▪ Usage as a redundant link

  ▪ Interface for Plant Asset Management applications  ▪ Functionally advanced and easy-to-integrate gateway package

FG-200

FG-200

ENGINEERINGComConf

PAC/PLC/RTU

ETHERNET

Modbus TCP

Modbus TCP / FF HSE

Modbus TCP / FF HSE

Foundation Fieldbus H1

PlantAssetManagementApplication

ModbusOPCServer

Field Barrier

Power Conditioner

Switch

FieldDevices

Page 2: FG-200 - Softing

YourlocalSoftingcontact:

Technicalchangesreserved©SoftingIndustrialAutomationGmbH,FG-200_D_EN_201007_3043,October2020

http://industrial.softing.com

FG-200Technical DataHardware Processor

StatusLEDs(Gateway)StatusLEDs(Fieldbus)

AlteraCycloneVSoCwithdual-coreARMCortex-A9PWR(powersupply),RUN(operation),ERR(error),RDL(redundancylink)FFH1activityperlink

Interfaces and Connectors

Ethernet

FundationFieldbusH1

2*IEEE802.3100BASE-TX/10BASE-T(onlyETH1supported)Connectors:RJ454FFH1links,complianttotype114ofFFphysicallayerprofile(eachlinkcapabletooperateindependentlyasLinkMasterand/orTimeMaster)Transferrate:31.25Kbit/sFieldbusvoltagerange:9VDC...32VDC,preferredvoltage:24VDCCurrentconsumption:10mA/linkConnectors:3-positionscrewconnection,galvanicallyisolated

Physical Properties

Dimensions(HxWxD)WeightPowerSupply

Operating/StorageTemperatureRelativeHumidityCoolingCoatingMountingProtectionClass

100mmx35mmx105mmApprox.0.25kg18VDC...32VDC;SELV/PELVpowersupplymandatory;Typicalinputcurrent:200mA,maximuminputcurrent:1A(allowingforin-rushcurrentatswitch-on)NopowersupplytoFFH1linksthroughFG-200HSE/FFModbus-40°C..+70°C/-40°C..+85°C(seedetailedmountingdescriptioninusermanual)10%...95%,non-condensingConvection,nofanConformalcoatingbasedonANSI/ISA-S71.04G3DINrail35mmIP20

Software ProtocolsRedundancy

FOUNDATIONFieldbusH1,FOUNDATIONFieldbusHSE,ModbusTCPDeviceredundancycomplianttotypeD-3accordingtospecificationFF-593

Conformity / Certifications

CEElectromagneticCompatibility(EMC)Vibration/ShockHazardousLocationCertifications

EN61000-6-2,EN61000-6-4,EN55022LimitClassA,EN55011FCCCRF47,Part15Section15.107and15.109(ClassA),VCCIClassAInformationTechnologyEquipment2002DINEN60068-2-6Vibration/DINEN60068-2-27SchockcULus:Class1,Division2,GroupsA,B,C,D(inpreperation)IECEx:ExnA[ic]IICT4GcATEX:II3GnA[ic]IICT4Gc

Order NumbersGLA-EK-024102 FG-200

ACA-ZZ-020631 RedundancyLink(3-pole),Cable(30cm)forconnectingredundantpairsofFG-200

Scope of DeliveryHardware FG-200

Software FFConfigurationTool,FDTCommDTM,PACTwareonCD-ROM

Documentation QuickStartupGuide,UserManualonCD-ROM