fg-200 - softing

2
CAPEX-efficient Integraon of FF-devices into Modbus Architectures Parallel support of up to 4 FF-H1 channels, each for max. 16 field devices Fast access to process data Suitable for use in hazardous areas Easy Commissioning: Optional support of R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply 9412 products (cabling reduced to a minimum) Modbus data import to web server reducing mapping efforts Device Redundancy Redundancy link enabling device redundancy (D-3 according to FF-593) Automac mirroring of configuraon data Very fast redundancy switch-over Prepared for Plant Asset Management tasks Visitor mode avoiding interference with network behavior Enabling asset management systems (e.g. Emerson’s AMS) and Field Device Tool (FDT) frame applicaons (e.g. SMART VISION, FieldMate, Field Device Manager, FieldCare, or PACTware) All Necessary Tools Included FF Configuraon Tool for configuraon of devices and cyclic communicaon PACTware for device configuraon and basic asset management tasks FF Network Integraon via Modbus Including Redundancy Implementation of FF advantages in Modbus host systems Usage as a redundant link Interface for Plant Asset Management applications Functionally advanced and easy-to-integrate gateway package FG-200 FG-200 ENGINEERING ComConf PAC / PLC / RTU ETHERNET Modbus TCP Modbus TCP / FF HSE Modbus TCP / FF HSE Foundation Fieldbus H1 Plant Asset Management Application Modbus OPC Server Field Barrier Power Conditioner Switch Field Devices

Upload: others

Post on 16-Oct-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FG-200 - Softing

CAPEX-efficient Integration of FF-devices into Modbus Architectures ▪ Parallelsupportofupto4FF-H1channels,eachformax.16fielddevices ▪ Fastaccesstoprocessdata ▪ Suitableforuseinhazardousareas ▪ EasyCommissioning:

• OptionalsupportofR.STAHLbus-CarrierSeries 9419andFieldbusPowerSupply9412products (cablingreducedtoaminimum)• Modbusdataimporttowebserverreducing mappingefforts

Device Redundancy ▪ Redundancylinkenablingdeviceredundancy(D-3accordingtoFF-593) ▪ Automaticmirroringofconfigurationdata ▪ Veryfastredundancyswitch-over

Prepared for Plant Asset Management tasks ▪ Visitormodeavoidinginterferencewithnetworkbehavior ▪ Enablingassetmanagementsystems(e.g.Emerson’sAMS)andFieldDeviceTool(FDT)frameapplications(e.g.SMARTVISION,FieldMate,FieldDeviceManager,FieldCare,orPACTware)

All Necessary Tools Included ▪ FFConfigurationToolforconfigurationofdevicesandcycliccommunication ▪ PACTwarefordeviceconfigurationandbasicassetmanagementtasks

FFNetworkIntegrationviaModbusIncludingRedundancy

  ▪ Implementation of FF advantages in Modbus host systems  ▪ Usage as a redundant link

  ▪ Interface for Plant Asset Management applications  ▪ Functionally advanced and easy-to-integrate gateway package

FG-200

FG-200

ENGINEERINGComConf

PAC/PLC/RTU

ETHERNET

Modbus TCP

Modbus TCP / FF HSE

Modbus TCP / FF HSE

Foundation Fieldbus H1

PlantAssetManagementApplication

ModbusOPCServer

Field Barrier

Power Conditioner

Switch

FieldDevices

Page 2: FG-200 - Softing

YourlocalSoftingcontact:

Technicalchangesreserved©SoftingIndustrialAutomationGmbH,FG-200_D_EN_201007_3043,October2020

http://industrial.softing.com

FG-200Technical DataHardware Processor

StatusLEDs(Gateway)StatusLEDs(Fieldbus)

AlteraCycloneVSoCwithdual-coreARMCortex-A9PWR(powersupply),RUN(operation),ERR(error),RDL(redundancylink)FFH1activityperlink

Interfaces and Connectors

Ethernet

FundationFieldbusH1

2*IEEE802.3100BASE-TX/10BASE-T(onlyETH1supported)Connectors:RJ454FFH1links,complianttotype114ofFFphysicallayerprofile(eachlinkcapabletooperateindependentlyasLinkMasterand/orTimeMaster)Transferrate:31.25Kbit/sFieldbusvoltagerange:9VDC...32VDC,preferredvoltage:24VDCCurrentconsumption:10mA/linkConnectors:3-positionscrewconnection,galvanicallyisolated

Physical Properties

Dimensions(HxWxD)WeightPowerSupply

Operating/StorageTemperatureRelativeHumidityCoolingCoatingMountingProtectionClass

100mmx35mmx105mmApprox.0.25kg18VDC...32VDC;SELV/PELVpowersupplymandatory;Typicalinputcurrent:200mA,maximuminputcurrent:1A(allowingforin-rushcurrentatswitch-on)NopowersupplytoFFH1linksthroughFG-200HSE/FFModbus-40°C..+70°C/-40°C..+85°C(seedetailedmountingdescriptioninusermanual)10%...95%,non-condensingConvection,nofanConformalcoatingbasedonANSI/ISA-S71.04G3DINrail35mmIP20

Software ProtocolsRedundancy

FOUNDATIONFieldbusH1,FOUNDATIONFieldbusHSE,ModbusTCPDeviceredundancycomplianttotypeD-3accordingtospecificationFF-593

Conformity / Certifications

CEElectromagneticCompatibility(EMC)Vibration/ShockHazardousLocationCertifications

EN61000-6-2,EN61000-6-4,EN55022LimitClassA,EN55011FCCCRF47,Part15Section15.107and15.109(ClassA),VCCIClassAInformationTechnologyEquipment2002DINEN60068-2-6Vibration/DINEN60068-2-27SchockcULus:Class1,Division2,GroupsA,B,C,D(inpreperation)IECEx:ExnA[ic]IICT4GcATEX:II3GnA[ic]IICT4Gc

Order NumbersGLA-EK-024102 FG-200

ACA-ZZ-020631 RedundancyLink(3-pole),Cable(30cm)forconnectingredundantpairsofFG-200

Scope of DeliveryHardware FG-200

Software FFConfigurationTool,FDTCommDTM,PACTwareonCD-ROM

Documentation QuickStartupGuide,UserManualonCD-ROM