G30 RelayApplication & Configuration
Craig WesterGE Multilin
![Page 2: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/2.jpg)
2
G30 is Member of
UR Relay Family
imagination at work
g
![Page 3: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/3.jpg)
3
The UR FamilyA Common Hardware/Software Architecture
Modular Construction Reduces Part Inventory
![Page 4: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/4.jpg)
4
Generation Protection G30 – Generator & Transformer Protection G60 – Generator Protection
Transformer Protection T35 – Transformer Protection (6 winding)T60 – Transformer Protection
Transmission Line Protection L60 – Line Phase Comparison Protection L90 – Line Differential Protection D30 – Backup Distance ProtectionD60 – Line Distance Protection (pilot schemes)
Bus ProtectionB30 – Bus Differential Protection (6 Circuits)B90 – Bus Differential System (8 to 24 Circuits)F35+HID – High Impedance Bus DifferentialF35 – Bus Overcurrent Protection
Feeder Protection F35 – Feeder Protection (1-6 feeders)F60 – Feeder Protection (with Hi-Z)
Capacitor Bank Protection C70 – Capacitor Bank Protection & Control
Motor Protection M60 – Motor Protection
Network Protection N60 – Network Protection and Synchrophasors (4 PMU’s)
Controllers C30 – ControllerC60 – Breaker Management
Covering all Protection and Control ApplicationsThe Universal Relay Family
![Page 5: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/5.jpg)
5
Topics Overview of application
ANSI functions in relay needed for application Modules needed Creating the part number Wiring to modules
• Terminals • Voltage monitoring • Current monitoring
Programming the relay • Protection summary • Trip Bus • FlexLogic • Viewpoint Engineer
![Page 6: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/6.jpg)
6
Overview of Application
imagination at work
g
![Page 7: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/7.jpg)
7
ANSI Functions within G30
![Page 8: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/8.jpg)
8
Single-Line DiagramWith Step-Up Transformer
Main Generator Protection uses Transformer High-side CTs & PTs
1
3
2 or 3
1, 2 or 3
3
1
87GT
87RGF
Y
![Page 9: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/9.jpg)
9
Single-Line DiagramNo Step-up Transformer
Main Generator Protection Assigned to Generator Terminal CTs & PTs
87GT
87RGF1
3
2 or 3
1, 2 or 33
![Page 10: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/10.jpg)
10
Modules Needed & Model Number
Selection
imagination at work
g
![Page 11: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/11.jpg)
Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXXH
ori
zon
tal M
od
el N
um
ber
Str
uctu
re
![Page 12: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/12.jpg)
Model: G30-N00-VLH-F8L-H6P-M8L-PXXV
ert
ical M
od
el N
um
ber
Str
uctu
re
![Page 13: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/13.jpg)
13
Module Details & Wiring
imagination at work
g
![Page 14: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/14.jpg)
14
Backlit Keypad
16 Large User Programmable Pushbuttons
3 Small User Programmable Pushbuttons
Status LED for Each Pushbutton
Eliminates Existing Panel Control Switches
Local Control/Display (Type L Faceplate)
![Page 15: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/15.jpg)
15
4CT (F1)4CT (M1)
Example Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXX
Rear Terminals of Horizontal G30 Relay
I/O(6P)
RTD(5C)
4VT (M5) 4VT (F5)
CPU PwrSupply
![Page 16: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/16.jpg)
16
Example Model: G30-N00-VLH-F8L-H6P-M8L-PXX
Rear Terminals of Vertical G30 Relay
![Page 17: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/17.jpg)
17
Pow
er
Su
pp
lyPower Supply
•Two Ranges •19-60 VDC (L)•88-300 VDC / 88-288 VAC (H) •Battery for Memory Backup
Power Supply Module
Control Power:B6b-B6a 24VdcB5b-B6a 125Vdc
GroundsB8a, B8b, Chassis Gnd
![Page 18: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/18.jpg)
18
CPU C
PU
Main
Pro
cessor
•High-speed 32-Bit RISC CPU> 50 MIPS, up to 120 MIPS
(MIPS - Million Instructions per Second)
FLASH memory •Easy firmware upgrades
•High-Speed Comms support
•10/100 Mbps Ethernet LAN•RS485
•IRIG-B Input•Capacitor Memory Backup
CPU Module
Ethernet Port
![Page 19: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/19.jpg)
19
• Internet/Intranet Ready - IP AddressInternet/Intranet Ready - IP Address
• Simple Network Time Protocol (SNTP) for Real Time Clock Simple Network Time Protocol (SNTP) for Real Time Clock SynchronizationSynchronization
• Modbus RTU protocolModbus RTU protocol– Standard Front Port: RS232 (point-to-point)Standard Front Port: RS232 (point-to-point)– Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or
10/100BaseF (Fiber Optic) 10/100BaseF (Fiber Optic) – Available over TCP/IPAvailable over TCP/IP
• DNP 3.0 Protocol (CERTIFIED)DNP 3.0 Protocol (CERTIFIED)– Rear Ports: RS485 up to 115kbps and 10/100BaseT/F EthernetRear Ports: RS485 up to 115kbps and 10/100BaseT/F Ethernet
• IEC61850 protocol (optional)IEC61850 protocol (optional)– Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) – Available Only on CPUs with Ethernet Port(s)Available Only on CPUs with Ethernet Port(s)
• HTML View Access with Netscape or Internet ExplorerHTML View Access with Netscape or Internet Explorer– Ethernet ConnectionsEthernet Connections
• Internet/Intranet Ready - IP AddressInternet/Intranet Ready - IP Address
• Simple Network Time Protocol (SNTP) for Real Time Clock Simple Network Time Protocol (SNTP) for Real Time Clock SynchronizationSynchronization
• Modbus RTU protocolModbus RTU protocol– Standard Front Port: RS232 (point-to-point)Standard Front Port: RS232 (point-to-point)– Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or
10/100BaseF (Fiber Optic) 10/100BaseF (Fiber Optic) – Available over TCP/IPAvailable over TCP/IP
• DNP 3.0 Protocol (CERTIFIED)DNP 3.0 Protocol (CERTIFIED)– Rear Ports: RS485 up to 115kbps and 10/100BaseT/F EthernetRear Ports: RS485 up to 115kbps and 10/100BaseT/F Ethernet
• IEC61850 protocol (optional)IEC61850 protocol (optional)– Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) – Available Only on CPUs with Ethernet Port(s)Available Only on CPUs with Ethernet Port(s)
• HTML View Access with Netscape or Internet ExplorerHTML View Access with Netscape or Internet Explorer– Ethernet ConnectionsEthernet Connections
Communication Protocols
DNP, Modbus, IEC61850 protocols simultaneously available on Ethernet port
![Page 20: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/20.jpg)
20
DSP + CT/VTD
SP
& M
ag
neti
cs
DS
P p
rocessor
+ C
T/V
Ts
•Modular CT/VT configurations • up to 8 CT/VTs
•High-speed digital sampling>16 Bit A/D converter> 64 samples / cycle
•High-speed 16-Bit DSP> 32 MIPS, up to 80 MIPS
•“Sources” ConceptUser Selects CT/VT Input forProtection Element
CT ShortingClip
CT/VT Modules (Type 8L)F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
CT ShortingClip
![Page 21: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/21.jpg)
21
Terminal Blocks
![Page 22: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/22.jpg)
22
•Control outputs •Solid State•Electromechanical - multiple types•Fast activation (< 4ms)
•Status inputs•Dry and Wet contacts•18 - 300 VDC•Fast detection speeds (0.5-16ms Selectable)
DIG
ITA
L I
/OS
tatu
s I
np
uts
/ C
on
trol O
utp
uts
Digital I/O • Many Module ChoicesMany Module Choices
– 2 Form A, 2 Form C and 8 Inputs2 Form A, 2 Form C and 8 Inputs– 2 Form A, 4 Form C and 4 Inputs2 Form A, 4 Form C and 4 Inputs– 8 Form C Outputs8 Form C Outputs– 4 Form C, 8 Inputs4 Form C, 8 Inputs– 8 Fast Form C 8 Fast Form C – 6 Form A, 4 Inputs6 Form A, 4 Inputs– 16 Inputs16 Inputs– 4 Form A, 8 Inputs (6N)4 Form A, 8 Inputs (6N)– 4 Form C, 8 Inputs (6P)4 Form C, 8 Inputs (6P)– 4 Form C, 4 Fast Form C4 Form C, 4 Fast Form C– 14 Latching Relays14 Latching Relays
• Transducer I/OTransducer I/O– 8 dcmA8 dcmA– 8 RTD inputs (5C)8 RTD inputs (5C)– 4 dcmA & 4 RTD4 dcmA & 4 RTD
• Digital Inputs FlexibilityDigital Inputs Flexibility– Dry or Wet Type (48 Vdc provided by Dry or Wet Type (48 Vdc provided by
relay)relay)– Minimum Pickup Value Software Minimum Pickup Value Software
SettingSetting– 17, 33, 84 or 166 Vdc17, 33, 84 or 166 Vdc
• Digital Output MonitoringDigital Output Monitoring– Current and Voltage Monitoring of Trip Current and Voltage Monitoring of Trip
& Close Circuits& Close Circuits
• Many Module ChoicesMany Module Choices– 2 Form A, 2 Form C and 8 Inputs2 Form A, 2 Form C and 8 Inputs– 2 Form A, 4 Form C and 4 Inputs2 Form A, 4 Form C and 4 Inputs– 8 Form C Outputs8 Form C Outputs– 4 Form C, 8 Inputs4 Form C, 8 Inputs– 8 Fast Form C 8 Fast Form C – 6 Form A, 4 Inputs6 Form A, 4 Inputs– 16 Inputs16 Inputs– 4 Form A, 8 Inputs (6N)4 Form A, 8 Inputs (6N)– 4 Form C, 8 Inputs (6P)4 Form C, 8 Inputs (6P)– 4 Form C, 4 Fast Form C4 Form C, 4 Fast Form C– 14 Latching Relays14 Latching Relays
• Transducer I/OTransducer I/O– 8 dcmA8 dcmA– 8 RTD inputs (5C)8 RTD inputs (5C)– 4 dcmA & 4 RTD4 dcmA & 4 RTD
• Digital Inputs FlexibilityDigital Inputs Flexibility– Dry or Wet Type (48 Vdc provided by Dry or Wet Type (48 Vdc provided by
relay)relay)– Minimum Pickup Value Software Minimum Pickup Value Software
SettingSetting– 17, 33, 84 or 166 Vdc17, 33, 84 or 166 Vdc
• Digital Output MonitoringDigital Output Monitoring– Current and Voltage Monitoring of Trip Current and Voltage Monitoring of Trip
& Close Circuits& Close Circuits
Input/Output Modules
![Page 23: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/23.jpg)
23
Input/Output Module (6P module in “H” slot)
H
HH
HH
H
H
HH
HHH
HH
HHH
HH
HHH
HH
H
H
H
H
H
H
H
HH
HH
![Page 24: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/24.jpg)
24
Input/Output Module (6N module in “H” slot)
H
HH
HH
H
HH
HH
H
H
HH
HHH
HH
HHHH
H
HH
HH
H
HH
HH
H
H
H
H
![Page 25: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/25.jpg)
25
Contact Input Wiring
Contact Inputs are polarity
sensitive
![Page 26: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/26.jpg)
26
• Transducer type inputs & outputs
•dcmA•RTD
Analog I/OA
NA
LO
G I
/OA
nalo
g T
ran
sd
ucer
I/O
dcMA or RTD Inputs/Outputs
26
PPPPP
PPPPP
PPPPP
PPPPP
P
RTD Inputs (Type 5C)
![Page 27: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/27.jpg)
27
4CT (F1)4CT (M1)
Example Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXX
Rear Terminals of G30 Relay
I/O(6P)
RTD(5C)
4VT (M5) 4VT (F5)
CPU PwrSupply
![Page 28: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/28.jpg)
28
Metering & Monitoring
• Current (Phase, Neutral and Ground) - [mag & ang]Current (Phase, Neutral and Ground) - [mag & ang]– Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating
(whichever is greater)(whichever is greater)• Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]
– Accuracy: ± 0.25% of reading from 10 to 208 VAccuracy: ± 0.25% of reading from 10 to 208 V• Sequence Components of I & VSequence Components of I & V
– I0, I1, I2, V0, V1, V2I0, I1, I2, V0, V1, V2
• Apparent Power (VA)Apparent Power (VA) - 1ph & 3ph - 1ph & 3ph– Accuracy: ± 1.0% of readingAccuracy: ± 1.0% of reading
• Real Power (Watts) - 1ph & 3phReal Power (Watts) - 1ph & 3ph– Accuracy: ± 1% of readingAccuracy: ± 1% of reading
• Reactive Power (Vars) - 1ph & 3phReactive Power (Vars) - 1ph & 3ph– Accuracy: ± 1%Accuracy: ± 1%
• Power Factor - 1ph & 3phPower Factor - 1ph & 3ph– Accuracy: ± 0.02Accuracy: ± 0.02
• Energy (Pos & Neg Wh, Varh) - 3phEnergy (Pos & Neg Wh, Varh) - 3ph
• FrequencyFrequency
• Differential CurrentsDifferential Currents
• Synchrocheck (V, Hz, Mag)Synchrocheck (V, Hz, Mag)
• Phasor DiagramsPhasor Diagrams
• Current (Phase, Neutral and Ground) - [mag & ang]Current (Phase, Neutral and Ground) - [mag & ang]– Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating
(whichever is greater)(whichever is greater)• Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]
– Accuracy: ± 0.25% of reading from 10 to 208 VAccuracy: ± 0.25% of reading from 10 to 208 V• Sequence Components of I & VSequence Components of I & V
– I0, I1, I2, V0, V1, V2I0, I1, I2, V0, V1, V2
• Apparent Power (VA)Apparent Power (VA) - 1ph & 3ph - 1ph & 3ph– Accuracy: ± 1.0% of readingAccuracy: ± 1.0% of reading
• Real Power (Watts) - 1ph & 3phReal Power (Watts) - 1ph & 3ph– Accuracy: ± 1% of readingAccuracy: ± 1% of reading
• Reactive Power (Vars) - 1ph & 3phReactive Power (Vars) - 1ph & 3ph– Accuracy: ± 1%Accuracy: ± 1%
• Power Factor - 1ph & 3phPower Factor - 1ph & 3ph– Accuracy: ± 0.02Accuracy: ± 0.02
• Energy (Pos & Neg Wh, Varh) - 3phEnergy (Pos & Neg Wh, Varh) - 3ph
• FrequencyFrequency
• Differential CurrentsDifferential Currents
• Synchrocheck (V, Hz, Mag)Synchrocheck (V, Hz, Mag)
• Phasor DiagramsPhasor Diagrams
![Page 29: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/29.jpg)
29
Large LED’sLarge Label Text
Easy Labeling
Programmable LEDs and Labels
![Page 30: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/30.jpg)
30
Programming Relay
imagination at work
g
![Page 31: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/31.jpg)
31
GE Multilin Software
•EnerVista UR Setup• Manages communications to all relays• Retrieves event logs, fault reports,
oscillography• Settings file firmware management and
firmware management• Lock configurations for repeatability
•ViewPoint Engineer• FlexLogic Editor to create logic using a
graphical interface• FlexLogic Monitor for real-time
debugging/testing/commissioning
![Page 32: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/32.jpg)
32
Functional Diagram
IEC61850 GSSEIEC61850 GOOSE
CT & VT Inputs
Remote InputsIEC61850 GSSEIEC61850 GOOSE
![Page 33: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/33.jpg)
33
Settings Configuration:• Communicate with multiple relays at the same time• Configure settings both On-Line and Offline• Copy and paste settings• Duplicate settings files• Easy to navigate menu tree• Quick connect communications• Common look and feel for all products
Metering:• Status of all inputs and outputs• Real-time metering with phasor diagrams• Analyzing of current and voltage harmonics• Viewing of relay front panel
Troubleshooting & Maintenance:• Analyzing of event records• Powerful oscillography COMTRADE viewer• Real time data logging and fault reports• Compare relay settings with setting file• Upgrade firmware
EnerVista: Setup Software. . . Simplified Device Configuration
![Page 34: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/34.jpg)
34
Protection Summary. . . Quickly Lists which Protection Functions are Enabled and Gives Link to That Function
![Page 35: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/35.jpg)
35
Trip Bus – Set Relay without Using Logic. . . 16 input OR gate….up to 6 TRIP BUS elements can be configured
![Page 36: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/36.jpg)
36
Sources and Transformer Configuration
Note CT polarities in Typical Wiring Diagram and connections to G30. These are necessary to correctly meter forward power. The transformer phase shift setting must compensate the measured relay currents for both the actual phase shift of the transformer, and any phase due to the CT polarities and connections.
![Page 37: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/37.jpg)
37
Sources and Transformer Configuration Assumption:
Step-up Transformer is -30° lagging (from line side to generator side)
Sources to match Typical Wiring Diagram:
Transformer Configuration
![Page 38: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/38.jpg)
38
Single-Line DiagramWith Step-Up Transformer
Main Generator Protection uses Transformer High-side CTs & PTs
1
3
2 or 3
1, 2 or 3
3
1
87GT
87RGF
Y
F1-F3
M1-M3
F8
F5-F7
M4
![Page 39: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/39.jpg)
39
Graphical Flexlogic Editor
• Create logic using a graphical editor
• Document logic and store documentation in setting file
• Detects errors commonly made in logic creation
• Allows for configuration through to elements, I/O, LEDs, etc.
• Capability to build and organize logic on separate worksheetsGraphical Flexlogic Analyzer
• Analyze the status of Flexlogic in Real-Time
• Easily detect problems in wiring• Simplify commissioning by easily
following status of logic on the screen
Programmable Logic - Viewpoint Engineer. . . Design Ease and Productivity Improvement
![Page 40: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/40.jpg)
40
Graphical Programmable Logic Designer. . . Customized Control and Operation Logic
![Page 41: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/41.jpg)
41
“Click To” Protection Elements for Editing . . . Reduces Engineering and Setting File Creation Time
![Page 42: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/42.jpg)
42
Highlights show asserted logic
Dynamic Logic Monitor. . . Aids in Troubleshooting and Reduces Installation Time
![Page 43: GE Multilin-g30 Training](https://reader030.vdocument.in/reader030/viewer/2022012307/546de3e2b4af9f09738b4e33/html5/thumbnails/43.jpg)
43