Installation and operation manualVRV IV-S system air conditioner English
Installation and operationmanual
VRV IV-S system air conditioner
RXYSCQ4TMV1B RXYSCQ5TMV1B
A~Ea b c d e eB eD
a
bc
d
e
eB
eD
A
BC
D
E
BHU
HD
H
B — ≥100A, B, C — ≥250 ≥100 ≥100B, E — ≥100 ≥1000 ≤500A, B, C, E — ≥250 ≥150 ≥150 ≥1000 ≤500D — ≥500D, E — ≥500 ≥1000 ≤500B, D — ≥100 ≥500B, D, E
1+2
1
HB<HD HB≤½HU ≥250 ≥750 ≥1000 ≤500½HU<HB≤HU ≥250 ≥1000 ≥1000 ≤500HB>HU
HB>HD HD≤½HU ≥100 ≥1000 ≥1000 ≤500½HU<HD≤HU ≥200 ≥1000 ≥1000 ≤500HD>HU
A, B, C — ≥250 ≥300 ≥1000A, B, C, E — ≥250 ≥300 ≥1000 ≥1000 ≤500D — ≥1000D, E — ≥1000 ≥1000 ≤500B, D HD>HU ≥300 ≥1000
HD≤½HU ≥250 ≥1500½HU<HD≤HU ≥300 ≥1500
B, D, E HB<HD HB≤½HU ≥300 ≥1000 ≥1000 ≤500½HU<HB≤HU ≥300 ≥1250 ≥1000 ≤500HB>HU
HB>HD HD≤½HU ≥250 ≥1000 ≥1000 ≤500½HU<HD≤HU ≥300 ≥1000 ≥1000 ≤500HD>HU
HB HD HU
(mm)
HU
a
b≥250
≥250c
d
e
eB
eD
A
BC
D
E
HB
HD
1
b (mm)
≥1000≥200
≥2000
≥100
≥3000
≥1500
b
≥250≥250
≥250≥250
≥250≥250
HB
HU
HB≤½HU b≥250½HU<HB≤HU b≥300
HB>HU
HB HU
2
A1
A2≥500
≥1000
A2≥500
≥300
≥250 ≥250
B1
A2
B2
≥100
≥300
≥250 ≥250
B2
≥100
≥1000
B2
3
2P406920-1A
CE - D
ECLA
RATIO
N-OF-C
ONFO
RMITY
CE - D
ECLA
RACIO
N-DE-C
ONFO
RMIDA
DCE
- DEC
LARA
ÇÃO-
DE-CO
NFOR
MIDA
DECE
- ERK
LÆRIN
G OM-
SAMS
VAR
CE - I
ZJAV
A-O-US
KLAĐ
ENOS
TICE
- IZJ
AVA O
SKLA
DNOS
TICE
- ATIT
IKTIES
-DEKL
ARAC
IJACE
- KON
FORM
ITÄTS
ERKL
ÄRUN
GCE
- DICH
IARAZ
IONE-D
I-CON
FORM
ITACE
- ЗАЯ
ВЛЕН
ИЕ-О
-СООТ
ВЕТС
ТВИИ
CE - I
LMOIT
US-YH
DENM
UKAIS
UUDE
STA
CE - M
EGFE
LELŐ
SÉGI-
NYILA
TKOZ
ATCE
- VAS
TAVU
SDEK
LARA
TSIOO
NCE
- ATB
ILSTĪB
AS-DE
KLAR
ĀCIJA
CE - D
ECLA
RATIO
N-DE-C
ONFO
RMITE
CE - Δ
HΛΩΣ
Η ΣΥΜ
ΜΟΡΦ
ΩΣΗΣ
CE - O
VERE
NSST
EMME
LSES
ERKL
ÆRING
CE - P
ROHL
ÁŠEN
Í-O-SH
ODĚ
CE - D
EKLA
RACJ
A-ZGO
DNOŚ
CICE
- ДЕК
ЛАРА
ЦИЯ-З
А-СЪО
ТВЕТ
СТВИ
ЕCE
- VYH
LÁSE
NIE-ZH
ODY
CE - C
ONFO
RMITE
ITSVE
RKLA
RING
CE - F
ÖRSÄ
KRAN
-OM-
ÖVER
ENST
ÄMME
LSE
CE - D
ECLA
RAŢIE
-DE-CO
NFOR
MITA
TECE
- UYG
UNLU
K-BEY
ANI
01
02
03
04
05
06
07
08
decla
res un
der it
s sole
resp
onsib
ility th
at the
air c
ondit
ioning
mod
els to
which
this d
eclar
ation
relat
es:
erklär
t auf
seine
allein
ige Ve
rantwo
rtung
daß d
ie Mo
delle
der K
limag
eräte
für di
e dies
e Erkl
ärung
bestim
mt ist
:dé
clare
sous
sa se
ule re
spon
sabili
té qu
e les
appa
reils d
'air co
nditio
nné v
isés p
ar la
prése
nte dé
clarat
ion:
verkl
aart h
ierbij
op ei
gen e
xclus
ieve v
erantw
oorde
lijkhe
id da
t de a
ircon
dition
ing un
its wa
arop d
eze v
erklar
ing be
trekki
ng he
eft:
decla
ra ba
ja su
única
resp
onsa
bilida
d que
los m
odelo
s de a
ire ac
ondic
ionad
o a lo
s cua
les ha
ce re
feren
cia la
decla
ración
:dic
hiara
sotto
sua r
espo
nsab
ilità ch
e i co
ndizio
nator
i mod
ello a
cui è
riferi
ta qu
esta
dichia
razion
e:δη
λώνει
με απ
οκλει
στική
της ε
υθύν
η ότι τ
α μον
τέλα τ
ων κλ
ιματισ
τικών
συσκ
ευών σ
τα οπ
οία αν
αφέρε
ται η
παρο
ύσα δ
ήλωσ
η:de
clara
sob s
ua ex
clusiv
a res
pons
abilid
ade q
ue os
mod
elos d
e ar c
ondic
ionad
o a qu
e esta
decla
ração
se re
fere:
09
10
11
12
13
14
15
16
заявл
яет, и
сключ
итель
но по
д сво
ю отв
етстве
ннос
ть, чт
о мод
ели к
онди
цион
еров
возд
уха, к
котор
ым от
носи
тся на
стоящ
ее за
явле
ние:
erklæ
rer un
der e
nean
svar, a
t klim
aanlæ
gmod
ellerne
, som
denn
e dek
larati
on ve
drører
:de
klarer
ar i e
gens
kap a
v huv
udan
svarig
, att l
uftko
nditio
nerin
gsmo
deller
na so
m be
rörs a
v den
na de
klarat
ion in
nebä
r att:
erklæ
rer et
fullst
endig
ansva
r for a
t de l
uftko
ndisjo
nerin
gsmo
deller
som
berør
es av
denn
e dek
laras
jon, in
nebæ
rer at
:ilm
oittaa
yksin
omaa
n oma
lla va
stuulla
an, e
ttä tä
män i
lmoit
ukse
n tark
oittam
at ilm
astoi
ntilait
teide
n malli
t:pro
hlašu
je ve
své p
lné od
pově
dnos
ti, že
mod
ely kli
matiza
ce, k
nimž
se to
to pro
hláše
ní vzt
ahuje
:izja
vljuje
pod i
sključ
ivo vla
stitom
odgo
vorno
šću da
su m
odeli
klima u
ređaja
na ko
je se
ova i
zjava
odno
si:tel
jes fe
lelőssé
ge tu
datáb
an kij
elenti
, hog
y a klí
mabe
rende
zés m
odelle
k, me
lyekre
e ny
ilatko
zat v
onatk
ozik:
17
18
19
20
21
22
23
24
25
dekla
ruje n
a włas
ną i w
yłączn
ą odp
owied
zialno
ść, że
mod
ele kli
matyz
atorów
, któr
ych do
tyczy
niniejs
za de
klarac
ja:de
clară
pe pr
oprie
răsp
unde
re că
apara
tele d
e aer
cond
iţiona
t la ca
re se
refer
ă ace
astă
decla
raţie:
z vso
odgo
vorno
stjo izj
avlja,
da so
mod
eli klim
atskih
napra
v, na
kater
e se i
zjava
nana
ša:
kinnit
ab om
a täie
likul va
stutus
el, et
käes
oleva
dekla
ratsio
oni a
lla ku
uluva
d kliim
asea
dmete
mud
elid:
декла
рира
на св
оя от
говор
ност,
че мо
дели
те кли
матич
на ин
стала
ция,
за кои
то се
отна
ся та
зи де
клара
ция:
visišk
a sav
o atsa
komy
be sk
elbia,
kad o
ro ko
ndicio
navim
o prie
taisų
mod
eliai, k
uriem
s yra
taiko
ma ši
dekla
racija:
ar piln
u atbi
ldību
apliec
ina, k
a tālā
k uzsk
aitīto
mod
eļu ga
isa ko
ndicio
nētāj
i, uz k
uriem
attie
cas š
ī dek
larāc
ija:vyh
lasuje
na vla
stnú z
odpo
vedn
osť, ž
e tiet
o klim
atiza
čné m
odely
, na k
toré s
a vzťa
huje
toto v
yhlás
enie:
tamam
en ke
ndi so
rumlulu
ǧund
a olm
ak üz
ere bu
bildir
inin ilg
ili oldu
ǧu kli
ma m
odelle
rinin
aşaǧ
ıdaki g
ibi old
uǧun
u bey
an ed
er:
01 02 03 04 05 06 07
are in
confo
rmity
with t
he fo
llowing
stan
dard(
s) or
other
norm
ative
docu
ment(
s), pr
ovide
d tha
t thes
e are
used
in ac
corda
nce w
ith ou
r instr
uctio
ns:
der/d
en fo
lgend
en No
rm(en
) ode
r eine
m an
deren
Norm
doku
ment
oder
-doku
mente
n ents
prich
t/ents
prech
en, u
nter d
er Vo
rausse
tzung
, daß
sie ge
mäß
unse
ren An
weisu
ngen
eing
esetz
t werd
en:
sont
confo
rmes
à la/
aux n
orme(s
) ou a
utre(s
) doc
umen
t(s) n
ormati
f(s), p
our a
utant
qu'ils
soien
t utilis
és co
nform
émen
t à no
s instr
uctio
ns:
confo
rm de
volge
nde n
orm(en
) of é
én of
mee
r and
ere bi
nden
de do
cume
nten z
ijn, op
voorw
aarde
dat z
e word
en ge
bruikt
overe
enko
mstig
onze
instru
cties:
están
en co
nform
idad c
on la
(s) sig
uiente
(s) no
rma(s
) u ot
ro(s)
docu
mento
(s) no
rmati
vo(s)
, siem
pre qu
e sea
n utiliz
ados
de ac
uerdo
con n
uestr
asins
trucci
ones
:so
no co
nform
i al(i)
segu
ente(
i) stan
dard(
s) o a
ltro(i)
docu
mento
(i) a c
aratte
re no
rmati
vo, a
patto
che v
enga
no us
ati in
confo
rmità
alle
nostr
e istr
uzion
i:είν
αι σύ
μφων
α με τ
ο(α) α
κόλο
υθο(α
) πρό
τυπο(α
) ή άλ
λο έγ
γραφ
ο(α) κ
ανον
ισμών
, υπό
την π
ροϋπ
όθεσ
η ότι χ
ρησιμ
οποιο
ύνται
σύμφ
ωνα μ
ε τις ο
δηγίε
ς μας
:
08 09 10 11 12 13 14 15
estão
em co
nform
idade
com
a(s) s
eguin
te(s)
norm
a(s) o
u outr
o(s) d
ocum
ento(
s) no
rmati
vo(s)
, des
de qu
e este
s seja
m uti
lizado
s de
acord
o com
as no
ssas in
struç
ões:
соотв
етству
ют сл
едую
щим с
танда
ртам и
ли др
угим н
орма
тивны
м доку
мента
м, пр
и усл
овии
их ис
поль
зован
ия со
гласн
о наш
им ин
струкц
иям:
overh
older
følge
nde s
tanda
rd(er)
eller
ande
t/and
re ret
nings
given
de do
kume
nt(er)
, forud
sat a
t diss
e anv
ende
s i he
nhold
til vo
re ins
trukse
r:res
pektiv
e utru
stning
är ut
förd i
övere
nsstä
mmels
e med
och f
öljer fö
ljande
stan
dard(
er) el
ler an
dra no
rmgiv
ande
doku
ment,
unde
r förut
sättn
ing at
tan
vänd
ning s
ker i
övere
nsstä
mmels
e med
våra
instru
ktione
r:res
pektiv
e utst
yr er
i ove
rensst
emme
lse m
ed fø
lgend
e stan
dard(
er) el
ler an
dre no
rmgiv
ende
doku
ment(
er), u
nder
foruts
setni
ng av
at di
sse br
ukes
ihe
nhold
til vå
re ins
trukse
r:va
staav
at se
uraav
ien st
anda
rdien
ja m
uiden
ohjee
llisten
doku
mentt
ien va
atimu
ksia e
dellyt
täen,
että n
iitä kä
ytetää
n ohje
idemm
e muk
aises
ti:za
před
pokla
du, ž
e jso
u vyu
žíván
y v so
uladu
s na
šimi p
okyn
y, od
povíd
ají ná
sledu
jícím
norm
ám ne
bo no
rmati
vním
doku
mentů
m:u s
kladu
sa sli
jedeć
im st
anda
rdom(
ima)
ili drug
im no
rmati
vnim
doku
mento
m(im
a), uz
uvjet
da se
oni ko
riste
u skla
du s
našim
uputa
ma:
16 17 18 19 20 21 22 23 24 25
megfe
lelnek
az al
ábbi
szabv
ány(o
k)nak
vagy
egyé
b irán
yadó
doku
mentu
m(ok
)nak,
ha az
okat
előírá
s sze
rint h
aszn
álják:
spełn
iają wy
mogi
nastę
pując
ych no
rm i in
nych
doku
mentó
w norm
alizac
yjnych
, pod
warun
kiem
że uż
ywan
e są z
godn
ie z n
aszym
i instr
ukcja
mi:
sunt
în co
nform
itate
cu ur
mător
ul (ur
mătoa
rele)
stand
ard(e)
sau a
lt(e) d
ocum
ent(e
) norm
ativ(e
), cu c
ondiţ
ia ca
aces
tea să
fie ut
ilizate
în co
nform
itate
cuins
trucţiu
nile no
astre
:skl
adni
z nas
lednjim
i stan
dardi
in dr
ugim
i norm
ativi,
pod p
ogoje
m, da
se up
orablja
jo v s
kladu
z na
šimi n
avod
ili:on
vasta
vuse
s järgm
is(t)e
stan
dardi
(te)ga
või te
iste no
rmati
ivsete
doku
menti
dega
, kui
neid
kasu
tatak
se va
stava
lt meie
juhe
ndite
le:съ
ответс
тват н
а сле
дните
стан
дарти
или д
руги
норм
ативн
и доку
менти
, при
усло
вие,
че се
изпо
лзва
т съгл
асно
наши
те ин
струкц
ии:
atitin
ka že
miau
nurod
ytus s
tanda
rtus ir
(arba
) kitu
s norm
inius d
okum
entus
su są
lyga,
kad y
ra na
udoja
mi pa
gal m
ūsų n
urody
mus:
tad, ja
lietot
i atbi
lstoši r
ažotā
ja no
rādīju
miem
, atbi
lst se
kojoš
iem st
anda
rtiem
un cit
iem no
rmatī
viem
doku
menti
em:
sú v
zhod
e s na
sledo
vnou
(ými) n
ormou
(ami) a
lebo i
ným(
i) norm
atívn
ym(i)
doku
mento
m(am
i), za
pred
pokla
du, ž
e sa p
oužív
ajú v
súlad
e s na
šimná
vodo
m:ürü
nün,
talim
atları
mıza
göre
kullan
ılmas
ı koş
uluyla
aşağ
ıdaki s
tanda
rtlar v
e norm
belirt
en be
lgeler
le uy
umlud
ur:
01 02 03 04 05 06 07 08 09
follow
ing th
e prov
isions
of:
gemä
ß den
Vorsc
hrifte
n der:
confo
rmém
ent a
ux st
ipulat
ions d
es:
overe
enko
mstig
de be
paling
en va
n:sig
uiend
o las
disp
osicio
nes d
e:se
cond
o le p
rescri
zioni
per:
με τήρ
ηση τ
ων δι
ατάξεω
ν των
:de
acord
o com
o pre
visto
em:
в соо
тветст
вии с
поло
жени
ями:
10 11 12 13 14 15 16 17 18
unde
r iagtt
agels
e af b
estem
melse
rne i:
enligt
villko
ren i:
gitt i
henh
old til
beste
mmels
ene i
:no
udatt
aen m
ääräy
ksiä:
za do
držen
í usta
nove
ní pře
dpisu
:pre
ma od
redba
ma:
köve
ti a(z)
:zg
odnie
z po
stano
wienia
mi Dy
rektyw
:în
urma p
reved
erilor
:
19 20 21 22 23 24 25
ob up
oštev
anju
določ
b:va
stava
lt nõu
etele:
след
вайки
клау
зите н
а:laik
antis
nuos
tatų,
patei
kiamų
:iev
ērojot
pras
ības,
kas n
oteikta
s:od
ržiav
ajúc u
stano
venia
:bu
nun k
oşulla
rına u
ygun
olara
k:
01 02 03 04 05 06 07 08 09
Direc
tives,
as am
ende
d.Dir
ektive
n, ge
mäß Ä
nderu
ng.
Direc
tives,
telles
que m
odifié
es.
Richtl
ijnen,
zoals
geam
ende
erd.
Direc
tivas,
segú
n lo e
nmen
dado
.Dir
ettive
, com
e da m
odific
a.Οδ
ηγιών
, όπω
ς έχο
υν τρ
οποπ
οιηθεί
.Dir
ectiva
s, co
nform
e alte
ração
em.
Дире
ктив с
о все
ми по
прав
ками.
10 11 12 13 14 15 16 17
Direk
tiver, m
ed se
nere
ændri
nger.
Direk
tiv, m
ed fö
retag
na än
dring
ar.Dir
ektive
r, med
foret
atte e
ndrin
ger.
Direk
tiivejä
, sella
isina k
uin ne
ovat
muute
ttuina
.v p
latné
m zn
ění.
Smjer
nice,
kako
je izm
ijenjen
o.irá
nyelv
(ek) é
s mód
osítá
saik r
ende
lkezé
seit.
z póź
niejsz
ymi p
opraw
kami
.
18 19 20 21 22 23 24 25
Direc
tivelor
, cu a
mend
amen
tele r
espe
ctive.
Direk
tive z
vsemi
sprem
emba
mi.
Direk
tiivid
koos
muu
datus
tega.
Дире
ктиви
, с те
хните
изме
нени
я.Dir
ektyv
ose s
u pap
ildyma
is.Dir
ektīv
ās un
to pa
pildinā
jumos
.Sm
ernice
, v pl
atnom
znen
í.De
ğiştiri
lmiş h
alleriy
le Yö
netm
elikler
.
01 No
te*
02 Hi
nweis
*
03 Re
marqu
e*
04 Be
merk*
05 No
ta*
as se
t out
in <A
> and
judg
ed po
sitive
ly by <
B>ac
cordi
ng to
the C
ertific
ate <C
>.wie
in <A
> aufg
eführt
und v
on <B
> pos
itivbe
urteilt
gemä
ß Zert
ifikat
<C>.
tel qu
e défi
ni da
ns <A
> et é
valué
positi
veme
nt pa
r <B>
confo
rmém
ent a
u Cert
ificat
<C>.
zoals
verm
eld in
<A> e
n pos
itief b
eoord
eeld
door
<B>
overe
enko
mstig
Certif
icaat
<C>.
como
se es
tablec
e en <
A> y
es va
lorad
opo
sitiva
mente
por <
B> de
acue
rdo co
n el
Certif
icado
<C>.
06 No
ta*
07 Ση
μείω
ση*
08 No
ta*
09 Пр
имеч
ание
*
10 Be
mærk*
deline
ato ne
l <A>
e giu
dicato
positi
vame
nte da
<B>
seco
ndo i
l Cert
ificato
<C>.
όπως
καθο
ρίζετα
ι στο
<A> κ
αι κρ
ίνεται
θετικ
άαπ
ό το <
B> σύ
μφων
α με τ
ο Πιστ
οποιη
τικό <
C>.
tal co
mo es
tabele
cido e
m <A
> e co
m o p
arece
r pos
itivo
de <B
> de a
cordo
com
o Cert
ificad
o <C>
.как
указа
но в
<A> и
в со
ответс
твии с
поло
жител
ьным
реше
нием
<B> с
оглас
но Св
идете
льств
у <C>
.so
m an
ført i
<A> o
g pos
itivt v
urdere
t af <
B> i h
enho
ld til
Certif
ikat <
C>.
11 In
forma
tion*
12 M
erk*
13 Hu
om*
14 Po
znám
ka*
15 Na
pome
na*
enligt
<A> o
ch go
dkän
ts av
<B> e
nligt
Certif
ikatet
<C>.
som
det fr
emko
mmer
i <A>
og gj
enno
m po
sitiv
bedø
mmels
e av <
B> ifø
lge Se
rtifika
t <C>
.jot
ka on
esite
tty as
iakirja
ssa <A
> ja j
otka <
B>on
hyvä
ksyny
t Sert
ifikaa
tin <C
> muk
aises
ti.jak
bylo
uved
eno v
<A> a
poziti
vně z
jištěn
o<B
> v so
uladu
s os
vědč
ením
<C>.
kako
je izl
ožen
o u <A
> i po
zitivn
o ocije
njeno
od st
rane
<B> p
rema C
ertifik
atu <C
>.
16 M
egjeg
yzés*
17 Uw
aga*
18 No
tă*
19 Op
omba
*
20 M
ärkus
*
a(z) <
A> al
apján
, a(z)
<B> i
gazo
lta a
megfe
lelést,
a(z)
<C> t
anús
ítván
y sze
rint.
zgod
nie z
doku
menta
cją <A
>, po
zytyw
nąop
inią <B
> i Św
iadec
twem
<C>.
aşa c
um es
te sta
bilit în
<A> ş
i apre
ciat p
ozitiv
de <B
>în
confo
rmita
te cu
Certif
icatul
<C>.
kot je
določ
eno v
<A> i
n odo
breno
s str
ani <
B>v s
kladu
s ce
rtifika
tom <C
>.na
gu on
näida
tud do
kume
ndis <
A> ja
heak
s kiide
tud<B
> järg
i vasta
valt s
ertifik
aadil
e <C>
.
21 За
беле
жка*
22 Pa
staba
*
23 Pi
ezīme
s*
24 Po
znám
ka*
25 No
t*
както
е изл
ожен
о в <A
> и оц
енен
о пол
ожите
лно о
т <B>
съгла
сно С
ерти
фикат
а <C>
.ka
ip nu
statyt
a <A>
ir ka
ip tei
giama
i nus
pręsta
<B> p
agal
Sertif
ikatą
<C>.
kā no
rādīts
<A> u
n atbi
lstoši <
B> po
zitīva
jam vē
rtējum
amsa
skaņā
ar se
rtifikā
tu <C
>.ak
o bolo
uved
ené v
<A> a
pozití
vne z
istené
<B> v
súlad
es o
sved
čením
<C>.
<A>’d
a belir
tildiği
gibi ve
<C> S
ertifik
asına
göre
<B>
tarafı
ndan
olum
lu ola
rak de
ğerle
ndirild
iği gib
i.
01**
02**
03**
04**
05**
06**
Daikin
Europ
e N.V.
is au
thoris
ed to
comp
ile the
Tech
nical
Cons
tructio
n File.
Daikin
Europ
e N.V.
hat d
ie Be
rechti
gung
die T
echn
ische
Kons
truktio
nsak
te zu
samm
enzu
stellen
.Da
ikin Eu
rope N
.V. es
t auto
risé à
comp
iler le
Dossi
er de
Cons
tructio
n Tec
hniqu
e.Da
ikin Eu
rope N
.V. is
bevo
egd o
m he
t Tec
hnisc
h Con
struc
tiedo
ssier
same
n te s
tellen
.Da
ikin Eu
rope N
.V. es
tá au
toriza
do a
comp
ilar el
Arch
ivo de
Cons
trucci
ón Té
cnica
.Da
ikin Eu
rope N
.V. è
autor
izzata
a red
igere
il File
Tecn
ico di
Costr
uzion
e.
07**
08**
09**
10**
11**
12**
Η Daik
in Eu
rope N
.V. είν
αι εξο
υσιοδ
οτημέν
η να σ
υντάξ
ει τον
Τεχν
ικό φά
κελο κ
ατασκ
ευής.
A Daik
in Eu
rope N
.V. es
tá au
toriza
da a
comp
ilar a
docu
menta
ção t
écnic
a de f
abric
o.Ко
мпан
ия Da
ikin Eu
rope N
.V. уп
олно
моче
на со
стави
ть Ко
мпле
кт тех
ниче
ской д
окуме
нтаци
и.Da
ikin Eu
rope N
.V. er
autor
iseret
til at
udarb
ejde d
e tek
niske
kons
truktio
nsda
ta.Da
ikin Eu
rope N
.V. är
bemy
ndiga
de at
t sam
mans
tälla
den t
eknis
ka ko
nstru
ktions
filen.
Daikin
Europ
e N.V.
har ti
llatels
e til å
komp
ilere d
en Te
knisk
e kon
struk
sjons
filen.
13**
14**
15**
16**
17**
18**
Daikin
Europ
e N.V.
on va
ltuute
ttu la
atima
an Te
knise
n asia
kirjan
.Sp
olečn
ost D
aikin
Europ
e N.V.
má o
právn
ění k
e kom
pilaci s
oubo
ru tec
hnick
é kon
struk
ce.
Daikin
Europ
e N.V.
je ov
lašten
za izr
adu D
atotek
e o te
hničk
oj ko
nstru
kciji.
A Daik
in Eu
rope N
.V. jo
gosu
lt a m
űsza
ki kon
struk
ciós d
okum
entác
ió ös
szeállí
tására
.Da
ikin Eu
rope N
.V. m
a upo
ważn
ienie
do zb
ieran
ia i o
praco
wywa
nia do
kume
ntacji
kons
trukcy
jnej.
Daikin
Europ
e N.V.
este
autor
izat s
ă com
pileze
Dosa
rul te
hnic d
e con
struc
ţie.
19**
20**
21**
22**
23**
24**
25**
Daikin
Europ
e N.V.
je po
oblaš
čen z
a ses
tavo d
atotek
e s te
hničn
o map
o.Da
ikin Eu
rope N
.V. on
volita
tud ko
ostam
a teh
nilist
doku
menta
tsioon
i.Da
ikin Eu
rope N
.V. е
отори
зиран
а да с
ъстав
и Акта
за те
хнич
еска
констр
укция
.Da
ikin Eu
rope N
.V. yr
a įga
liota s
udary
ti šį te
chnin
ės ko
nstru
kcijos
failą.
Daikin
Europ
e N.V.
ir au
torizē
ts sa
stādīt
tehn
isko d
okum
entāc
iju.Sp
oločn
osť D
aikin
Europ
e N.V.
je op
rávne
ná vy
tvoriť
súbo
r tech
nicke
j konš
trukci
e.Da
ikin Eu
rope N
.V. Te
knik Y
apı D
osya
sını d
erlem
eye y
etkilid
ir.
Dai
kin
Euro
pe N
.V.
RXY
SCQ
4TM
V1B
*, R
XYSC
Q5T
MV1
B*,
* = ,
, 1,
2, 3,
..., 9
EN
6033
5-2-
40,
Mac
hine
ry 2
006/
42/E
CE
lect
rom
agne
tic C
ompa
tibili
ty 2
014/
30/E
U** *
CE - D
ECLA
RATIO
N-OF-C
ONFO
RMITY
CE - D
ECLA
RACIO
N-DE-C
ONFO
RMIDA
DCE
- DEC
LARA
ÇÃO-
DE-CO
NFOR
MIDA
DECE
- ERK
LÆRIN
G OM-
SAMS
VAR
CE - I
ZJAV
A-O-US
KLAĐ
ENOS
TICE
- IZJ
AVA O
SKLA
DNOS
TICE
- ATIT
IKTIES
-DEKL
ARAC
IJACE
- KON
FORM
ITÄTS
ERKL
ÄRUN
GCE
- DICH
IARAZ
IONE-D
I-CON
FORM
ITACE
- ЗАЯ
ВЛЕН
ИЕ-О
-СООТ
ВЕТС
ТВИИ
CE - I
LMOIT
US-YH
DENM
UKAIS
UUDE
STA
CE - M
EGFE
LELŐ
SÉGI-
NYILA
TKOZ
ATCE
- VAS
TAVU
SDEK
LARA
TSIOO
NCE
- ATB
ILSTĪB
AS-DE
KLAR
ĀCIJA
CE - D
ECLA
RATIO
N-DE-C
ONFO
RMITE
CE - Δ
HΛΩΣ
Η ΣΥΜ
ΜΟΡΦ
ΩΣΗΣ
CE - O
VERE
NSST
EMME
LSES
ERKL
ÆRING
CE - P
ROHL
ÁŠEN
Í-O-SH
ODĚ
CE - D
EKLA
RACJ
A-ZGO
DNOŚ
CICE
- ДЕК
ЛАРА
ЦИЯ-З
А-СЪО
ТВЕТ
СТВИ
ЕCE
- VYH
LÁSE
NIE-ZH
ODY
CE - C
ONFO
RMITE
ITSVE
RKLA
RING
CE - F
ÖRSÄ
KRAN
-OM-
ÖVER
ENST
ÄMME
LSE
CE - D
ECLA
RAŢIE
-DE-CO
NFOR
MITA
TECE
- UYG
UNLU
K-BEY
ANI
01
02
03
04
05
06
07
08
decla
res un
der it
s sole
resp
onsib
ility th
at the
air c
ondit
ioning
mod
els to
which
this d
eclar
ation
relat
es:
erklär
t auf
seine
allein
ige Ve
rantwo
rtung
daß d
ie Mo
delle
der K
limag
eräte
für di
e dies
e Erkl
ärung
bestim
mt ist
:dé
clare
sous
sa se
ule re
spon
sabili
té qu
e les
appa
reils d
'air co
nditio
nné v
isés p
ar la
prése
nte dé
clarat
ion:
verkl
aart h
ierbij
op ei
gen e
xclus
ieve v
erantw
oorde
lijkhe
id da
t de a
ircon
dition
ing un
its wa
arop d
eze v
erklar
ing be
trekki
ng he
eft:
decla
ra ba
ja su
única
resp
onsa
bilida
d que
los m
odelo
s de a
ire ac
ondic
ionad
o a lo
s cua
les ha
ce re
feren
cia la
decla
ración
:dic
hiara
sotto
sua r
espo
nsab
ilità ch
e i co
ndizio
nator
i mod
ello a
cui è
riferi
ta qu
esta
dichia
razion
e:δη
λώνει
με απ
οκλει
στική
της ε
υθύν
η ότι τ
α μον
τέλα τ
ων κλ
ιματισ
τικών
συσκ
ευών σ
τα οπ
οία αν
αφέρε
ται η
παρο
ύσα δ
ήλωσ
η:de
clara
sob s
ua ex
clusiv
a res
pons
abilid
ade q
ue os
mod
elos d
e ar c
ondic
ionad
o a qu
e esta
decla
ração
se re
fere:
09
10
11
12
13
14
15
16
заявл
яет, и
сключ
итель
но по
д сво
ю отв
етстве
ннос
ть, чт
о мод
ели к
онди
цион
еров
возд
уха, к
котор
ым от
носи
тся на
стоящ
ее за
явле
ние:
erklæ
rer un
der e
nean
svar, a
t klim
aanlæ
gmod
ellerne
, som
denn
e dek
larati
on ve
drører
:de
klarer
ar i e
gens
kap a
v huv
udan
svarig
, att l
uftko
nditio
nerin
gsmo
deller
na so
m be
rörs a
v den
na de
klarat
ion in
nebä
r att:
erklæ
rer et
fullst
endig
ansva
r for a
t de l
uftko
ndisjo
nerin
gsmo
deller
som
berør
es av
denn
e dek
laras
jon, in
nebæ
rer at
:ilm
oittaa
yksin
omaa
n oma
lla va
stuulla
an, e
ttä tä
män i
lmoit
ukse
n tark
oittam
at ilm
astoi
ntilait
teide
n malli
t:pro
hlašu
je ve
své p
lné od
pově
dnos
ti, že
mod
ely kli
matiza
ce, k
nimž
se to
to pro
hláše
ní vzt
ahuje
:izja
vljuje
pod i
sključ
ivo vla
stitom
odgo
vorno
šću da
su m
odeli
klima u
ređaja
na ko
je se
ova i
zjava
odno
si:tel
jes fe
lelőssé
ge tu
datáb
an kij
elenti
, hog
y a klí
mabe
rende
zés m
odelle
k, me
lyekre
e ny
ilatko
zat v
onatk
ozik:
17
18
19
20
21
22
23
24
25
dekla
ruje n
a włas
ną i w
yłączn
ą odp
owied
zialno
ść, że
mod
ele kli
matyz
atorów
, któr
ych do
tyczy
niniejs
za de
klarac
ja:de
clară
pe pr
oprie
răsp
unde
re că
apara
tele d
e aer
cond
iţiona
t la ca
re se
refer
ă ace
astă
decla
raţie:
z vso
odgo
vorno
stjo izj
avlja,
da so
mod
eli klim
atskih
napra
v, na
kater
e se i
zjava
nana
ša:
kinnit
ab om
a täie
likul va
stutus
el, et
käes
oleva
dekla
ratsio
oni a
lla ku
uluva
d kliim
asea
dmete
mud
elid:
декла
рира
на св
оя от
говор
ност,
че мо
дели
те кли
матич
на ин
стала
ция,
за кои
то се
отна
ся та
зи де
клара
ция:
visišk
a sav
o atsa
komy
be sk
elbia,
kad o
ro ko
ndicio
navim
o prie
taisų
mod
eliai, k
uriem
s yra
taiko
ma ši
dekla
racija:
ar piln
u atbi
ldību
apliec
ina, k
a tālā
k uzsk
aitīto
mod
eļu ga
isa ko
ndicio
nētāj
i, uz k
uriem
attie
cas š
ī dek
larāc
ija:vyh
lasuje
na vla
stnú z
odpo
vedn
osť, ž
e tiet
o klim
atiza
čné m
odely
, na k
toré s
a vzťa
huje
toto v
yhlás
enie:
tamam
en ke
ndi so
rumlulu
ǧund
a olm
ak üz
ere bu
bildir
inin ilg
ili oldu
ǧu kli
ma m
odelle
rinin
aşaǧ
ıdaki g
ibi old
uǧun
u bey
an ed
er:
01 02 03 04 05 06 07
are in
confo
rmity
with t
he fo
llowing
stan
dard(
s) or
other
norm
ative
docu
ment(
s), pr
ovide
d tha
t thes
e are
used
in ac
corda
nce w
ith ou
r instr
uctio
ns:
der/d
en fo
lgend
en No
rm(en
) ode
r eine
m an
deren
Norm
doku
ment
oder
-doku
mente
n ents
prich
t/ents
prech
en, u
nter d
er Vo
rausse
tzung
, daß
sie ge
mäß
unse
ren An
weisu
ngen
eing
esetz
t werd
en:
sont
confo
rmes
à la/
aux n
orme(s
) ou a
utre(s
) doc
umen
t(s) n
ormati
f(s), p
our a
utant
qu'ils
soien
t utilis
és co
nform
émen
t à no
s instr
uctio
ns:
confo
rm de
volge
nde n
orm(en
) of é
én of
mee
r and
ere bi
nden
de do
cume
nten z
ijn, op
voorw
aarde
dat z
e word
en ge
bruikt
overe
enko
mstig
onze
instru
cties:
están
en co
nform
idad c
on la
(s) sig
uiente
(s) no
rma(s
) u ot
ro(s)
docu
mento
(s) no
rmati
vo(s)
, siem
pre qu
e sea
n utiliz
ados
de ac
uerdo
con n
uestr
asins
trucci
ones
:so
no co
nform
i al(i)
segu
ente(
i) stan
dard(
s) o a
ltro(i)
docu
mento
(i) a c
aratte
re no
rmati
vo, a
patto
che v
enga
no us
ati in
confo
rmità
alle
nostr
e istr
uzion
i:είν
αι σύ
μφων
α με τ
ο(α) α
κόλο
υθο(α
) πρό
τυπο(α
) ή άλ
λο έγ
γραφ
ο(α) κ
ανον
ισμών
, υπό
την π
ροϋπ
όθεσ
η ότι χ
ρησιμ
οποιο
ύνται
σύμφ
ωνα μ
ε τις ο
δηγίε
ς μας
:
08 09 10 11 12 13 14 15
estão
em co
nform
idade
com
a(s) s
eguin
te(s)
norm
a(s) o
u outr
o(s) d
ocum
ento(
s) no
rmati
vo(s)
, des
de qu
e este
s seja
m uti
lizado
s de
acord
o com
as no
ssas in
struç
ões:
соотв
етству
ют сл
едую
щим с
танда
ртам и
ли др
угим н
орма
тивны
м доку
мента
м, пр
и усл
овии
их ис
поль
зован
ия со
гласн
о наш
им ин
струкц
иям:
overh
older
følge
nde s
tanda
rd(er)
eller
ande
t/and
re ret
nings
given
de do
kume
nt(er)
, forud
sat a
t diss
e anv
ende
s i he
nhold
til vo
re ins
trukse
r:res
pektiv
e utru
stning
är ut
förd i
övere
nsstä
mmels
e med
och f
öljer fö
ljande
stan
dard(
er) el
ler an
dra no
rmgiv
ande
doku
ment,
unde
r förut
sättn
ing at
tan
vänd
ning s
ker i
övere
nsstä
mmels
e med
våra
instru
ktione
r:res
pektiv
e utst
yr er
i ove
rensst
emme
lse m
ed fø
lgend
e stan
dard(
er) el
ler an
dre no
rmgiv
ende
doku
ment(
er), u
nder
foruts
setni
ng av
at di
sse br
ukes
ihe
nhold
til vå
re ins
trukse
r:va
staav
at se
uraav
ien st
anda
rdien
ja m
uiden
ohjee
llisten
doku
mentt
ien va
atimu
ksia e
dellyt
täen,
että n
iitä kä
ytetää
n ohje
idemm
e muk
aises
ti:za
před
pokla
du, ž
e jso
u vyu
žíván
y v so
uladu
s na
šimi p
okyn
y, od
povíd
ají ná
sledu
jícím
norm
ám ne
bo no
rmati
vním
doku
mentů
m:u s
kladu
sa sli
jedeć
im st
anda
rdom(
ima)
ili drug
im no
rmati
vnim
doku
mento
m(im
a), uz
uvjet
da se
oni ko
riste
u skla
du s
našim
uputa
ma:
16 17 18 19 20 21 22 23 24 25
megfe
lelnek
az al
ábbi
szabv
ány(o
k)nak
vagy
egyé
b irán
yadó
doku
mentu
m(ok
)nak,
ha az
okat
előírá
s sze
rint h
aszn
álják:
spełn
iają wy
mogi
nastę
pując
ych no
rm i in
nych
doku
mentó
w norm
alizac
yjnych
, pod
warun
kiem
że uż
ywan
e są z
godn
ie z n
aszym
i instr
ukcja
mi:
sunt
în co
nform
itate
cu ur
mător
ul (ur
mătoa
rele)
stand
ard(e)
sau a
lt(e) d
ocum
ent(e
) norm
ativ(e
), cu c
ondiţ
ia ca
aces
tea să
fie ut
ilizate
în co
nform
itate
cuins
trucţiu
nile no
astre
:skl
adni
z nas
lednjim
i stan
dardi
in dr
ugim
i norm
ativi,
pod p
ogoje
m, da
se up
orablja
jo v s
kladu
z na
šimi n
avod
ili:on
vasta
vuse
s järgm
is(t)e
stan
dardi
(te)ga
või te
iste no
rmati
ivsete
doku
menti
dega
, kui
neid
kasu
tatak
se va
stava
lt meie
juhe
ndite
le:съ
ответс
тват н
а сле
дните
стан
дарти
или д
руги
норм
ативн
и доку
менти
, при
усло
вие,
че се
изпо
лзва
т съгл
асно
наши
те ин
струкц
ии:
atitin
ka že
miau
nurod
ytus s
tanda
rtus ir
(arba
) kitu
s norm
inius d
okum
entus
su są
lyga,
kad y
ra na
udoja
mi pa
gal m
ūsų n
urody
mus:
tad, ja
lietot
i atbi
lstoši r
ažotā
ja no
rādīju
miem
, atbi
lst se
kojoš
iem st
anda
rtiem
un cit
iem no
rmatī
viem
doku
menti
em:
sú v
zhod
e s na
sledo
vnou
(ými) n
ormou
(ami) a
lebo i
ným(
i) norm
atívn
ym(i)
doku
mento
m(am
i), za
pred
pokla
du, ž
e sa p
oužív
ajú v
súlad
e s na
šimná
vodo
m:ürü
nün,
talim
atları
mıza
göre
kullan
ılmas
ı koş
uluyla
aşağ
ıdaki s
tanda
rtlar v
e norm
belirt
en be
lgeler
le uy
umlud
ur:
01 02 03 04 05 06 07 08 09
follow
ing th
e prov
isions
of:
gemä
ß den
Vorsc
hrifte
n der:
confo
rmém
ent a
ux st
ipulat
ions d
es:
overe
enko
mstig
de be
paling
en va
n:sig
uiend
o las
disp
osicio
nes d
e:se
cond
o le p
rescri
zioni
per:
με τήρ
ηση τ
ων δι
ατάξεω
ν των
:de
acord
o com
o pre
visto
em:
в соо
тветст
вии с
поло
жени
ями:
10 11 12 13 14 15 16 17 18
unde
r iagtt
agels
e af b
estem
melse
rne i:
enligt
villko
ren i:
gitt i
henh
old til
beste
mmels
ene i
:no
udatt
aen m
ääräy
ksiä:
za do
držen
í usta
nove
ní pře
dpisu
:pre
ma od
redba
ma:
köve
ti a(z)
:zg
odnie
z po
stano
wienia
mi Dy
rektyw
:în
urma p
reved
erilor
:
19 20 21 22 23 24 25
ob up
oštev
anju
določ
b:va
stava
lt nõu
etele:
след
вайки
клау
зите н
а:laik
antis
nuos
tatų,
patei
kiamų
:iev
ērojot
pras
ības,
kas n
oteikta
s:od
ržiav
ajúc u
stano
venia
:bu
nun k
oşulla
rına u
ygun
olara
k:
01 02 03 04 05 06 07 08 09
Direc
tives,
as am
ende
d.Dir
ektive
n, ge
mäß Ä
nderu
ng.
Direc
tives,
telles
que m
odifié
es.
Richtl
ijnen,
zoals
geam
ende
erd.
Direc
tivas,
segú
n lo e
nmen
dado
.Dir
ettive
, com
e da m
odific
a.Οδ
ηγιών
, όπω
ς έχο
υν τρ
οποπ
οιηθεί
.Dir
ectiva
s, co
nform
e alte
ração
em.
Дире
ктив с
о все
ми по
прав
ками.
10 11 12 13 14 15 16 17
Direk
tiver, m
ed se
nere
ændri
nger.
Direk
tiv, m
ed fö
retag
na än
dring
ar.Dir
ektive
r, med
foret
atte e
ndrin
ger.
Direk
tiivejä
, sella
isina k
uin ne
ovat
muute
ttuina
.v p
latné
m zn
ění.
Smjer
nice,
kako
je izm
ijenjen
o.irá
nyelv
(ek) é
s mód
osítá
saik r
ende
lkezé
seit.
z póź
niejsz
ymi p
opraw
kami
.
18 19 20 21 22 23 24 25
Direc
tivelor
, cu a
mend
amen
tele r
espe
ctive.
Direk
tive z
vsemi
sprem
emba
mi.
Direk
tiivid
koos
muu
datus
tega.
Дире
ктиви
, с те
хните
изме
нени
я.Dir
ektyv
ose s
u pap
ildyma
is.Dir
ektīv
ās un
to pa
pildinā
jumos
.Sm
ernice
, v pl
atnom
znen
í.De
ğiştiri
lmiş h
alleriy
le Yö
netm
elikler
.
01 No
te*
02 Hi
nweis
*
03 Re
marqu
e*
04 Be
merk*
05 No
ta*
as se
t out
in <A
> and
judg
ed po
sitive
ly by <
B>ac
cordi
ng to
the C
ertific
ate <C
>.wie
in <A
> aufg
eführt
und v
on <B
> pos
itivbe
urteilt
gemä
ß Zert
ifikat
<C>.
tel qu
e défi
ni da
ns <A
> et é
valué
positi
veme
nt pa
r <B>
confo
rmém
ent a
u Cert
ificat
<C>.
zoals
verm
eld in
<A> e
n pos
itief b
eoord
eeld
door
<B>
overe
enko
mstig
Certif
icaat
<C>.
como
se es
tablec
e en <
A> y
es va
lorad
opo
sitiva
mente
por <
B> de
acue
rdo co
n el
Certif
icado
<C>.
06 No
ta*
07 Ση
μείω
ση*
08 No
ta*
09 Пр
имеч
ание
*
10 Be
mærk*
deline
ato ne
l <A>
e giu
dicato
positi
vame
nte da
<B>
seco
ndo i
l Cert
ificato
<C>.
όπως
καθο
ρίζετα
ι στο
<A> κ
αι κρ
ίνεται
θετικ
άαπ
ό το <
B> σύ
μφων
α με τ
ο Πιστ
οποιη
τικό <
C>.
tal co
mo es
tabele
cido e
m <A
> e co
m o p
arece
r pos
itivo
de <B
> de a
cordo
com
o Cert
ificad
o <C>
.как
указа
но в
<A> и
в со
ответс
твии с
поло
жител
ьным
реше
нием
<B> с
оглас
но Св
идете
льств
у <C>
.so
m an
ført i
<A> o
g pos
itivt v
urdere
t af <
B> i h
enho
ld til
Certif
ikat <
C>.
11 In
forma
tion*
12 M
erk*
13 Hu
om*
14 Po
znám
ka*
15 Na
pome
na*
enligt
<A> o
ch go
dkän
ts av
<B> e
nligt
Certif
ikatet
<C>.
som
det fr
emko
mmer
i <A>
og gj
enno
m po
sitiv
bedø
mmels
e av <
B> ifø
lge Se
rtifika
t <C>
.jot
ka on
esite
tty as
iakirja
ssa <A
> ja j
otka <
B>on
hyvä
ksyny
t Sert
ifikaa
tin <C
> muk
aises
ti.jak
bylo
uved
eno v
<A> a
poziti
vně z
jištěn
o<B
> v so
uladu
s os
vědč
ením
<C>.
kako
je izl
ožen
o u <A
> i po
zitivn
o ocije
njeno
od st
rane
<B> p
rema C
ertifik
atu <C
>.
16 M
egjeg
yzés*
17 Uw
aga*
18 No
tă*
19 Op
omba
*
20 M
ärkus
*
a(z) <
A> al
apján
, a(z)
<B> i
gazo
lta a
megfe
lelést,
a(z)
<C> t
anús
ítván
y sze
rint.
zgod
nie z
doku
menta
cją <A
>, po
zytyw
nąop
inią <B
> i Św
iadec
twem
<C>.
aşa c
um es
te sta
bilit în
<A> ş
i apre
ciat p
ozitiv
de <B
>în
confo
rmita
te cu
Certif
icatul
<C>.
kot je
določ
eno v
<A> i
n odo
breno
s str
ani <
B>v s
kladu
s ce
rtifika
tom <C
>.na
gu on
näida
tud do
kume
ndis <
A> ja
heak
s kiide
tud<B
> järg
i vasta
valt s
ertifik
aadil
e <C>
.
21 За
беле
жка*
22 Pa
staba
*
23 Pi
ezīme
s*
24 Po
znám
ka*
25 No
t*
както
е изл
ожен
о в <A
> и оц
енен
о пол
ожите
лно о
т <B>
съгла
сно С
ерти
фикат
а <C>
.ka
ip nu
statyt
a <A>
ir ka
ip tei
giama
i nus
pręsta
<B> p
agal
Sertif
ikatą
<C>.
kā no
rādīts
<A> u
n atbi
lstoši <
B> po
zitīva
jam vē
rtējum
amsa
skaņā
ar se
rtifikā
tu <C
>.ak
o bolo
uved
ené v
<A> a
pozití
vne z
istené
<B> v
súlad
es o
sved
čením
<C>.
<A>’d
a belir
tildiği
gibi ve
<C> S
ertifik
asına
göre
<B>
tarafı
ndan
olum
lu ola
rak de
ğerle
ndirild
iği gib
i.
<A>
<B>
<C>
TÜV
(NB
1856
)
1208
0901
.T30
DA
IKIN
.TC
F.03
0A12
/04-
2015
01**
02**
03**
04**
05**
06**
Daikin
Europ
e N.V.
is au
thoris
ed to
comp
ile the
Tech
nical
Cons
tructio
n File.
Daikin
Europ
e N.V.
hat d
ie Be
rechti
gung
die T
echn
ische
Kons
truktio
nsak
te zu
samm
enzu
stellen
.Da
ikin Eu
rope N
.V. es
t auto
risé à
comp
iler le
Dossi
er de
Cons
tructio
n Tec
hniqu
e.Da
ikin Eu
rope N
.V. is
bevo
egd o
m he
t Tec
hnisc
h Con
struc
tiedo
ssier
same
n te s
tellen
.Da
ikin Eu
rope N
.V. es
tá au
toriza
do a
comp
ilar el
Arch
ivo de
Cons
trucci
ón Té
cnica
.Da
ikin Eu
rope N
.V. è
autor
izzata
a red
igere
il File
Tecn
ico di
Costr
uzion
e.
07**
08**
09**
10**
11**
12**
Η Daik
in Eu
rope N
.V. είν
αι εξο
υσιοδ
οτημέν
η να σ
υντάξ
ει τον
Τεχν
ικό φά
κελο κ
ατασκ
ευής.
A Daik
in Eu
rope N
.V. es
tá au
toriza
da a
comp
ilar a
docu
menta
ção t
écnic
a de f
abric
o.Ко
мпан
ия Da
ikin Eu
rope N
.V. уп
олно
моче
на со
стави
ть Ко
мпле
кт тех
ниче
ской д
окуме
нтаци
и.Da
ikin Eu
rope N
.V. er
autor
iseret
til at
udarb
ejde d
e tek
niske
kons
truktio
nsda
ta.Da
ikin Eu
rope N
.V. är
bemy
ndiga
de at
t sam
mans
tälla
den t
eknis
ka ko
nstru
ktions
filen.
Daikin
Europ
e N.V.
har ti
llatels
e til å
komp
ilere d
en Te
knisk
e kon
struk
sjons
filen.
13**
14**
15**
16**
17**
18**
Daikin
Europ
e N.V.
on va
ltuute
ttu la
atima
an Te
knise
n asia
kirjan
.Sp
olečn
ost D
aikin
Europ
e N.V.
má o
právn
ění k
e kom
pilaci s
oubo
ru tec
hnick
é kon
struk
ce.
Daikin
Europ
e N.V.
je ov
lašten
za izr
adu D
atotek
e o te
hničk
oj ko
nstru
kciji.
A Daik
in Eu
rope N
.V. jo
gosu
lt a m
űsza
ki kon
struk
ciós d
okum
entác
ió ös
szeállí
tására
.Da
ikin Eu
rope N
.V. m
a upo
ważn
ienie
do zb
ieran
ia i o
praco
wywa
nia do
kume
ntacji
kons
trukcy
jnej.
Daikin
Europ
e N.V.
este
autor
izat s
ă com
pileze
Dosa
rul te
hnic d
e con
struc
ţie.
19**
20**
21**
22**
23**
24**
25**
Daikin
Europ
e N.V.
je po
oblaš
čen z
a ses
tavo d
atotek
e s te
hničn
o map
o.Da
ikin Eu
rope N
.V. on
volita
tud ko
ostam
a teh
nilist
doku
menta
tsioon
i.Da
ikin Eu
rope N
.V. е
отори
зиран
а да с
ъстав
и Акта
за те
хнич
еска
констр
укция
.Da
ikin Eu
rope N
.V. yr
a įga
liota s
udary
ti šį te
chnin
ės ko
nstru
kcijos
failą.
Daikin
Europ
e N.V.
ir au
torizē
ts sa
stādīt
tehn
isko d
okum
entāc
iju.Sp
oločn
osť D
aikin
Europ
e N.V.
je op
rávne
ná vy
tvoriť
súbo
r tech
nicke
j konš
trukci
e.Da
ikin Eu
rope N
.V. Te
knik Y
apı D
osya
sını d
erlem
eye y
etkilid
ir.
Shi
geki
Mor
itaD
irect
orO
sten
d, 1
st o
f Apr
il 20
16
Table of Contents
Installation and operation manual
4RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
Table of Contents
1 About the documentation 51.1 About this document.................................................................. 5
For the installer 5
2 About the box 52.1 Outdoor unit............................................................................... 5
2.1.1 To remove the accessories from the outdoor unit....... 5
3 About the units and options 53.1 About the outdoor unit ............................................................... 53.2 System layout............................................................................ 5
4 Preparation 64.1 Preparing installation site .......................................................... 6
4.1.1 Installation site requirements of the outdoor unit ........ 64.1.2 Additional installation site requirements of the
outdoor unit in cold climates ....................................... 64.2 Preparing refrigerant piping....................................................... 6
4.2.1 Refrigerant piping requirements.................................. 64.2.2 Refrigerant piping material.......................................... 64.2.3 To select the piping size ............................................. 64.2.4 To select refrigerant branch kits.................................. 7
4.3 Preparing electrical wiring ......................................................... 74.3.1 Safety device requirements ........................................ 7
5 Installation 85.1 Opening the units ...................................................................... 8
5.1.1 To open the outdoor unit............................................. 85.2 Mounting the outdoor unit.......................................................... 8
5.2.1 To provide the installation structure ............................ 85.2.2 To install the outdoor unit............................................ 85.2.3 To provide drainage .................................................... 85.2.4 To prevent the outdoor unit from falling over .............. 9
5.3 Connecting the refrigerant piping .............................................. 95.3.1 Using the stop valve and service port ......................... 95.3.2 To connect the refrigerant piping to the outdoor unit .. 9
5.4 Checking the refrigerant piping ................................................. 105.4.1 About checking the refrigerant piping ......................... 105.4.2 Checking refrigerant piping: General guidelines ......... 115.4.3 Checking refrigerant piping: Setup.............................. 115.4.4 To perform a leak test ................................................. 115.4.5 To perform vacuum drying .......................................... 11
5.5 To insulate the refrigerant piping............................................... 115.6 Charging refrigerant .................................................................. 12
5.6.1 Precautions when charging refrigerant ....................... 125.6.2 To determine the additional refrigerant amount .......... 125.6.3 To charge refrigerant .................................................. 125.6.4 Error codes when charging refrigerant........................ 135.6.5 To fix the fluorinated greenhouse gases label ............ 13
5.7 Connecting the electrical wiring................................................. 135.7.1 Field wiring: Overview................................................. 135.7.2 Guidelines when knocking out knockout holes ........... 145.7.3 Guidelines when connecting the electrical wiring ....... 145.7.4 To connect the electrical wiring on the outdoor unit.... 14
5.8 Finishing the outdoor unit installation ........................................ 155.8.1 To finish the transmission wiring................................. 15
6 Configuration 156.1 Making field settings.................................................................. 15
6.1.1 About making field settings ......................................... 156.1.2 To access the field setting components...................... 156.1.3 Field setting components ............................................ 156.1.4 To access mode 1 or 2 ............................................... 166.1.5 To use mode 1 ............................................................ 16
6.1.6 To use mode 2 ............................................................. 176.1.7 Mode 1 (and default situation): Monitoring settings ..... 176.1.8 Mode 2: Field settings.................................................. 186.1.9 To connect the PC configurator to the outdoor unit ..... 20
7 Commissioning 207.1 Precautions when commissioning .............................................. 207.2 Checklist before commissioning................................................. 207.3 Checklist during commissioning ................................................. 20
7.3.1 About test run............................................................... 217.3.2 To perform a test run (7-LEDs display)........................ 217.3.3 Correcting after abnormal completion of the test run... 217.3.4 Operating the unit ........................................................ 21
8 Troubleshooting 218.1 Solving problems based on error codes..................................... 21
8.1.1 Error codes: Overview ................................................. 21
9 Technical data 229.1 Service space: Outdoor unit ....................................................... 239.2 Piping diagram: Outdoor unit...................................................... 239.3 Wiring diagram: Outdoor unit ..................................................... 24
For the user 25
10 About the system 2510.1 System layout............................................................................. 25
11 User interface 25
12 Operation 2512.1 Operation range ......................................................................... 2512.2 Operating the system ................................................................. 25
12.2.1 About operating the system ......................................... 2512.2.2 About cooling, heating, fan only, and automatic
operation ...................................................................... 2512.2.3 About the heating operation......................................... 2512.2.4 To operate the system ................................................. 26
12.3 Using the dry program................................................................ 2612.3.1 About the dry program ................................................. 2612.3.2 To use the dry program................................................ 26
12.4 Adjusting the air flow direction.................................................... 2612.4.1 About the air flow flap .................................................. 26
12.5 Setting the master user interface ............................................... 2612.5.1 About setting the master user interface ....................... 2612.5.2 To designate the master user interface (VRV DX)....... 2712.5.3 To designate the master user interface (RA DX) ......... 27
13 Maintenance and service 2713.1 About the refrigerant................................................................... 2713.2 After-sales service and warranty ................................................ 27
13.2.1 Warranty period ........................................................... 2713.2.2 Recommended maintenance and inspection............... 27
14 Troubleshooting 2814.1 Error codes: Overview................................................................ 2814.2 Symptoms that are not air conditioner troubles.......................... 29
14.2.1 Symptom: The system does not operate ..................... 2914.2.2 Symptom: Fan operation is possible, but cooling and
heating do not work...................................................... 2914.2.3 Symptom: The fan strength does not correspond to
the setting .................................................................... 2914.2.4 Symptom: The fan direction does not correspond to
the setting .................................................................... 2914.2.5 Symptom: White mist comes out of a unit (Indoor
unit) .............................................................................. 2914.2.6 Symptom: White mist comes out of a unit (Indoor
unit, outdoor unit) ......................................................... 2914.2.7 Symptom: The user interface display reads "U4" or
"U5" and stops, but then restarts after a few minutes.. 2914.2.8 Symptom: Noise of air conditioners (Indoor unit)......... 30
1 About the documentation
Installation and operation manual
5RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
14.2.9 Symptom: Noise of air conditioners (Indoor unit,outdoor unit)................................................................ 30
14.2.10 Symptom: Noise of air conditioners (Outdoor unit) ..... 3014.2.11 Symptom: Dust comes out of the unit ......................... 3014.2.12 Symptom: The units can give off odours..................... 3014.2.13 Symptom: The outdoor unit fan does not spin ............ 3014.2.14 Symptom: The display shows "88".............................. 3014.2.15 Symptom: The compressor in the outdoor unit does
not stop after a short heating operation ...................... 3014.2.16 Symptom: The inside of an outdoor unit is warm
even when the unit has stopped ................................. 3014.2.17 Symptom: Hot air can be felt when the indoor unit is
stopped ....................................................................... 30
15 Relocation 30
16 Disposal 30
1 About the documentation
1.1 About this documentTarget audienceAuthorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trainedusers in shops, in light industry and on farms, or forcommercial use by lay persons.
Documentation setThis document is part of a documentation set. The complete setconsists of:
▪ General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the outdoor unit)
▪ Outdoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪ Installer and user reference guide:
▪ Preparation of the installation, technical specifications,reference data,…
▪ Detailed step-by-step instructions and background informationfor basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available onthe regional Daikin website or via your dealer.
The original documentation is written in English. All other languagesare translations.
For the installer
2 About the box
2.1 Outdoor unit
2.1.1 To remove the accessories from theoutdoor unit
1 Remove the service cover. See "5.1.1 To open the outdoorunit" on page 8.
2 Remove the accessories.
a1×
b1×
c1×
d e1× 2×
a General safety precautionsb Outdoor unit installation and operation manualc Fluorinated greenhouse gases labeld Installation information stickere Cable tie
3 About the units and options
3.1 About the outdoor unitThis installation manual concerns the VRV IV-S, full inverter driven,heat pump system.
These units are intended for outdoor installation and aimed for air toair heat pump applications.
Specification RXYSCQ4+5Capacity Heating 14.2~16.0 kW
Cooling 12.1~14.0 kWAmbient designtemperature
Heating –20~15.5°C WBCooling –5~46°C DB
3.2 System layoutNOTICE
Design of the system must not be done at temperaturesbelow –15°C.
gd d
c c
f
eb
a
g
f
e
4 Preparation
Installation and operation manual
6RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
a VRV IV-S Heat pump outdoor unitb Refrigerant pipingc VRV direct expansion (DX) indoor unitd User interface (dedicated depending on indoor unit type)e BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)f Residential Air (RA) direct expansion (DX) indoor unitsg User interface (wireless, dedicated depending on indoor
unit type)
4 Preparation
4.1 Preparing installation site
4.1.1 Installation site requirements of theoutdoor unit
Mind the spacing guidelines. See the "Technical data" chapter, andthe figures on the inside of the front cover.
4.1.2 Additional installation site requirementsof the outdoor unit in cold climates
NOTICE
When operating the unit in heating in a low outdoorambient temperature with high humidity conditions, makesure to take precautions to keep the drain holes of the unitfree by using proper equipment.
In heating:
T AO (°
C W
B) a b
20
15.515
10
5
0
–5
–10
–15
–20
10 15 20 25 27 30
TAI (°C DB)
a Warming up operation range
b Operation range
TAI Ambient indoor temperature
TAO Ambient outdoor temperature
If the unit is selected to operate at ambient temperatureslower than –5°C for 5 days or longer, with relative humiditylevels exceeding 95%, we recommend to apply a Daikinrange specifically designed for such application and/or tocontact your dealer for further advice.
4.2 Preparing refrigerant piping
4.2.1 Refrigerant piping requirements
NOTICE
Refrigerant R410A requires strict cautions for keeping thesystem clean and dry. Foreign materials (including mineraloils or moisture) should be prevented from getting mixedinto the system.
NOTICE
The piping and other pressure-containing parts shall besuitable for refrigerant. Use phosphoric acid deoxidisedseamless copper for refrigerant.
▪ Foreign materials inside pipes (including oils for fabrication) mustbe ≤30 mg/10 m.
4.2.2 Refrigerant piping material▪ Piping material: Phosphoric acid deoxidised seamless copper.
▪ Piping temper grade and thickness:
Outer diameter(Ø)
Temper grade Thickness (t)(a)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Annealed (O) ≥0.80 mmt
Ø
15.9 mm (5/8") Annealed (O) ≥0.99 mm(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unitname plate), larger piping thickness might be required.
▪ Flare connections: Only use annealed material.
4.2.3 To select the piping sizeDetermine the proper size referring to following tables and referencefigure (only for indication).
INFORMATION
▪ Combination of VRV DX and RA DX indoor units is notallowed.
▪ Combination of RA DX and AHU indoor units is notallowed.
▪ Combination of RA DX and aircurtain indoor units is notallowed.
INFORMATION
If you install RA DX indoor units, you have to configurefield setting [2‑38] (= type of installed indoor units). See"6.1.8 Mode 2: Field settings" on page 18.
A
B-1 B-2
C-1 C-2 C-3 C-4 E E E E
1 1
3-1 3-2 3-3 3-4
A
D
RA DXVRV DX
D
44
5 5 5 5
2 2
2 2
1 Outdoor unit2 Refrigerant branch kits
4 Preparation
Installation and operation manual
7RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
3-1~3-4 VRV DX indoor units4 BP units5 RA DX indoor unitsA Piping between outdoor unit and (first) refrigerant branch
kitB-1 B-2 Piping between refrigerant branch kits
C-1~C-4 Piping between refrigerant branch kit and indoor unitD Piping between refrigerant branch kit and BP unitE Piping between BP unit and RA DX indoor unit
In case the required pipe sizes (inch sizes) are not available, it isalso allowed to use other diameters (mm sizes), taken the followinginto account:
▪ Select the pipe size nearest to the required size.
▪ Use the suitable adapters for the change-over from inch to mmpipes (field supply).
▪ The additional refrigerant calculation has to be adjusted asmentioned in "5.6.2 To determine the additional refrigerantamount" on page 12.
A: Piping between outdoor unit and (first)refrigerant branch kitWhen the equivalent pipe length between outdoor and indoor units is90 m or more, the size of the main gas pipe must be increased (size-up). If the recommended gas pipe (size-up) is not available, youmust use the standard size (which might result in a small capacitydecrease).
a eb c
d
a Outdoor unitb Main gas pipec Increased First refrigerant branch kite Indoor unit
Outdoor unitcapacity type (HP)
Piping outer diameter size (mm)Gas pipe Liquid pipe
Standard Size-up4+5 15.9 19.1 9.5
B: Piping between refrigerant branch kitsChoose from the following table in accordance with the indoor unittotal capacity type, connected downstream. Do not let theconnection piping exceed the refrigerant piping size chosen by thegeneral system model name.
Indoor unit capacityindex
Piping outer diameter size (mm)Gas pipe Liquid pipe
<150 15.9 9.5150≤x≤162.5 19.1
Example: Downstream capacity for B-1 = capacity index of unit 3-1+ capacity index of unit 3-2
C: Piping between refrigerant branch kit andindoor unitUse the same diameters as the connections (liquid, gas) on theindoor units. The diameters of the indoor units are as follows:
Indoor unit capacityindex
Piping outer diameter size (mm)Gas pipe Liquid pipe
15~50 12.7 6.463~140 15.9 9.5
D: Piping between refrigerant branch kit and BPunit
Total capacity indexof connected indoor
units
Piping outer diameter size (mm)Gas pipe Liquid pipe
15~62 12.7 6.463~149 15.9 9.5
E: Piping between BP unit and RA DX indoor unit
Indoor unit capacityindex
Piping outer diameter size (mm)Gas pipe Liquid pipe
15~42 9.5 6.450 12.760 9.571 15.9
4.2.4 To select refrigerant branch kitsFor piping example, refer to "4.2.3 To select the piping size" onpage 6.
Refnet joint at first branch (counting from outdoor unit)When using refnet joints at the first branch counted from the outdoorunit side, choose from the following table in accordance with thecapacity of the outdoor unit. Example: Refnet joint A→B‑1.
Outdoor unit capacity type(HP)
Refrigerant branch kit
4+5 KHRQ22M20T
Refnet joints at other branchesFor refnet joints other than the first branch, select the proper branchkit model based on the total capacity index of all indoor unitsconnected after the refrigerant branch. Example: Refnet jointB‑1→C‑1.
Indoor unit capacity index Refrigerant branch kit<162.5 KHRQ22M20T
Refnet headersConcerning refnet headers, choose from the following table inaccordance with the total capacity of all the indoor units connectedbelow the refnet header.
Indoor unit capacity index Refrigerant branch kit<162.5 KHRQ22M29H
INFORMATION
Maximum 8 branches can be connected to a header.
4.3 Preparing electrical wiring
4.3.1 Safety device requirementsThe power supply must be protected with the required safetydevices, i.e. a main switch, a slow blow fuse on each phase and anearth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance withthe applicable legislation based on the information mentioned in thetable below.
Model Minimum circuitampacity
Recommendedfuses
RXYSCQ4+5 29.1 A 32 A
For all models:
5 Installation
Installation and operation manual
8RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
▪ Phase and frequency: 1~ 50 Hz
▪ Voltage: 220-240 V
▪ Transmission line section:
Transmission wiring Vinyl cords with 0.75 to1.25 mm² sheath or cables
(2‑core wires)Maximum wiring length
(= distance between outdoorand furthest indoor unit)
300 m
Total wiring length
(= distance between outdoorand all indoors)
600 m
If the total transmission wiring exceeds these limits, it mayresult in communication error.
5 Installation
5.1 Opening the units
5.1.1 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
5×
5.2 Mounting the outdoor unit
5.2.1 To provide the installation structurePrepare 4 sets of anchor bolts, nuts and washers (field supply) asfollows:
(mm) >150
620(485-495)
490
4× M12
a
a Make sure not to cover the drain holes.
INFORMATION
The recommended height of the upper protruding part ofthe bolts is 20 mm.
20
NOTICE
Fix the outdoor unit to the foundation bolts using nuts withresin washers (a). If the coating on the fastening area isstripped off, the nuts rust easily.
a
5.2.2 To install the outdoor unit
4× M12
5.2.3 To provide drainage▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is a properdrainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drainwaste water surrounding the unit.
▪ Avoid drain water flowing over the footpath, so that it does notbecome slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within150 mm of the bottom side of the unit in order to prevent theinvasion of water in the unit and to avoid the drain water dripping(see the following illustration).
NOTICE
If drain holes of the outdoor unit are covered by a mountingbase or by floor surface, raise the unit to provide a freespace of more than 150 mm under the outdoor unit.
≥150
mm
5 Installation
Installation and operation manual
9RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
Drain holes (dimensions in mm)52
102
118
5962
216 130
2098
21 89
32
a
a Drain holes
5.2.4 To prevent the outdoor unit from fallingover
1 Prepare 2 cables as indicated in the following illustration (fieldsupply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unitto prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.
5.3 Connecting the refrigerant pipingDANGER: RISK OF BURNING
5.3.1 Using the stop valve and service port
To handle the stop valve▪ Make sure to keep all stop valves open during operation.
▪ The stop valve is factory closed.
To open the stop valve1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stopvalve counterclockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now open.
1
23
4
To close the stop valve1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stopvalve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now closed.
Closing direction:
To handle the stop valve cover▪ The stop valve cover is sealed where indicated by the arrow. Take
care not to damage it.
▪ After handling the stop valve, make sure to tighten the stop valvecover securely. For the tightening torque, refer to the table below.
▪ Check for refrigerant leaks after tightening the stop valve cover.
To handle the service port▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the serviceport cover securely. For the tightening torque, refer to the tablebelow.
▪ Check for refrigerant leaks after tightening the service port cover.
Tightening torques
Stop valvesize (mm)
Tightening torque N•m (turn clockwise to close)Shaft
Valve body Hexagonalwrench
Cap (valvelid)
Serviceport
Ø9.5 5.4~6.6 4 mm 13.5~16.5 11.5~13.9Ø15.9 13.5~16.5 6 mm 22.5~27.5
5.3.2 To connect the refrigerant piping to theoutdoor unit
NOTICE
Be sure that the field installed piping does not touch otherpipes, the bottom panel or side panel. Especially for thebottom and side connection, be sure to protect the pipingwith suitable insulation, to prevent it from coming intocontact with the casing.
1 Do the following:
▪ Remove the service cover. See "5.1.1 To open the outdoorunit" on page 8.
▪ Remove the piping intake plate (a) with screw (b).
ab
2 Choose a piping route (a, b or c).
5 Installation
Installation and operation manual
10RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
ab
c
3 If you have chosen the downwards piping route:
▪ Drill (a, 4×) and remove the knockout hole (b).▪ Cut out the slits (c) with a metal saw.
cc
ba4× Ø6 mm
4 Do the following:
▪ Connect the liquid pipe (a) to the liquid stop valve.▪ Connect the gas pipe (b) to the gas stop valve.
ab
5 Reattach the service cover and the piping intake plate.
6 Seal all gaps (example: a) to prevent snow and small animalsfrom entering the system.
a
WARNING
Provide adequate measures to prevent that the unit can beused as a shelter by small animals. Small animals thatmake contact with electrical parts can cause malfunctions,smoke or fire.
NOTICE
Make sure to open the stop valves after installing therefrigerant piping and performing vacuum drying. Runningthe system with the stop valves closed may break thecompressor.
5.4 Checking the refrigerant piping
5.4.1 About checking the refrigerant pipingRefrigerant piping works are finished?
The indoor units and/or outdoor unit were already powered ON?
Use procedure:"Method 2: After power ON".
Finish piping work.
Use procedure:"Method 1: Before power ON (regular method)".
Yes
No
No
Yes
It is very important that all refrigerant piping work is done before theunits (outdoor or indoor) are powered on.
When the units are powered on, the expansion valves will initialise.This means that they will close. Leak test and vacuum drying of fieldpiping and indoor units is impossible when this happens.
Therefore, there will be explained 2 methods for initial installation,leak test and vacuum drying.
Method 1: Before power ONIf the system has not yet been powered on, no special action isrequired to perform the leak test and the vacuum drying.
Method 2: After power ONIf the system has already been powered on, activate setting [2‑21](refer to "6.1.4 To access mode 1 or 2" on page 16). This settingwill open field expansion valves to guarantee a R410A pipingpathway and make it possible to perform the leak test and thevacuum drying.
NOTICE
Make sure that all indoor units connected to the outdoorunit are powered on.
NOTICE
Wait until the outdoor unit has finished the initialisation toapply setting [2‑21].
Leak test and vacuum dryingChecking the refrigerant piping involves:
▪ Checking for any leakages in the refrigerant piping.
▪ Performing vacuum drying to remove all moisture, air or nitrogenin the refrigerant piping.
If there is a possibility of moisture being present in the refrigerantpiping (for example, water may have entered the piping), first carryout the vacuum drying procedure below until all moisture has beenremoved.
All piping inside the unit has been factory tested for leaks.
Only field installed refrigerant piping needs to be checked.Therefore, make sure that all the outdoor unit stop valves are firmlyclosed before performing leak test or vacuum drying.
NOTICE
Make sure that all (field supplied) field piping valves areOPEN (not outdoor unit stop valves!) before you start leaktest and vacuuming.
5 Installation
Installation and operation manual
11RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
For more information on the state of the valves, refer to"5.4.3 Checking refrigerant piping: Setup" on page 11.
5.4.2 Checking refrigerant piping: Generalguidelines
Connect the vacuum pump through a manifold to the service port ofall stop valves to increase efficiency (refer to "5.4.3 Checkingrefrigerant piping: Setup" on page 11).
NOTICE
Use a 2-stage vacuum pump with a non-return valve or asolenoid valve that can evacuate to a gauge pressure of–100.7 kPa (5 Torr absolute).
NOTICE
Make sure the pump oil does not flow oppositely into thesystem while the pump is not working.
NOTICE
Do not purge the air with refrigerants. Use a vacuum pumpto evacuate the installation.
5.4.3 Checking refrigerant piping: Setupp< p>
N2
C
b c e
agf
d
A B
a Pressure reducing valveb Nitrogenc Weighing scalesd Refrigerant R410A tank (siphon system)e Vacuum pumpf Liquid line stop valveg Gas line stop valveA Valve AB Valve BC Valve C
Valve State of valveValve A OpenValve B OpenValve C OpenLiquid line stop valve CloseGas line stop valve Close
NOTICE
The connections to the indoor units and all indoor unitsshould also be leak and vacuum tested. Keep any possible(field supplied) field piping valves open as well.
Refer to the indoor unit installation manual for more details.Leak test and vacuum drying should be done before thepower supply is set to the unit. If not, see also the flowchart earlier described in this chapter (see "5.4.1 Aboutchecking the refrigerant piping" on page 10).
5.4.4 To perform a leak testThe leak test must satisfy the specifications of EN378‑2.
To check for leaks: Vacuum leak test1 Evacuate the system from the liquid and gas piping to
–100.7 kPa (–1.007 bar/5 Torr) for more than 2 hours.
2 Once reached, turn off the vacuum pump and check that thepressure does not rise for at least 1 minute.
3 Should the pressure rise, the system may either containmoisture (see vacuum drying below) or have leaks.
To check for leaks: Pressure leak test1 Break the vacuum by pressurising with nitrogen gas to a
minimum gauge pressure of 0.2 MPa (2 bar). Never set thegauge pressure higher than the maximum operation pressure ofthe unit, i.e. 4.0 MPa (40 bar).
2 Test for leaks by applying a bubble test solution to all pipingconnections.
3 Discharge all nitrogen gas.
NOTICE
Make sure to use a recommended bubble test solutionfrom your wholesaler. Do not use soap water, which maycause cracking of flare nuts (soap water may contain salt,which absorbs moisture that will freeze when the pipinggets cold), and/or lead to corrosion of flared joints (soapwater may contain ammonia which causes a corrosiveeffect between the brass flare nut and the copper flare).
5.4.5 To perform vacuum dryingTo remove all moisture from the system, proceed as follows:
1 Evacuate the system for at least 2 hours to a target vacuum of–100.7 kPa (–1.007 bar/5 Torr).
2 Check that, with the vacuum pump turned off, the targetvacuum is maintained for at least 1 hour.
3 Should you fail to reach the target vacuum within 2 hours ormaintain the vacuum for 1 hour, the system may contain toomuch moisture. In that case, break the vacuum by pressurisingwith nitrogen gas to a gauge pressure of 0.05 MPa (0.5 bar)and repeat steps 1 to 3 until all moisture has been removed.
4 Depending on whether you want to immediately chargerefrigerant through the refrigerant charge port or first pre-chargea portion of refrigerant through the liquid line, either open theoutdoor unit stop valves, or keep them closed. See "5.6.3 Tocharge refrigerant" on page 12 for more information.
5.5 To insulate the refrigerant pipingAfter finishing the leak test and vacuum drying, the piping must beinsulated. Take into account the following points:
▪ Make sure to insulate the connection piping and refrigerant branchkits entirely.
▪ Be sure to insulate the liquid and gas piping (for all units).
▪ Use heat resistant polyethylene foam which can withstand atemperature of 70°C for liquid piping and polyethylene foam whichcan withstand a temperature of 120°C for gas piping.
▪ Reinforce the insulation on the refrigerant piping according to theinstallation environment.
Ambienttemperature
Humidity Minimum thickness
≤30°C 75% to 80% RH 15 mm>30°C ≥80% RH 20 mm
Condensation might form on the surface of the insulation.
▪ If there is a possibility that condensation on the stop valve mightdrip down into the indoor unit through gaps in the insulation andpiping because the outdoor unit is located higher than the indoorunit, this must be prevented by sealing up the connections. Seebelow figure.
5 Installation
Installation and operation manual
12RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
b
a
a Insulation materialb Caulking etc.
5.6 Charging refrigerant
5.6.1 Precautions when charging refrigerant
WARNING
▪ Only use R410A as refrigerant. Other substances maycause explosions and accidents.
▪ R410A contains fluorinated greenhouse gases. Itsglobal warming potential (GWP) value is 2087.5. DoNOT vent these gases into the atmosphere.
▪ When charging refrigerant, always use protectivegloves and safety glasses.
NOTICE
If the power of some units is turned off, the chargingprocedure cannot be finished properly.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
NOTICE
If operation is performed within 12 minutes after the indoorand outdoor units are turned on, the compressor will notoperate before the communication is established in acorrect way between outdoor unit(s) and indoor units.
NOTICE
Before starting charging procedures, check if the 7‑LEDsdisplay is as normal (see "6.1.4 To access mode 1 or 2" onpage 16), and there is no malfunction code on the userinterface of the indoor unit. If a malfunction code ispresent, see "8.1 Solving problems based on errorcodes" on page 21.
NOTICE
Make sure all connected indoor units are recognised(setting [1‑5]).
NOTICE
Close the front panel before any refrigerant chargeoperation is executed. Without the front panel attached theunit cannot judge correctly whether it is operating properlyor not.
NOTICE
In case of maintenance and the system (outdoor unit+fieldpiping+indoor units) does not contain any refrigerant anymore (e.g., after refrigerant reclaim operation), the unit hasto be charged with its original amount of refrigerant (referto the nameplate on the unit) and the determined additionalrefrigerant amount.
5.6.2 To determine the additional refrigerantamount
INFORMATION
For final charge adjustment in a test laboratory, contactyour dealer.
Additional refrigerant to be charged=R (kg). R should be rounded offin units of 0.1 kg.
R=[(X1×Ø9.5)×0.059+(X2×Ø6.4)×0.022]
X1...2=Total length (m) of liquid piping size at Øa
INFORMATION
Piping length is considered the distance from the outdoorunit to the farthest indoor unit.
When using metric piping, please take into account following tableconcerning the weight factor to be allocated. It should be substitutedin the formula for R.
Inch piping Metric pipingSize (Ø) (mm) Weight factor Size (Ø) (mm) Weight factor
6.4 0.022 6 0.0189.5 0.059 10 0.065
5.6.3 To charge refrigerantTo speed up the refrigerant charging process, it is in case of largersystems recommended to first pre-charge a portion of refrigerantthrough the liquid line before proceeding with the manual charging. Itcan be skipped, but charging will take longer then.
Pre-charging refrigerantPre-charging can be done without compressor operation, byconnecting the refrigerant bottle to the service port of the liquid stopvalve.
1 Connect as shown. Make sure that all outdoor unit stop valves,as well as valve A are closed.
p< p>
N2
C
b c e
agf
d
A B
a Pressure reducing valveb Nitrogenc Weighing scalesd Refrigerant R410A tank (siphon system)e Vacuum pumpf Liquid line stop valveg Gas line stop valveA Valve AB Valve BC Valve C
2 Open valves C and B.
3 Pre‑charge refrigerant until the determined additional refrigerantamount is reached or pre‑charging is not possible anymore, andthen close valves C and B.
4 Do one of the following:
If ThenThe determined additionalrefrigerant amount is reached
Disconnect the manifold fromthe liquid line.
You do not have to perform the"Charging refrigerant (inmanual additional refrigerantcharge mode)" instructions.
5 Installation
Installation and operation manual
13RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
If ThenToo much refrigerant ischarged
Recover refrigerant.
Disconnect the manifold fromthe liquid line.
You do not have to perform the"Charging refrigerant (inmanual additional refrigerantcharge mode)" instructions.
The determined additionalrefrigerant amount is notreached yet
Disconnect the manifold fromthe liquid line.
Continue with the "Chargingrefrigerant (in manualadditional refrigerant chargemode)" instructions.
Charging refrigerant (in manual additional refrigerant chargemode)The remaining additional refrigerant charge can be charged byoperating the outdoor unit by means of the manual additionalrefrigerant charge mode.
5 Connect as shown. Make sure valve A is closed.
p< p>
R410A
a c
db
Ad
a Weighing scalesb Refrigerant R410A tank (siphon system)c Vacuum pumpd Refrigerant charge portA Valve A
NOTICE
The refrigerant charging port is connected to the pipinginside the unit. The unit's internal piping is already factorycharged with refrigerant, so be careful when connectingthe charge hose.
6 Open all outdoor unit stop valves. At this point, valve A mustremain closed!
7 Take all the precautions mentioned in "6 Configuration" onpage 15 and "7 Commissioning" on page 20 into account.
8 Turn on the power of the indoor units and outdoor unit.
9 Activate setting [2‑20] to start the manual additional refrigerantcharge mode. For details, see "6.1.8 Mode 2: Field settings" onpage 18.
Result: The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automaticallystop within 30 minutes. If charging is not completed after30 minutes, perform the additional refrigerant chargingoperation again.
INFORMATION
▪ When a malfunction is detected during the procedure(e.g., in case of closed stop valve), a malfunction codewill be displayed. In that case, refer to "5.6.4 Errorcodes when charging refrigerant" on page 13 andsolve the malfunction accordingly. Resetting themalfunction can be done by pushing BS3. You canrestart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible bypushing BS3. The unit will stop and return to idlecondition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additionalrefrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant chargemode.
NOTICE
Make sure to open all stop valves after (pre-) charging therefrigerant.
Operating with the stop valves closed will damage thecompressor.
NOTICE
After adding the refrigerant, do not forget to close the lid ofthe refrigerant charging port. The tightening torque for thelid is 11.5 to 13.9 N•m.
5.6.4 Error codes when charging refrigerant
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm themalfunction code and take corresponding action, "8.1 Solvingproblems based on error codes" on page 21.
5.6.5 To fix the fluorinated greenhouse gaseslabel
1 Fill in the label as follows:
bContains fluorinated greenhouse gases
21 1
1
2
2 kgtCO2eq
GWP × kg1000
==
+
kg=
kg=GWP: XXX
RXXXa
fc
de
a If a multilingual fluorinated greenhouse gases label isdelivered with the unit (see accessories), peel off theapplicable language and stick it on top of a.
b Factory refrigerant charge: see unit name platec Additional refrigerant amount chargedd Total refrigerant chargee Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO2-equivalentf GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the totalrefrigerant charge in the system (expressed as tonnesCO2-equivalent) is used to determine the maintenanceintervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:GWP value of the refrigerant × Total refrigerant charge [inkg] / 1000
2 Fix the label on the inside of the outdoor unit. There is adedicated place for it on the wiring diagram label.
5.7 Connecting the electrical wiring
5.7.1 Field wiring: OverviewField wiring consists of power supply (always including earth) andindoor-outdoor communication (= transmission) wiring.
Example:
5 Installation
Installation and operation manual
14RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
a
b
d
c
b g g
fffh
eee
a
h h hh h
c
a Field power supply (with earth leakage protector)b Main switchc Earth connectiond Outdoor unite Indoor unitf User interfaceg Power supply wiring (sheathed cable) (230 V)h Transmission wiring (sheathed cable) (16 V)
Power supply 1~ 50 HzEarth wiring
5.7.2 Guidelines when knocking out knockoutholes
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend youremove the burrs and paint the edges and areasaround the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockoutholes, wrap the wiring with protective tape to preventdamage.
b caa Knockout holeb Burrc Sealant etc.
5.7.3 Guidelines when connecting the electricalwiring
Tightening torques
Wiring Screw size Tightening torque(N•m)
Power supply wiring
(power supply +shielded ground)
M5 2.0~3.0
Transmission wiring M3.5 0.8~0.97
5.7.4 To connect the electrical wiring on theoutdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstructproper reattachment of the service cover.
1 Remove the service cover.
2 Connect the transmission wiring as follows:
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
a
b
X2M
TO OUT/DTO IN/D
a Use the conductor of sheathed wire (2 wire) (no polarity)b Terminal board (field supply)
WARNING
You must use shielded wire and connect the earth to thetransmission terminal (X2M).
TO IN/D UNIT
F1 F2 F1 F2
TO OUT/D UNIT
a
a Earth
3 Connect the power supply as follows:1~ 50 Hz
220-240 V
X1M
ab
c
a Earth leakage circuit breakerb Fusec Power supply cable
4 Fix the cables (power supply and transmission wiring) withcable ties.
NL
a
X1M
X2M
ba
a Cable tieb Attachment plate
X1M Power supplyX2M Transmission wiring
5 Route the wiring through the frame and connect it to it.
6 Configuration
Installation and operation manual
15RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
Routing throughthe frame
ab
a Power supply cable
b Transmission wiring cableConnecting to theframe
When cables are routed from the unit, aprotection sleeve for the conduits (PGinsertions) can be inserted at the knockouthole.
When you do not use a wire conduit,protect the wires with vinyl tubes toprevent the edge of the knockout hole fromcutting the wires.
a b c d e
A B
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
6 Reattach the service cover.
7 Connect an earth leakage circuit breaker and fuse to the powersupply line.
5.8 Finishing the outdoor unitinstallation
5.8.1 To finish the transmission wiringAfter installing the transmission wires inside the unit, wrap themalong with the on-site refrigerant pipes using finishing tape, asshown in figure below.
a bc de
a Liquid pipeb Gas pipec Insulatord Transmission wiring (F1/F2)e Finishing tape
6 ConfigurationINFORMATION
It is important that all information in this chapter is readsequentially by the installer and that the system isconfigured as applicable.
DANGER: RISK OF ELECTROCUTION
6.1 Making field settings
6.1.1 About making field settingsTo configure the heat pump system, you must give input to theoutdoor unit's main PCB (A1P). This involves the following fieldsetting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
Field settings are defined by their mode, setting and value. Example:[2‑8]=4.
PC configuratorFor VRV IV-S heat pump system it is alternatively possible to makeseveral commissioning field settings through a personal computerinterface (for this, option EKPCCAB is required). The installer canprepare the configuration (off-site) on PC and afterwards upload theconfiguration to the system.
See also: "6.1.9 To connect the PC configurator to the outdoorunit" on page 20.
Mode 1 and 2
Mode DescriptionMode 1
(monitoringsettings)
Mode 1 can be used to monitor the currentsituation of the outdoor unit. Some field settingcontents can be monitored as well.
Mode 2
(field settings)
Mode 2 is used to change the field settings ofthe system. Consulting the current field settingvalue and changing the current field settingvalue is possible.
In general, normal operation can be resumedwithout special intervention after changing fieldsettings.
Some field settings are used for specialoperation (e.g., 1 time operation, recovery/vacuuming setting, manual adding refrigerantsetting, etc.). In such a case, it is required toabort the special operation before normaloperation can restart. It will be indicated inbelow explanations.
6.1.2 To access the field setting componentsSee "5.1.1 To open the outdoor unit" on page 8.
6.1.3 Field setting components
NOTICE
The DIP switch (DS1 on A1P) is not used. Do NOT changethe factory setting.
The components to make field settings are as follows:
A1PX1M X2M
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H1P H2P H3P H4P H5P H6P H7P
MODETEST:
L.N.O.P. DEMANDC/H SELECT
HWL: IND MASTER SLAVE
H8P
MULTI
BS1~BS5 Push buttonsH1P~H7P 7‑LEDs display
H8P LED for indication during initialisationON ( ) OFF ( ) Flashing ( )
6 Configuration
Installation and operation manual
16RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
Push buttonsUse the push buttons to make the field settings. Operate the pushbuttons with an insulated stick (such as a closed ball-point pen) toavoid touching of live parts.
BS1 MODE: For changing the set modeBS2 SET: For field settingBS3 RETURN: For field settingBS4 TEST: For test operationBS5 RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
7‑LEDs displayThe display gives feedback about the field settings, which aredefined as [Mode-Setting]=Value.
H1P Shows the modeH2P~H7P Shows the settings and values, represented in binary code
Example:
H1P H2P H3P H4P H5P H6P H7P
- + + + + +[H1P 32 16 8 4 2 1] Description
(H1P OFF)
Default situation
(H1P flashing)
Mode 1
(H1P ON)
Mode 2
+ + + + +0 0 8 0 0 0
(H2P~H7P = binary 8)
Setting 8
(in mode 2)
+ + + + +0 0 0 4 0 0
(H2P~H7P = binary 4)
Value 4
(in mode 2)
6.1.4 To access mode 1 or 2After the units are turned ON, the display goes to its defaultsituation. From there, you can access mode 1 and mode 2.
Initialisation: default situation
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
Turn on the power supply of the outdoor unit and all indoor units.When the communication between indoor units and outdoor unit isestablished and normal, the display indication state will be as below(default situation when shipped from factory).
10~12 min
b
c
a
a Power ONb Default situationc LED indication when there is a malfunction
If the default situation is not displayed after 10~12 minutes, checkthe malfunction code on the indoor unit user interface. Solve themalfunction code accordingly. First, check the communication wiring.
Switching between modesUse BS1 to switch between the default situation, mode 1 andmode 2.
BS1 [5 s]BS1BS1 BS1
a
cba Default situation (H1P OFF)b Mode 1 (H1P flashing)c Mode 2 (H1P ON)
BS1 Press BS1.BS1 [5 s] Press BS1 for at least 5 s.
INFORMATION
If you get confused in the middle of the process, press BS1to return to the default situation.
6.1.5 To use mode 1In mode 1 (and in default situation) you can read out someinformation.
Example: 7‑LEDs display – Default situationYou can read out the status of low noise operation as follows:
# Action Button/display1 Make sure the LEDs are
showing the default situation.(H1P OFF)
2 Check the status of LEDH6P. H6P OFF: Unit is currently
not operating under low noiserestrictions.
H6P ON: Unit is currentlyoperating under low noiserestrictions.
Example: 7‑LEDs display – Mode 1You can read out setting [1‑5] (= the total number of connectedindoor units) as follows:
# Action Button/display1 Start from the default
situation.2 Select mode 1. BS1 [1×]
3 Select setting 5.
("X×" depends on the settingthat you want to select.)
BS2 [X×]
(= binary 5)4 Display the value of setting 5.
(there are 8 indoor unitsconnected)
BS3 [1×]
(= binary 8)5 Quit mode 1. BS1 [1×]
6 Configuration
Installation and operation manual
17RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
6.1.6 To use mode 2In mode 2 you can make field settings to configure the system.
Example: 7‑LEDs display – Mode 2You can change the value of setting [2‑8] (= Te target temperatureduring cooling operation) to 4 (= 8°C) as follows:
# Action Button/display1 Start from the default
situation.2 Select mode 2. BS1 [5 s]
3 Select setting 8.
("X×" depends on the settingthat you want to select.)
BS2 [X×]
(= binary 8)4 Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"depends on the currentvalue, and the value that youwant to select.)
c: Enter the value in thesystem.
d: Confirm. The system startsoperating according to thesetting.
BS2 [X×]b
a
BS3 [1×]c
BS3 [1×]d
BS3 [1×]
5 Quit mode 2. BS1 [1×]
6.1.7 Mode 1 (and default situation): Monitoringsettings
In mode 1 (and in default situation) you can read out someinformation.
7‑LEDs display – Default situation (H1P OFF)You can read out the following information:
Value / DescriptionH6P Shows the status of low noise operation.
OFF
Unit is currently not operating under low noiserestrictions.
ON
Unit is currently operating under low noiserestrictions.
Low noise operation reduces the sound generated by theunit compared to nominal operating conditions.
Low noise operation can be set in mode 2. There are twomethods to activate low noise operation of the outdoor unitsystem.
▪ The first method is to enable an automatic low noiseoperation during night time by field setting. The unit willoperate at the selected low noise level during theselected time frames.
▪ The second method is to enable low noise operationbased on an external input. For this operation an optionalaccessory is required.
Value / DescriptionH7P Shows the status of power consumption limitation operation.
OFF
Unit is currently not operating under powerconsumption limitations.
ON
Unit is currently operating under power consumptionlimitation.
Power consumption limitation reduces the powerconsumption of the unit compared to nominal operatingconditions.
Power consumption limitation can be set in mode 2. Thereare two methods to activate power consumption limitation ofthe outdoor unit system.
▪ The first method is to enable a forced power consumptionlimitation by field setting. The unit will always operate atthe selected power consumption limitation.
▪ The second method is to enable power consumptionlimitation based on an external input. For this operationan optional accessory is required.
7‑LEDs display – Mode 1 (H1P flashing)You can read out the following information:
Setting( )
Value / Description
[1‑5]
Shows the total number ofconnected indoor units.
It can be convenient to check ifthe total number of indoor unitswhich are installed match thetotal number of indoor unitswhich are recognised by thesystem. In case there is amismatch, it is advised to checkthe communication wiring pathbetween outdoor and indoor units(F1/F2 communication line).
[1‑14]
Shows the latest malfunctioncode.
When the latest malfunctioncodes were reset by accident onan indoor unit user interface, theycan be checked again throughthis monitoring settings.
For the content or reason behindthe malfunction code see"8.1 Solving problems based onerror codes" on page 21, wheremost relevant malfunction codesare explained. Detailedinformation about malfunctioncodes can be consulted in theservice manual of this unit.
To obtain more detailedinformation about the malfunctioncode, press BS2 up to 3 times.
[1‑15]
Shows the 2nd last malfunctioncode.[1‑16]
Shows the 3rd last malfunctioncode.
6 Configuration
Installation and operation manual
18RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
6.1.8 Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The LEDs give a binary representation of the setting/value number.
Setting
(= binary)
ValueDescription
[2‑8]
Te target temperature during cooling operation.
6°C
(default)
Auto
8°C9°C
10°C11°C
[2‑9]
Tc target temperature during heating operation. (default)
Auto
46°C43°C
[2‑12]
Enable the low noise function and/or power consumption limitationvia external control adaptor (DTA104A61/62).
If the system needs to be running under low noise operation orunder power consumption limitation conditions when an externalsignal is sent to the unit, this setting should be changed. Thissetting will only be effective when the optional external controladaptor (DTA104A61/62) is installed in the indoor unit.
(default)
Deactivated.
Activated.
[2‑18]
Fan high static pressure setting.
In order to increase the static pressure the outdoor unit fan isdelivering, this setting should be activated. For details about thissetting, see technical specifications.
(default)
Deactivated.
Activated.
[2‑20]
Manual additional refrigerant charge.
In order to add the additional refrigerant charge amount in amanual way (without automatic refrigerant charging functionality),following setting should be applied.
(default)
Deactivated.
Activated.
To stop the manual additional refrigerantcharge operation (when the required additionalrefrigerant amount is charged), push BS3. Ifthis function was not aborted by pushing BS3,the unit will stop its operation after 30 minutes.If 30 minutes was not sufficient to add theneeded refrigerant amount, the function can bereactivated by changing the field setting again.
[2‑21]
Refrigerant recovery/vacuuming mode.
In order to achieve a free pathway to reclaim refrigerant out of thesystem or to remove residual substances or to vacuum the systemit is necessary to apply a setting which will open required valves inthe refrigerant circuit so the reclaim of refrigerant or vacuumingprocess can be done properly.
(default)
Deactivated.
Activated.
To stop the refrigerant recovery/vacuumingmode, push BS1. If BS1 is not pushed, thesystem will remain in refrigerant recovery/vacuuming mode.
[2‑22]
Automatic low noise setting and level during night time.
By changing this setting, you activate the automatic low noiseoperation function of the unit and define the level of operation.Depending on the chosen level, the noise level will be lowered.The start and stop moments for this function are defined undersetting [2‑26] and [2‑27].
(default)
Deactivated
Level 1 Level 3<Level 2<Level 1Level 2Level 3
6 Configuration
Installation and operation manual
19RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
Setting
(= binary)
ValueDescription
[2‑25]
Low noise operation level via the external control adaptor.
If the system needs to be running under low noise operationconditions when an external signal is sent to the unit, this settingdefines the level of low noise that will be applied.
This setting will only be effective when the optional external controladaptor (DTA104A61/62) is installed and the setting [2‑12] wasactivated.
Level 1 Level 3<Level 2<Level 1
(default)
Level 2
Level 3
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
20h00
(default)
22h00
24h00[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
6h007h00
(default)
8h00
[2‑30]
Power consumption limitation level (step 1) via the external controladaptor (DTA104A61/62).
If the system needs to be running under power consumptionlimitation conditions when an external signal is sent to the unit, thissetting defines the level power consumption limitation that will beapplied for step 1. The level is according to the table.
60%
(default)
70%
80%
[2‑31]
Power consumption limitation level (step 2) via the external controladaptor (DTA104A61/62).
If the system needs to be running under power consumptionlimitation conditions when an external signal is sent to the unit, thissetting defines the level power consumption limitation that will beapplied for step 2. The level is according to the table.
30%
(default)
40%
50%
[2‑32]
Forced, all time, power consumption limitation operation (noexternal control adaptor is required to perform power consumptionlimitation).
If the system always needs to be running under powerconsumption limitation conditions, this setting activates and definesthe level power consumption limitation that will be appliedcontinuously. The level is according to the table.
(default)
Function not active.
Follows [2‑30] setting.Follows [2‑31] setting.
[2‑38]
Type of indoor units
After changing this setting, you have to power OFF the system,wait for 20 s, and then power ON again. If not, the setting will notbe processed and malfunction codes might occur.
(default)
VRV DX indoor units installed
RA DX indoor units installed
[2‑41]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
Eco
(default)
Mild
QuickPowerful
[2‑42]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
Eco
(default)
Mild
QuickPowerful
7 Commissioning
Installation and operation manual
20RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
6.1.9 To connect the PC configurator to theoutdoor unit
23
45
H JS
T
a b
c (X41A)
A1P
a PCb Cable (EKPCCAB)
c (X41A) Extension cable connected to X41AA1P Outdoor unit main PCB
7 CommissioningAfter installation and once the field settings are defined, the installeris obliged to verify correct operation. Therefore a test run must beperformed according to the procedures described below.
7.1 Precautions when commissioningCAUTION
Do not perform the test operation while working on theindoor units.
When performing the test operation, not only the outdoorunit, but the connected indoor unit will operate as well.Working on an indoor unit while performing a test operationis dangerous.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
During test operation, the outdoor unit and the indoor units will startup. Make sure that the preparations of all indoor units are finished(field piping, electrical wiring, air purge, ...). See installation manualof the indoor units for details.
7.2 Checklist before commissioningAfter the installation of the unit, first check the following items. Onceall below checks are fulfilled, the unit must be closed, only then canthe unit be powered up.
You read the complete installation and operationinstructions, as described in the installer and userreference guide.Installation
Check that the unit is properly installed, to avoid abnormalnoises and vibrations when starting up the unit.Field wiring
Be sure that the field wiring has been carried outaccording to the instructions described in the chapter"5.7 Connecting the electrical wiring" on page 13,according to the wiring diagrams and according to theapplicable legislation.
Power supply voltage
Check the power supply voltage on the local supply panel.The voltage must correspond to the voltage on theidentification label of the unit.Earth wiring
Be sure that the earth wires have been connectedproperly and that the earth terminals are tightened.Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulationresistance of 2 MΩ or more is attained by applying avoltage of 500 V DC between power terminals and earth.Never use the megatester for the transmission wiring.Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locallyinstalled protection devices are of the size and typespecified in the chapter "4.3.1 Safety devicerequirements" on page 7. Be sure that neither a fuse nor aprotection device has been bypassed.Internal wiring
Visually check the electrical component box and theinside of the unit on loose connections or damagedelectrical components.Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that theinsulation work is properly executed.Stop valves
Be sure that the stop valves are open on both liquid andgas side.Damaged equipment
Check the inside of the unit on damaged components orsqueezed pipes.Refrigerant leak
Check the inside of the unit on refrigerant leakage. If thereis a refrigerant leak, try to repair the leak. If the repair isunsuccessful, call your local dealer. Do not touch anyrefrigerant which has leaked out from refrigerant pipingconnections. This may result in frostbite.Oil leak
Check the compressor for oil leakage. If there is an oilleak, try to repair the leak. If the repairing is unsuccessful,call your local dealer.Air inlet/outlet
Check that the air inlet and outlet of the unit is notobstructed by paper sheets, cardboard, or any othermaterial.Additional refrigerant charge
The amount of refrigerant to be added to the unit shall bewritten on the included "Added refrigerant" plate andattached to the rear side of the front cover.Installation date and field setting
Be sure to keep record of the installation date on thesticker on the rear of the front panel according toEN60335‑2‑40 and keep record of the contents of the fieldsetting(s).
7.3 Checklist during commissioningTo perform a test run.
8 Troubleshooting
Installation and operation manual
21RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
7.3.1 About test runThe procedure below describes the test operation of the completesystem. This operation checks and judges following items:
▪ Check of wrong wiring (communication check with indoor units).
▪ Check of the stop valves opening.
▪ Judgement of piping length.
Make sure to carry out the system test operation after the firstinstallation. Otherwise, the malfunction code will be displayed onthe user interface and normal operation or individual indoor unit testrun cannot be carried out.
Abnormalities on indoor units cannot be checked for each unitseparately. After the test operation is finished, check the indoor unitsone by one by performing a normal operation using the userinterface. Refer to the indoor unit installation manual for more detailsconcerning the individual test run.
INFORMATION
▪ It may take 10 minutes to achieve a uniform refrigerantstate before the compressor starts.
▪ During the test operation, the refrigerant running soundor the magnetic sound of a solenoid valve may becomeloud and the display indication may change. These arenot malfunctions.
7.3.2 To perform a test run (7-LEDs display)1 Make sure all field settings you want are set; see "6.1 Making
field settings" on page 15.
2 Turn ON the power to the outdoor unit and the connectedindoor units.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
3 Make sure the default (idle) situation is existing (H1P is OFF);see "6.1.4 To access mode 1 or 2" on page 16. Push BS4 for 5seconds or more. The unit will start test operation.
Result: The test operation is automatically carried out, theoutdoor unit H2P flashes and the indication "Test operation"and "Under centralised control" will display on the user interfaceof indoor units.
Steps during the automatic system test run procedure:
Step DescriptionControl before start up (pressureequalisation)Cooling start up controlCooling stable conditionCommunication checkStop valve checkPipe length checkPump down operationUnit stop
INFORMATION
During the test operation, it is not possible to stop the unitoperation from a user interface. To abort the operation,press BS3. The unit will stop after ±30 seconds.
4 Check the test operation results on the outdoor unit 7‑LEDsdisplay.
Completion DescriptionNormalcompletionAbnormalcompletion Refer to "7.3.3 Correcting after abnormal
completion of the test run" on page 21 to takeactions for correcting the abnormality. Whenthe test operation is fully completed, normaloperation will be possible after 5 minutes.
7.3.3 Correcting after abnormal completion ofthe test run
The test operation is only completed if there is no malfunction codedisplayed. In case of a displayed malfunction code, performcorrecting actions as explained in the malfunction code table. Carryout the test operation again and confirm that the abnormality isproperly corrected.
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
INFORMATION
Refer to the installation manual of the indoor unit for otherdetailed malfunction codes related to indoor units.
7.3.4 Operating the unitOnce the unit is installed and test operation of outdoor unit andindoor units is finished, the operation of the system can start.
For operating the indoor unit, the user interface of the indoor unitshould be switched ON. Refer to the indoor unit operation manual formore details.
8 Troubleshooting
8.1 Solving problems based on errorcodes
In case of a displayed malfunction code, perform correcting actionsas explained in the malfunction code table.
After correcting the abnormality, press BS3 to reset the malfunctioncode and retry operation.
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
8.1.1 Error codes: Overview
Main code Cause Solution▪ The stop valve of an outdoor unit is left closed.
▪ Refrigerant overcharge
▪ Open the stop valve on both the gas and liquid side.
▪ Recalculate the required amount of refrigerant from thepiping length and correct the refrigerant charge level byrecovering any excessive refrigerant with a refrigerantrecovery machine.
9 Technical data
Installation and operation manual
22RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
Main code Cause Solution▪ The stop valve of an outdoor unit is left closed.
▪ Insufficient refrigerant
▪ Open the stop valve on both the gas and liquid side.
▪ Check if the additional refrigerant charge has beenfinished correctly. Recalculate the required amount ofrefrigerant from the piping length and add an adequateamount of refrigerant.
Electronic expansion valve malfunction
(Y1E) - A1P (X21A)
(Y3E) - A1P (X22A)
Check connection on PCB or actuator.
▪ The stop valve of an outdoor unit is left closed.
▪ Insufficient refrigerant
▪ Open the stop valve on both the gas and liquid side.
▪ Check if the additional refrigerant charge has beenfinished correctly. Recalculate the required amount ofrefrigerant from the piping length and add an adequateamount of refrigerant.
Refrigerant overcharge Recalculate the required amount of refrigerant from thepiping length and correct the refrigerant charge level byrecovering any excessive refrigerant with a refrigerantrecovery machine.
Ambient temperature sensor malfunction (R1T) - A1P(X11A)
Check connection on PCB or actuator.
Discharge temperature sensor malfunction (R2T): opencircuit / short circuit - A1P (X12A)
Check connection on PCB or actuator.
Suction temperature sensor malfunction
(R3T) - A1P (X12A)
(R5T) - A1P (X12A)
Check connection on PCB or actuator.
Liquid temperature sensor (coil) malfunction (R4T) - A1P(X12A)
Check connection on PCB or actuator.
Liquid temperature sensor (after subcool HE) malfunction(R7T) - A1P (X13A)
Check connection on PCB or actuator.
Gas temperature sensor (after subcool HE) malfunction(R6T) - A1P (X13A)
Check connection on PCB or actuator.
High pressure sensor malfunction (S1NPH): open circuit /short circuit - A1P (X17A)
Check connection on PCB or actuator.
Low pressure sensor malfunction (S1NPL): open circuit /short circuit - A1P (X18A)
Check connection on PCB or actuator.
Transmission outdoor unit - inverter: INV1 / FAN1transmission trouble
Check connection.
INV1 unbalanced power supply voltage Check if power supply is within range.Insufficient supply voltage Check if the supply voltage is supplied properly.Malfunction code: System test run not yet executed (systemoperation not possible)
Execute system test run.
No power is supplied to the outdoor unit. Check if the power wiring for the outdoor unit is connectedcorrectly.
Faulty wiring to Q1/Q2 Check Q1/Q2 wiring.System mismatch. Wrong type of indoor units combined(R410A, R407C, RA, etc)
Indoor unit malfunction
Check if other indoor units have malfunction and confirmindoor unit mix is allowed.
Improper type of indoor units are connected. Check the type of indoor units that are currently connected.If they are not proper, replace them with proper ones.
Incorrect interconnections between units. Connect interconnections F1 and F2 of the connected BPunit correctly to the outdoor unit's PCB (TO BP UNIT). Makesure that the communication with the BP unit is enabled.
▪ The stop valve of an outdoor unit is left closed.
▪ The piping and wiring of the specified indoor unit are notconnected correctly to the outdoor unit.
▪ Open the stop valve on both the gas and liquid side.
▪ Confirm that the piping and wiring of the specified indoorunit are connected correctly to the outdoor unit.
9 Technical dataLatest information can be found in the technical engineering data.
9 Technical data
Installation and operation manual
23RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
9.1 Service space: Outdoor unitWhen mounting units side by side, the piping route must be to the front or downwards. In this case the piping route to the side is not possible.
Single unit ( ) | Single row of units ( )See figure 1 on the inside of the front cover.
A,B,C,D Obstacles (walls/baffle plates)E Obstacle (roof)
a,b,c,d,e Minimum service space between the unit and obstacles A, B, C, D and EeB Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle BeD Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle DHU Height of the unit
HB,HD Height of obstacles B and D1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit.2 Maximum two units can be installed.
Not allowed
Multiple rows of units ( )See figure 2 on the inside of the front cover.
Stacked units (max. 2 levels) ( )See figure 3 on the inside of the front cover.
A1=>A2 (A1) If there is danger of drainage dripping and freezing between the upper and lower units…(A2) Then install a roof between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at theupper unit's bottom plate.
B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and lower units…(B2) Then it is not required to install a roof, but seal the gap between the upper and lower units to prevent discharged air from flowing back to thesuction side through the bottom of the unit.
9.2 Piping diagram: Outdoor unit
R1T
a
b
c
e
c
g
h
f
d
R4T
M1F
R2T
R5T
R7T
R3T
R6T
S1NPLS1PH
S1NPH
M1C
INV
Y1E
Y3E
Y1S
i
j
k
l
cmn
a Stop valve (gas)b Stop valve (liquid)c Filter (3×)d Subcool heat exchangere Heat sink PCBf Pressure regulating valveg Heat exchangerh Service port (high pressure)i Muffler
j Check valvek Compressor accumulatorl Capillary tube
m Service port (refrigerant charge)n Accumulator
M1C CompressorM1F Fan motorR1T Thermistor (air)R2T Thermistor (discharge)
9 Technical data
Installation and operation manual
24RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
R3T Thermistor (suction 1)R4T Thermistor (heat exchanger de-icer)R5T Thermistor (suction 2)R6T Thermistor (subcool heat exchanger)R7T Thermistor (liquid pipe)
S1NPH High pressure sensorS1NPL Low pressure sensor
S1PH High pressure switchY1E Electronic expansion valve (main)Y3E Electronic expansion valve (subcool heat exchanger)Y1S Solenoid valve (4‑way valve)
HeatingCooling
9.3 Wiring diagram: Outdoor unitThe wiring diagram is delivered with the unit, located at the inside ofthe service cover.
Notes for RXYSCQ4+5:
1 This wiring diagram applies only to the outdoor unit.
2 Symbols (see below).
3 Refer to the installation manual for how to use the BS1~BS5and DS1+DS2 switches.
4 When operating, do not short-circuit protective device S1PH.
5 Colours (see below).
6 Refer to the installation manual for connection wiring toINDOOR-OUTDOOR transmission F1-F2.
7 When using the central control system, connect OUTDOOR-OUTDOOR transmission F1-F2.
Symbols:
L Live
N Neutral
Field wiring
Terminal strip
Connector
Fixed connector
Movable connector
Protective earth (screw)
Noiseless earth
Terminal
Colours:
BLK Black
BLU Blue
BRN Brown
GRN Green
ORG Orange
RED Red
WHT White
YLW Yellow
Legend for wiring diagram RXYSCQ4+5:
A1P Printed circuit board (main)
A2P Printed circuit board
BS1~BS5 Push button switch
C1 Capacitor
DS1 DIP switch
E1HC Crankcase heater
F1U Fuse
F3U, F4U Fuse (T 6.3 A / 250 V)
F6U Fuse (T 5.0 A / 250 V)H1P~H8P Light‑emitting diode (service monitor orange)
H2P:
▪ Prepare, test: Flickering
▪ Malfunction detection: Light up
HAP Light-emitting diode (service monitor is green)
HBP Light-emitting diode (service monitor is green)
K11M Magnetic contactor
K1R Magnetic relay (Y1S)
K4R Magnetic relay (E1HC)
K10R Magnetic relay
L1R~L3R Reactor
M1C Motor (compressor)
M1F Motor (fan)
PS Switching power supply
R1, R2 Resistor
R1T Thermistor (air)
R2T Thermistor (discharge)
R3T Thermistor (suction 1)
R4T Thermistor (heat exchanger de-icer)
R5T Thermistor (suction 2)
R6T Thermistor (subcool heat exchanger)
R7T Thermistor (liquid pipe)
FINTH Thermistor (fin)
S1NPH High pressure sensor
S1NPL Low pressure sensor
S1PH High pressure switch
V1R IGBT power module
V2R Diode module
V1T~V3T Insulated gate bipolar transistor (IGBT)
V1D~V3D Diode
X1M, X2M Terminal strip
X37A Connector
Y1E Electronic expansion valve (main)
Y3E Electronic expansion valve (subcool heat exchanger)
Y1S Solenoid valve (4‑way valve)
Z1C~Z7C Noise filter (ferrite core)
Z1F~Z5F Noise filter
10 About the system
Installation and operation manual
25RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
For the user
10 About the systemThe indoor unit part of VRV IV-S heat pump system can be used forheating/cooling applications. The type of indoor unit which can beused depends on the outdoor units series.
NOTICE
Do not use the air conditioner for other purposes. In orderto avoid any quality deterioration, do not use the unit forcooling precision instruments, food, plants, animals orworks of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for futuresystem extensions) is available in technical engineeringdata and should be consulted. Contact your installer toreceive more information and professional advice.
INFORMATION
▪ Combination of VRV DX and RA DX indoor units is notallowed.
▪ Combination of RA DX and AHU indoor units is notallowed.
▪ Combination of RA DX and aircurtain indoor units is notallowed.
10.1 System layout
gd d
c c
f
eb
a
g
f
e
a VRV IV-S Heat pump outdoor unitb Refrigerant pipingc VRV direct expansion (DX) indoor unitd User interface (dedicated depending on indoor unit type)e BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)f Residential Air (RA) direct expansion (DX) indoor unitsg User interface (wireless, dedicated depending on indoor
unit type)
11 User interfaceCAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside aredangerous to touch and appliance problems may happen.For checking and adjusting the internal parts, contact yourdealer.
This operation manual will give a non-exhaustive overview of themain functions of the system.
Detailed information on required actions to achieve certain functionscan be found in the dedicated installation and operation manual ofthe indoor unit.
Refer to the operation manual of the installed user interface.
12 Operation
12.1 Operation rangeUse the system in the following temperature and humidity ranges forsafe and effective operation.
Cooling HeatingOutdoortemperature
–5~46°C DB –20~21°C DB
–20~15.5°C WBIndoortemperature
21~32°C DB
14~25°C WB
15~27°C DB
Indoor humidity ≤80%(a)
(a) To avoid condensation and water dripping out of the unit. Ifthe temperature or the humidity is beyond these conditions,safety devices may be put in action and the air conditionermay not operate.
Above operation range is only valid in case direct expansion indoorunits are connected to the VRV IV-S system.
Special operation ranges are valid in case of using AHU. They canbe found in the installation/operation manual of the dedicated unit.Latest information can be found in the technical engineering data.
12.2 Operating the system
12.2.1 About operating the system▪ Operation procedure varies according to the combination of
outdoor unit and user interface.
▪ To protect the unit, turn on the main power switch 6 hours beforeoperation.
▪ If the main power supply is turned off during operation, operationwill restart automatically after the power turns back on again.
12.2.2 About cooling, heating, fan only, andautomatic operation
▪ Changeover cannot be made with a user interface whose displayshows "change-over under centralised control" (refer toinstallation and operation manual of the user interface).
▪ When the display "change-over under centralised control"flashes, refer to "12.5.1 About setting the master userinterface" on page 26.
▪ The fan may keep on running for about 1 minute after the heatingoperation stops.
▪ The air flow rate may adjust itself depending on the roomtemperature or the fan may stop immediately. This is not amalfunction.
12.2.3 About the heating operationIt may take longer to reach the set temperature for general heatingoperation than for cooling operation.
The following operation is performed in order to prevent the heatingcapacity from dropping or cold air from blowing.
12 Operation
Installation and operation manual
26RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
Defrost operationIn heating operation, freezing of the outdoor unit's air cooled coilincreases over time, restricting the energy transfer to the outdoorunit's coil. Heating capability decreases and the system needs to gointo defrost operation to be able to deliver enough heat to the indoorunits.
The indoor unit will stop fan operation, the refrigerant cycle willreverse and energy from inside the building will be used to defrostthe outdoor unit coil.
The indoor unit will indicate defrost operation on the displays.
Hot startIn order to prevent cold air from blowing out of an indoor unit at thestart of heating operation, the indoor fan is automatically stopped.The display of the user interface shows . It may take sometime before the fan starts. This is not a malfunction.
12.2.4 To operate the system1 Press the operation mode selector button on the user interface
several times and select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system startsoperating.
12.3 Using the dry program
12.3.1 About the dry program▪ The function of this program is to decrease the humidity in your
room with minimal temperature decrease (minimal room cooling).
▪ The micro computer automatically determines temperature andfan speed (cannot be set by the user interface).
▪ The system does not go into operation if the room temperature islow (<20°C).
12.3.2 To use the dry programTo start1 Press the operation mode selector button on the user interface
several times and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system startsoperating.
3 Press the air flow direction adjust button (only for double-flow,multi-flow, corner, ceiling-suspended and wall-mounted). Referto "12.4 Adjusting the air flow direction" on page 26 for details.
To stop4 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stopsoperating.
NOTICE
Do not turn off power immediately after the unit stops, butwait for at least 5 minutes.
12.4 Adjusting the air flow directionRefer to the operation manual of the user interface.
12.4.1 About the air flow flap
Double flow+multi-flow units
Corner units
Ceiling suspended units
Wall-mounted units
For the following conditions, a micro computer controls the air flowdirection which may be different from the display.
Cooling Heating▪ When the room temperature is
lower than the settemperature.
▪ When starting operation.
▪ When the room temperature ishigher than the settemperature.
▪ At defrost operation.▪ When operating continuously at horizontal air flow direction.
▪ When continuous operation with downward air flow is performedat the time of cooling with a ceiling-suspended or a wall-mountedunit, the micro computer may control the flow direction, and thenthe user interface indication will also change.
The air flow direction can be adjusted in one of the following ways:
▪ The air flow flap itself adjusts its position.
▪ The air flow direction can be fixed by the user.
▪ Automatic and desired position .
WARNING
Never touch the air outlet or the horizontal blades while theswing flap is in operation. Fingers may become caught orthe unit may break down.
NOTICE
▪ The movable limit of the flap is changeable. Contactyour dealer for details. (only for double-flow, multi-flow,corner, ceiling-suspended and wall-mounted).
▪ Avoid operating in the horizontal direction . It maycause dew or dust to settle on the ceiling or flap.
12.5 Setting the master user interface
12.5.1 About setting the master user interface
gd d
c c
f
eb
a
g
f
e
a VRV IV-S Heat pump outdoor unitb Refrigerant pipingc VRV direct expansion (DX) indoor unitd User interface (dedicated depending on indoor unit type)e BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)f Residential Air (RA) direct expansion (DX) indoor unitsg User interface (wireless, dedicated depending on indoor
unit type)
13 Maintenance and service
Installation and operation manual
27RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
When the system is installed as shown in the figure above, it isnecessary to designate one of the user interfaces as the master userinterface.
The displays of slave user interfaces show (change-overunder centralised control) and slave user interfaces automaticallyfollow the operation mode directed by the master user interface.
Only the master user interface can select heating or cooling mode.
12.5.2 To designate the master user interface(VRV DX)
In case only VRV DX indoor units are connected to the VRV IV-Ssystem:
1 Press the operation mode selector button of the current masteruser interface for 4 seconds. In case this procedure was not yetperformed, the procedure can be executed on the first userinterface operated.
Result: The display showing (change-over undercentralised control) of all slave user interfaces connected to thesame outdoor unit flashes.
2 Press the operation mode selector button of the controller thatyou wish to designate as the master user interface.
Result: Designation is completed. This user interface isdesignated as the master user interface and the displayshowing (change-over under centralised control)vanishes. The displays of other user interfaces show (change-over under centralised control).
12.5.3 To designate the master user interface(RA DX)
In case only RA DX indoor units are connected to the VRV IV-Ssystem:
1 Stop all indoor units.
2 When the system is not operating (all indoor units thermo OFF),you can define the master RA DX indoor unit by addressing thatunit with infrared user interface (instruct thermo ON in desiredmode).
The only way to change the master unit is by repeating the previousprocedure. A cool/heat switchover (or opposite) is only possible bychanging the operation mode of the defined master indoor unit.
13 Maintenance and serviceNOTICE
Never inspect or service the unit by yourself. Ask aqualified service person to perform this work.
WARNING
Never replace a fuse with a fuse of a wrong ampere ratingsor other wires when a fuse blows out. Use of wire orcopper wire may cause the unit to break down or cause afire.
CAUTION
Do not insert fingers, rods or other objects into the air inletor outlet. Do not remove the fan guard. When the fan isrotating at high speed, it will cause injury.
CAUTION
After a long use, check the unit stand and fitting fordamage. If damaged, the unit may fall and result in injury.
NOTICE
Do not wipe the controller operation panel with benzine,thinner, chemical dust cloth, etc. The panel may getdiscoloured or the coating peeled off. If it is heavily dirty,soak a cloth in water-diluted neutral detergent, squeeze itwell and wipe the panel clean. Wipe it with another drycloth.
13.1 About the refrigerantThis product contains fluorinated greenhouse gases. Do NOT ventgases into the atmosphere.
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5
NOTICE
In Europe, the greenhouse gas emissions of the totalrefrigerant charge in the system (expressed as tonnesCO2-equivalent) is used to determine the maintenanceintervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:GWP value of the refrigerant × Total refrigerant charge [inkg] / 1000
Please contact your installer for more information.
WARNING
The refrigerant in the air conditioner is safe and normallydoes not leak. If the refrigerant leaks in the room, contactwith a fire of a burner, a heater or a cooker may result in aharmful gas.
Turn off any combustible heating devices, ventilate theroom and contact the dealer where you purchased the unit.
Do not use the air conditioner until a service personconfirms that the portion where the refrigerant leaks isrepaired.
13.2 After-sales service and warranty
13.2.1 Warranty period▪ This product includes a warranty card that was filled in by the
dealer at the time of installation. The completed card has to bechecked by the customer and stored carefully.
▪ If repairs to the air conditioner are necessary within the warrantyperiod, contact your dealer and keep the warranty card at hand.
13.2.2 Recommended maintenance andinspection
Since dust collects when using the unit for several years,performance of the unit will deteriorate to some extent. As takingapart and cleaning interiors of units requires technical expertise andin order to ensure the best possible maintenance of your units, werecommend to enter into a maintenance and inspection contract ontop of normal maintenance activities. Our network of dealers hasaccess to a permanent stock of essential components in order tokeep your air conditioner in operation as long as possible. Contactyour dealer for more information.
When asking your dealer for an intervention, always state:▪ The complete model name of the air conditioner.
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
14 Troubleshooting
Installation and operation manual
28RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
WARNING
▪ Do not modify, disassemble, remove, reinstall or repairthe unit yourself as incorrect dismantling or installationmay cause an electric shock or fire. Contact yourdealer.
▪ In case of accidental refrigerant leaks, make sure thereare no naked flames. The refrigerant itself is entirelysafe, non-toxic and non-combustible, but it willgenerate toxic gas when it accidentally leaks into aroom where combustible air from fan heaters, gascookers, etc. is present. Always have qualified servicepersonnel confirm that the point of leakage has beenrepaired or corrected before resuming operation.
14 TroubleshootingIf one of the following malfunctions occur, take the measures shownbelow and contact your dealer.
WARNING
Stop operation and shut off the power if anythingunusual occurs (burning smells etc.).
Leaving the unit running under such circumstances maycause breakage, electric shock or fire. Contact your dealer.
The system must be repaired by a qualified service person:
Malfunction MeasureIf a safety device such as a fuse, abreaker or an earth leakage breakerfrequently actuates or the ON/OFFswitch does not properly work.
Turn off the main powerswitch.
If water leaks from the unit. Stop the operation.The operation switch does not workwell.
Turn off the power.
If the user interface display indicates theunit number, the operation lamp flashesand the malfunction code appears.
Notify your installer andreport the malfunctioncode.
If the system does not properly operate except for the abovementioned cases and none of the above mentioned malfunctions isevident, investigate the system according to the followingprocedures.
Malfunction MeasureIf the system does notoperate at all.
▪ Check if there is no power failure. Waituntil power is restored. If power failureoccurs during operation, the systemautomatically restarts immediately afterthe power supply is recovered.
▪ Check if no fuse has blown or breakerhas worked. Change the fuse or reset thebreaker if necessary.
If the system goes intofan only operation, butas soon as it goes intoheating or coolingoperation, the systemstops.
▪ Check if air inlet or outlet of outdoor orindoor unit is not blocked by obstacles.Remove any obstacle and make it well-ventilated.
▪ Check if the user interface display shows (time to clean the air filter). (Refer to
"13 Maintenance and service" onpage 27 and "Maintenance" in the indoorunit manual.)
Malfunction MeasureThe system operatesbut cooling or heatingis insufficient.
▪ Check if air inlet or outlet of outdoor orindoor unit is not blocked by obstacles.Remove any obstacle and make it well-ventilated.
▪ Check if the air filter is not clogged (referto "Maintenance" in the indoor unitmanual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your userinterface.
▪ Check for open doors or windows. Shutdoors and windows to prevent wind fromcoming in.
▪ Check if there are too many occupants inthe room during cooling operation. Checkif the heat source of the room isexcessive.
▪ Check if direct sunlight enters the room.Use curtains or blinds.
▪ Check if the air flow angle is proper.
If after checking all above items, it is impossible to fix the problemyourself, contact your installer and state the symptoms, the completemodel name of the air conditioner (with manufacturing number ifpossible) and the installation date (possibly listed on the warrantycard).
14.1 Error codes: OverviewIn case a malfunction code appears on the indoor unit user interfacedisplay, contact your installer and inform the malfunction code, theunit type, and serial number (you can find this information on thenameplate of the unit).
For your reference, a list with malfunction codes is provided. Youcan, depending on the level of the malfunction code, reset the codeby pushing the ON/OFF button. If not, ask your installer for advice.
Main code ContentsExternal protection device was activatedEEPROM failure (indoor)Drain system malfunction (indoor)Fan motor malfunction (indoor)Swing flap motor malfunction (indoor)Expansion valve malfunction (indoor)Drain malfunction (indoor unit)Filter dust chamber malfunction (indoor)Capacity setting malfunction (indoor)Transmission malfunction between main PCB and subPCB (indoor)Heat exchanger thermistor malfunction (indoor; liquid)Heat exchanger thermistor malfunction (indoor; gas)Suction air thermistor malfunction (indoor)Discharge air thermistor malfunction (indoor)Movement detector or floor temperature sensormalfunction (indoor)User interface thermistor malfunction (indoor)PCB malfunction (outdoor)High pressure switch was activatedLow pressure malfunction (outdoor)Compressor lock detection (outdoor)Fan motor malfunction (outdoor)
14 Troubleshooting
Installation and operation manual
29RXYSCQ4+5TMV1BVRV IV-S system air conditioner4P399985-1D – 2016.03
Main code ContentsElectronic expansion valve malfunction (outdoor)Discharge temperature malfunction (outdoor)Abnormal suction temperature (outdoor)Refrigerant overcharge detectionHigh pressure switch malfunctionLow pressure switch malfunctionFan motor trouble (outdoor)Ambient temperature sensor malfunction (outdoor)Pressure sensor malfunctionCurrent sensor malfunctionDischarge temperature sensor malfunction (outdoor)Heat exchanger gas temperature sensor malfunction(outdoor)Suction temperature sensor malfunction (outdoor)De-icing temperature sensor malfunction (outdoor)Liquid temperature sensor (after subcool HE)malfunction (outdoor)Gas temperature sensor (after subcool HE)malfunction (outdoor)High pressure sensor malfunction (S1NPH)Low pressure sensor malfunction (S1NPL)INV PCB abnormalFin temperature abnormalInverter PCB faultyCompressor over current detectedCompressor lock (startup)Transmission outdoor unit - inverter: INV transmissiontroubleINV unbalanced power supply voltageFin thermistor malfunctionCapacity setting malfunction (outdoor)Abnormal low pressure drop, faulty expansion valveINV voltage power shortageSystem test run not yet executedFaulty wiring indoor/outdoorAbnormal user interface - indoor communicationFaulty wiring to outdoor/outdoorAbnormal main-sub user interface communicationSystem mismatch. Wrong type of indoor unitscombined. Indoor unit malfunction.Connection malfunction over indoor units or typemismatchCentralised address duplicationMalfunction in communication centralised controldevice - indoor unitAuto address malfunction (inconsistency)Auto address malfunction (inconsistency)
14.2 Symptoms that are not airconditioner troubles
Following symptoms are not air conditioner troubles:
14.2.1 Symptom: The system does not operate▪ The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamplights, the system is in normal condition. To prevent overloading of
the compressor motor, the air conditioner starts 5 minutes after itis turned ON again in case it was turned OFF just before. Thesame starting delay occurs after the operation mode selectorbutton was used.
▪ If "Under Centralized Control" is displayed on the user interface,pressing the operation button causes the display to blink for a fewseconds. The blinking display indicates that the user interfacecannot be used.
▪ The system does not start immediately after the power supply isturned on. Wait one minute until the micro computer is preparedfor operation.
14.2.2 Symptom: Fan operation is possible, butcooling and heating do not work
Immediately after the power is turned on. The micro computer isgetting ready to operate and is performing a communication checkwith all indoor units. Please wait 12 minutes (max.) till this process isfinished.
14.2.3 Symptom: The fan strength does notcorrespond to the setting
The fan speed does not change even if the fan speed adjustmentbutton in pressed. During heating operation, when the roomtemperature reaches the set temperature, the outdoor unit goes offand the indoor unit changes to whisper fan speed. This is to preventcold air blowing directly on occupants of the room. The fan speedwill not change even when another indoor unit is in heatingoperation, if the button is pressed.
14.2.4 Symptom: The fan direction does notcorrespond to the setting
The fan direction does not correspond with the user interfacedisplay. The fan direction does not swing. This is because the unit isbeing controlled by the micro computer.
14.2.5 Symptom: White mist comes out of a unit(Indoor unit)
▪ When humidity is high during cooling operation. If the interior of anindoor unit is extremely contaminated, the temperature distributioninside a room becomes uneven. It is necessary to clean theinterior of the indoor unit. Ask your dealer for details on cleaningthe unit. This operation requires a qualified service person.
▪ Immediately after the cooling operation stops and if the roomtemperature and humidity are low. This is because warmrefrigerant gas flows back into the indoor unit and generatessteam.
14.2.6 Symptom: White mist comes out of a unit(Indoor unit, outdoor unit)
When the system is changed over to heating operation after defrostoperation. Moisture generated by defrost becomes steam and isexhausted.
14.2.7 Symptom: The user interface displayreads "U4" or "U5" and stops, but thenrestarts after a few minutes
This is because the user interface is intercepting noise from electricappliances other than the air conditioner. The noise preventscommunication between the units, causing them to stop. Operationautomatically restarts when the noise ceases.
15 Relocation
Installation and operation manual
30RXYSCQ4+5TMV1B
VRV IV-S system air conditioner4P399985-1D – 2016.03
14.2.8 Symptom: Noise of air conditioners(Indoor unit)
▪ A "zeen" sound is heard immediately after the power supply isturned on. The electronic expansion valve inside an indoor unitstarts working and makes the noise. Its volume will reduce inabout one minute.
▪ A continuous low "shah" sound is heard when the system is incooling operation or at a stop. When the drain pump (optionalaccessories) is in operation, this noise is heard.
▪ A "pishi-pishi" squeaking sound is heard when the system stopsafter heating operation. Expansion and contraction of plastic partscaused by temperature change make this noise.
▪ A low "sah", "choro-choro" sound is heard while the indoor unit isstopped. When another indoor unit is in operation, this noise isheard. In order to prevent oil and refrigerant from remaining in thesystem, a small amount of refrigerant is kept flowing.
14.2.9 Symptom: Noise of air conditioners(Indoor unit, outdoor unit)
▪ A continuous low hissing sound is heard when the system is incooling or defrost operation. This is the sound of refrigerant gasflowing through both indoor and outdoor units.
▪ A hissing sound which is heard at the start or immediately afterstopping operation or defrost operation. This is the noise ofrefrigerant caused by flow stop or flow change.
14.2.10 Symptom: Noise of air conditioners(Outdoor unit)
When the tone of operating noise changes. This noise is caused bythe change of frequency.
14.2.11 Symptom: Dust comes out of the unitWhen the unit is used for the first time in a long time. This isbecause dust has gotten into the unit.
14.2.12 Symptom: The units can give off odoursThe unit can absorb the smell of rooms, furniture, cigarettes, etc.,and then emit it again.
14.2.13 Symptom: The outdoor unit fan does notspin
During operation. The speed of the fan is controlled in order tooptimise product operation.
14.2.14 Symptom: The display shows "88"This is the case immediately after the main power supply switch isturned on and means that the user interface is in normal condition.This continues for one minute.
14.2.15 Symptom: The compressor in the outdoorunit does not stop after a short heatingoperation
This is to prevent refrigerant from remaining in the compressor. Theunit will stop after 5 to 10 minutes.
14.2.16 Symptom: The inside of an outdoor unit iswarm even when the unit has stopped
This is because the crankcase heater is warming the compressor sothat the compressor can start smoothly.
14.2.17 Symptom: Hot air can be felt when theindoor unit is stopped
Several different indoor units are being run on the same system.When another unit is running, some refrigerant will still flow throughthe unit.
15 RelocationContact your dealer for removing and reinstalling the total unit.Moving units requires technical expertise.
16 DisposalThis unit uses hydrofluorocarbon. Contact your dealer whendiscarding this unit. It is required by law to collect, transport anddiscard the refrigerant in accordance with the "hydrofluorocarboncollection and destruction" regulations.
4P399985-1D 2016.03
Cop
yrig
ht 2
015
Dai
kin