Download - Load Estimate
8/19/2019 Load Estimate
http://slidepdf.com/reader/full/load-estimate 1/5
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING (HALLWAY) 210 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
2 LIGHTING (ENTRANCE) 45 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
3 LIGHTING (STALL 1) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
4 LIGHTING (STALL 2) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
5 LIGHTING (STALL 3) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
6 LIGHTING (STALL 4) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
7 LIGHTING (GROCERY) 84 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
8 LIGHTING (CR-MALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
9 LIGHTING (CR-FEMALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
10 LIGHTING (STAIR 1) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
11 LIGHTING (STAIR 2) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
12 LIGHTING (STAIR 3) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
13 LIGHTING (RAMP) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
14 LIGHTING (MECH. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
15 LIGHTING (ELECT. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
16 CO (STALL 2 / STALL 1 / ELECT. ROOM / MECH. ROOM) 2160 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
17 CO (RAMP / GROCERY) 1080 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
18 CO (STALL 4 / STALL 3 / CR-FEMALE / CR-MALE) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
TOTAL CONNECTED LOAD 5261
PROTECTION WIRES RACEWAY
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP
1 LIGHTING PANEL 5261 30 100 2 2-5.5mm2THHW + 1-5.5mm
2 TW (GW) 20mm n PVC SCHED 40
2 1HP 230V 8A WINDOW TYPE ACU (STALL 1) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
3 1HP 230V 8A WINDOW TYPE ACU (STALL 2) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
4 1HP 230V 8A WINDOW TYPE ACU (STALL 3) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
5 1HP 230V 8A WINDOW TYPE ACU (STALL 4) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
6 5 HP 230V 8A GENERAL ACU 1 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
7 5 HP 230V 8A GENERAL ACU 2 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
8 5 HP 230V 8A GENERAL ACU 3 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
TOTAL CONNECTED LOAD 31941
TOTAL LIGHTING LOAD 581 W
TOTAL CONVENIENCE OUTLET LOAD 4680 W
TOTAL ACU LOAD 26680 W
LOAD SCHEDULE
GROUND FLOOR
8/19/2019 Load Estimate
http://slidepdf.com/reader/full/load-estimate 2/5
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING (HALLWAY) 220 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
2 LIGHTING (STALL 1) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
3 LIGHTING (STALL 2) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
4 LIGHTING (STALL 3) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
5 LIGHTING (STALL 4) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
6 LIGHTING (STALL 5) 28 15 100 2 2-2.0mm2
THW + 1-2.0mm2
TW (GW) 15mm n PVC SCHED 407 LIGHTING (STALL 6) 28 15 100 2 2-2.0mm
2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
8 LIGHTING (STALL 7) 42 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
9 LIGHTING (STALL 8) 42 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
10 LIGHTING (CR-MALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
11 LIGHTING (CR-FEMALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
12 LIGHTING (STAIR 1) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
13 LIGHTING (STAIR 2) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
14 LIGHTING (STAIR 3) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
15 LIGHTING (RAMP) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
16 LIGHTING (MECH. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
17 LIGHTING (ELECT. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
18 CO (STALL 2 / STALL 1 / ELECT. ROOM / MECH. ROOM) 2160 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
19 CO (STALL 6 / STALL 5 / RAMP) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
20 CO (STALL 4 / STALL 3 / CR-FEMALE / CR-MALE) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
21 CO (STALL 7 / STALL 8) 1080 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
TOTAL CONNECTED LOAD 6722
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING PANEL 6722 30 100 2 2-5.5mm2THHW + 1-5.5mm
2 TW (GW) 20mm n PVC SCHED 40
2 1HP 230V 8A WINDOW TYPE ACU (STALL 1) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
3 1HP 230V 8A WINDOW TYPE ACU (STALL 2) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
4 1HP 230V 8A WINDOW TYPE ACU (STALL 3) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
5 1HP 230V 8A WINDOW TYPE ACU (STALL 4) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
6 1HP 230V 8A WINDOW TYPE ACU (STALL 5) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
7 1HP 230V 8A WINDOW TYPE ACU (STALL 6) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
8 1HP 230V 8A WINDOW TYPE ACU (STALL 7) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
9 1HP 230V 8A WINDOW TYPE ACU (STALL 8) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
10 5 HP 230V 8A GENERAL ACU 1 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
11 5 HP 230V 8A GENERAL ACU 2 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
12 5 HP 230V 8A GENERAL ACU 3 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
TOTAL CONNECTED LOAD 40762
TOTAL LIGHTING LOAD 602 W
TOTAL CONVENIENCE OUTLET LOAD 6120 W
TOTAL ACU LOAD 34040 W
SECOND FLOOR
8/19/2019 Load Estimate
http://slidepdf.com/reader/full/load-estimate 3/5
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING (HALLWAY) 220 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
2 LIGHTING (STALL 1) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
3 LIGHTING (STALL 2) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
4 LIGHTING (STALL 3) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
5 LIGHTING (STALL 4) 28 15 100 2 2-2.0mm2 THW + 1-2.0mm2 TW (GW) 15mm n PVC SCHED 40
6 LIGHTING (STALL 5) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
7 LIGHTING (STALL 6) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
8 LIGHTING (STALL 7) 42 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
9 LIGHTING (STALL 8) 42 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
10 LIGHTING (CR-MALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
11 LIGHTING (CR-FEMALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
12 LIGHTING (STAIR 1) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
13 LIGHTING (STAIR 2) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
14 LIGHTING (STAIR 3) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
15 LIGHTING (RAMP) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
16 LIGHTING (MECH. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
17 LIGHTING (ELECT. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
18 CO (STALL 2 / STALL 1 / ELECT. ROOM / MECH. ROOM) 2160 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
19 CO (STALL 6 / STALL 5 / RAMP) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
20 CO (STALL 4 / STALL 3 / CR-FEMALE / CR-MALE) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
21 CO (STALL 7 / STALL 8) 1080 20 100 2 2-3.5mm2
THW + 1-3.5mm2
TW (GW) 20mm n PVC SCHED 40
TOTAL CONNECTED LOAD 6722
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING PANEL 6722 30 100 2 2-5.5mm2THHW + 1-5.5mm
2 TW (GW) 20mm n PVC SCHED 40
2 1HP 230V 8A WINDOW TYPE ACU (STALL 1) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
3 1HP 230V 8A WINDOW TYPE ACU (STALL 2) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
4 1HP 230V 8A WINDOW TYPE ACU (STALL 3) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
5 1HP 230V 8A WINDOW TYPE ACU (STALL 4) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
6 1HP 230V 8A WINDOW TYPE ACU (STALL 5) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
7 1HP 230V 8A WINDOW TYPE ACU (STALL 6) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
8 1HP 230V 8A WINDOW TYPE ACU (STALL 7) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
9 1HP 230V 8A WINDOW TYPE ACU (STALL 8) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
10 5 HP 230V 8A GENERAL ACU 1 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
11 5 HP 230V 8A GENERAL ACU 2 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
12 5 HP 230V 8A GENERAL ACU 3 6440 30 100 2 2-8.0mm2 THW + 1-5.5mm2 TW (GW) 25mm n PVC SCHED 40
TOTAL CONNECTED LOAD 40762
TOTAL LIGHTING LOAD 602 W
TOTAL CONVENIENCE OUTLET LOAD 6120 W
TOTAL ACU LOAD 34040 W
THIRD FLOOR
8/19/2019 Load Estimate
http://slidepdf.com/reader/full/load-estimate 4/5
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING (HALLWAY) 275 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
2 LIGHTING (STALL 1) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
3 LIGHTING (STALL 2) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
4 LIGHTING (STALL 3) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
5 LIGHTING (STALL 4) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
6 LIGHTING (STALL 5) 28 15 100 2 2-2.0mm2 THW + 1-2.0mm2 TW (GW) 15mm n PVC SCHED 40
7 LIGHTING (STALL 6) 28 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
8 LIGHTING (CR-MALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
9 LIGHTING (CR-FEMALE) 30 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
10 LIGHTING (STAIR 1) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
11 LIGHTING (STAIR 2) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
12 LIGHTING (STAIR 3) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
13 LIGHTING (RAMP) 10 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
14 LIGHTING (MECH. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
15 LIGHTING (ELECT. ROOM) 15 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 15mm n PVC SCHED 40
16 CO (STALL 2 / STALL 1 / ELECT. ROOM / MECH. ROOM) 2160 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
17 CO (STALL 6 / STALL 5 / RAMP) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
18 CO (STALL 4 / STALL 3 / CR-FEMALE / CR-MALE) 1440 20 100 2 2-3.5mm2THW + 1-3.5mm
2 TW (GW) 20mm n PVC SCHED 40
TOTAL CONNECTED LOAD 5613
PROTECTIONCKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
1 LIGHTING PANEL 5613 30 100 2 2-5.5mm2THHW + 1-5.5mm
2 TW (GW) 20mm n PVC SCHED 40
2 1HP REFRIGERATOR (STALL 1) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 40
3 1HP REFRIGERATOR (STALL 2) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 41
4 1HP REFRIGERATOR (STALL 3) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 42
5 1HP REFRIGERATOR (STALL 4) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 43
6 1HP REFRIGERATOR (STALL 5) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 44
7 1HP REFRIGERATOR (STALL 5) 1840 15 100 2 2-2.0mm2THW + 1-2.0mm
2 TW (GW) 25mm n PVC SCHED 45
8 5 HP 230V 8A GENERAL ACU 1 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
9 5 HP 230V 8A GENERAL ACU 2 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
10 5 HP 230V 8A GENERAL ACU 3 6440 30 100 2 2-8.0mm2THW + 1-5.5mm
2 TW (GW) 25mm n PVC SCHED 40
TOTAL CONNECTED LOAD 35973
TOTAL LIGHTING LOAD 573 W
TOTAL CONVENIENCE OUTLET LOAD 5040 W
TOTAL REFRIGERATOR LOAD 11040 WTOTAL ACU LOAD 19320 W
PROTECTION
CKT NO. LOAD DESCRIPTION CONNECTED LOAD (VA) AT AF NOP WIRES RACEWAY
ELEVATOR (10 HP MOTOR) 12880 125 225 2 2-30mm2THW + 1-8mm
2 TW (GW) 50mm n IMC
ESCALATOR (20 HP MOTOR) 25760 125 225 2 2-30mm2THW + 1-8mm
2 TW (GW) 50mm n IMC
OTHER LOADS
FOURTH FLOOR
8/19/2019 Load Estimate
http://slidepdf.com/reader/full/load-estimate 5/5