![Page 1: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/1.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
1
Principles of representative sampling and monitoring
Andrew Ryan
Workshop on Microbial Growth in Fuel Supply and Distribution
Brussels
16th March 2011
![Page 2: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/2.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
2
This presentation does not address health and safety or any regulatory
issues. Further guidance is available in some of the publications listed.
Reference should also be made to appropriate national safety regulations
and guidance provided by relevant petroleum industry codes.
Disclaimer
![Page 3: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/3.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
3
Contents
1 Sampling: what and why
2 Sampling: where and how
3 Monitoring (when)
4 Useful publications
5 Summary
![Page 4: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/4.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
4
1 Sampling: what and why
Are you assessing:
1.Condition of fuel?
or
2.Condition of the fuel system?
-Important to understand the
distinction.
![Page 5: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/5.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
5
Sampling points
1/6 Upper
5/6 Lower
3/6 Middle
Top
Bottom
There are several potential sampling points in most systems.
![Page 6: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/6.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
6
Inside a contaminated tank?
1/6 Upper
5/6 Lower
3/6 Middle
Top
Bottom
![Page 7: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/7.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
7
Sampling points - cont
Drain sample
Swab and scraping samples can be taken from
where slimes may accumulate.
Sludge samples
Swab samples?
![Page 8: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/8.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
8
Filters
Filter water separators
• Vulnerable to MBC
Evidence:
•Increased dp
•Spotting on sock
![Page 9: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/9.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
9
2 Sampling: where and how
![Page 10: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/10.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
10
Fuel/interface/water
1/6 Upper
5/6 Lower
3/6 Middle
Top
Bottom
Sample from top to bottom
To reduce potential contamination
![Page 11: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/11.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
11
Sampling devices
Bacon Bomb Any level sampler
Bottom sampling
All level sampling
Bottom sampling
All level sampling
Interface sampling?
![Page 12: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/12.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
12
Thief sampler
For sampling drums and cans
![Page 13: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/13.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
13
Brass sampling devices
Brass not recommended as copper affects
test results.
•Thermal stability
•Oxidation /storage stability
•Antimicrobial
Avoid cork/porous materials as they may host
microbes from previous samples.
![Page 14: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/14.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
14
Sample containers
Glass and (clear) plastic
preferred
![Page 15: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/15.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
15
Sample containers - cont
Clean (unused) containers
preferred
![Page 16: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/16.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
16
Sample storage
Time, temperature and other storage
conditions all affect the microbial
population in a sample…
Samples should be tested within 24 hours.
Samples should be kept at around 4 °C.
Leave some headspace (ullage), preferably 20 -30% to avoid
oxygen deficient conditions - unless testing for sulphate
reducing bacteria.
![Page 17: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/17.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
17
3 Monitoring (when)
![Page 18: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/18.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
18
Monitoring programme
Inspection period
– suitable for product/system
Visual inspection
-Limited information
-Water
-Haze
-Particulate
-Slimes
Bacteria: Typically 1-5 micron.
Fungi: Moulds. Can be several mm long
1-5 micron across.
Fungi: Yeasts:
spherical (5-10 micron across)
filamentous (1-5 micron across).
![Page 19: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/19.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
19
Particulate contamination
IP 387 filter porosity 1.6 micron
Note: Filter blockage most commonly
due to fuel-derived particulates.
Particle counting may be used:
Typical channels sizes
>4µ, >6µ, >14µ and larger.
Gravimetric or timed filtration:
Filter sizes typically 0.45µ, 0.80µ
![Page 20: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/20.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
20
Water samples
Routinely check for:
•Fuel degrading organisms
and/or
•Sulphate reducing bacteria
•Hydrogen sulphide
•pH
•Dissolved metals
•Iron sulphide
Other properties: hardness,
dissolved oxygen, nitrite, nitrate,
ammonia nitrogen.
(See ASTM Manual 47)
Evidence of srb corrosion
![Page 21: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/21.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
21
Monitoring programme - cont
Microbiological testing
-Apply suitable tests
-Develop suitable action/warning limits
-Develop suitable action plan
Guidance may be available from:
•Equipment manufacturer
•EI Guidelines
•IATA (aircraft fuel tanks)
Biofuels may require increased vigilance
![Page 22: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/22.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
22
4 Useful publications
![Page 23: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/23.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
23
•IP 475, EN ISO 3170, Petroleum liquids – Manual sampling (ISO 3170:2004)
•ASTM D4057 - 06 Standard Practice for Manual Sampling of Petroleum and
Petroleum Products
•IP 476, EN ISO 3171 Petroleum liquids – Automatic pipeline sampling (ISO
3171:1988).
•ASTM D4177 - 95(2010) Standard Practice for Automatic Sampling of
Petroleum and Petroleum Products.
•ASTM D7464 - 08 Standard Practice for Manual Sampling of Liquid Fuels,
Associated Materials and Fuel System Components for Microbiological
Testing.
Useful Publications - Sampling
![Page 24: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/24.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
24
•ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel
Systems.
•ASTM D5245 - 92(2005) Standard Practice for Cleaning Laboratory Glassware,
Plasticware, and Equipment Used in Microbiological Analyses.
•Determination of the viable aerobic microbial content of fuels and fuel components boiling
below 390°C - Filtration and culture method 1999
•IP 472 Determination of fungal fragment content of fuels boiling below 390°C 2002
•Fuel and fuel system microbiology- Fundamentals, diagnosis and contamination
control. ASTM Manual 47, 2003
•Guidelines for the investigation of the microbial content of petroleum fuels and for
the implementation of avoidance and remedial strategies. Energy Institute 2008
•IATA Guidance Material on Microbiological Contamination in Aircraft Fuel Tanks,
Edition 3, 2009.
Useful Publications - microbiological testing and control
![Page 25: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/25.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
25
5 Summary
![Page 26: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/26.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
26
Need to be clear on why samples are being taken: system health, fuel condition
and tests to be applied.
Take appropriate samples: i.e. water bottoms, fuel, swabs, scrapings, filters.
Use appropriate sampling devices.
Ensure that sampling practice, devices and containers do not introduce
contamination but maintain sample condition as far as reasonably practical.
Apply/develop suitable action/warning limits and action plan
Sampling and testing frequency must be appropriate to prevent problems
arising.
Summary
![Page 27: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/27.jpg)
© Copyright QinetiQ Limited 2011
Unclassified
27
Thank – you for your attention.
![Page 28: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard](https://reader030.vdocument.in/reader030/viewer/2022040907/5e7de12aa456d2501632a050/html5/thumbnails/28.jpg)
© Copyright QinetiQ Limited 2011
www.QinetiQ.com
28