principles of representative sampling and monitoring · •astm d6469 - 08e1 standard guide for...

28
© Copyright QinetiQ Limited 2011 Unclassified 1 Principles of representative sampling and monitoring Andrew Ryan Workshop on Microbial Growth in Fuel Supply and Distribution Brussels 16 th March 2011

Upload: others

Post on 20-Mar-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

1

Principles of representative sampling and monitoring

Andrew Ryan

Workshop on Microbial Growth in Fuel Supply and Distribution

Brussels

16th March 2011

Page 2: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

2

This presentation does not address health and safety or any regulatory

issues. Further guidance is available in some of the publications listed.

Reference should also be made to appropriate national safety regulations

and guidance provided by relevant petroleum industry codes.

Disclaimer

Page 3: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

3

Contents

1 Sampling: what and why

2 Sampling: where and how

3 Monitoring (when)

4 Useful publications

5 Summary

Page 4: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

4

1 Sampling: what and why

Are you assessing:

1.Condition of fuel?

or

2.Condition of the fuel system?

-Important to understand the

distinction.

Page 5: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

5

Sampling points

1/6 Upper

5/6 Lower

3/6 Middle

Top

Bottom

There are several potential sampling points in most systems.

Page 6: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

6

Inside a contaminated tank?

1/6 Upper

5/6 Lower

3/6 Middle

Top

Bottom

Page 7: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

7

Sampling points - cont

Drain sample

Swab and scraping samples can be taken from

where slimes may accumulate.

Sludge samples

Swab samples?

Page 8: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

8

Filters

Filter water separators

• Vulnerable to MBC

Evidence:

•Increased dp

•Spotting on sock

Page 9: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

9

2 Sampling: where and how

Page 10: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

10

Fuel/interface/water

1/6 Upper

5/6 Lower

3/6 Middle

Top

Bottom

Sample from top to bottom

To reduce potential contamination

Page 11: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

11

Sampling devices

Bacon Bomb Any level sampler

Bottom sampling

All level sampling

Bottom sampling

All level sampling

Interface sampling?

Page 12: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

12

Thief sampler

For sampling drums and cans

Page 13: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

13

Brass sampling devices

Brass not recommended as copper affects

test results.

•Thermal stability

•Oxidation /storage stability

•Antimicrobial

Avoid cork/porous materials as they may host

microbes from previous samples.

Page 14: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

14

Sample containers

Glass and (clear) plastic

preferred

Page 15: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

15

Sample containers - cont

Clean (unused) containers

preferred

Page 16: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

16

Sample storage

Time, temperature and other storage

conditions all affect the microbial

population in a sample…

Samples should be tested within 24 hours.

Samples should be kept at around 4 °C.

Leave some headspace (ullage), preferably 20 -30% to avoid

oxygen deficient conditions - unless testing for sulphate

reducing bacteria.

Page 17: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

17

3 Monitoring (when)

Page 18: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

18

Monitoring programme

Inspection period

– suitable for product/system

Visual inspection

-Limited information

-Water

-Haze

-Particulate

-Slimes

Bacteria: Typically 1-5 micron.

Fungi: Moulds. Can be several mm long

1-5 micron across.

Fungi: Yeasts:

spherical (5-10 micron across)

filamentous (1-5 micron across).

Page 19: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

19

Particulate contamination

IP 387 filter porosity 1.6 micron

Note: Filter blockage most commonly

due to fuel-derived particulates.

Particle counting may be used:

Typical channels sizes

>4µ, >6µ, >14µ and larger.

Gravimetric or timed filtration:

Filter sizes typically 0.45µ, 0.80µ

Page 20: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

20

Water samples

Routinely check for:

•Fuel degrading organisms

and/or

•Sulphate reducing bacteria

•Hydrogen sulphide

•pH

•Dissolved metals

•Iron sulphide

Other properties: hardness,

dissolved oxygen, nitrite, nitrate,

ammonia nitrogen.

(See ASTM Manual 47)

Evidence of srb corrosion

Page 21: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

21

Monitoring programme - cont

Microbiological testing

-Apply suitable tests

-Develop suitable action/warning limits

-Develop suitable action plan

Guidance may be available from:

•Equipment manufacturer

•EI Guidelines

•IATA (aircraft fuel tanks)

Biofuels may require increased vigilance

Page 22: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

22

4 Useful publications

Page 23: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

23

•IP 475, EN ISO 3170, Petroleum liquids – Manual sampling (ISO 3170:2004)

•ASTM D4057 - 06 Standard Practice for Manual Sampling of Petroleum and

Petroleum Products

•IP 476, EN ISO 3171 Petroleum liquids – Automatic pipeline sampling (ISO

3171:1988).

•ASTM D4177 - 95(2010) Standard Practice for Automatic Sampling of

Petroleum and Petroleum Products.

•ASTM D7464 - 08 Standard Practice for Manual Sampling of Liquid Fuels,

Associated Materials and Fuel System Components for Microbiological

Testing.

Useful Publications - Sampling

Page 24: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

24

•ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel

Systems.

•ASTM D5245 - 92(2005) Standard Practice for Cleaning Laboratory Glassware,

Plasticware, and Equipment Used in Microbiological Analyses.

•Determination of the viable aerobic microbial content of fuels and fuel components boiling

below 390°C - Filtration and culture method 1999

•IP 472 Determination of fungal fragment content of fuels boiling below 390°C 2002

•Fuel and fuel system microbiology- Fundamentals, diagnosis and contamination

control. ASTM Manual 47, 2003

•Guidelines for the investigation of the microbial content of petroleum fuels and for

the implementation of avoidance and remedial strategies. Energy Institute 2008

•IATA Guidance Material on Microbiological Contamination in Aircraft Fuel Tanks,

Edition 3, 2009.

Useful Publications - microbiological testing and control

Page 25: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

25

5 Summary

Page 26: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

26

Need to be clear on why samples are being taken: system health, fuel condition

and tests to be applied.

Take appropriate samples: i.e. water bottoms, fuel, swabs, scrapings, filters.

Use appropriate sampling devices.

Ensure that sampling practice, devices and containers do not introduce

contamination but maintain sample condition as far as reasonably practical.

Apply/develop suitable action/warning limits and action plan

Sampling and testing frequency must be appropriate to prevent problems

arising.

Summary

Page 27: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

Unclassified

27

Thank – you for your attention.

Page 28: Principles of representative sampling and monitoring · •ASTM D6469 - 08e1 Standard Guide for Microbial Contamination in Fuels and Fuel Systems. •ASTM D5245 - 92(2005) Standard

© Copyright QinetiQ Limited 2011

www.QinetiQ.com

28