Power and Signal Integrity Solutions™
RF | AC | DC | Data Protection
Coaxial RF Surge ProtectionUltra Low PIMDC BlockDC PassGrounding and Accessories
Data Line Surge ProtectionMulti-Protocol ProtectorsPoE ProtectorsGbE ProtectorsT1/E1 ProtectorsCCTV | Satellite ProtectorsLow Voltage Signal Protectors
AC Surge ProtectionPanel ProtectorsPlug-In ProtectorsComponent Protectors
DC Surge ProtectionComponent ProtectorsOutdoor Protectors
Power Distribution PanelsPrimary | Secondary Distribution
Integrated Power CabinetsOutdoor CabinetsIndoor Cabinets
Application DiagramsTelecommunicationsRail TransportationOil and Gas
A global manufacturer of proprietary coaxial RF surge protection solutions, PolyPhaser leads the market with innovative DC Block and DC Pass RF product portfolio.
As a market leader in silicon diode technology, Transtector engineers and manufactures a diverse product offering that includes AC, DC, data/signal, EMP, power conditioners, UPS, power distribution units and integrated cabinets.
Founded on the ability to provide custom engineered solutions, Dowin’s lightning protection solutions include AC, DC and signal systems including analog, digital and RF.
Dedicated to the design, testing and manufacturing of TVSS based equipment, LEA specializes in series filters and parallel surge protection devices used in new construction, broadcast and alternative power markets.
For over 20 years RO Associates has been committed to providing expertise and professional assistance in power and grounding consulting and educational courses.
The Protection Technology Group is a part of Smiths Interconnect, a division of Smiths Group plc, and includes five brands:
By synergistically combining the expertise of the individual brands, the Protection Technology Group is able to provide the best end-to-end power quality solutions for the telecommunications, medical imaging, transportation, energy, security, broadcast and military markets.
Visit www.protectiongroup.com for additional product information, market applications and corporate resources.
Our manufacturing facilities are ISO 9001:2008 and ISO 14001: 2004 certified. The Protection Technology Group is committed to quality and ensures all R&D, testing, manufacturing, product inspection and sales fully comply with ISO standards and regulations.
Meeting our customers’ needs will always be paramount to the Protection Technology Group’s efforts in creating highly satisfied customers. We lead the industry in on-time delivery and continually strive to engineer and manufacture power and signal integrity products that provide our customers with the highest quality solutions at competitive pricing.
Our companies were founded on the ability to provide custom engineered solutions for unique protection circumstances. Regardless of your requirements, PolyPhaser, Transtector, Dowin, and LEA have the proven ability to design, develop and manufacture the solution.
Our engineers are business leaders and decision makers within regulatory agencies including IEC, IEEE, UL, IWPC, AISG and NEC. We continually strive to meet the needs of our customers by providing innovative product offerings for global markets.
Smiths Interconnect is a leading provider of specialized electronic and radio frequency products for the wireless telecommunications, aerospace, defense, and medical markets. It is part of Smiths Group, a global leader in advanced technologies. Smiths Group is comprised of 140 businesses grouped into five divisions in over 50 countries and employs 23,000 people in more than 400 locations.
5RF Intro Page
Whether your coaxial application is at the tower top, GPS or in the base station, PolyPhaser RF products have set the
standard for the industry.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection6
• PIM < -155 dBc
• Bidirectional broadband filter
• Bulkhead mount
• Tri-M3™ plating over brass
Features
• IEC 60529 IP 67
• Belcore #TA-NWT-000487
• Procedure 4.11, Wind Driven (120 MPH)
Standards and CertificatesTSXDC-DFM
Humidity < 95% non-condensing
Operating Temperature -50° C to +85° C
TSXDC-DFM
High performance, ultra low PIM RF protectors for 698 MHz to 2.5 GHz available in DC block and DC pass configurations.
Ultra Low PIM
TSX Series
Environmental
7
TSX-DFF
TUSX-DFM
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection8
Frequency Range RF Power Insertion Loss VSWR Operating Voltage Max Surge Current Turn on Voltage Throughput EnergySurge Side Connector
Protected Side Connector
TSXDC-DFM 698 MHz to 2.5 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.2:1 over frequency range ± 60 Vdc
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
+150 Vdc + 20%< 25 mJ 2kA IEC 61000-4-5 8/20 µs waveform
DIN Female DIN Male TSXDC-DFM
TSX-DFF 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Female TSX-DFF
TSX-DFM 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Male TSX-DFM
TUSX-DFF 300 MHz to 1.4 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Female TUSX-DFF
TUSX-DFM 300 MHz to 1.4 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Male TUSX-DFM
Ultra Low PIM
9
Frequency Range RF Power Insertion Loss VSWR Operating Voltage Max Surge Current Turn on Voltage Throughput EnergySurge Side Connector
Protected Side Connector
TSXDC-DFM 698 MHz to 2.5 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.2:1 over frequency range ± 60 Vdc
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
+150 Vdc + 20%< 25 mJ 2kA IEC 61000-4-5 8/20 µs waveform
DIN Female DIN Male TSXDC-DFM
TSX-DFF 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Female TSX-DFF
TSX-DFM 698 MHz to 2.7 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Male TSX-DFM
TUSX-DFF 300 MHz to 1.4 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Female TUSX-DFF
TUSX-DFM 300 MHz to 1.4 GHz 1 kW @ 920 MHz ≤ 0.1 dB < 1.1:1 over frequency range N/A
30 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 40 kA per IEC 61000-4-5 8/20 µs waveform for one strike
N/A< 5 nJ for 3kA 8/20 µs waveform
DIN Female DIN Male TUSX-DFM
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection10
• Ultra low PIM <-155 dBc 2 x 20 W
• Weather proof when installed
• 50 Ω impedance
• RoHS compliant
Features
• IEC 60529 IP67
• AISG compliant
Standards and Certificates
DAS-P-DFM30
Humidity 95% non-condensing
Operating/Storage Temperature -55°C to +85°C
DAS-P-DFM30
The DAS-P series is a dual band DC pass RF protector that offers outstanding throughput energy of <50V, while providing ultra PIM protection in a 30V unit.
Ultra Low PIM
DAS-P Series
Environmental
11
DAS-P-DMF30
DAS-P-DFF30
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection12
Ultra Low PIM - DAS-P Series
Frequency Range RF Power Insertion Loss VSWR PIM PerformanceMax Continuous Operating Current
Max Surge Current Surge Side Connector Protected Side Connector
DAS-P-DFF30
680 MHz to 1 GHz, 1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Female DAS-P-DFF30
DAS-P-DFM30
680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Male DAS-P-DFM30
DAS-P-DMF30
680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Male DIN Female DAS-P-DMF30
DGXJ-P-DFM-30680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,
<-155 dBc 2 x 20 W N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Male DGXJ-P-DFM-30
13
Frequency Range RF Power Insertion Loss VSWR PIM PerformanceMax Continuous Operating Current
Max Surge Current Surge Side Connector Protected Side Connector
DAS-P-DFF30
680 MHz to 1 GHz, 1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Female DAS-P-DFF30
DAS-P-DFM30
680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Male DAS-P-DFM30
DAS-P-DMF30
680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF2.0 MHz to 2.5 MHz Telemetry(AISG)
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz<0.4 dB @ 2.176 MHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,≤1.4:1 @ 2.176 MHz
<-155 dBc 2 x 20 W 4 A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Male DIN Female DAS-P-DMF30
DGXJ-P-DFM-30680 MHz to 1 GHz,1.7 GHz to 2.3 GHz RF
1.5 kW @ 920 MHz<0.1 dB @ 680 MHz to 1 GHz,<0.1 dB @ 1.7 GHz to 2.3 GHz
≤1.2:1 @ 680 MHz to 1 GHz,≤1.2:1 @ 1.7 GHz to 2.3 GHz,
<-155 dBc 2 x 20 W N/A
20 kA per IEC 61000-4-5 8/20 µs waveform for multiple strikes / 30 kA per IEC 61000-4-5 8/20 µs waveform for one strike
DIN Female DIN Male DGXJ-P-DFM-30
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection14
• Frequency range 1.5 - 1000 MHz
• Insertion loss: 0.1dB
• Ideal for HF, UHF, VHF radios
• DC blocked gas tube design
• No DC continuity between center pins
• Multi-strike capability
Features
• RoHS compliant
Standards and Certificates
IS-B50LN-C2
Operating Temperature -45°C to +50°C
Vibration 1 G up to 100 Hz
IS-B50LN-C2
DC blocked 50 ohm bulkhead mounted protector is ideal for two way radio and SCADA applications.
DC Block
B50 Series
Environmental
15
IS-B50HN-C0
IS-B50LN-C1
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection16
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-B50HN-C0 1.5 MHz to 400 MHz VHF 500 W, UHF 250 W, HF 3 kW ≤ 0.1 dB ≤ 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC1000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 20 mJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C0
IS-B50HN-C1 50 MHz to 700 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 1 mJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C1
IS-B50HN-C2 125 MHz to 1000 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 800 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C2
IS-B50HU-C0 1.5 MHz to 400 MHz HF 3 kW, VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 20 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50HU-C0
IS-B50HU-C1 50 MHz to 700 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 1 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50HU-C1
IS-B50LN-C0 1.5 MHz to 400 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 10 mJ for 3 kA, 8/20 µs waveform
N Female N Female IS-B50LN-C0
IS-B50LN-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 600 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50LN-C1
IS-B50LN-C2 125 MHz to 1 GHz VHF 375 W, UHF 125 to 50 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 220 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50LN-C2
IS-B50LU-C0 1.5 MHz to 400 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 10 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50LU-C0
IS-B50LU-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 600 µJ for 3 kA, 8/20 µs waveform
UHF Female UHF Female IS-B50LU-C1
DC Block - B50 Series
17
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-B50HN-C0 1.5 MHz to 400 MHz VHF 500 W, UHF 250 W, HF 3 kW ≤ 0.1 dB ≤ 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC1000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 20 mJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C0
IS-B50HN-C1 50 MHz to 700 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 1 mJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C1
IS-B50HN-C2 125 MHz to 1000 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 800 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50HN-C2
IS-B50HU-C0 1.5 MHz to 400 MHz HF 3 kW, VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 20 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50HU-C0
IS-B50HU-C1 50 MHz to 700 MHz VHF 500 W, UHF 250 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform
±1200 Vdc ± 20 % 7 ns for 2 kV / ns< 1 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50HU-C1
IS-B50LN-C0 1.5 MHz to 400 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 10 mJ for 3 kA, 8/20 µs waveform
N Female N Female IS-B50LN-C0
IS-B50LN-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 600 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50LN-C1
IS-B50LN-C2 125 MHz to 1 GHz VHF 375 W, UHF 125 to 50 W ≤ 0.1 dB ≤ 1.1 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 220 µJ for 3kA, 8/20 µs waveform
N Female N Female IS-B50LN-C2
IS-B50LU-C0 1.5 MHz to 400 MHz HF 2 kW, VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 10 mJ for 3kA, 8/20 µs waveform
UHF Female UHF Female IS-B50LU-C0
IS-B50LU-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB ≤ 1.2 to 1 over frequency range50 kA per IEC 61000-4-5 8/20 µs waveform
±600 Vdc ± 20 % 2.5 ns for 2 kV / ns< 600 µJ for 3 kA, 8/20 µs waveform
UHF Female UHF Female IS-B50LU-C1
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection18
• High surge current capability
• Low let-through voltage and throughput energy
• DC shorted filter design, no DC continuity between center pins
• Ideal use for applications where DC is not required on the coaxial cable
• Fully weatherized housing
• Elongated female connector allows for mounting through a 1/4” bulkhead or grounding bar
• Multi-strike capability
Features
• IEC 60529 IP65
• Bellcore # TA-NWT-00487
• Procedure 4.11, wind driven
• UL 497B
• RoHS compliant
Standards and Certificates
DSXL
Humidity 100% condensing
Operating/Storage Temperature -40°C to +85°C
Vibration 1 G @ 5 Hz to 100 HzDSXL Series
Patented SX radio frequency DC blocked filter protectors are ideal for RF coaxial applications where DC is not required. The SX can be used on high-powered RF feeder lines in the range of 350 to 2,300 MHz, as well as low-powered microwave sites at 2 to 10 GHz. The SX is available in a multitude of connector configurations each exhibiting low return loss, insertion loss and let-through voltage.
DC Block
SX Series
Environmental
19
AL-LSXM
DSXL-D-MA
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection20
Frequency Range VSWR RF Power Insertion Loss PIM Performance Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
AL-LSXM 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W< 0.1 dB Typical (< 0.2 dB Max)
N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female AL-LSXM
AL-LSXM-MA 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W< 0.1 dB Typical (< 0.2 dB Max)
N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female AL-LSXM-MA
WSXM 6.0 GHz to 10.0 GHz < 1.2 to 1 over frequency range 10 W < 0.1 dB N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female WSXM
DSXL800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female DSXL
DSXL-D800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female DSXL-D
DSXL-D-MA800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA
DSXL-D-MA-BF800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA-BF
DSXL-D-MA-P2-BF800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB -120 dBm 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA-P2-BF
DSXL-D-ME800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Male DSXL-D-ME
DSXL-D-SP800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
500 W @ 85º C, 750 W @ 40º C, 1 kW @ 20º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female DSXL-D-SP
DSXL-DN-MA800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
500 W @ 85º C, 700 W @ 40º C, 1 kW @ 20º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male N Female DSXL-DN-MA
DSXL-MA800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA
DSXL-MA-SP800 MHz to 2.0 GHz800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA-SP
DSXL-MA-BF800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA-BF
DSXL-ME800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male DSXL-ME
DSXL-P800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB -110 dBm 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female DSXL-P
DC Block - SX Series
21
Frequency Range VSWR RF Power Insertion Loss PIM Performance Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
AL-LSXM 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W< 0.1 dB Typical (< 0.2 dB Max)
N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female AL-LSXM
AL-LSXM-MA 2.0 GHz to 6.0 GHz < 1.2 to 1 over frequency range 10 W< 0.1 dB Typical (< 0.2 dB Max)
N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female AL-LSXM-MA
WSXM 6.0 GHz to 10.0 GHz < 1.2 to 1 over frequency range 10 W < 0.1 dB N/A 10 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female WSXM
DSXL800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female DSXL
DSXL-D800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female DSXL-D
DSXL-D-MA800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA
DSXL-D-MA-BF800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA-BF
DSXL-D-MA-P2-BF800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB -120 dBm 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male DIN Female DSXL-D-MA-P2-BF
DSXL-D-ME800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 40º C, 1 kW @ 20º C, 500 W @ 85º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Male DSXL-D-ME
DSXL-D-SP800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
500 W @ 85º C, 750 W @ 40º C, 1 kW @ 20º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female DSXL-D-SP
DSXL-DN-MA800 MHz to 2.3 GHz700 MHz to 2.5 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
500 W @ 85º C, 700 W @ 40º C, 1 kW @ 20º C
< 0.1 dB N/A 30 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Male N Female DSXL-DN-MA
DSXL-MA800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA
DSXL-MA-SP800 MHz to 2.0 GHz800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA-SP
DSXL-MA-BF800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Male N Female DSXL-MA-BF
DSXL-ME800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male DSXL-ME
DSXL-P800 MHz to 2.3 GHz700 MHz to 2.7 GHz
< 1.1 to 1 over frequency range< 1.2 to 1 over frequency range
750 W @ 50º C, 500 W @ 920º MHz
< 0.1 dB -110 dBm 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female DSXL-P
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection22
Frequency Range VSWR RF Power Insertion Loss PIM Performance Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
PSXL 1.2 GHz to 2.8 GHz < 1.1 to 1 over frequency range 300 W < 0.1dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female PSXL
LSXL1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz
< 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female LSXL
LSXL-ME1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz
< 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male LSXL-ME
USXL-D350 MHz to 1.2 GHz
< 1.1 to 1 over frequency range1 kW @ 85 °C @ 450 MHz,2 kW @ 20 °C @ 450 MHz
< 0.1dB N/A 25 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female USXL-D
DC Block - SX Series
23
Frequency Range VSWR RF Power Insertion Loss PIM Performance Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
PSXL 1.2 GHz to 2.8 GHz < 1.1 to 1 over frequency range 300 W < 0.1dB N/A 20 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female PSXL
LSXL1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz
< 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Female LSXL
LSXL-ME1.8 GHz to 3.8 GHz 4.2 GHz to 6.0 GHz
< 1.2 to 1 over frequency range 10 W < 0.2dB N/A 18 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform N Female N Male LSXL-ME
USXL-D350 MHz to 1.2 GHz
< 1.1 to 1 over frequency range1 kW @ 85 °C @ 450 MHz,2 kW @ 20 °C @ 450 MHz
< 0.1dB N/A 25 kA per IEC 61000-4-5 8/20 µs waveform < 0.5 µJ for 3 kA, 8/20 µs waveform DIN Female DIN Female USXL-D
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection24
• Multi-strike capability
• Low throughput energy
• Mount to bracket or flat single point grounding panel
• Flange and bulkhead mounting options
Features
• RoHS compliant
Standards and Certificates
IS-50NX-C1-ME
Operating Temperature -45°C to +50°C
Vibration 1 G up to 100 Hz
IS-50NX-CO
The IS-50 series is a DC block broadband HF/VHF/UHF coaxial protector that operates in the frequency range of 1.5 to 1000 MHz.
DC Block
IS-50 Series
Environmental
25
IS-50NX-C0
IS-50NX-C0-MA
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection26
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-50NX-C0 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C0
IS-50NX-C0-MA 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C0-MA
IS-50NX-C0-ME 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C0-ME
IS-50NX-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C1
IS-50NX-C1-MA 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C1-MA
IS-50NX-C1-ME 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C1-ME
IS-50NX-C2 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C2
IS-50NX-C2-MA 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C2-MA
IS-50NX-C2-ME 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C2-ME
IS-50UX-C0 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Female UHF Female IS-50UX-C0
IS-50UX-C0-MA 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Male UHF Female IS-50UX-C0-MA
IS-50UX-C0-ME 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Female UHF Male IS-50UX-C0-ME
IS-50UX-C1 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Female UHF Female IS-50UX-C1
IS-50UX-C1-MA 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Male UHF Female IS-50UX-C1-MA
IS-50UX-C1-ME 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Female UHF Male IS-50UX-C1-ME
DC Block - IS-50 Series
27
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-50NX-C0 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C0
IS-50NX-C0-MA 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C0-MA
IS-50NX-C0-ME 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.1 to 1 for 2 to 400 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ 6 kV / 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C0-ME
IS-50NX-C1 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C1
IS-50NX-C1-MA 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C1-MA
IS-50NX-C1-ME 50 MHz to 700 MHz VHF 375 W, UHF 125 W ≤ 0.1 dB≤1.1 to 1 for 60 to 700 MHz
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 600 µJ for 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C1-ME
IS-50NX-C2 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Female N Female IS-50NX-C2
IS-50NX-C2-MA 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Male N Female IS-50NX-C2-MA
IS-50NX-C2-ME 125 MHz to 1 GHz125 to 220 MHz @ 375 W, 220 to 700 MHz @ 125 W, 700 to 1000 MHz @ 50 W
≤ 0.1 dB≤1.1 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 220 µJ for 3 kA, 8/20 µs waveform
N Female N Male IS-50NX-C2-ME
IS-50UX-C0 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Female UHF Female IS-50UX-C0
IS-50UX-C0-MA 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Male UHF Female IS-50UX-C0-MA
IS-50UX-C0-ME 1.5 MHz to 400 MHzHF 2 kW, VHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns≤ 10 mJ for 3 kA, 8/20 µs waveform
UHF Female UHF Male IS-50UX-C0-ME
IS-50UX-C1 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Female UHF Female IS-50UX-C1
IS-50UX-C1-MA 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Male UHF Female IS-50UX-C1-MA
IS-50UX-C1-ME 50 MHz to 700 MHzVHF 375 W, UHF 125 W
≤ 0.1 dB≤1.2 to 1 over frequency range
50 kA per IEC 1000-4-5 8/20 µs waveform 500 J
600 Vdc ± 20 % 2.5 ns for 2 kV/ns ≤ 600 µJ for 2 kV/ns UHF Female UHF Male IS-50UX-C1-ME
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection28
• Low throughput energy
• High surge current capability
• Ultra fast response
• VHF and UHF applications
• Bulkhead mount
Features
• RoHS compliant
Standards and Certificates
IS-NEMP-C0
Operating Temperature -45°C to +50°C
Vibration 1 G @ 5 Hz to 100 Hz
IS-NEMP-C0-MA
Ultra fast NEMP protection for frequency range of 1.5 to 1000 MHz, used in emergency radio communications equipment.
DC Block
NEMP Series
Environmental
29
IS-NEMP-C1-MA
IS-NEMP-C2-ME
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection30
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-NEMP-C0 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C0
IS-NEMP-C0-MA 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C0-MA
IS-NEMP-C0-ME 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C0-ME
IS-NEMP-C1 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 570 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C1
IS-NEMP-C1-MA 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 313 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C1-MA
IS-NEMP-C1-ME 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 313 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C1-ME
IS-NEMP-C2 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C2
IS-NEMP-C2-MA 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C2-MA
IS-NEMP-C2-ME 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C2-ME
DC Block - NEMP Series
31
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Turn on Voltage Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
IS-NEMP-C0 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 2 MHz to 400 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C0
IS-NEMP-C0-MA 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C0-MA
IS-NEMP-C0-ME 1.5 MHz to 400 MHz 500 W HF, 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 1100 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C0-ME
IS-NEMP-C1 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 570 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C1
IS-NEMP-C1-MA 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 313 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C1-MA
IS-NEMP-C1-ME 50 MHz to 700 MHz 200 W VHF, 100 W UHF ≤ 0.1dB < 1.1 to 1 @ 60 MHz to 700 MHz50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 313 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C1-ME
IS-NEMP-C2 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Female N Female IS-NEMP-C2
IS-NEMP-C2-MA 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Male N Female IS-NEMP-C2-MA
IS-NEMP-C2-ME 125 MHz to 1.0 GHz 200 W VHF, 100 W UHF, 50 W 800 MHz ≤ 0.1dB < 1.1 to 1 over frequency range50 kA per IEC1000-4-5 8/20 µs waveform 500 J
330 Vdc ± 20% 1.5 ns for 2 kV / ns< 250 µJ for 8/20 µs waveform
N Female N Male IS-NEMP-C2-ME
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection32
• High surge current capability with filter design
• Low let-through voltage and throughput energy
• No DC continuity between center pins
• Weatherized housing
• Insertion loss 0.1 dB
• High powered public safety, TETRA and UHF/VHF radio application
• Standard N, 7/16 DIN Connectors
Features
• IEC 61000-4-5
Standards and Certificates
UHF50HN
Humidity 95% non-condensing
Operating/Storage Temperature -50°C to +85°C
VHF50HN
DC block filter design provides for the ultimate in equipment protection producing the industry’s lowest let-through voltage and throughouput energy. Designed to protect multiple or high power single RF transmitter applications where DC is not required on the coaxial cable.
DC Block
HF Series
Environmental
33
VHF50HD-MA
VHF50HN
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection34
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
UHF50HD 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Female UHF50HD
UHF50HD-MA 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Male DIN Female UHF50HD-MA
UHF50HD-ME 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Male UHF50HD-ME
UHF50HN 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Female UHF50HN
UHF50HN-MA 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Male N Female UHF50HN-MA
UHF50HN-ME 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Male UHF50HN-ME
VHF50HD 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Female VHF50HD
VHF50HD-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Male DIN Female VHF50HD-MA
VHF50HD-ME 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Male VHF50HD-ME
VHF50HN 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Female VHF50HN
VHF50HN-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Male N Female VHF50HN-MA
VHF50HN-ME 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Male VHF50HN-ME
DC Block - HF Series
35
Frequency Range RF Power Insertion Loss VSWR Max Surge Current Throughput EnergySurge Side Connector
Protected Side Connector
UHF50HD 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Female UHF50HD
UHF50HD-MA 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Male DIN Female UHF50HD-MA
UHF50HD-ME 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Male UHF50HD-ME
UHF50HN 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Female UHF50HN
UHF50HN-MA 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Male N Female UHF50HN-MA
UHF50HN-ME 300 MHz to 700 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Male UHF50HN-ME
VHF50HD 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Female VHF50HD
VHF50HD-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Male DIN Female VHF50HD-MA
VHF50HD-ME 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform DIN Female DIN Male VHF50HD-ME
VHF50HN 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Female VHF50HN
VHF50HN-MA 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Male N Female VHF50HN-MA
VHF50HN-ME 100 MHz to 512 MHz 750 W < 0.1 dB < 1.1 to 1 over frequency range 20 kA per IEC 61000-4-5 8/20 µs waveform < 500 nJ for 3 kA, 8/20 µs waveform N Female N Male VHF50HN-ME
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection36
• Patented dual path RF and DC protection
• Multi-strike capacity
• Weatherized housing
• Low throughput energy
• Wide bandwith
Features
• IEC 60529IP67
• Bellcore #TA-NWT-00487
• UL 497B
• RoHS compliant
Standards and Certificates
DGXZ+06NFNF-A
Humidity 95% non-condensing
Operating/Storage Temperature -50°C to +85°C
Vibration 1 G @ 5 Hz to 500 HzDGXZ+06NFNF-A
The GX Series radio frequency DC pass filter protectors are ideal for RF coaxial applications where DC is required. The GX Series can be used on GPS and point to point radios as well as active tower mounted electronic equipment that operate in the range of 30 to 2,500 MHz. The GX Series is available in a multitude of connector configurations each exhibiting low return loss, insertion loss and let-through voltage.
DC Pass
GXZ Series
Environmental
37
DGXZ+24DFDF-A
DGXZ+06DFDM-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection38
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
BGXZ+24NFNF-A 30 MHz to 400 MHz 6.25 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A3 kA per IEC 61000-4-5 8/20 µs waveform
+26 Vdc 4 ns for 2 kV/ns≤ 1300 µJ for 3 kA, 8/20 µs waveform
N Female N Female BGXZ+24NFNF-A
CGXZ+15NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+15NFNF-A
CGXZ+24NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+24NFNF-A
CGXZ+36NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+36 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+40 Vdc 4 ns for 2 kV/ns≤ 1500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+36NFNF-A
CGXZ+48NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+48NFNF-A
CGXZ-15NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
-15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ-15NFNF-A
CGXZ-48NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ-48NFNF-A
DGXZ+06DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+06DFDF-A
DGXZ+06NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+06NFNF-A
DGXZ+06NMNF-U 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
N Male N Female DGXZ+06NMNF-U
DGXZ+06TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
TNC Female TNC Female DGXZ+06TFTF-A
DGXZ+15DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+15DFDF-A
DGXZ+15NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+15NFNF-A
DGXZ+15TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
TNC Female TNC Female DGXZ+15TFTF-A
DGXZ+24DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+24DFDF-A
DGXZ+24NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+24NFNF-A
DGXZ+36NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+36 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+40 Vdc 4 ns for 2 kV/ns≤ 1.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+36NFNF-A
DGXZ+48DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+48DFDF-A
DC Pass - GXZ Series
39
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
BGXZ+24NFNF-A 30 MHz to 400 MHz 6.25 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A3 kA per IEC 61000-4-5 8/20 µs waveform
+26 Vdc 4 ns for 2 kV/ns≤ 1300 µJ for 3 kA, 8/20 µs waveform
N Female N Female BGXZ+24NFNF-A
CGXZ+15NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+15NFNF-A
CGXZ+24NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+24NFNF-A
CGXZ+36NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+36 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+40 Vdc 4 ns for 2 kV/ns≤ 1500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+36NFNF-A
CGXZ+48NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ+48NFNF-A
CGXZ-15NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
-15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ-15NFNF-A
CGXZ-48NFNF-A 400 MHz to 1200 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female CGXZ-48NFNF-A
DGXZ+06DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+06DFDF-A
DGXZ+06NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+06NFNF-A
DGXZ+06NMNF-U 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
N Male N Female DGXZ+06NMNF-U
DGXZ+06TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+ 6 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+6.5 Vdc 4 ns for 2 kV/ns≤ 175 µJ for 3 kA, 8/20 µs waveform
TNC Female TNC Female DGXZ+06TFTF-A
DGXZ+15DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+15DFDF-A
DGXZ+15NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+15NFNF-A
DGXZ+15TFTF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+15 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+16.5 Vdc 4 ns for 2 kV/ns≤ 500 µJ for 3 kA, 8/20 µs waveform
TNC Female TNC Female DGXZ+15TFTF-A
DGXZ+24DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+24DFDF-A
DGXZ+24NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+24 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+26.5 Vdc 4 ns for 2 kV/ns≤ 1 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+24NFNF-A
DGXZ+36NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+36 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+40 Vdc 4 ns for 2 kV/ns≤ 1.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+36NFNF-A
DGXZ+48DFDF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ+48DFDF-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection40
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
DGXZ+48NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+48NFNF-A
DGXZ+60NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+60 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+66.5 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+60NFNF-A
DGXZ-48DFDF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ-48DFDF-A
DGXZ-48NFNF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ-48NFNF-A
DGXZ-60NFNF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-60 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-66.5 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ-60NFNF-A
DGXE+30NMNF-A 650 MHz to 2700 MHz 400 Wrms average < 0.1 dB< 1.1 to 1 over frequency range
+30 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+33 Vdc 4ns for 2 kV/ns
4 ns for 2 kV/ns≤ 1.5 mJ for 3 kA, 8/20 µs waveform
N Male N Female DGXE+30NMNF-A
DC Pass - GXZ Series
41
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
DGXZ+48NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+48NFNF-A
DGXZ+60NFNF-A 800 MHz to 2500 MHz 300 W < 0.1 dB< 1.1 to 1 over frequency range
+60 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+66.5 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ+60NFNF-A
DGXZ-48DFDF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXZ-48DFDF-A
DGXZ-48NFNF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-48 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-54 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ-48NFNF-A
DGXZ-60NFNF-A 800 MHz to 2500 MHz 40 W < 0.1 dB< 1.1 to 1 over frequency range
-60 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
-66.5 Vdc 4 ns for 2 kV/ns≤ 2.5 mJ for 3 kA, 8/20 µs waveform
N Female N Female DGXZ-60NFNF-A
DGXE+30NMNF-A 650 MHz to 2700 MHz 400 Wrms average < 0.1 dB< 1.1 to 1 over frequency range
+30 Vdc < 4.0 A20 kA per IEC 61000-4-5 8/20 µs waveform
+33 Vdc 4ns for 2 kV/ns
4 ns for 2 kV/ns≤ 1.5 mJ for 3 kA, 8/20 µs waveform
N Male N Female DGXE+30NMNF-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection42
• Coaxial RF protection with integrated Bias-T
• Patented technology
• VSWR: ≤1.1:1 over frequency range
• Multi-strike capability, high MTBF
• Low throughput energy
• Weatherized
Features
• IEC 61000-4-5
• IEC 60529
• UL 497B
• RoHS compliant
Standards and Certificates
CGXJ+30NFNM-A
Humidity 95% non-condensing
Operating/Storage Temperature -50°C to +85°C
Enclosure Rating IEC 60529, IP 67
CGXJ+30NFNM-A
Integrated Bias-T, hybrid, multi-stage, multi-strike, fast response, high current capacity, DC pass coaxial lightning protection available with DIN and N connectors with frequency ranges of 400 MHz to 1.2 GHz and 800 MHz to 2.5 GHz.
DC Pass
GXJ Series
Environmental
43
DGXJ+15NFNF-A
DGXJ+36DFDF-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection44
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
CGXJ+15NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+15NFNF-A
CGXJ+24NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+24NFNF-A
CGXJ+30NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+30 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +33 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+30NFNM-A
CGXJ+36DFDF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female CGXJ+36DFDF-A
CGXJ+36DFDM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male CGXJ+36DFDM-A
CGXJ+15NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+15NFNM-A
CGXJ+36NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+36NFNF-A
CGXJ+36NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+36NFNM-A
CGXJ+36NMNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Male N Female CGXJ+36NMNF-A
DGXJ+15DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+15DFDF-A
DGXJ+15DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+15DFDM-A
DGXJ+15DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+15DMDF-A
DGXJ+15NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+15NFNF-A
DGXJ+24DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+24DFDF-A
DGXJ+24DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+24DFDM-A
DC Pass - GXJ Series
45
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
CGXJ+15NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+15NFNF-A
CGXJ+24NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+24NFNF-A
CGXJ+30NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+30 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +33 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+30NFNM-A
CGXJ+36DFDF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female CGXJ+36DFDF-A
CGXJ+36DFDM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male CGXJ+36DFDM-A
CGXJ+15NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+15NFNM-A
CGXJ+36NFNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female CGXJ+36NFNF-A
CGXJ+36NFNM-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male CGXJ+36NFNM-A
CGXJ+36NMNF-A 400 MHz to 1.2 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Male N Female CGXJ+36NMNF-A
DGXJ+15DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+15DFDF-A
DGXJ+15DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+15DFDM-A
DGXJ+15DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+15DMDF-A
DGXJ+15NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+15 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +20 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+15NFNF-A
DGXJ+24DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+24DFDF-A
DGXJ+24DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+24DFDM-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection46
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
DGXJ+24DFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female N Male DGXJ+24DFNM-A
DGXJ+24DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+24DMDF-A
DGXJ+24NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+24NFNF-A
DGXJ+24NFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male DGXJ+24NFNM-A
DGXJ+36DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+36DFDF-A
DGXJ+36DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+36DFDM-A
DGXJ+36DFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female N Male DGXJ+36DFNM-A
DGXJ+36DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+36DMDF-A
DGXJ+48DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+48DFDF-A
DGXJ+48NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+48NFNF-A
DGXJ-48DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
-48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs -53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ-48DFDM-A
DGXJ-48NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
-48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs -53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ-48NFNF-A
DC Pass - GXJ Series
47
Frequency Range RF Power Insertion Loss VSWR
Max Continuous Operating Voltage
Max Continuous Operating Current
Max Surge CurrentTurn on Voltage
Turn on Time Throughput EnergySurge Side Connector
Protected Side Connector
DGXJ+24DFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female N Male DGXJ+24DFNM-A
DGXJ+24DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+24DMDF-A
DGXJ+24NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+24NFNF-A
DGXJ+24NFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+24 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +26 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Male DGXJ+24NFNM-A
DGXJ+36DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+36DFDF-A
DGXJ+36DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Male DGXJ+36DFDM-A
DGXJ+36DFNM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female N Male DGXJ+36DFNM-A
DGXJ+36DMDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+36 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +40 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Male DIN Female DGXJ+36DMDF-A
DGXJ+48DFDF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ+48DFDF-A
DGXJ+48NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
+48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs +53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ+48NFNF-A
DGXJ-48DFDM-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
-48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs -53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
DIN Female DIN Female DGXJ-48DFDM-A
DGXJ-48NFNF-A 800 MHz to 2.5 GHz 300 W average≤ 0.1 dB over frequency range
≤ 1.1:1 over frequency range
-48 Vdc ≤ 4.0 A 20 kA per IEC 6100-4-5 8/20µs -53 Vdc 4 ns for 2 kV ns<25 µJ for 3 kA, 8/20 µs waveform
N Female N Female DGXJ-48NFNF-A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection48
• High surge current capability
• High power configurations available
• ±60 Vdc pass configurations available (DT models)
• Weatherized
Features
• IEC 61000-4-5
Standards and Certificates
GT-NFF-AL
Humidity 95% non-condensing
Operating/Storage Temperature -55°C to +85°C
GT-NFF-AL
High performance gas tube coaxial protection for RF signals. Performs well in applications where a higher voltage let-through is acceptable, yet good RF performance is essential.
DC Pass
GT Series
Environmental
49
GT-DFM-AL
GT-NFSF-AL
DT-NFM
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection50
Frequency Range RF Power Insertion Loss VSWRMax Continuous Operating Current
Max Surge Current Surge Side Connector Protected Side Connector
GT-NFF-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFF-AL
GT-NFSF-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFSF-AL
GT-NFM-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GT-NFM-AL
GT-DFF-AL DC to 3.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz ≤1.1:1 DC to 3.0 GHz 10 A 20 kA 8/20 µs per IEC 61000-4-5 DIN Female DIN Female GT-DFF-AL
GT-DFM-AL DC to 3.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz ≤1.1:1 DC to 3.0 GHz 10 A 20 kA 8/20 µs per IEC 61000-4-5 DIN Female DIN Male GT-DFM-AL
GTH-NFF-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GTH-NFF-AL
GTH-NFM-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GTH-NFM-AL
GT-TFF-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz
≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Female GT-TFF-AL
GT-TFM-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz
≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Male GT-TFM-AL
DT-NFF DC to 3.0 GHz 40 W @ 30 MHz≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz
≤1.1:1 DC to 1.0 GHz 10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Female DT-NFF
DT-NFM DC to 3.0 GHz 40 W @ 30 MHz≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz
≤1.1:1 DC to 1.0 GHz, ≤1.15:1 DC to 3.0 GHz
10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Male DT-NFM
DC Pass - GT Series
51
Frequency Range RF Power Insertion Loss VSWRMax Continuous Operating Current
Max Surge Current Surge Side Connector Protected Side Connector
GT-NFF-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFF-AL
GT-NFSF-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GT-NFSF-AL
GT-NFM-AL DC to 7.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GT-NFM-AL
GT-DFF-AL DC to 3.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz ≤1.1:1 DC to 3.0 GHz 10 A 20 kA 8/20 µs per IEC 61000-4-5 DIN Female DIN Female GT-DFF-AL
GT-DFM-AL DC to 3.0 GHz90 W @ 30 MHz, 9 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz ≤1.1:1 DC to 3.0 GHz 10 A 20 kA 8/20 µs per IEC 61000-4-5 DIN Female DIN Male GT-DFM-AL
GTH-NFF-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Female GTH-NFF-AL
GTH-NFM-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 7.0 GHz
≤1.1:1 DC to 3.0 GHz, ≤1.2:1 3.0 to 4.0 GHz, ≤1.4:1 4.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 N Female N Male GTH-NFM-AL
GT-TFF-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz
≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Female GT-TFF-AL
GT-TFM-AL DC to 7.0 GHz1 kW @ 30 MHz, 300 W @ 3 GHz
≤0.1 dB @ DC to 3.0 GHz, ≤0.25 dB @ 3.0 to 5.0 GHz, ≤0.5 dB @ 5.0 to 7.0 GHz
≤1.1:1 DC to 2.0 GHz, ≤1.2:1 2.0 to 3.0 GHz, ≤1.4:1 3.0 to 7.0 GHz
10 A 20 kA 8/20 µs per IEC 61000-4-5 TNC Female TNC Male GT-TFM-AL
DT-NFF DC to 3.0 GHz 40 W @ 30 MHz≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz
≤1.1:1 DC to 1.0 GHz 10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Female DT-NFF
DT-NFM DC to 3.0 GHz 40 W @ 30 MHz≤0.1 dB @ DC to 1.0 GHz, ≤0.25 dB @ 1.0 to 3.0 GHz
≤1.1:1 DC to 1.0 GHz, ≤1.15:1 DC to 3.0 GHz
10 A 4 kA 8/20 µs per IEC 61000-4-5 N Female N Male DT-NFM
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Coaxial RF Surge Protection52
• 3, 5 and 8 port earthed entrance panels
• Building entry panels
Features
5PEEP-M
Single point grounding is the most important part of any lightning protection system. PolyPhaser entry establishes a single point grounding solution. Whether you have a thick wall, thin wall, or multiple lines, PolyPhaser provides both panels and accessories to support all grounding requirements.
Grounding and Accessories
Grounding
Wall Thickness # of Ports Max. Cable Diameter
3PEEP > 8” 3 3.13”
5PB-M 10” 5 3.13”
5PEEP-M > 8” 5 3.13”
8PB-M 10” 8 3.13”
8PEEP-M > 8” 8 3.13”
5PEEP-M
53
• Shield grounding kits
• Copper grounding kits
• Clamps
• Copper straps
• Adaptors
Options for Accessories
PolyPhaser offers a full line of accessories needed to complete any professional single point grounding project.
Accessories
Grounding Clamp Product Description Application
58R-112S Bonding Clamp Copper Strap Clamp
J-1 Transition Clamp for 0.5” to 1.33” diameter Wire/copper rod transition clamp
J-2 Transition Clamp for 1.5” to 2.25” diameter Wire/copper rod transition clamp
Grounding Kit Product Description Application
CCK Kit, Copper Cleaning Copper Cleaning Kit
CU-SPGP Copper Single Point Ground Panel Grounding Plate 16” on center
Device Ground Adaptor
Product Description Application
GSA-KIT-N Kit, Ground Strap Adaptor N connector Ground Strap Adaptor SX Series
Copper Grounding Strap
Width Length
CS112-25 1.5” 25’
CS112-50 1.5” 50’
CS112-100 1.5” 100’
CS3-25 3” 25’
CS3-50 3” 50’
CS3-100 3” 100’
CS6-25 6” 25’
CS6-50 6” 50’
CS6-100 6” 100’
Coaxial Shield Grounding Kit
Shield Diameter Shield Material Grounding to
UNI-KIT-4CC 2.125” to 4” Copper or Brass Aluminum, Tin or Galvanized
UNI-KIT-4CT 2.125” to 4” Copper or Brass Copper or Brass
UNI-KIT-4TC 2.125” to 4” Aluminum, Tin or Galvanized Aluminum, Tin or Galvanized
58R-112S
CCK
GSA-KIT-N
CS Series
UNI-KIT-4CC
J-2
CU-SPGP
55
End to end data line protection solutions are available in both custom as well as commercial
off-the-shelf products for digital and analog signals in both indoor and outdoor enclosures.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 56
• Low capacitance (3 pF) high surge current capacity (20 kA)
• Compact 1 RU modular chassis fits up to 16 modules
• Fused options satisfy GR-1089-CORE Issue 4 EIPP installation requirements
• Coordinated Level I & Level II lightning protection
• Front access, modular for multi-protocol installations: 10/100 Ethernet, GbE and T1/E1
• Dual lug grounding studs
Features
• GR-1089-CORE Issue 4
• UL 497A (fused)
• UL 497B (non-fused)
• IEEE 802.3
• ITU 703
Standards and Certificates
1101-977
High density, modular, multi-protocol, coordinated Level I and Level II surge protection for OSP environments.
Multi-Protocol Equipment Protector
CPX Series
57
Input/Output Connector RJ-45
Chassis Dimensions (H x W x D) in
1.75 x 19.0 x 3.3
Chassis Dimensions (H x W x D) cm
4.5 x 48.3 x 8.4
Chassis Weight (max) lb, kg
3.0, 1.36
Module Weight (max) lb, kg
0.1, 0.05
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +75°C
Protocol Ethernet T1/E1 Gigabit Ethernet
Data Rate 10 / 100 Mb/s 1.544 / 2.048 Mb/s 10 / 100 / 1000 Mb/s
Pins Protected (1, 2) and (3, 6) (1, 2) and (4, 5) (1, 2), (3, 6), (4, 5) and (7, 8)
Pins Bonded to Ground (4, 5) and (7, 8) (3, 6) and (7, 8) n / a
Nominal Voltage 5 Vdc 3.3 Vdc 5 Vdc
Max Continuous Operating Voltage
< 11 Vpk
Max Continuous Operating Amperage
< 180 mA
Max Surge Current 20 kA 8/20 µs per Level II GR 1089-CORE Issue 4, port type 3 & 5 surge
Mechanical
Environmental
Electrical
Part Name 10/100BTFused
10/100BTNon-Fused
T1/E1Fused
T1/E1Non-Fused
GbEFused
GbENon-Fused
Module 1000-1268 1000-1268-NF 1000-1269 1000-1269-NF 1000-1270 1000-1270-NF
16 Port Chassis 1101-984 1101-974 1101-986 1101-976 1101-985 1101-975
8 Port Chassis 1101-987 1101-977 1101-989 1101-979 1101-988 1101-978
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 58
• Easy installation with ground stud and RJ-45 jacks
• High surge current capacity
Features
• UL 497B Listed
• RoHS compliant
Standards and Certificates
1101-994
Compact data line surge protection for T1, gigabit PoE, GbE, PoE and Ethernet with 48 Vdc power.
Multi-Protocol Equipment Protector
TSJ Series
59
Input/Output Connector Shielded RJ-45 Shielded RJ-45 Shielded RJ-45 Shielded RJ-45 Non-shielded RJ-45
Max Dimensions (H x W x D) in
3.2 x 2.2 x 1.7
Max Dimensions (H x W x D) cm
8.1 x 5.6 x 4.3
Weight (max) lb, kg 0.2, 0.1
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +85°C
Enclosure Rating UL 94V-0
Application Gigabit PoE Gigabit PoE 56 Ethernet 48 CLT
Data Rate 1000 Mb/s 1000 Mb/s 10/100 Mb/s 10/100 Mb/s 1.44/2.048 Mb/s
Pins Protected All pins L-L and L-G 1, 2, 3, 6 1, 2, 4, 5
Nominal Voltage 48 Vdc 5 Vdc 48 Vdc 5 Vdc 12 Vdc
Max Continuous Operating Voltage
56 Vdc 11 Vdc 56 Vdc 11 Vdc 12 Vdc
Max Surge Current 10/1000 µs per Telecordia GR 1089
1 kA L-L, L-G 500 A L-L, L-G 100 A L-L, L-G 500 A L-L, L-G 100 A L-L, L-G
Max Surge Current 8/20 µs per IEC 6100-4-5
20 kA L-L, L-G 5 kA L-L, L-G 1.5 kA L-L, L-G 5 kA L-L, L-G 2.5 kA L-L
Mechanical
Environmental
Electrical
Part Name TSJ GbE PoE TSJ GbE TSJ POE 56 TSJ 10/100 TSJ 48 CLT
Part Number 1101-994 1101-990 1101-991 1101-1001 1101-300-1
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 60
• Non-degradable, low clamping silicon diode suppression technology (except 1101-911)
• Line and load bidirectional protection
• 1RU chassis holds up to 16 modules and is adjustable to fit 19” or 23” racks
• Unprotected pins bonded to ground
Features
• GR-1089
• NEC 800.100 and 830.100
• IEEE 802.3af
• ITU 703
Standards and Certificates
1000-1206
Modular, reconfigurable, rack, wall or DIN rail mount surge protection for PoE, GbE, Ethernet, T1/E1 and xDSL.
Multi-Protocol Equipment Protector
DPR (Data Protection Rack)
61
Input/Output Connector RJ-45
Module Dimensions (H x W x D) in
1.0 x 1.0 x 3.7
Module Dimensions (H x W x D) cm
2.5 x 2.5 x 9.4
Chassis Dimensions (H x W x D) in
1.8 x 19.0 x 3.7
Chassis Dimensions (H x W x D) cm
4.4 x 48.3 x 9.4
Module Weight (max) lb, kg
1.5, 0.7
Chassis Weight (max) lb, kg
5.2, 2.4
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +75°C
Enclosure Rating UL 94V-0
Protocol Ethernet T1/E1 xDSL GbE PoE GbE / PoE
Data Rate 10/100 Mb/s 1.544/2.048 Mb/s 6.312 Mb/s 10/100/1000 Mb/s 10/100 Mb/s 10/100/1000 Mb/s
Pins Protected(1,2) (3,6) (4,5) and (7,8)
(1,2) and (4,5) (1,2) and (4,5)(1,2) (3,6) (4,5) and (7,8)
(1,2) (3,6) (4,5) and (7,8)
(1,2) (3,6) (4,5) and (7,8)
Nominal Voltage 5 Vpk 3 Vpk 3 Vpk 3.3 Vpk 48 Vpk 60 Vpk
Max Continuous Operating Voltage
6Vpk 6 Vpk 5.5 Vpk 6 Vpk 60 Vpk 75 Vpk
Surge Suppression<25 Vpk @ 100 A 10/1000 µs
<25 Vpk @ 100 A / 10/1000 µs
<25 Vpk @ 100 A / 10/1000 µs
<22Vpk @ 100 A / 2/10µs
<75Vpk @ 100 A / 10/1000µs
<100 Vpk @ 100 A / 10/1000 µs
Mechanical
Environmental
Electrical
Part Name DPR Ethernet DPR T1/E1 DPR XDSL DPR 1000 Base T DPR POE 60 V DPR GT
Part Number 1101-828 1101-830 1101-829 1101-882 1101-905 1101-911
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
62 Data Line Surge Protection
• Non-degradable, low clamping silicon diode protection
• Line and load bidirectional protection
• External ground lug
• 6 individual circuits
• Easy to install
• Unprotected pins bonded to ground
• Replacement modules available
Features
• GR 1089 CORE
Standards and Certificates
1101-995
Six port data line protector for T1/E1 and Ethernet applications.
Multi-Protocol Equipment Protector
TSJ X6 Series
Input/Output Connector RJ-45 (unshielded) RJ-45 (shielded) RJ-45 (shielded)
Enclosure Dimensions (H x W x D) in
5.3 x 5.7 x 1.2
Enclosure Dimensions (H x W x D) cm
13.5 x 14.5 x 3.0
Weight (max) lb, kg 0.5, 0.2
Application T1/E1 Ethernet Gigabit Ethernet
Data Rate 1.44/2.048 Mb/s 10/100 Mb/s 1000 Mb/s
Pins ProtectedData (1, 2) and (4, 5)
Data (1, 2) and (3,6 )
(1, 2)(4,5)(3,6) and (7,8)
Nominal Voltage 3 Vpk 5 Vpk 3.3 V
MCOV Data 12 Vpk 12 Vpk 11 Vpk
Voltage Protection Level <26 Vpk @ 100 A 10/1000 µs
Max Surge Current 100 A @ 10/1000 µs500 A @ 8/20 μs, 100 A @ 10/1000 µs
5 kA @ 8/20 μs, 100 A @ 10/1000 µs
Mechanical
Environmental
Electrical
Part Name TSJ X6A TSJ 10/100 TSJ X6 GbE
Part Number 1101-772-A 1101-995 1101-1044
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +85°C
Enclosure Rating UL94V-0
Data Line Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 63
• High surge current capacity
• Optimized for signal throughput
Features
• IEC 6100-4-5
• Telecordia GR 1089
• IEEE 802.3
Standards and Certificates
1101-1028
Outdoor, RJ-45, bulkhead mount, IP 67, surge protector for 10/100 Mb/s PoE, gigabit Ethernet and gigabit PoE.
Multi-Protocol Equipment Protector
TB (Thunderbolt) Series
Input/Output Connector RJ-45
Enclosure Dimensions (H x W x D) in
1.5 x 1.5 x 4.0
Enclosure Dimensions (H x W x D) cm
3.6 x 3.6 x 10.0
Weight (lb, kg) 0.2, 0.1
Application PoE Gigabit Ethernet Gigabit PoE
Data Rate 10/100 Mb/s 1000 Mb/s 1000 Mb/s
Pins Protected Data (1, 2) and (3 ,6), DC power (4, 5) and (7, 8)
(1, 2), (3 ,6), (4, 5) and (7, 8)
(1, 2), (3 ,6), (4, 5) and (7, 8)
Nominal Voltage 48 Vdc 3.3 Vdc 48 Vdc
Max Continuous Operating Voltage
90 Vpk (pins 4, 5, 7, 8)11 Vpk (pins 1, 2, 3, 6)
11 Vpk 90 Vpk
Max Surge Current 5 kA 8/20 µs
Mechanical
Environmental
Electrical
Part Name TB 10/100/PoE TB GbE TB GbE PoE
Part Number 1101-1028 1101-1029 1101-1030
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +75°C
Enclosure Rating IP 67
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 64
• Non-degradable, quick response silicon diode technology
• Optimized for point-to-point and point-to-multipoint radios
• Line and load bidirectional protection
• UL 497 protection from powerline cross, sneak current and over voltage (1101-640)
• ALPU Pole Mounting Kit (1000-1164)
Features
• UL 497
• IEEE/ANSI C62.41
Standards and Certificates
1101-640
Gigabit Ethernet and Power over Ethernet pole-mountable lightning protection.
Multi-Protocol Equipment Protector
ALPU Series
65
Input/Output Connector IDC punch down block (10 pair) RJ-45 and screw terminal IDC punch down block (8 pair)
Enclosure Dimensions (H x W x D) in
7.3 x 4.7 x 2.5
Enclosure Dimensions (H x W x D) cm
18.4 x 11.9 x 6.4
Weight (max) lb, kg 1.7, 0.8
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +85°C
Enclosure Rating UL 94-V5 / NEMA 3R
Protocol Ethernet, PoE Ethernet, PoE GbE, PoE
Data Rate 100 Mb/s 100 Mb/s 1000 Mb/s
Pins Protected(1, 2), (3, 6), (4, 5) and (7, 8) + reset wire and LED signal wire
Data (1, 2), (3, 6), DC (4, 5) (7, 8) (1, 2), (3, 6), (4, 5) and (7, 8)
Nominal Voltage 55 Vdc Data 6 Vdc, DC 48 Vdc 55 Vdc
Max Continuous Operating Voltage
90 Vpk Data 13 Vdc, DC 60 Vdc 94 Vpk pins (1, 2) and (3, 6) and 99 Vdc pins (4, 5) and (7, 8)
Voltage Protection Level<130 Vpk @ 150 A 10/1000 µs, 152 Vpk 1.5 kA 8/20 µs
21.5 Vpk on data and 86 Vpk on DC pairs @ 27 Vpk on data and 108 Vpk on DC pairs @ 2.5 kA 8/20 µs
152 Vpk @ 1.5 kA8/20 µs
Max Surge Current 1.5 kA 8/20 µs, 150 A 10/1000 µs 2.5 kA 8/20 µs, 200 A 10/1000 µs 120 A 10/1000 µs
Mechanical
Environmental
Electrical
Part Name ALPU ALVR ALPU-TSU ALPU-ORT
Part Number 1101-640 1101-656 1101-778
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection66
• DC modules optimized to 12, 24, 48, 56 or 72 Vdc
• Data line modules optimized for POTS, Telco Trunk, T1/E1, RS-232, RS-422, RS-485 Ethernet or PoE
• Weatherized enclosure
• Available with isolated ground
• SMCP-OD pair configuration available
• Boards available in bags of 50
• Pole mount kit offered
Features
Part Number Matrix
• UL 497 B
• GR-1089
• RoHS compliant
Standards and Certificates
IX-2H2DC48
Configurable, modular, weatherized, twisted pair surge protection for up to five pairs.
Multi-Protocol Equipment Protector
IX Series
Board Application Turn on Voltage
SeriesImpedance
Capacitance(Differential)
Capacitance(Common)
H Cat5, UTP, STP +9 Vdc ±10% I ohm ±20% 30 pF Typical 15 pF Typical
L T1/E1, RS4223, RS485
± 12 Typical I ohm ±20% 100 pF Typical 100 pF Typical
M RS232 ± 31 Typical I ohm ±20% 100 pF Typical 100 pF Typical
N PoE ±64 Typical I ohm ±20% 50 pF Typical 50 pF Typical
P POTS/ext Lines ± 110 Typical I ohm ±20% 40 pF Typical 40 pF Typical
TRing Voltage, DSL, ADSL, HDSL
± 210 Typical I ohm ±20% 30 pF Typical 30 pF Typical
DC 12 12 Vdc Power +18 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 24 24 Vdc Power +33 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 48 48 Vdc Power +56 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 56 56 Vdc Power +68 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 72 72 Vdc Power +82 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 12-IG 12 Vdc Power +18 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 24-IG 24 Vdc Power +33 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 48-IG 48 Vdc Power +56 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 56-IG 56 Vdc Power +68 Vdc ±10% 0.05 ohm ±20% N/A N/A
DC 72-IG 72 Vdc Power +82 Vdc ±10% 0.05 ohm ±20% N/A N/A
Mechanical
Input/Output Connector 28 to 16 AWG terminal screw
Dimensions (H x W x D) in 5.3 x 2.5 x 1.7
Dimensions (H x W x D) cm 13.3 x 6.4 x 4.3
Weight (max) lb, kg 0.7, 0.4
Environmental
Operating Temperature -40°C to +65°C
Note: If not using either power or data boards, simply drop them from the part number
Isolated groundVoltage of power boardPower board designatorNumber of power boardsType of data boardsNumber of data boardsSeries designator
IX - 2 H 1 DC 48 - IG
Data Line Surge Protection 67
IX Series
Model Name/Number IX-1T IX-2H1DC56-IG IX-2H1DC24-IG IX-2H1DC48-IG IX-2L IX-2T
Application xDSL PoE PoE PoET1/E1 or RS-422/RS-485
Dual Telco Trunk
Data Rate Up to 25 Mb/s 10/100 Mb/s 10/100 Mb/s 10/100 Mb/s Up to 25 Mb/s Up to 25 Mb/s
Data Turn On @ 10 mA ±210 Vdc±9 Vdc ±10% per board
±9 Vdc ±10% ±9 Vdc ±10% ±12 Vdc ±10 % ±210 Vdc ±10 %
Data Series Resistance 1.0 Ohm ±2%
Data Voltage Protection 100 Vdc/sec
< ±260 Vdc < ±9.6 Vdc < ±9.6 Vdc < ±9.6 Vdc < ±13 Vdc < 260 Vdc
DC Nominal Voltage N/A ±56 Vdc ±24 Vdc ±48 Vdc N/A N/A
DC Turn On @ 2 A N/A ±68 Vdc ±10 % ±33 Vdc ±10 % ±56 Vdc ±10 % N/A N/A
DC Voltage Protection 100 Vdc/sec
N/A < ±75 Vdc < ±34 Vdc < ±58 Vdc N/A N/A
DC Series Resistance 0.05 Ohms ±2%
Max Surge Current 100 A @10/1000 µs per Telecordia GR-1089
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 68
• UL 94V-0 flame rated plastic and aluminum enclosures available
• Compact design
• 1/4-20 ground stud
Features
• GR-1089
• NEC 800.100 and 830.100
• IEEE 802.3af
• CE
• RoHS compliant
Standards and Certificates
1101-873
Compact, outdoor, RJ-45, Power over Ethernet surge protection for point-to-point and point-to-multi-point radios.
PoE Protector
ALPU POE Series
69
Input/Output Connector RJ-45 shielded 100 Ohm
Dimensions (H x W x D) in 7.2 x 3.0 x 1.7 6.7 x 3.7 x 1.7 7.2 x 3.0 x 1.7 6.7 x 3.7 x 1.7 7.2 x 3.0 x 1.7 6.7 x 3.7 x 1.7
Dimensions (H x W x D) cm 18.2 x 7.7 x 4.2 17.1 x 9.4 x 4.2 18.2 x 7.7 x 4.2 17.1 x 9.4 x 4.2 18.2 x 7.7 x 4.2 17.1 x 9.4 x 4.2
Weight (max) lb, kg 0.8, 0.4 0.5, 0.2 0.8, 0.4 0.5, 0.2 0.8, 0.4 0.5, 0.2
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +80°C
Protocol Power over Ethernet
Data Rate 100 Mb/s
Pins Protected Data (1,2) and (3,6), DC power (4,5) and (7,8)
Data Nominal Voltage 5 Vpk 5 Vpk 48 Vpk 48 Vpk 75 Vpk 75 Vpk
DC Nominal Voltage 48 Vdc 48 Vdc 48 Vdc 48 Vdc 75 Vdc 75 Vdc
MCOV Data 6 Vpk 6 Vpk 48 Vpk 48 Vpk 75 Vpk 75 Vpk
MCOV DC Power 60 Vpk 60 Vpk 48 Vpk 48 Vpk 75 Vpk 75 Vpk
Data Voltage Protection Level
< 25 Vpk @ 100 A 10/1000 μs < 75 Vpk @ 100 A 10/1000 μs < 150 Vpk @ 100 A 10/1000 μs
DC Power Voltage Protection Level
< 75 Vpk @ 100 A 10/1000 μs < 75 Vpk @ 100 A 10/1000 μs < 150 Vpk @ 100 A 10/1000 μs
Impedance 85 to 115 Ohms
Mechanical
Environmental
Electrical
Part Name ALPU-POE-06-M ALPU-POE-06 ALPU-POE-60-M ALPU-POE-60 ALPU-POE-90-M ALPU-POE-90
Part Number 1101-932 1101-873 1101-933 1101-897 1101-934 1101-898
Enlosure Material Cast Aluminum Plastic Cast Aluminum Plastic Cast Aluminum Plastic
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
70 Data Line Surge Protection
• High surge current capacity
• Ideal for Motorola canopy systems with 8 PoE lines
Features
• IEC 6100-4-5
• GR 1089 CORE
• IEEE 802.3
Standards and Certificates
1101-805
Eight port, outdoor, PoE protector with RJ-45 connectors.
PoE Protector
ALPU CMM3
Input/Output Connector RJ-45 Shielded
Enclosure Dimensions in (H x W x D )
17.0 x 11.0 x 6.0
Enclosure Dimensions cm (H x W x D )
43.0 x 28.0 x 15.0
Weight (max) lb, kg 7.0, 3.2
Data Rate 10/100 Mb/s
Pins Protected (1, 2), (3, 6), (4, 5) and (7, 8)
Max Continuous Operating Voltage 90 Vpk
Max Surge Current 800 A 8/20 µs, 200 A 10/1000 µs
Mechanical
Environmental
Electrical
Part Name ALPU CMM3
Part Number 1101-805
Humidity 90% non-condensing
Operating/Storage Temperature -20°C to +65°C
Enclosure Rating UL 1863
Data Line Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 71
• Non-degradable, low clamping, leadless silicon diode protection
• Line and load bidirectional protection
• Functions as bridge clip
• Ground bar (1101-621)
Features
• Bellcore 1089
Standards and Certificates
1101-115
Data line surge protection for 66 punch down block applications.
Punch Down Block Protector
PBM Series
Input/Output Connector 66 punch down block - IDC (replaces bridge clip)
Enclosure Dimensions in (H x W x D )
1.8 x 0.9 x 0.4
Enclosure Dimensions cm (H x W x D )
4.5 x 2.3 x 0.9
Weight (max) lb, kg 0.1, 0.05
Application Telco Trunk T1 (1 pair of wires)
Nominal Voltage 230 V 40 V
Max Continuous Operating Voltage
270 Vpk 45 Vpk
Max Surge Current 100 A @ 10/1000 µs,150 A @ 8/20 µs
100 A @ 10/1000 µs,150 A @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name PBM 6605 PBM 6607
Part Number 1101-115 1101-162
Operating/Storage Temperature
-20°C to +50°C
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 72
• Non degradable, low clamping, leadless, silicon avalanche diode
• Line and load bidirectional protection
• Optimized for RS422, RS485 and 4-20mA loops
• Protects up to two balanced pairs and shields
• Shield is pass-through
Features
FSP 4001 MC1101-372-1
High-speed, high-current, silicon avalanche data line surge protector designed for RS422, RS485 and 4-20mA loops double wire pair equipment. Product family can accomodate 12 Vdc, 27 Vdc, 52 Vdc and 280 Vdc service voltage applications.
Two-Pair Signal Protector
FSP 4000 MC Series
73
Suppression Terminal Input and output clamping screw terminal 14-4 AWG (25 mm2 max)
Dimensions (H x W x D) in 3.2 x 2.2 x 1.4
Dimensions (H x W x D) cm 5.6 x 8.1 x 3.6
Weight (max) lb, g 0.2, 73
Humidity 90% non-condensing
Operating Temperature -40°C to +65°C
Enclosure Rating 94 V5
Service Voltage 12 Vdc 27 Vdc 52 Vdc 280 Vdc
Max Continuous Operating Voltage 13 Vpk 27 Vpk 54 Vpk 290 Vpk
Voltage Protection Level 50 V 65 V 100 V <500 V @ 10 kA 8/20 µs
Max Surge Current Rating 10/1000 μs 200 A 134 A 67 A 21.4 A
Configuration 2 balanced pairs + 2 shields
Input Connection Terminal block
Connector Positions 6 in 6 out
Protection Modes L-L, L-G
Response Time < 5 ns
Mechanical
Environmental
Electrical
Part Name FSP 4001 MC FSP 4002 MC FSP 4003 MC FSP 4005 MC-GT
Part Number 1101-372-1 1101-372-2 1101-372-3 1101-372-6
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 74
• Non-degradable, low clamping, leadless silicon diode protection
• Line and load bidirectional protection
• BNC connectors for video and protection circuit for RS-232/RS-422/RS-485
• 22 to 16 AWG screw terminal for DC circuit protection
Features
• IEEE/ANSI C62.41
• UL 497B Listed CCTV configured (1101-607)
Standards and Certificates
1101-607
Data line and DC surge protection for pan-tilt-zoom surveillance systems with power and signal circuits.
CCTV Equipment Protector
CCTV Series
75
Input/Output Connector BNC female in and out, two (in/out) five position screw terminals
Enclosure Dimensions (H x W x D) in 3.2 x 3.2 x 1.7
Enclosure Dimensions (H x W x D) cm
8.1 x 8.1 x 4.3
Weight (max) lb, kg 0.2, 0.1
Application Triple circuit protector for coax, 24 V AC/DC and RS-232/RS-422/RS-485
Triple circuit protector for coax, and two pairs RS-232/RS-422/RS-485
MCOV Signal 12 Vdc tip to ring, 40 Vdc ring to ground
Max Surge Current Signal 140 A 10/1000 µs
MCOV Data 24 Vdc
Max Surge Current Data 190 A 10/1000 µs
MCOV AC/DC 28 Vac, 40 Vdc n/a
Max Surge Current DC 150 A 10/1000 µs n/a
Mechanical
Environmental
Electrical
Part Name CCTV-PTZ CCTV-PTZ-4
Part Number 1101-607 1101-613
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating UL94-VO
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
76 Data Line Surge ProtectionData Line Surge Protection
• Non-degradable, low clamping, leadless silicon diode protection
• Line and load bidirectional protection
• Mounts on standard 19 inch racks
• Low capacitance design, less than 20 pF
• CCTV 75 ohm application
Features
• IEEE/ANSI C62.41
Standards and Certificates
1101-704
High-speed, high-current, solid state silicon device designed to protect (16) CCTV lines.
CCTV Equipment Protector
RMP - CCTV
Input/Output Connector 75 ohm, BNC female
Enclosure Dimensions in (H x W x D )
3.5 x 19.0 x 1.2
Enclosure Dimensions cm (H x W x D )
8.9 x 48.3 x 2.9
Weight (max) lb, kg 2.3, 1.1
Protection Modes Signal to Return, Signal/Return to GND
Max Continuous Operating Voltage 7.5 Vpk
Max Surge Current 1800 A 8/20 µs, 286 A 10/1000 µs
Mechanical
Environmental
Electrical
Part Name RMP CCTV 16
Part Number 1101-704
Operating/Storage Temperature -30°C to +65°C
Data Line Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 77Data Line Surge Protection
Part Name RMP CCTV 16
Part Number 1101-704
• High surge current capacity
• Flange mount
• CCTV application
Features
• IEC 1000-4-5
Standards and Certificates
IS-75BB/1.5
75 Ohm baseband unit that passes 1.5 Vdc for use in network LAN or video operations.
CCTV Equipment Protector
IS-75BB
Input/Output Connector BNC female
Enclosure Dimensions in (H x W x D )
5.1 x 2.3 x 1.4
Enclosure Dimensions cm (H x W x D )
12.9 x 5.7 x 3.4
Weight (max) lb, kg 0.5, 0.2
Nominal Voltage ±1.5 Vdc 18 Vdc
Turn On Voltage ±2.3 Vdc 19 Vdc
Frequency Range DC to 30 MHz
Current 3 A continuous
Max Surge Current 18 kA per IEC 61000-4-5 8/20 µs
Insertion Loss ≤0.3 dB
Impedance 75 ohm
Mechanical
Environmental
Electrical
Part Name/Number IS-75BB/1.5 IS-75BB/18
Operating/Storage Temperature
-45°C to +45°C
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
78 Data Line Surge ProtectionData Line Surge Protection
• Engineered for RF and telemetry performance
• High surge current capacity
Features
• IEC 6100-4-5
Standards and Certificates
MDS+24-F-F
Flange mount, 75 ohm surge protection with telemetry and F female connector for satellite systems.
Satellite Equipment Protector
MDS
Input/Output Connector F female
Enclosure Dimensions in (H x W x D )
3.3 x 2.2 x 1.5
Enclosure Dimensions cm (H x W x D )
8.4 x 5.5 x 3.7
Weight (max) lb, kg 0.5, 0.2
RF Frequency Range 300 MHz to 2.5 GHz
RF Power 50 W
Telemetry Frequency Range 10 kHz to 150 kHz and 10 MHz to 100 MHz
Telemetry Operating Voltage 24 Vdc
Max Surge Current 3 kA 8/20 µs, 3 kA 10/350 µs
Impedance 75 ohm
Mechanical
Environmental
Electrical
Part Name/Number MDS+24-F-F
Humidity 100% non-condensing
Operating/Storage Temperature -50°C to +90°C
Operating Vibration/Shock ETS 300 019-2-4, Class 4M3
Data Line Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 79Data Line Surge Protection
• Rugged gas tube, SASD hybrid circuit
• Fits single or dual conduit ports
• 1/2” NPT thread for series or “T” conduit attachment
Features
• Telecordia GR 1089
• FM Approval Class I Division II
• EX
• CE
Standards and Certificates
1101-587
Submersible, low voltage, low frequency, signal surge protection with 18 AWG leads for series wiring.
Submersible Signal Protector
PDS Series
Input/Output Connector 16 AWG leads (1.5 mm2)
Enclosure Dimensions (in) 0.5” diameter, 5.0” length
Enclosure Dimensions (cm) 1.3 diameter x 12.7 length
Weight (max) lb, kg 0.1, 0.05
Max Continuous Operating Voltage
< 28 Vpk
Voltage Protection Level 8/20 µs @ 3 kA 6 kV
~ 125 Vpk @ L-L, L-G
Voltage Protection Level 8/20 µs @ 10 kA 20 kV
~ 250 Vpk @ L-L, L-G
Voltage Protection Level 10/1000 µs @ 100 A
~ 250 Vpk @ L-L, L-G
Max Surge Current 10 kA @ 20 kV 8/20 µs
Parasitic Capacitance 8 pF L-L
Mechanical
Environmental
Electrical
Part Name PDS1 - Parallel Conduit “T” Branch
PDS2 - Series Installed Conduit
Part Number 1101-586 1101-587
Operating/Storage Temperature
-40°C to +65°C
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 80
• Illuminated and remote (dry contact relay) status indication
• Easy installation; 24 to 18 AWG cage clamp
• Modular - replace suppressor module without disconnecting circuit
• Non-degradable, fast acting silicon diode surge suppression
• DIN rail mounted
Features
• FM approval Class I Division II
• CE
Standards and Certificates
1101-869
Modular, single or dual twisted pair 28 to 12 AWG, data line surge protection for AC and DC circuits with visual indication of suppressor status for circuits with power applied.
Data/Power Equipment Protector
DRI Series
81
Input/Output Connector Cage clamp 28 to 12 AWG
Enclosure Dimensions in (H x W x D )
3.4 x 2.9 x 1.4
Enclosure Dimensions cm (H x W x D )
8.6 x 7.4 x 3.6
Weight (max) lb, kg 0.3, 0.2
Data Rate DC to 30 kb/s
Nominal Voltage 170 Vdc (120 Vac) 24 Vdc
Max Continuous Operating Voltage
180 Vpk 34 Vpk
Indicating Electrical Service 110 to 125 Vac
Voltage Protection Level 8/20 µs
<310 Vpk @ 1000 A <110 Vpk @ 1000 A
Voltage Protection Level 10/1000 µs
<250 Vpk @ 85 A <48 Vpk @ 100 A
Max Surge Current 1 kA 10/1000 µs
Mechanical
Environmental
Electrical
Part Name DRI 120 DRI 24
Part Number 1101-870 1101-869
Humidity 99% non-condensing
Operating/Storage Temperature
-40°C to +85°C
Enclosure Rating 94V-0
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Data Line Surge Protection 82
• Non-degradable, low clamping, leadless silicon diode protection
• Line and load bidirectional protection
• Gas discharge tube back-up protection
• Visual status indication
Features
• ANSI/IEEE C62.45
• IEEE C62.41
• AREMA
Standards and Certificates
1101-707
The SXRR series suppressors are high-speed, high-current solid state silicon devices that are designed to provide equalization protection for railroad signaling and Positive Train Control (PTC) applications.
Railroad Equipment Protector
SXRR Series
Input/Output Connector 1/4 inch terminal clips
Enclosure Dimensions (H x W x D) in
2.1 x 2.9 x 1.0
Enclosure Dimensions (H x W x D) cm
5.3 x 7.4 x 2.5
Weight (max) lb, kg 0.1, 0.05
Operating/Storage Temperature
-40°C to +75°C
Enclosure Rating UL 94V-0
Nominal Voltage 12 V 90 V 120 V
Max Continous Operating Voltage
35 Vac, 50 Vdc 110 Vdc 130 Vac
Voltage Protection Level290 Vpk @ 20 kA 8/20 µs
340 Vpk @ 20 kA 8/20 µs
450 Vpk @ 20 kA 8/20 µs
Max Surge Current 20 kA @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name SXRR 50 SXRR 90 SXRR 120
Part Number 1101-707 1101-744 1101-764
83
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Smart Surge Recorder
1104-09-001
DIN Transient Surge Monitor and Counter
A smart surge recorder used to monitor and capture the number and time of transient surges.
I2R SSR
Enclosure Dimensions (H x W x D) in 3.6 x 1.4 x 2.6
Enclosure Dimensions (H x W x D) cm
9.1 x 3.7 x 6.7
Weight (max) lb, kg 0.24, 0.11
Sensitivity Level 1 kA - 3 kA counting (8/20 µs)
Visual Indication LCD
Estimated Lifespan 8 years
Mechanical
Environmental
Electrical
Part Name I2R SSR
Part Number 1104-09-001
Relative Humidity 95% non-condensing
Operating Temperature 0°C to +70°C
• Transient incident record of number and date (up to 80 records)
• Long lasting lithium battery
• Low energy consumption (at dormant state)
• Easy installation
• DIN rail mount
Features
85
Our AC surge protection product offering leads the industry with silicon
diode and MOV protection options available in AC panel, integrated power
distribution cabinets, self-contained enclosures, modular DIN rail, and rack
mount configurations.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection86
• Hybrid silicon diode/MOV design or MOV only
• Visual and remote status monitoring
• Line and load bidirectional protection
• Thermally protected MOV
• Replacement modules
• Outdoor enclosure
• Motorola R-56 approved
Features
• UL 1449 3rd Edition
• ANSI/IEEE C62.45
• IEEE C62.412002 C High
Standards and Certificates
1101-808
1101-809-M
Modular, 160 kA per phase, hybrid panel surge protector with remote and visual status monitoring in outdoor enclosure.
Panel Protector
IMAX Series
87
Max Dimensions (H x W x D) in
12.5 x 10.5 x 6.6 12.5 x 10.5 x 6.6 12.0 x 10.0 x 8.0 12.5 x 10.5 x 6.6 12.5 x 10.5 x 6.6 12.0 x 10.0 x 8.0
Max Dimensions (H x W x D) cm
31.8 x 26.7 x 16.7 31.8 x 26.7 x 16.7 31.8 x 25.4 x 20.3 31.8 x 26.7 x 16.7 31.8 x 26.7 x 16.7 31.8 x 25.4 x 20.3
Weight (max) lb, kg 14.0, 6.5 14.0 , 6.5 24.0, 10.9 14.0, 6.5 14.0, 6.5 24.0, 10.9
Humidity 100% non-condensing
Operating/Storage Temperature
-40°C to +75°C
Enclosure Rating NEMA 4X NEMA 4X NEMA 12 metal NEMA 4X NEMA 4X NEMA 12 metal
Technology Silicon / MOV Silicon / MOV Silicon / MOV MOV MOV MOV
Voltage Configuration120/240 split phase
120/208 3-phase wye
120/208 3-phase wye
120/240 split phase
120/208 3-phase wye
120/208 3-phase wye
Max Continuous Operating Voltage
138 Vac L-N
Imax 160 kA @ 4 kV 8/20 µs per IEC 61643-1 Class II
Fault Current Rating 65 kAIC per NEC 285.6
Mechanical
Environmental
Electrical
Part Name/Number 1101-808 1101-809 1101-809-M 1101-808-MM 1101-809-MM 1101-809-M-MM
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection88
Terminal TypeWiring lugs sized for 6 AWG to 1/0 AWG (16 mm2 to 50 mm2)
Status Indication Terminal C/NC/NO 22 to 14 AWG rated 15 A/300 Vdc (250 Vac)
Dimensions (H x W x D) in 12.5 x 10.5 x 6.6
Dimensions (H x W x D) cm 31.8 x 26.7 x 16.7
Weight (max) lb, kg 10.5, 4.8
Humidity 95% non-condensing
Operating Temperature -40°C to +65°C
Enclosure Rating NEMA 4X/CSA Type 4, IP 66
Technology Silicon Silicon/MOV Silicon/MOV
Voltage Configuration240/415 Vac 3-phase wye
120/240 Vac split phase
120/208 Vac 3-phase wye
Max Continuous Operating Voltage 276/477 Vrms 138/276 Vrms 138 Vrms
Max Surge Current 8/20 μs10 kA per phase
10 kA silicon/ 30 kA MOV per phase
10 kA silicon/ 30 kA MOV per phase
Fault Current Rating 65 kAIC
Mechanical
Environmental
Electrical
Part Name APEX IV X5 240WI
APEX IV X5 120TMR
APEX IV X5 120WMR
Part Number 1101-446-43 1101-460 1101-464
1101-460
Robust, high surge current capacity AC panel surge protection with visual and remote status indication per phase in outdoor enclosure.
Panel Protector
APEX IV Series
• Non-degradable, low clamping silicon diode suppression with robust, high surge current capacity MOV
• Visual and remote status monitoring
• Line and load bidirectional protection
• Thermally protected MOV
• Plug-in modules
• Outdoor enclosure
Features
• UL 1449 3rd Edition (1101-460, 1101-464)
Standards and Certificates
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection 89
Terminal Type Wiring lugs sized for 6 AWG to 1/0 AWG (16 mm2 to 50 mm2)
Status Indication Terminal C/NC/NO 22 to 14 AWG rated 15 A/300 Vdc (250 Vac)
Dimensions (H x W x D) in 12.5 x 10.5 x 6.6
Dimensions (H x W x D) cm 31.8 x 26.7 x 16.7
Weight (max) lb, kg 10.5, 4.8
Humidity 95% non-condensing
Operating Temperature -40°C to +65°C
Enclosure Rating NEMA 4X
Voltage Configuration 120/240 Vac split phase 120/208 Vac 3-phase wye
Max Continuous Operating Voltage 150 Vrms
Voltage Protection Level 8/20 μs 800 Vpk @ 500/6 kV
Max Surge Current 8/20 μs 30 kA per phase
Mechanical
Environmental
Electrical
Part Name APEX 120TR MOV APEX 120WMR MOV
Part Number 1101-338 1101-546
1101-338
Robust, high surge current capacity AC panel surge protection with visual and remote status indication per phase in outdoor enclosure.
Panel Protector
APEX MOV
• Visual and remote status indication (dry relay contacts) per phase
• Robust, high surge current capacity MOV technology
• Line and load bidirectional protection
• Easy to remove, plug-in modules
Features
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection90
• Non-degradable, low clamping silicon diode suppression with robust, high surge current capacity MOV
• Visual and remote status indication per phase
• Line and load bidirectional protection
• Surge counter (1101-771)
Features
• IEEE C62.41
• IEC 61643-1
• NEMA 4X enclosure
Standards and Certificates
1101-424
Low clamping, high surge current capacity AC panel surge protection with visual and remote status indication per phase in outdoor enclosure.
Panel Protector - Outdoor
MCP-OD Series
91
Terminal Type Three 10 AWG (6 mm2) Three 10 AWG (6 mm2) Four 10 AWG (6 mm2) Four 10 AWG (6 mm2)
Status Indication Terminal
18 AWG (1.2 mm) three pin euro style DC pluggable terminal block C/NC/NO
Dimensions(H x W x D) in
11.0 x 9.0 x 6.2 11.0 x 9.0 x 6.2 11.0 x 9.0 x 6.2 13.0 x 10.5 x 6.5
Dimensions(H x W x D) cm
27.9 x 22.9 x 15.9 27.9 x 22.9 x 15.9 27.9 x 22.9 x 15.9 33.0 x 26.7 x 16.5
Weight (max) lb, kg 5.8, 2.6 5.8, 2.6 5.8, 2.6 7.5, 2.9
Technology Silicon / MOV MOV Silicon / MOV Silicon / MOV
Voltage Configuration 120/240 Vac split phase 120/240 Vac split phase 120/208 Vac 3-phase wye 120/208 Vac 3-phase wye
Max Continuous Operating Voltage
140/280 Vrms 160 Vrms 160 Vrms 160 Vrms
Turn on Voltage 230 Vpk @ 5 mA
Voltage Protection Level 8/20 µs
330 Vpk L-N @ 500 A
Max Surge Current 8/20 µs
10 kA 200 kA 100 kA 10 kA /100 kA
IEEE Rating C High
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating UL 94-5V
Mechanical
Environmental
Electrical
Part Name MCP 120TA-10M-OD MCP-MOV 120TA-200K-OD MCP 120W SASD/MOV-ODMCP 120W SASD/MOV-OD-COUNTER
Part Number 1101-424 1101-645 1101-738 1101-771
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
92 AC Surge Protection
• Audible alarm with disable switch
• Surge counter – counts suppressed transients
• Visual and remote status indication (dry relay contacts) per phase
• Robust, thermally protected MOV technology
• EMI/RFI noise filtering
• Modular per mode
• All mode protection - L-N, L-G, N-G & L-L
• Available with or without disconnect
Features
• UL 1449 3rd Edition
• NEC
• IEEE
• CBEMA/ITIC
• NEMA LS
• Article 100/285
Standards and Certificates
PV Plus
Robust, modular, UL 1449 3rd Edition surge protection device with up to 600 kA of surge current capacity per phase.
Panel Protector
PV Plus Series
AC Surge Protection 93
Dimensions(H x W x D) in
24.0 x 16.0 x 8.9
Dimensions(H x W x D) cm
61.0 x 41.0 x 22.4
Weight (max) lb, kg 60, 27
Voltage Configuration 120/240 Vac split phase, 120/208 3-phase wye, 277/480 3-phase wye, 480 delta
Max Surge Current per Phase 8/20 µs
200 kA 400 kA 600 kA
Max Surge Current per Mode 8/20 µs
100 kA 200 kA 300 kA
Nominal Discharge Current Rating (In)
20 kA per phase
Fault Rating (SCCR) 100 kAIC
Operating Frequency 47-63 Hz
IEEE Location C-High
UL Location Type 2
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating NEMA 3R
Operating Altitude 12,000 feet above sea level
Mechanical
Environmental
Electrical
Part Name PV 200 PV 400 PV 600
Contact 1.800.882.9110 or visit www.protectiongroup.com for product configuration support.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
94 AC Surge Protection
LS 100
Compact, modular, thermally protected surge protection device.
Panel Protector
LS Plus
• Visual status indication per phase
• Remote status indication (dry relay contacts)
• Audible alarm with disable switch
• Surge counter for suppressed transients
• Robust, thermally protected MOV technology
• All mode protection - L-N, L-G, N-G & L-L
Features
• UL 1449 3rd Edition
• NEC
• IEEE
• CBEMA/ITIC
• NEMA LS
• NEC Article 100/285
Standards and Certificates
AC Surge Protection 95
Terminal Type #14 - 4 AWG (25 mm2 max)
Dimensions (H x W x D) in 14.0 x 12.0 x 6.0 20.0 x 16.0 x 7.0 20.0 x 16.0 x 7.0
Dimensions (H x W x D) cm 35.6 x 30.5 x 15.2 50.8 x 40.6 x 17.8 50.8 x 40.6 x 17.8
Status Indication Terminal #22 - #14 AWG
Weight (max) lb, kg 30.0, 13.6 32.0, 14.6 35.0, 15.9
Humidity 95% non-condensing
Operating/Storage Temperature -40° C to +60° C
Enclosure Rating NEMA 3R
Voltage Configuration 120/240 V split phase, 120/208 V 3-phase wye, 277/480 V 3-phase wye
Max Surge Current Per Phase 8/20µs 100 kA 200 kA 300 kA
Max Surge Current Per Mode 8/20µs 50 kA L-G, L-N, N-G, L-L 100 kA L-N, N-G, L-G, L-L 150 kA L-N, L-L, L-G, N-G
Nominal Discharge Current Rating (In) 20 kA per phase
Fault Rating (SCCR) 100 kAIC
Mechanical
Environmental
Electrical
Part Name LS Plus LS Plus LS Plus
Part Number LS 100 LS 200 LS 300
Contact 1.800.882.9110 or visit www.protectiongroup.com for product configuration support.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
96 AC Surge Protection
SP200
SP100
Robust, modular, UL 1449 3rd Edition surge protection device with up to 200 kA of surge current capacity per phase.
Panel Protector
SP Plus Series
• Visual status indication per phase
• Remote status indication (dry relay contacts)
• Audible alarm with optional disable switch
• Robust, thermally protected MOV technology
• EMI/RFI noise filtering
• All mode protection - L-N, L-G, N-G & L-L
Features
• UL 1449 3rd Edition
• NEC Article 285
Standards and Certificates
AC Surge Protection 97
Terminal Type # 10 AWG leads (6 mm2)
Dimensions (H x W x D) in 6.3 x 6.3 x 3.5 9.5 x 6.3 x 3.5
Dimensions (H x W x D) cm 16.0 x 16.0 x 8.9 24.1 x 16.0 x 8.9
Weight (max) lb, kg 3, 1.4 5, 2.3
Humidity 95% non-condensing
Operating/Storage Temperature -40° C to +60° C
Enclosure Rating NEMA 4 (NEMA 1 w/disable switch option)
Voltage Configuration 120/240 V split phase, 120/208 V 3-phase wye, 277/480 V 3-phase wye, 480 V delta (SP 200 only)
Max Surge Current Per Phase 8/20µs 100 kA 200 kA
Max Surge Current Per Mode 8/20µs 50 kA 100 kA
Nominal Discharge Current Rating (In) 8/20µs
Up to 20 kA Up to 20 kA
Fault Rating (SCCR) 100 kAIC 100 kAIC
Mechanical
Environmental
Electrical
Part Name SP Plus SP Plus
Part Number SP 100 SP 200
Contact 1.800.882.9110 or visit www.protectiongroup.com for product configuration support.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
98 AC Surge Protection
• Non-degradable, low clamping silicon diode suppression with robust, high surge current capacity MOV patented linear-sharing Wagon Wheel technology
• Incorporated LC filter for superior protection
• Also available in international voltage configurations
• Remote status monitor
Features
DS21 Model
DS30 Model
Series connected, modular, hybrid silicon avalanche diode with coordinated, robust MOV technology for high lightning exposure environments.
Panel Protector
Dyna System Series
• NEMA 12 standard
Standards and Certificates
AC Surge Protection 99
Dimensions (H x W x D) in
18.9 x 14.4 x 7.9 48.0 x 24.0 x 8.8 30.0 x 24.0 x 8.8 48.0 x 36.0 x 10.0 60.0 x 36.0 x 13.2 72.0 x 36.0 x 13.2
Dimensions (H x W x D) cm
48.0 x 36.6 x 20.1 122.0 x 61.0 x 23.0 76.0 x 61.0 x 23.0 122.0 x 92.0 x 26.0 152.4 x 91.4 x 33.5 182.9 x 91.4 x 33.5
Weight (max) lb, kg 40.0, 18.1 80.0, 36.3 80.0, 36.3 530.0, 240.0 495.0, 225.0 950.0, 431.0
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating NEMA 12 Standard
Voltage Configuration Options
120/240 Vac split phase, 120/208 3-phase wye, 277/480 3-phase wye, 480 delta, 230 D, 220/380, 240/415
Nominal Amperage 80 A 150 A 225 A 300 A 600 A 1200 A
Max Surge Current Per Phase 8/20µs
225 kA @ 6 kV 225 kA @ 6 kV 225 kA @ 6 kV 225 kA @ 6 kV 337.5 kA @ 6 kV 337.5 kA @ 6 kV
Max Surge Current Per Mode 8/20µs
L-N: 112.5 kA L-N, 225 kA L-L, 225 kA L-G, 112.5 kA N-G @ 6 kV
Filter Component 1 µH coil 1 µH coil 1 µH coil 100 µH coil Triax 100 µH coil Triax 100 µH coil Triax
Mechanical
Environmental
Electrical
Part Name DS 21 DS 21 DS 21 DS 20 DS 30 DS 30
Part Number DS21-80A DS21-150A DS21-225A DS20-300A DS30-600A DS30-1200A
Call 1.800.654.8087 or visit www.protectiongroup.com for product configuration support.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection100
• Visual and remote (dry contact relay) status indication
• High surge current capacity, ≤40 kA per phase
Features
1101-980
Modular, compact 120 Vac and 240 Vac single phase, silicon diode, DIN rail surge protection with visual and remote status indication.
Panel Protector
I2R CDS Series
101
Terminal Type 10 AWG leads (6 mm2) 10 AWG leads (6 mm2) 10 AWG leads (6 mm2)
Max Dimensions (H x W x D) in
8.7 x 8.1 x 5.6 8.5 x 6.5 x 4.5 6.5 x 5.5 x 4.0
Max Dimensions (H x W x D) cm
22.1 x 20.6 x 14.0 22.2 x 16.6 x 11.5 16.6 x 14.0 x 10.2
Status Indication Terminal Form C dry relay contacts, 0.5 A/ 75 Vdc, 0.1 A/250 Vdc, 0.5 A/250 Vac, 22 to 14 AWG (2 mm maximum)
Humidity 100% non-condensing 100% non-condensing 90% non-condensing
Operating/Storage Temperature
-40°C to +85°C
Enclosure Rating NEMA 3R
Voltage Configuration 120/240 Vac Split Phase 120/240 Vac Split Phase 120/208 Vac 3-phase wye
Max Continuous Operating Voltage
145 Vrms L-N 145 Vrms L-N 150 Vrms L-N, 300 Vrms L-L
Voltage Protection Level 400 Vpk @ 3 kA 6 kV 8/20 µs L-N 590 Vpk @ 3 kA 6 kV 8/20 µs L-N 330 Vpk @ 500 A 6 kV 8/20 µs L-N
Max Surge Current 45 kA per phase 8/20 µs 40 kA per phase 8/20 µs 40 kA per phase 8/20 µs
Mechanical
Environmental
Electrical
Part Name I2R 120/240 RR I2R 120/240 MMRR MCP 120W BM
Part Number 1101-980 1101-981 1101-872
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection102
• Robust, high surge current capacity
• MOV linear sharing technology
• Flush mount option available
Features
Robust, compact, 120 kA surge current capacity per phase surge protection.
Panel Protector
CFS Series
Terminal Type #10 AWG leads (6 mm2)
Max Dimensions (H x W x D) in
5.2 x 5.2 x 2.5
Max Dimensions (H x W x D) cm
13.3 x 13.3 x 6.4
Weight (max) lb, kg 5, 2.3
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating NEMA 4X
Voltage Configuration Available
120/240 Vac split phase, 120/208 3-phase wye, 277/480 3-phase wye, 120/240 CPGD, 480-D, 240 single phase
Max Surge Current per Phase
120 kA 8/20 µs per phase
Max Surge Current per Mode
60 kA L-N, L-L, & L-G 8/20 µs
Mechanical
Environmental
Electrical
Part Name CFS
Part Number A70-00-5006, A70-00-5007, A70-00-5008, A70-00-5010, A70-00-5011, A70-00-5002
Contact 1.800.882.9110 or visit www.protectiongroup.com for product configuration support.
A70-00-5007
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
103AC Surge Protection
• Non degradable, low clamping silicon diode suppression
• RJ-11 jack for dial-up phone protection
• Visual status indication
• 6 foot power cord with NEMA 5-15 swivel prong plug
• Eight NEMA 5-15 receptacles
Features
• IEEE C62.41
Standards and Certificates
1102-007-1A
120 Vac, 15 A, plug-in, eight receptacle silicon diode surge protector.
Plug-In Protector
DPS Series
Plug Type NEMA 5-15
Receptacle Type Eight NEMA 5-15
Max Dimensions (H x W x D) in
3.6 x 9.5 x 1.5
Max Dimensions (H x W x D) cm
9.1 x 24.1 x 3.8
Weight (max) lb, kg 1.5, 0.7
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Voltage Configuration 120 Vac single phase
Max Surge Current 1 kA @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name DPS 8T SASD (GRAY CASE)
Part Number 1102-007-1A
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection104
• Non-degradable, low clamping, leadless silicon diode protection
• Illuminated status indication
• Bi-polar, bi-directional protection
Features
SL 120 Series1104-29-000
The SL Series AC surge protectors are a solid-state SASD (Silicon Avalanche Suppressor Diode) device designed to protect electronic equipment and systems from transient overvoltages on 120 Vac single phase services. The SL Series offers continuous bi-polar, bi-directional, non-interrupting protection.
Plug-In Protector
SL Series
105
Enclosure PA66, UL94 V-O
Enclosure Dimensions (H x W x D) in 2.9 x 2.8 x 2.4
Enclosure Dimensions (H x W x D) cm
7.5 x 7.2 x 6.1
Weight (max) lb, kg 0.3, 0.1
Nominal Operating Voltage 120 V, 50/60 Hz (L-N)
Maximum Continuous Operating Voltage 150 V, 50/60 Hz (L-N)
Maximum Discharge Current 5 kA (L-N)
Voltage Protrection Level 500 V @ 6 kV, 3 kA
Status Indication GREEN - SPD functioningRED - Power continues to be supplied to load
GREEN - SPD functioningRED - Power removed from load
Mechanical
Environmental
Electrical
Part Name SL 120 SLN 120
Part Number 1104-29-000 1104-29-001
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +70°C
Enclosure Rating IP20
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection106
• Non-degradable, low clamping silicon diode suppression
• Illuminated status indication
• Compact 1RU
• NEMA 5-15 and 5-20 rated plugs and receptacles
• Switched outlets (1102-007-9)
Features
• IEEE C62.41
Standards and Certificates
1102-007-9
120 Vac single phase, multiple outlet, 19” rack mount, silicon diode surge protection.
Plug-In Protector
RMP Series
107
Plug Type NEMA 5-15 Dual NEMA 5-20 (twist lock) NEMA 5-20
Receptacle Type Six NEMA 5-15 Eight NEMA 5-20 (4 per input) Nine NEMA 5-20
Max Dimensions (H x W x D) in
1.8 x 19.0 x 3.5 1.8 x 19.0 x 4.8 1.8 x 19.0 x 4.8
Max Dimensions (H x W x D) cm
4.6 x 48.3 x 8.9 4.6 x 48.3 x 11.5 4.6 x 48.3 x 11.5
Weight (max) lb, kg 4.5, 2.1 9.0, 4.1 9.0, 4.1
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Voltage Configuration 120 Vac single phase
Nominal Amperage 15 A (fused) 20 A 20 A
Max Surge Current 3 kA 8/20 µs 3 kA 8/20 µs 1.5 kA 8/20 µs
Mechanical
Environmental
Electrical
Part Name RMP 615A RMP2 420A RMP 920A
Part Number 1101-534 1101-560 1102-007-9
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection108
• Non-degradable, low clamping silicon diode suppression with robust, high surge current capacity MOV technology
• Visual and remote status indication per phase
• Line and load bidirectional protection
Features
• IEEE C62.41
• IEC 61643-1
• UL 1449 3rd Edition (1101-299)
Standards and Certificates
Low clamping, high surge current capacity AC component surge protection with visual and remote status indication per phase.
Component Protector
MCP Series
1101-299
109
Terminal Type Three 10 AWG (6 mm2) wire leads Three 10 AWG (6 mm2) wire leads Four 10 AWG (6 mm2) wire leads
Status Indication Terminal
18 AWG (1.2 mm2) three pin, removable, terminal block C/NC/NO
Max Dimensions (H x W x D) in
6.6 x 4.2 x 3.3
Max Dimensions (H x W x D) cm
16.8 x 10.6 x 8.3
Weight (max) lb, kg 2.5, 1.1
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating UL 94V-0
Nominal Operating Voltage
120/240 Vac split phase 120/240 Vac split phase 120/208 Vac 3-phase wye
Max Continuous Operating Voltage
138/267 Vrms
Mechanical
Environmental
Electrical
Part Name MCP 120TA-10M MCP 120TA-20M MCP 120W SASD/MOV
Part Number 1101-299 1101-689 1101-732
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection110
• Illuminated status indication
• Non-degradable, low clamping silicon diode suppression
• Line and load bidirectional protection
• DIN rail mount with remote status monitoring (1101-739)
• Fused outputs (1100-739, 1100-954)
Features
• IEEE C62.41
Standards and Certificates
1100-629
Hardwired, compact, silicon, 120 Vac single phase surge protection.
Component Protector
ACP 100 Series
111
Terminal or Plug TypeFour position terminal strip
Four position terminal strip
Four position terminal strip
24 to 10 AWG screw terminal
6 inch 14 AWG leads
Max Dimensions (H x W x D) in
6.3 x 3.4 x 2.4 6.3 x 3.4 x 2.4 6.3 x 3.4 x 2.4 6.5 x 3.0 x 2.5 2.2 x 3.2 x 1.7
Max Dimensions (H x W x D) cm
15.9 x 8.6 x 6.0 15.9 x 8.6 x 6.0 15.9 x 8.6 x 6.0 16.6 x 7.7 x 6.4 5.6 x 8.2 x 4.3
Weight (max) lb, kg 0.7, 0.3 0.7, 0.3 0.7, 0.3 0.7, 0.3 0.2, 0.1
Humidity 95 % non-condensing
Operating/Storage Temperature
-40°C to +65°C
Enclosure Rating IP 20
Voltage Configuration 120 Vac single phase
Max Continuous Operating Voltage
220 Vrms
Nominal Amperage 10 A 15 A 15 A (fused) 15 A 15 A (fused)
Voltage Protection Level 330 Vpk L-NC 500 A 8/20 µs
Mechanical
Environmental
Electrical
Part Name ACP 100 BW3 ACP 100 BW3R ACP 100 BWN3 ACP 100 DR2 5-15 ACP 100 MN
Part Number 1100-629 1100-855 1100-954 1101-608 1100-647
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection112
• Compact, high surge current capacity, non-degrading silicon diode
• High current activated MOV sharing circuit
• Visual and remote (dry contact relay) status indication
• Line and load bidirectional protection
• Overload disconnect per phase
• IP65 enclosure (1101-901)
Features
• IEC 61643-1 Class I and Class II
Standards and Certificates
1101-826
240 and 240/415, hybrid silicon diode with combined MOV, hardwired, Class I and Class II IEC surge suppressor with remote monitoring.
Component Protector
SuperHy Series
113
Wire Size (max) 16 mm2 (stranded), 25 mm2 (solid) #6 to #4 AWG
Max Dimensions (H x W x D) in
3.6 x 2.2 x 2.7 8.7 x 10.9 x 5.4
Max Dimensions (H x W x D) cm
9.1 x 5.5 x 6.8 22.0 x 27.6 x 13.6
Weight (max) lb, kg 0.7, 0.3 6.2, 2.8
Humidity 90% non-condensing
Operating/Storage Temperature
-40°C to +80°C
Voltage Configuration 240 Vac single phase 240/415 Vac 3 phase w/ NPE
Nominal Operating Voltage (Un)
230 V 50/60 Hz
Max Continuous Operating Voltage (Uc)
320 V 50/60 Hz
Impulse Current (Iimp) 20 kA @ 10/350 µs
Nominal Discharge Current (In)
20 kA @ 8/20 µs
Max Discharge Current (Imax) 120 kA @ 8/20 µs
Voltage Protection Level (Up)
1.2 kV @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name SuperHy 240 SuperHy 240W CM Enclosure
Part Number 1101-826 1101-901
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection114
• Non-degrading, low clamping, leadless silicon diode protection
• LED status indication
• Line and load bidirectional protection
• DIN or screw mounting
Features
• IEEE C62.41
• UL 1449 3rd Edition (1101-627)
Standards and Certificates
1101-627
Modular, 120 Vac and 240 Vac single phase, silicon diode, DIN rail surge protection with visual status indication.
Component Protector
I2R ICP Series
Terminal Type Screw Terminal 14 to 4 AWG (2.5 mm2 to 25 mm2)
Max Dimensions (H x W x D) in
2.7 x 1.0 x 2.7
Max Dimensions (H x W x D) cm
6.9 x 2.5 x 6.9
Weight (max) lb, kg 0.4, 0.2
Humidity 95% non-condensing
Operating/Storage Temperature
-40°C to +80°C
Norminal Operating Voltage 120 Vac single phase 240 Vac single phase
Max Continuous Operating Voltage
138 Vrms 280 Vrms
Voltage Protection Rating 500 Vpk @ 3 kA 8/20 µs N/A
Voltage Protection Level N/A 600 Vpk @ 500A 8/20µs
Max Surge Current 7 kA @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name 120 V SASD 240 V SASD
Part Number 1101-627 1101-629
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection 115
Component Protector
DIN rail mountable 120 Vac surge protection device (SPD) that offers high performance silicon avalanche suppression diode (SASD) technology protection.
I2R IEP 120-10
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Location Category Indoor only, Type 1
Enclosure Dimensions in (H x W x D )
3.5 x 1.4 x 2.4
Enclosure Dimensions cm (H x W x D )
8.9 x 3.6 x 6.1
Weight (max) lb, kg 0.26, 0.12
Nominal Operating Voltage (Un) 150 Vac
Nominal Discharge Current (In) (8/20µs) 5 kA
Maximum Discharge Current (Imax) (8/20µs) 10 kA
Voltage Protection Level (Up) (8/20µs) 600 V
Leakage Current (Ur) <5 µA
Mechanical
Environmental
Electrical
Part Name I2R IEP 120-10
Part Number 1104-15-000
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP20 (IEC EN 60529)
• Silicon diode surge protection
• Replaceable modules
• DIN rail mount
• Visual and remote status indication
Features
• IEC 61643-1
• RoHS compliant
Standards and Certificates
1104-15-000
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection116
• Visual and remote (dry relay contact) status indication
• DIN rail mounted
Features
• IEEE C62.41
• RoHS compliant
Standards and Certificates
1104-15-001
The I2R Storm is a DIN rail mountable, 120 Vac, surge protection device that offers high performance silicon avalanche suppression diode (SASD) technology protection.
Component Protector
I2R Storm Series
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Location Category Indoor only, Type 1
Enclosure Dimensions (H x W x D) in
3.5 x 0.7 x 2.4
Enclosure Dimensions (H x W x D) cm
9.0 x 1.8 x 6.1
Weight (max) lb, kg 0.26, 0.12
Max Continuous Operating Voltage (Uc) 150 Vac
Maximum Discharge Current (Imax) 10 kA (Type 4)
Nominal Discharge Current (In) 5 kA
Voltage Protection Level (Up) 600 V @ 8/20 µs
Leakage Current (Ur) <5 µA
Mechanical
Environmental
Electrical
Part Name I2R Storm 120-10
Part Number 1104-15-001
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP 20
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection 117
• RoHS compliant
Standards and Certificates
• High surge current thermally protected MOV
• Visual and remote (dry contact relay) status indication
• DIN rail mount
Features
Component Protector
1104-15-002
DIN rail, class II MOV surge protection device for 120 Vac with pluggable modules.
I2R SA 120-50M
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Location Category Indoor only, Type 2
Enclosure Dimensions (H x W x D) in
3.5 x 0.7 x 2.6
Enclosure Dimensions (H x W x D) cm
9.0 x 1.8 x 6.7
Weight (max) lb, kg 0.2, 0.1
Voltage Configuration 120 Vac single phase
Max Continuous Operating Voltage (Uc) 180 Vac
Nominal Discharge Current (In) 20 kA @ 8/20 µs
Maximum Discharge Current (Imax) 50 kA @ 8/20 µs
Leakage Current <10 µA
Voltage Protection Level (Up) 700 V
Mechanical
Environmental
Electrical
Part Name I2R SA 120-50M(Modular)
Part Number 1104-15-002
Relative Humidity 95% non-condensing
Operating Temperature -40°C to +80°C
IP Rating IP 20
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection118
• Visual and remote (dry relay contact) status indication
• DIN rail mount
• Rugged, compact and easy to install
Features
• IEC 61643-1
• UL 1449 3rd Edition (1102-014-42, 1102-014-43)
• CE
• RoHS compliant (1102-014-42, 1102-014-43)
Standards and Certificates
1102-014-43
High surge current capacity, DIN rail mount, AC surge protection.
Component Protector
I2R SA Series
119
Terminal TypeScrew terminal accepts 14-6 AWG (3.3 mm2 max)
Screw terminal accepts 14-6 AWG (3.3 mm2 max)
Screw terminal accepts up to 4 AWG (25 mm2 max)
Screw terminal accepts up to 4 AWG (25 mm2 max)
Max Dimensions (H x W x D) in
4.1 x 0.8 x 2.7 4.1 x 0.8 x 2.7 3.5 x 0.7 x 2.7 3.5 x 0.7 x 2.7
Max Dimensions (H x W x D) cm
10.4 x 2.0 x 6.9 10.4 x 2.0 x 6.9 9.0 x 1.8 x 6.7 9.0 x 1.8 x 6.7
Status Indication Terminal
Screw terminal accepts up to 16 AWG (1.5 mm2)
Screw terminal accepts up to 16 AWG (1.5 mm2)
Screw terminal accepts up to 10 AWG (6 mm2)
Screw terminal accepts up to 10 AWG (6 mm2)
Weight (max) lb, kg 0.2, 0.1 0.2, 0.1 0.2, 0.1 0.9, 0.4
Humidity 95% non-condensing
Operating Temperature -40°C to +65°C
Enclosure Rating IP 20/UL 94V-0
Voltage Configuration 120 Vac single phase 277 Vac single phase 120 Vac single phase 480 Vac 3-phase delta
Max Continuous Operating Voltage (Uc)
180 Vrms 320 Vrms 170 Vrms 600 Vrms
VPR 500 Vpk @ 3 kA/6 kV 900 Vpk @ 3 kA/6 kV 850 Vpk @ 3 kA/6 kV 850 Vpk @ 3 kA/6 kV
Nominal Discharge Current (In)
20 kA @ 8/20 µs 20 kA @ 8/20 µs 20 kA @ 8/20 µs 20 kA @ 8/20 µs
Max Discharge Current (Imax)
50 kA 8/20 µs 50 kA 8/20 µs 40 kA 8/20 µs 40 kA 8/20 µs
SCRR 200 kA 200 kA 60 kA(ef) 60 kA(ef)
Mechanical
Environmental
Electrical
Part Name I2R SA 120-50 I2R SA 277-50 I2R SA120-40 I2R SA480D-40
Part Number 1102-014-43 1102-014-42 1102-014-13-1 1102-014-26
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection120
• DIN rail mounted
• Rugged MOV technology
• Visual status indicator
• Electrically isolated Form-C dry contacts with a three pin removable terminal plug
Features
• IEC 61643-1 Class II
• RoHS compliant
• Housing FRNC-UL94 V-O
Standards and Certificates
1102-014-7
The I2R SA 230-40 protector is a RoHS compliant, DIN rail mounted 230 Vac surge suppression device that offers high performance MOV technology protection.
Component Protector
I2R SA 230-40
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Enclosure Dimensions (H x W x D) in
3.5 x 0.7 x 2.6
Enclosure Dimensions (H x W x D) cm
9.0 x 1.8 x 6.7
Weight (max) lb, kg 0.2, 0.1
Nominal Operating Voltage (Un) 230 V single phase
Max Continuous Operating Voltage (Uc) 320 Vrms
Nominal Discharge Current (In) 20 kA @ 8/20 µs
Maximum Discharge Current (Imax) 40 kA @ 8/20 µs
Voltage Protection Level (Up) < 1.4 kV
Mechanical
Environmental
Electrical
Part Name I2R SA 230-40
Part Number 1102-014-7
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP 20
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection 121
• DIN rail mounted
• Rugged Spark Gap technology
Features
• IEC 61643-1 Class II
• RoHS compliant
Standards and Certificates
Component Protector
1102-014-8
The I2R CM 230-20 is a RoHS compliant, DIN rail mounted surge arrester designed for the protection of sensitive electronic power systems for 230 Vac service applications that require neutral-to-ground suppression.
I2R CM 230-20
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Enclosure Dimensions (H x W x D) in
3.5 x 0.7 x 2.6
Enclosure Dimensions (H x W x D) cm
9.0 x 1.8 x 6.7
Weight (max) lb, kg 0.2, 0.1
Nominal Operating Voltage (Un) 230 V single phase
Max Continuous Operating Voltage (Uc) 260 Vrms
Nominal Discharge Current (In) 20 kA @ 8/20 µs
Maximum Discharge Current (Imax) 50 kA @ 8/20 µs
Mechanical
Environmental
Electrical
Part Name I2R CM 230-20
Part Number 1102-014-8
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP 20
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection122
• DIN rail mounted
• Visual and remote (dry relay contact) status indication
• Spark Gap technology
Features
• IEC 61643-1 Class I
• RoHS compliant
• IEC EN60529
Standards and Certificates
1102-014-5
The I2R LA is a RoHS compliant, DIN rail mounted surge arrester designed for the protection of electronic systems.
Component Protector
I2R LA Series
Maximum Wire Size 25 mm2 (stranded) - 35 mm2 (solid) #4 to #2 AWG
Enclosure Dimensions (H x W x D) in 3.6 x 1.4 x 2.7
Enclosure Dimensions (H x W x D) cm
9.0 x 3.6 x 6.8
Weight (max) lb, kg 0.7, 0.3
Nominal Operating Voltage (Un) 230 Vac single phase
Max Continuous Operating Voltage (Uc) 320 Vrms 260 Vrms
Nominal Discharge Current (In) 20 kA @ 8/20 µs
Maximum Discharge Current (Imax) 50 kA @ 8/20 µs 100 kA @ 8/20 µs
Voltage Protection Level (Up) <2.0 kV
Mechanical
Environmental
Electrical
Part Name I2R LA 230-50 I2R LA 230-100
Part Number 1102-014-5 1102-014-6
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP 20
AC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
AC Surge Protection 123
• Replaceable module
• DIN rail mount
• Status indicator
• RoHS compliant
• MOV and GDT technology
Features
1104-29-000
Railway Track Circuit Protector
Railway Track Circuit 48 V SPD features visual status indication. The indicator is normally green and turns red if module needs replacement.
I2R RSA 48 3-40
Maximum Wire Size 2.5 mm2 (#14 AWG)
Terminal Type Screw cage clamp
Enclosure Dimensions in (H x W x D )
3.5 x 1.4 x 2.7
Enclosure Dimensions cm (H x W x D )
8.9 x 3.6 x 6.8
Weight (max) lb, kg 0.4, 1.8
Nominal Operating Voltage (Un) 48 Vdc
Max Continuous Operating Voltage (Uc) 60 Vdc
Nominal Discharge Current (In) (8/20µs) 10 kA
Maximum Discharge Current (Imax) (8/20µs) 20 kA
Mechanical
Environmental
Electrical
Part Name I2R RSA 48 3-40
Part Number 1104-04-000
Humidity 95% non-condensing
Operating Temperature -40°C to +70°C
125
For communications equipment operating on DC power, the Protection Technology Group
offers surge suppressors that incorporate fast acting, superior performance, and high
reliability surge suppression elements.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Surge Protection126
• Non-degradable, low clamping, leadless, silicon diode surge suppression
• Engineered for bidirectional, line and load protection
• Replaceable suppression module, no rewiring required
• Fused to protect equipment from extraordinary surge currents
• Optimized for low frequency data circuits including RS-422, RS-485 and 4-20mA loops
• 2 pair/4 wire 28-12 AWG screws
Features
• IEEE C 62.41
• ANSI C 62.41
• FM Approval Class 1 Division II
• CE
• ATEX EU Directive 94/9/EC
• UL 497B (except DRDC-70)
Standards and Certificates
1101-680
Bidirectional, low clamping silicon diode, DIN rail mounted surge protection for DC power and low frequency data lines operating at up to 10 A.
Component Protector
DRDC Series
DC Surge Protection 127
Terminal 2 pair/4 wire 28-12 AWG Screw (4 mm2 max)
Dimensions (H x W x D) in 4.0 x 0.5 x 4.0
Dimensions (H x W x D) cm 10.2 x 1.3 x 10.2
Weight (maximum) lb, kg 0.1, 0.2
Humidity 95% non-condensing
Operating Temperature -40°C to +80°C
Nominal Voltage 7 Vdc 12 Vdc 24 Vdc 48 Vdc 70 Vdc
Max Continuous Operating Voltage 13 Vdc 16 Vdc 32 Vdc 64 Vdc 118 Vdc
Max Surge Current 1.4 kA @ 10/1000 μs 1.2 kA @ 10/1000 μs 1.2 kA @ 10/1000 μs 1.2 kA @ 10/1000 μs 600 A @ 10/1000 μs
Voltage Protection Level 10/1000 μsIEEE/ANSI C62.41
20 Vpk @ 164 A 25 Vpk @ 134 A 50 Vpk @ 134 A 100 Vpk @ 134 A 165 Vpk @ 66 A
Voltage Protection Level 8/20 μsIEEE/ANSI C62.41
25 Vpk @ 1.4 kA 30 Vpk @ 1.2 kA 60 Vpk @ 1.2 kA 120 Vpk @ 1.2 kA 185 Vpk @ 600 A
Response Time < 5 ns
Mechanical
Environmental
Electrical
Part Name DRDC 7 DRDC 12 DRDC 24 DRDC 48 DRDC 70
Part Number 1101-678 1101-679 1101-680 1101-681 1101-724
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Surge Protection128
1104-11-000
Component Protector
Modular indoor, DIN rail, Class II silicon surge protection device for 12, 24 and 48 Vdc
I2R IEP Series
Maximum Wire Size 16 mm2 (stranded) - 25 mm2 (solid) #6 to #4 AWG
Location Category Indoor only
Enclosure Dimensions (H x W x D) in 3.5 x 0.7 x 2.6
Enclosure Dimensions (H x W x D) cm
9.0 x 1.8 x 6.7
Weight (max) lb, kg 0.23, 0.10
Nominal Operating Voltage (Un) 12 Vdc 24 Vdc 48 Vdc
Max Continuous Operating Voltage (Uc) 14 Vdc 28 Vdc 57 Vdc
Nominal Discharge Current (In) (8/20µs) 5 kA (Class II)
Maximum Discharge Current (Imax) (8/20µs) 2.5 kA
Nominal Discharge Current (Up) (8/20µs) <70 V <83 V <125 V
Leakage Current (Ur) <10 µA
Mechanical
Environmental
Electrical
Part Name I2R IEP 12-5 I2R IEP 24-5 I2R IEP 48-5
Part Number1104-11-000 1104-11-001 1104-11-002
Relative Humidity 95% non-condensing
Operating/Storage Temperature -40°C to +80°C
Enclosure Rating IP20
• Silicon diode surge protection
• Replaceable modules
• DIN rail mount
• Visual and remote status indication
Features
• IEC 61643-1
• RoHS compliant
Standards and Certificates
DC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
129DC Surge Protection
• Visual and remote status monitoring
• Engineered for bidirectional line and load protection
• Replaceable suppression module, no rewiring required
• Electrically isolated Form-C dry contacts with a three pin removable terminal plug
• DIN rail mounted
Features
• IEC 61643-1 Class I
• RoHS compliant
• Houseing FRNC-UL94VO
• IEC EN 60529
Standards and Certificates
1102-014-38-2
The I2R SA 48-40 is a RoHS compliant, DIN rail mounted, modular surge suppression device designed for the protection of sensitive DC power systems.
Component Protector
I2R SA Series
Maximum Wire Size 25 mm2 (solid), 16 mm2 (stranded) #6 to #4 AWG
Status Indication Terminal Eurostyle terminal plug
Dimensions (H x W x D) in 3.5 x 0.7 x 2.6 3.5 x 2.1 x 2.6
Dimensions (H x W x D) cm 9.0 x 1.8 x 6.7 9.0 x 4.5 x 6.7
Weight (max) lb, kg 0.2, 0.1 0.7, 0.3
Humidity 95% non-condensing
Operating Temperature -40°C to +80°C
Enclosure Rating IP 20
Nominal Operating Voltage (Un) 48 Vdc single phase 48 Vdc
Max Continuous Operating Voltage (Uc) 75 Vdc 75 Vdc
Max Discharge Current (Imax) 40 kA 8/20 μs 40 kA 8/20 μs
Max Voltage Protection Level (Up) 700 Vpl
Response Time < 25 ns < 25 ns
Mechanical
Environmental
Electrical
Part Name I2R SA 48-40 I2R SA 48 3-40
Part Number 1102-014-38-2 1104-11-005
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Surge Protection130
• Non-degrading, low clamping, leadless silicon diode protection
• Illuminated and remote dry contact relay status indication
• Line and load bidirectional protection
• Plug-in suppressor module
• Two pair / four wire protection
Features
• FM Approval Class I Division II
• CE
• ATEX EU Directive 94/9/EC
Standards and Certificates
24 Vdc low power signal, silicon diode, DIN rail equipment surge suppressor with visual status indication. DRI 24 is approved for hazardous locations that require a rating of Class I Division II Groups A, B, C and D.
Component Protector
DRI 24
Dimensions (H x W x D) in 2.9 x 1.7 x 3.4
Dimensions (H x W x D) cm 7.3 x 4.3 x 8.6
Weight (max) lb, kg 0.3, 0.14
Humidity 95% non-condensing
Operating Temperature -40°C to +65°C
Service Voltage 24 Vdc
Signal Rate DC power to 30 Kb/s
Protection Modes L-L, L-G
Protection Level 48 Vpk
Max Continuous Operating Voltage
34 Vpk
Max Pass Through Current 5 A
Response Time 5 ns
Mechanical
Environmental
Electrical
Part Name DRI 24
Part Number 1101-869
1101-869
DC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
131DC Surge Protection
• Non-degradable, low clamping, silicon avalanche diode surge suppression
• Visual and remote status monitoring
• Bi-directional, line and load protection
• Bullet style breakers
Features
1101-511
Circuit breaker style silicon surge protection for DC power distribution systems with reverse polarity protection from power cross and inductive swells.
Component Protector
CB Series
Suppression Terminal 10-32 bullet style 10-32 bullet style
Dimensions (H x W x D) in 2.5 x 2.5 x 0.7
Dimensions (H x W x D) cm 6.3 x 6.3 x 1.9
Weight (max) lb, kg 0.3, 0.1
Humidity 95% non-condensing
Operating Temperature -30°C to +65°C
Nominal Voltage + 48 Vdc + 48 Vdc
Max Continuous Operating Voltage 60 Vpk 60 Vpk
Max Surge Current 10/1000 μs 1100 A 380 A
Max Surge Current 8/20 μs 15 kA 3 kA
Voltage Protection Level 10/1000 μs 75 Vdc 150 Vdc
Voltage Protection Level 8/20 μs 75 Vdc 150 Vdc
Response Time < 5 ns < 5 ns
Mechanical
Environmental
Electrical
Part Name CB-48-RD-DW CB-48-RD
Part Number 1101-686 1101-511
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Surge Protection132
• MOV technology
• Low let-through voltage
• High surge current capacity
• All mode protection series device
Features
1101-1014
48 Vdc protector that utilizes MOV technology to provide high surge current capacity and low let-through voltage.
Component Protector
3DC48-20 Series
Connection Terminals #6 - #20 AWG (16 mm2 max)
Dimensions(H x W x D) in
3.6 x 6.0 x 2.5
Dimensions(H x W x D) cm
9.1 x 15.2 x 6.4
Weight (max) lb, kg 0.8, 0.3
Operating Temperature -40°C to +65°C
Nominal Operating Voltage
±48 Vdc
Max Continuous Operating Voltage
±60 Vdc
Max Continuous Operating Current
20 A
Surge Capabilities 30 kA 8/20 µs per mode maximum
Protection Modes Pos-Neg, Pos-GND, Neg-GND
Mechanical
Environmental
Electrical
Part Name 3DC48-20
Part Number 1101-1014
DC Surge Protection
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
133DC Surge Protection
• Non-degradable, low clamping, silicon avalanche diode suppression
• Options available to protect 24 Vdc and 48 Vdc applications
• Outdoor NEMA 3R enclosure
• Three mode protection: supply to return, return to ground and supply to ground
• Shunt protectors that also provide a wired “in-line” input and output lug connectors
• Dry contacts for alarming
Features
1101-1024
The DCOD series of products offer SASD-based technology that provides non-degrading, silicon protection for DC power supplies up to 25 A in an outdoor enclosure.
Outdoor Protector
DCOD Series
Wire Range #8 to #6 AWG (16 mm2 max)
Terminal Torque 10 lb-in
Mounting #8 screws 4” centers
Remote Indication 3 pin No/NC/C contacts
Remote Contact Current Rating 2 A
Dimensions (H x W x D) in 7.2 x 5.9 x 2.5
Dimensions (H x W x D) cm 18.3 x 14.9 x 6.4
Weight (max) lb, kg 1.0, 0.4
Operating Temperature -40°C to +85°C
Nominal Voltage 24 Vdc 24 Vdc 48 Vdc 48 Vdc
Max Continuous Operating Voltage 44 Vdc 44 Vdc 88 Vdc 88 Vdc
Nominal Discharge Current (8/20 µs) 2.5 kA 5 kA 2.5 kA 5 kA
Voltage Protection Level 50 V 50 V 100 V 100 V
Mechanical
Environmental
Electrical
DCOD Series 24-2.5 24-5 48-2.5 48-5
Part Number1101-1024
1101-1026
1101-1025
1101-1027
135Power Distribution Intro Page
Transtector’s DC Edge™ high amperage, compact, rack mount DC distribution
panels are available with voltage settings and options that support both primary and
secondary power distribution.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Power Distribution Panel136
• Compact 1RU PDU
• High current capability - two 350 A inputs
• Universal voltage
• Front load TFD housing or circuit beaker
• 19” or 23” rack mount
• Front panel alarm status LED and discrete dry relay contacts
Features
• UL 60950, Listed
• NEBS-3V
• RoHS compliant
Standards and Certificates
DC Edge™ II
Compact high-power, high-current, universal voltage (+ 24 Vdc to -48 Vdc) power panel featuring dual-feed 350 A buses for either primary or secondary power distribution.
Primary or Secondary Distribution
DC Edge™ II
Dimensions (H x W x D) in 1.7 x 19.0 x 12.0
Dimensions (H x W x D) cm 4.3 x 48.3 x 30.4
Weight (max) lb, kg 16.5, 7.5
Chassis Ground Single, dual 1/4” - 20 on 5/8” stud centers
Humidity 90% non-condensing
Operating Temperature -40°C to +55°C
Enclosure Rating Indoor UL60950
Part Name/Number DC EDGE 350 DF 4/4 / 1101-900
Input Positions (quantity/type) Dual 3/8” - 16 on 1” stud centers
Operating Voltage Range + 20 to + 60 Vdc
Max Input Current per Feed 350 A
Output Positions per Input Four 1/4” - 20 on 5/8” stud centers
Input Rating 350 A per feed, max
Input Interrupt Device 450 A per feed, max
Max Current per Breaker 100 A, Airpax
Max Current per Fuse 125 A, TLS; 70 A, TPS
Fuse Type TPS and TLS
Monitoring Connection Terminal strip for Dry Form-C contacts
Mechanical
Environmental
Electrical
DC Power Distribution Panel
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
DC Power Distribution Panel 137
• Compact 1RU PDU
• High current capability - four 100 A inputs
• Universal voltage
• Front load circuit beaker
• 19” or 23” rack mount
• Front panel alarm status LED and discrete dry relay contacts
Features
DC Edge™ III
Compact mid-current, universal voltage (+ 24 Vdc to -48 Vdc) power panel featuring quad-feed 100 A buses for secondary power distribution.
Secondary Distribution
DC Edge™ III
Dimensions (H x W x D) in 1.7 x 19.0 x 12.4
Dimensions (H x W x D) cm 4.4 x 48.3 x 31.5
Weight (max) lb, kg 11.5, 5.2
Chassis Ground Single, dual 1/4” - 20 on 5/8” stud centers
Humidity 90% non-condensing
Operating Temperature -10°C to +65°C
Enclosure Rating Indoor UL60950
Part Name / Number DC EDGE III 200QF 8/8 / 1101-1006
Input Positions (quantity / type) Dual 1/4” - 20 studs on 5/8” centers
Operating Voltage Range + 20 to + 74 Vdc
Max Input current per Feed 100 A
Output Positions per Input Four two-pin, keyed Molex male connectors
Input Rating100 A per feed, max (two inputs per side = A1, A2 and B1, B2)
Input Interrupt Device 125 A per feed, max
Max Current per Breaker 30 A
Monitoring Connection HD-15 pin connectors (two), standard and bay alarms
Mechanical
Environmental
Electrical
139
Our integrated power protection cabinets provide full functionality for quick site setup, low lead times and
termination of both electrical and communication utility feeds. They include AC, DC and data line surge protection options for indoor and outdoor
communication sites with multiple power sources.
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
140
Nominal Operating Voltage
120/240 Vac 120/240 Vac
Ampere Rating 100 A 200 A
Material Heavy gauge aluminum
Finish Powder coat
Dimensions (H x W x D) in 30.0 x 24.0 x 10.0
Dimensions (H x W x D) cm 76.2 x 61.0 x 25.4
Weight (max) lb, kg 65.0, 29.5
Mount Wall or H frame, 4x Ø 0.44” mounting holes
Enclosure Type NEMA 3R
Surge Suppression Silicon diode with MOV secondary, or MOV only
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
• NEMA 3R cabinet enclosure
• Three-point latching system and pad lockable handle
• Integrated surge protection (meets UL 1449 3rd Edition)
• Illuminated power and surge suppression status indication
• Remote status monitoring
• GFCI convenience outlet
• UL 891 listed
Features
• Choice of load center sizes:
• 16 or 24 position for 100 A
• 24 position for 200 A
• Mechanically interlocked main breakers
• Numerous configurations available
• Choice of auxillary power connections:
• Appleton AR20044-RS
• Side Mounted Cam-Lok® connectors
Options
AC power protection cabinet suitable for service entrance applications.
Outdoor Cabinet
Compact, Power Protection Cabinet
Model 100 A 200 A
Part Number 1101-1032-21111 1101-1032-32113
Compact Cabinet
Cam-Lok® Connection Available
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Integrated Power Protection Cabinets 141
Material Heavy gauge aluminum
Finish Powder coat
Dimensions (H x W x D) in 40.0 x 24.0 x 10.0 58.0 x 24.0 x 20.0
Dimensions (H x W x D) cm 101.6 x 61.0 x 25.4 147.3 x 60.9 x 50.8
Mount Wall or H frame
Enclosure Type NEMA 3R
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
• Louver style ventilation
• Air flow filter
• 3/4” plywood back panel
• Multi-point ground bar
• Easy access front cover panel
Features
• Intrusion alarm contact
• 120 AC thermostatically controlled fan with guard
• 66 punch down block
• 12 position terminal strip
• Fluorescent lamp
• Numerous T1/E1 or Ethernet configurations available
Options
Demarcation Cabinet
Indoor/outdoor telecommunications demarcation cabinet with integrated signal line surge suppression options.
Outdoor Cabinet
Demarcation Cabinet
Model Name 40 inch 58 inch
Part Number 1101-751-T 1101-658
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
142
• Mechanically interlocked mains
• Integrated surge suppression
• 24 position load center
• Three-point latching system and pad lockable handle
• 135° wind stop
• GFCI convenience outlet
• UL 891 Listed on selected models
Features
• 100 A or 200 A generator receptacle
• Thermostatically controlled fan
• Integrated T1/E1 and/or Ethernet protection
• Integrated Cat5 punch down block
• 12 position terminal strip
• Remote status monitoring
• Numerous configurations available
Options
Combination Cabinet
120/240 Vac single phase, 100 A or 200 A, combination ACpower and telecommunications cabinet.
Outdoor Cabinet
AC Power and TelecommunicationsCombination Cabinets
Material Heavy gauge aluminum
Finish Powder coat
Dimensions (H x W x D) in 64.0 x 30.0 x 12.0
Dimensions (H x W x D) cm 162.6 x 76.2 x 30.5
Weight (max) lb, kg 150.0, 68.0
Mount Wall, concrete pad or H frame
Enclosure Type NEMA 3R
Surge Suppression Silicon diode with MOV secondary
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
Model Name PTC Cabinet
Part Number 1101-781
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Integrated Power Protection Cabinets 143
Max Continuous Operating Voltage
120/240 Vac 120/208 Vac 3 phase
Material Heavy gauge aluminum
Finish Powder coat
Dimensions (H x W x D) in 64.0 x 30.0 x 12.0
Dimensions (H x W x D) cm 162.6 x 76.2 x 30.5
Weight (max) lb, kg 150.0, 68.0
Mount Wall, concrete pad or H frame
Enclosure Type NEMA 3R
Surge Suppression Silicon diode with MOV secondary
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
• Provides main breakers for incoming power, and ATS for transfer between utility and generator sources
• 42 position load center
• LED status indication
• ASCO 300, 200 A, 2 pole ATS (automatic transfer switch)
• ASCO 300, 200 A, 3 pole ATS (automatic transfer switch)
• Remote status monitoring
Features
• Numerous configurations available
Options
Outdoor ATS Cabinet
120/240 Vac single phase, 120/208 3-phase or 200 A power protection cabinet with ATS (automatic transfer switch).
Outdoor Cabinet
Automatic Transfer Switch (ATS)
Model Name ATS 120/240 ATS 120/208 3-phase
Part Number 1101-740 1101-790-3
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
144
Material Heavy gauge aluminum
Finish Powder coat
Dimensions (H x W x D) in
63.0 x 30.0 x 12.0
Dimensions (H x W x D) cm
157.5 x 76.2 x 30.5
Weight (max) lb, kg 150.0, 68.0
Mount Wall, concrete pad or H frame
Enclosure Type NEMA 3R
Surge Suppression Silicon diode with MOV secondary
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
• Voltage sensing with automatic and manual switching between utility power and two backup power services
• GE/Zenith, 200 A ATS (automatic transfer switch)
• Remote status monitoring
Features
• Numerous AC/DC/data/signal surge protection configurations available
Options
Dual ATS Cabinet
100 A, 20 position, outdoor power protection cabinet with ATS (automatic transfer switch), intended for use in critical applications that require continuous, protected AC power to sensitive loads.
Outdoor Cabinet
Dual Automatic Transfer Switch Cabinet (ATS)
Model Name Dual ATS
Part Number 1101-892
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Integrated Power Protection Cabinets 145
Material 16 gauge steel
Finish Powder coat
Dimensions (H x W x D) in 24.0 x 24.0 x 10.0
Dimensions (H x W x D) cm 61.0 x 61.0 x 25.4
Mount Wall or pole mount
Enclosure Type NEMA 4
Relative Humidity 100% non-condensing
Operating Temperature -40°C to +75°C
Specifications
• Automated, programable, environmental control system
• AC distribution with silicon diode surge protection
• Multi-point ground bar (six position)
• Grounded metal backplane
Features
TransComm
Rugged cabinet for sensitive railway communications equipment.
Outdoor Cabinet
TransComm Rail Cabinet
Model Name TransComm
Part Number 1101-906
Integrated Power Protection Cabinets
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Integrated Power Protection Cabinets146
Material 16 gauge steel
Finish Powder coat
Dimensions(H x W x D) in
27.0 x 20.0 x 8.0 44.0 x 20.0 x 8.0 56.0 x 20.0 x 8.0 68.0 x 20.0 x 8.0
Dimensions(H x W x D) cm
68.6 x 50.9 x 30.5
111.8 x 50.9 x 30.5
142.2 x 50.9 x 30.5
172.7 x 50.9 x 30.5
Mount Wall mount
Enclosure Type
NEMA 1
Surge Suppression
Silicon diode with MOV secondary or MOV
Relative Humidity
100% non-condensing
Operating Temperature
-40°C to +75°C
Specifications
• Single main breaker, mechanically interlocked mains, and ATS versions available
• Secure front cover panel for unit installation and load circuit additions
• Recessed circuit breaker panel
• Integrated surge protection
• Heavy duty ground bar
• UL 891 Listed on selected models
Features
• 27”, 44”, 56” or 68” configurations available
• 120/240 single phase or 120/208 three phase
• 100 A, 200 A or 400 A main breaker options
• 24, 30 or 42 position load centers
• ATS (automatic transfer switch)
Options
Interior Service Panel
Indoor AC power panel with integrated surge suppression.
Indoor Cabinet
Interior Service Panel
Model Name ISP 27 ISP 44 ISP 56 ISP 68
Integrated Power Protection Cabinets 147
This reference section includes both a catalog index and application drawings
to assist in identifying products, applications and specifications needed for network
planning and maintenance.
Additional information on the Protection Technology Group’s full
end-to-end product offering can also be found at protectiongroup.com
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Telecommunications148
Mission critical communication providers protect their systems from maintenance costs, equipment replacement outlay, lost revenue and customer dissatisfaction by investing in transient surge protection. This network drawing is designed to provide a basic understanding of RF, AC, DC and data line protection placement in the backhaul network. Contact the Protection Technology Group at 1.800.882.9110 or 208.772.8515 to further review your specific communication network and surge protection requirements.
Cellular Backhaul Network
Cell Site
149
Mobile Telephone Switching Office
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
150 Rail
Railway communication systems are vital to safe and profitable rail operation, but can easily become vulnerable to lightning and power anomalies. PolyPhaser, Transtector and LEA provide RF, AC, DC and data line surge protection solutions for onboard and wayside rail applications required for Positive Train Control deployment. Contact our dedicated PTC sales and engineering teams at 1.800.882.9110 or 208.772.8515 for further information and network support.
Positive Train Control
151
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
Oil and Gas152
For over four decades PolyPhaser, Transtector and LEA have worked to become industry leaders in the development, design and manufacturing of power and signal integrity solutions for the oil and gas industry. Contact our dedicated sales and engineering teams 1.800.882.9110 or 208.772.8515 to further discuss your specific requirements and review the Class I Division II products that are in place to safely support your network.
Class I Division II Approved
IO/Modem/PLC
Communication Sites
153
Refining/Processing
Pumping Station Offshore Production
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
154 Index
DRDC, 126, 127DRI 120, 80, 81DRI 24, 80, 81, 130Dual ATS, 144Dyna Systems Series, 98, 99
EEthernet, 56-69, 141, 142
FFSP 4000 MC Series, 72, 73
GGas Tube, 14, 48, 79GbE, 56-65GbE PoE, 59, 63GR 1089, 57-63, 70, 74Grounding Accessories, 52, 53GT Series, 48-51GXJ Series, 42-47GXZ Series, 36-41
HHF Radios, 14, 24HF Series, 32-35
II2R CDS Series, 100-101I2R ICP Series, 114I2R IEP 120-50, 115I2R IEP Series, 128I2R RSA 48 3-40, 123I2R CM 230-20, 121I2R LA Series, 122I2R SA Series, 118, 119, 129I2R SA 120-50M, 117I2R SA 230-40, 120I2R SA 120-50M, 117I2R Series, 129I2R SSR, 83I2R Storm Series, 116IEC 1000-4-5, 26, 77IEC 60529, 10, 18, 42IEC 60529 IP 67, 6IEC 61000-4-5, 9, 13, 17, 21, 23, 32,
35, 39, 41, 42, 48, 51IEC 61643-1, 87-90, 108, 112-115,
118-122IEEE C62.41, 82, 90, 103, 106, 110,
114, 116IEEE C62.45, 82, 86IMAX Series, 86, 87
10/100, 56, 593DC48-20 Series, 132
AAC Cabinet, 142AC Protection, 84-123ACP 100 Series, 110, 111ACP Series, 110, 111ALPU CMM3, 70ALPU PoE Series, 68, 69ALPU Series, 64, 65APEX IV Series, 88APEX MOV, 89Application Drawings, 148-153AREMA, 82ATS Cabinet, 143, 146
BB50 Series, 14-17Belcore, 6Bridge Clip, 71Bulkhead Mount, 6, 14, 18, 24, 28
CCabinets, 138-146CB Series, 131CCTV, 74, 75CE, 68, 79, 180, 118, 126, 130CFS Series, 102Class I Division II, 79, 80, 130, 152Compact Power Cabinet, 140Component Protector, 108, 110, 112,
115, 116, 117, 120, 121, 122, 126, 128, 129, 130, 131
CPX, 56, 57
DDAS-P Series, 10-13Data Protection, 54-83DC Block, 14, 16, 18, 20, 22, 24, 26,
28, 30, 32, 34DC Edge II, 136DC Edge III, 137DC Pass, 36, 38, 40, 42, 44, 46, 48, 50DC Power Distribution, 136, 137DC Protection, 124-133DCOD Series, 133Demarcation Cabinet, 141Device Ground Adaptor, 53DIN Rail Mount, 60, 80, 83, 100, 110,
114-123, 126-130DPR, 60, 61DPS Series, 103
Indoor Cabinet, 136, 138IP 20, 111,117, 119, 121-129IS-50 Series, 24-27IS-75BB, 77ISP Cabinet, 146ITU 703, 56, 60IX Series, 66, 67
LLS Plus, 94, 95
MMCP Series, 108, 109MCP-OD, 90, 91MDS, 78MOV, 86-98, 102, 108, 109, 112,
117, 121-123, 132, 140-146
NNEBS 3V, 136NEC, 60, 68, 87, 92-96NEMA 1, 146NEMA 12, 87, 98, 99NEMA 3R, 65, 93, 101, 133, 140-144NEMA 4, 97, 145NEMA 4X, 87-90, 102NEMA LS, 92, 94NEMP Series, 28-31
OOutdoor Enclosure, 140-145
PPanel Protector, 86-102PBM Series, 71PDS Series, 79PDU, 136, 137PEEP, 52PIM, 6, 8, 10-13, 20-22PoE, 58-70PTC Cabinet, 142PV Plus Series, 92, 93
RRack Mount, 60, 106, 136, 137RF Protection, 4-51RJ-45, 57-70RMP Series, 106, 107RMP-CCTV, 76
155Index
1000-1270, 571000-1270-NF, 571100-608, 1111100-629, 110, 1111100-647, 1111100-855, 1111100-954, 1111101-115, 711101-162, 711101-299, 108, 1091101-300-1, 591101-338, 891101-372-1, 72, 731101-372-2, 731101-372-3, 731101-372-6, 731101-424, 90, 911101-446-43, 881101-460, 881101-464, 881101-511, 1311101-534, 1071101-546, 891101-560, 1071101-586, 791101-587, 791101-607, 74, 751101-608, 1111101-613, 751101-627, 1141101-629, 1141101-640, 64, 651101-645, 911101-656, 651101-678, 1271101-679, 1271101-680, 126, 1271101-681, 1271101-686, 1311101-689, 1091101-704, 761101-707, 821101-724, 1271101-732, 1091101-738, 911101-744, 821101-764, 821101-771, 911101-772-A, 621101-778, 651101-805, 701101-808, 86, 871101-808-MM, 871101-809, 871101-809-M, 86, 871101-809-MM, 871101-809-M-MM, 871101-826, 112, 1131101-828, 611101-829, 611101-830, 611101-869, 80, 81, 130
1101-870, 811101-872, 1011101-873, 68, 691101-882, 611101-897, 691101-898, 691101-900, 1361101-901, 112, 1131101-905, 611101-911, 611101-932, 691101-933, 691101-934, 691101-974, 571101-975, 571101-976, 571101-977, 56, 571101-978, 571101-979, 571101-980, 100, 1011101-981, 1011101-984, 571101-985, 571101-986, 571101-987, 571101-988, 571101-989, 571101-990, 591101-991, 591101-994, 58, 591101-995, 621101-1001, 591101-1044, 621101-1006, 1371101-1014, 1321101-1024, 1331101-1025, 1331101-1026, 1331101-1027, 1331101-1028, 631101-1029, 631101-1030, 631102-007-1A, 1031102-007-9, 106, 1071102-014-5, 1221102-014-6, 1221102-014-7, 1201102-014-8, 1211102-014-13-1, 1191102-014-26, 1191102-014-38-2, 1291102-014-42, 1191102-014-43, 118, 1191104-04-000, 1231104-09-001, 831104-11-000, 1281104-11-001, 1281104-11-002, 1281104-11-005, 1291104-15-000, 1151104-15-001, 1161104-15-002, 117
RoHS, 10, 14, 18, 24, 28, 36, 42, 58, 60, 68, 115-123, 128, 129, 136
RS232, 66RS422, 72RS485, 66, 72
SSilicon (SASD), 60-64, 71, 72-76, 88,
82, 90, 98, 100, 103, 104-108, 110-116, 126, 128, 131, 133, 140-146
Silicon | MOV, 86-88, 91, 140SL Series, 104, 105SP Plus, 96, 97SuperHy Series, 112, 113SX Series, 18-23SXRR Series, 82
TT1/E1, 55, 57, 60-62, 66, 67, 141,
142TB (Thunderbolt) Series, 63TransComm Cabinet, 145TSJ, 58, 59TSJ X6 Series, 62TSX Series, 6-9
UUL 1449 3rd Edition, 86, 88, 9;2, 96,
108, 114, 118, 140UL 497, 64UL 497A, 56UL 497B, 18, 36, 42, 56, 58, 74, 126UL 60950, 136UL 891, 140, 142, 146UL 94-5V, 91
VVHF Radios, 14
XxDSL, 60, 61, 67
Part Number1000-1206, 601000-1268, 571000-1268-NF, 571000-1269, 571000-1269-NF, 57
©2011 Transtector Systems, Inc. All rights reserved.An ISO 9001:2008 and ISO 14001:2004 certified company.
156 Index
1104-29-000, 104, 1051104-29-001, 1053PEEP, 5258R-112S, 535PB-M, 525PEEP-M, 528PB-M, 528PEEP-M, 52A70-00-5002, 102A70-00-5006, 102A70-00-5007, 102A70-00-5008, 102A70-00-5010, 102A70-00-5011, 102AL-LSXM, 19, 20, 21AL-LSXM-MA, 20, 21BGXZ+24NFNF-A, 38, 39CCK, 53CGXJ+15NFNF-A, 44, 45CGXJ+15NFNM-A, 44, 45CGXJ+24NFNF-A, 44, 45CGXJ+30NFNM-A, 42, 44, 45CGXJ+36DFDF-A, 44, 45CGXJ+36DFDM-A, 44, 45CGXJ+36NFNF-A, 44, 45CGXJ+36NFNM-A, 44, 45CGXJ+36NMNF-A, 44, 45CGXZ+15NFNF-A, 38, 39CGXZ+24NFNF-A, 38, 39CGXZ+36NFNF-A, 38, 39CGXZ+48NFNF-A, 38, 39CGXZ-15NFNF-A, 38, 39CGXZ-48NFNF-A, 38, 39CS112-25, 53CS112-50, 53CS112-100, 53CS3-25, 53CS3-50, 53CS3-100, 53CS6-25, 53CS6-50, 53CS6-100, 53CU-SPGP, 53DAS-P-DFF30, 10, 12, 13DAS-P-DFM30, 12, 13DAS-P-DMF30, 12, 13DGXE+30NMNF-A, 40, 41DGXJ-P-DFM30, 12DGXJ+15DFDF-A, 44, 45DGXJ+15DFDM-A, 44, 45DGXJ+15DMDF-A, 44, 45DGXJ+15NFNF-A, 44, 45DGXJ+24DFDF-A, 44, 45DGXJ+24DFDM-A, 44, 45DGXJ+24DFNM-A, 46, 47DGXJ+24DMDF-A, 46, 47DGXJ+24NFNF-A, 46, 47DGXJ+24NFNM-A, 46, 47DGXJ+36DFDF-A, 46, 47DGXJ+36DFDM-A, 46, 47DGXJ+36DFNM-A, 46, 47DGXJ+36DMDF-A, 46, 47
DGXJ+48DFDF-A, 46, 47DGXJ+48DFDM-A, 46, 47DGXJ+48NFNF-A, 46, 47DGXJ-48NFNF-A, 46, 47DGXZ+06NFNF-A, 36, 38, 39DGXZ+06DFDF-A, 38, 39DGXZ+06NMNF-U, 38, 39DGXZ+06TFTF-A, 38, 39DGXZ+15DFDF-A, 38, 39DGXZ+15NFNF-A, 38, 39DGXZ+15TFTF-A, 38, 39DGXZ+24NFNF-A, 38, 39DGXZ+24DFDF-A, 38, 39DGXZ+36NFNF-A, 38, 39DGXZ+48DFDF-A, 38, 39DGXZ+48NFNF-A, 40, 41DGXZ+60NFNF-A, 40, 41DGXZ-48DFDF-A, 40, 41DGXZ-48NFNF-A, 40, 41DGXZ-60NFNF-A, 40, 41DS20-300A, 99DS21-80A, 99DS21-150A, 99DS21-225A, 99DS21-300A, 99DS30-600A, 99DS30-1200A, 99DSXL, 18, 20, 21DSXL-D, 20, 21DSXL-D-MA, 20, 21DSXL-D-MA-BF, 20, 21DSXL-D-MA-P2-BF, 20, 21DSXL-D-ME, 20, 21DSXL-D-SP, 20, 21DSXL-DN-MA, 20, 21DSXL-MA, 20, 21DSXL-MA-BF, 20, 21DSXL-MA-SP, 20, 21DSXL-ME, 20, 21DSXL-P, 20, 21DT-NFF, 50, 51DT-NFM, 50, 51GSA-KIT-N, 53GT-DFF-AL, 50, 51GT-DFM-AL, 50, 51GTH-NFF-AL, 50, 51GTH-NFM-AL, 50, 51GT-NFF-AL, 48, 50, 51GT-NFM-AL, 50, 51GT-NFSF-AL, 50, 51GT-TFF-AL, 50, 51GT-TFM-AL, 50, 51IS-50NX-C1, 26, 27IS-50NX-C1-MA, 26, 27IS-50NX-C1-ME, 26, 27IS-50NX-C2, 26, 27IS-50NX-C2-MA, 26, 27IS-50NX-C2-ME, 26, 27IS-50NX-CO, 24, 26, 27IS-50NX-CO-MA, 26, 27IS-50NX-CO-ME, 26, 27IS-50UX-C1, 26, 27
IS-50UX-C1-MA, 26, 27IS-50UX-C1-ME, 26, 27IS-50UX-CO, 26, 27IS-50UX-CO-MA, 26, 27IS-50UX-CO-ME, 26, 27IS-75BB/1.5, 77IS-75BB/18, 77IS-B50HN-C1, 16, 17IS-B50HN-C2, 16, 17IS-B50HN-CO, 16, 17IS-B50HU-C1, 16, 17IS-B50HU-CO, 16, 17IS-B50LN-C1, 16, 17IS-B50LN-C2, 14, 16, 17IS-B50LN-CO, 14, 16, 17IS-B50LU-C1, 16, 17IS-B50LU-CO, 16, 17IS-NEMP-C1, 30, 31IS-NEMP-C1-MA, 30, 31IS-NEMP-C1-ME, 30, 31IS-NEMP-C2, 30, 31IS-NEMP-C2-MA, 30, 31IS-NEMP-C2-ME, 30, 31IS-NEMP-CO, 30, 31IS-NEMP-CO-MA, 28, 30, 31IS-NEMP-CO-ME, 30, 31IX-1T, 67IX-2H2DC48, 66IX-2H1DC56-IG, 67IX-2H1DC24-IG, 67IX-2H1DC48-IG, 67IX-2L, 67IX-2T, 67J-1, 53J-2, 53LS 100, 94, 95LS 200, 95LS 300, 95LSXL, 22, 23LSXL-ME, 22, 23MDS+24-F-F, 78PSXL, 22, 23PV 200, 93PV 400, 93PV 600, 93SP 100, 96, 97SP 200, 96, 97TSXDC-DFM, 6, 8, 9TSX-DFF, 8, 9TSX-DFM, 8, 9TUSX-DFF, 8, 9TUSX-DFM, 8, 9UHF50HD, 34, 35UHF50HD-MA, 34, 35UHF50HD-ME, 34, 35UHF50HN, 34, 35UHF50HN-MA, 34, 35UHF50HN-ME, 34, 35UNI-KIT-4CC, 53UNI-KIT-4CT, 53UNI-KIT-4TC, 53USXL-D, 22, 23
157Index
VHF50HD, 34, 35VHF50HD-MA, 34, 35VHF50HD-ME, 34, 35VHF50HN, 32, 34, 35VHF50HN-MA, 34, 35VHF50HN-ME, 34, 35WSXM, 20, 21
800.882.9110 | 208.772.8515 | www.ProtectionGroup.com