fr 1PS100-24 Vc / PS100-48 Vc
S1B1233100-05 1/8
en en
fr
fr
3
4 Description / Description
p PS100 is a power supply unit that supplies backup operating power for:p MV switchgear motor mechanismsp Transmission equipment (e.g. radio)p Control units such as RTU or Automatic Transfer Systemp Protection relays, Fault Passage Indicators and others electronic devices.
p PS100 fournit une alimentation secourue pour :p La motorisation des cellules moyenne tension,p les équipements de communication (par exemple radio),p les unités de commande comme les RTU ou les automatismes de transfert de sources,p les relais de protection, les indicateurs de défaut et autres équipements électroniques.
Features / Fonctions
2 Unpacking / Déballage
EMS58580 24 VcEMS58581 48 Vc
en110/230 Va power supply terminal blockBattery state indication output contact
AB
110/230 Va power supply presence indication output contact Network voltage absence (red LED)
C
DBattery state not OK (red LED) PS100 internal fault (red LED)
EF
24/48 Vc output presence (green LED)12 Vc output presence (green LED)
GH
Modbus communication indicator (yellow LED)Power supply fault reset push button / energy back up activation
J
K
Battery connection terminal12 Vc output terminal
LM
24/48 Vc output terminalRJ45 Modbus network connectors
NP
Modbus address (rotary switches)Q
Bornier d'alimentation 110/230 Va
Contact de la sortie de signalisation de l’état de charge de la batterie
AB
Contact de la sortie de signalisation dela présence de l'alimentation 110/230 Va Absence de tension réseau (voyant rouge)
C
DEtat de la batterie non OK (voyant rouge) Faute interne PS100 (voyant rouge)
EF
Présence tension sortie 24/48 Vc (voyant vert)Présence tension sortie 12 Vc (voyant vert)
GH
Indicateur de communication Modbus(voyant jaune)Bouton de réarmement après défaut de l'alimentation / Activation réserve d'énergie
J
K
Connecteur batterieBornier de sortie 12 Vc
LM
Bornier de sortie 24/48 Vc
Connecteurs RJ45 réseau ModbusNP
Adresse Modbus (roues codeuses)Q
48V
12V
Test / Reset
Easergy
PS 100 - 48V
EMS58581
OK
OK
x10
N0
91
82
73
45 6
09
1
82
73
45 6
x1Ph.
48V12V
48V
12V
Test / Reset
Easergy
PS 100 - 48V
EMS58581
OK
OK
x10
N0
91
82
73
45 6
09
1
82
73
45 6
x1Ph.
48V12V
D
F
H
E
G
J
K
B C
NP M LQ
A
Product references / Références produit
PS100-24 VcEMS58580
Bat 12V 24 AhEMS58582
PS100-48 VcEMS58581
Bat 12V 38 AhEMS58583
Les batteries doivent être commandées séparément / Batteries have to be ordered separately
5 Dimensions / Dimensions
6 Installation / Installation
165
15 7
1
2
160
125
3
Click!
S1B1233100-05 2/8
Important: check recommendations for the enclosure installation
Important : voir les recommandations pour l'installation en coffret
en
fr
Ph
+-
N
7 Connection / Raccordement
A
A
B
C
M
M
N
12 Vc
12 Vc
24/48 Vc
+-
12 Vc 24/38 Ah
Modbus
+-
C
Ph / N
8 mm 1.35 N.m4 mm2
10 mm 1.75 N.m10 mm2
N 24 / 48 Vc
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASHTurn off all power supplying this equipment before working on the equipment.Failure to follow these instructions will result in death or serious injury.
RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU D’ARC ELECTRIQUECoupez l'alimentation de ce matériel avant intervention.Le non-respect de ces instructions provoquera la mort ou des blessures graves.
DANGER
C
BB C
Important: do not connect the battery to PS100 before performing the installation and the commissionning.
Important : ne pas raccorder la batterie au PS100 avant l'installation et la mise en service.
en
fr
S1B1233100-05 3/8
++ -- +-
12 Vc
24/48 Vc
+ +
Limited length for the battery cable / Longueur limitée pour le câble batterie
8.1 Battery monitoring / Etat de la batterie
24/48 Vc coupling / Couplage du 24/48 Vc (availability increased / disponibilité accrue) :
en Test performed when battery fully loaded and when 12V current ouput is higher than 1Ap Automatically every 12 h (can be adjusted)p By pushing the Test / Reset button
fr Test effectué quand la batterie est complètement chargéeet lorsque le courant sur la sortie 12V est supérieur à 1Ap Automatiquement, toutes les 12 h (paramétrable)p En appuyant sur le bouton Test / Reset
8 Battery Control / Gestion de la batterie
Voltage
Energy
Voltage
Energy
1 2
8.2 Battery Testing / Test de la batterie
Serious discharge thresholdSeuil de décharge critique
OFF éteinte
ON allumée
Backup thresholdSeuil de réserve1
2
(Red / Rouge) (Green / Vert)
7 Connection / Raccordement (to be continued / suite)
Energy back-upactivation Activationréserve d'énergie
With energy back up / Avec réserve d'énergie
Without energy back up / Sans réserve d'énergie
2
S1B1233100-05 4/8
Modbus address 01 99Adresse Modbus 01 99
9 Modbus Communication / Communication Modbus
x10 x1
+ = 01
Modbus cableCâble Modbus0.3 m VW3 A8 306 R031 m VW3 A8 306 R103 m VW3 A8 306 R30
Baud rateVitesse de transmission 9600 / 19200 / 38400
Parity / ParitéFormat / Format
Available values by automatic detection after power-up or long push on reset button.Permanent traffic is necessary to allow automatic detection.
Valeurs possibles par détection automatique après mise sous tension ou après un appuilong sur le bouton reset. Un trafic permanent est nécessaire pour la détection automatique.
No parity - 2 stop-bitEven parity - 1 stop-bitOdd parity - 1 stop-bit
Side female connectorCôté connecteur femelle
Modbus
...Modbus terminationTerminaison ModbusVW3 A8 306 RC
CommonD0D1
1
MeasuringWord Address Format Unit Range Default
valueFunction code
Description
16S % 0 -100 % 03, 04 Battery charge indicator 16S 0.1V 0-60V 03, 04 48V (or 24V) output voltage16S 0.1V 0-16V 03, 0416S 0.1V 0-16V 03, 0416S 0.1A 0-15A 03, 0416S 0.1A - 200 ... +200A 03, 04
Description
Tension de sortie 48V (ou 24V)Tension de sortie 12 VTension de batterie 12 VCourant de sortie 12 VCourant batterie
0400h (1024dec)0401h (1025dec)0402h (1026dec)0403h (1027dec)0405h (1029dec)0406h (1030dec)
12 V output voltage12 V battery voltage12 V output currentBattery current
Indicateur de charge batterie
Modbus Register Table / Tableaux des registres Modbus
S1B1233100-05 5/8
DescriptionStatusBit Address(*)
Format Unit Range Default value
Function code
1008h (4104dec) Bit 01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
01, 02, 03, 04
coverable fault1: PS100 detected an internal minor problem which can be recovered (overtemperature, overcurrent, overvoltage).
Faute mineure récupérableMinor re1 : PS100 a détecté un problème interne mineur qui peut être récupéré (surtempérature, surcourant, surtension).
Faute majeure non récupérable1 : PS100 a détecté un problème interne majeur qui ne peut être récupéré.
Bit
100Bh (4107dec) Bit Major unrecoverable fault1: PS100 detected an internal major problem which
1010h (4112dec) AC power supply off (< 30 % Vac)0 = On, 1= Off
Alimentation secteur arrêtée (< 30 % Vca)0 = Marche, 1 = Arrêt
1011h (4113dec) Bit General shutdown0 = No shut down 1 = Imminent shut down
Arrêt général0 = Pas d’arrêt1 = Arrêt imminent
1012h (4114dec) Bit Battery low0 = Charged 1 = Discharged (< backup threshold) or (10% charge left)
Batterie faible0 = Chargée1 = Déchargée (< seuil de réserve) ou (10% charge restante)
1013h (4115dec) Bit Battery fault0 = Operational1 = Disconnected or out of order
Défaut batterie0 = Opérationnelle1 = Déconnectée ou hors service
1014h (4116dec) Bit Charger fault0 = Operational 1 = Out of order
Défaut chargeur0 = Opérationnel1 = Hors service
1015h (4117dec) Bit 12 V power supply failure0 = 12 V presence 1 = 12 V absence
Défaillance alimentation 12 V0 = Présence 12 V1 =Absence 12 V
1016h (4118dec) Bit
AC power supply low0 = On1 = Low (< 75% Vac during 1.5 s)
Défaillance alimentation 24/48 V0 = Présence 24/48 V 1 = Absence 24/48 V
can not be recovered.
01, 02, 03, 04
1017h (4119dec) Bit
24/48 V power supply failure0 = 24/48 V presence 1 = 24/48 V absence
Alimentation secteur basse0 = OK 1 = Niveau bas (< 75% Vca pendant 1,5 s)
(*) Word address = 3 first digits of bit address, example bit address = 1013h, word addess = 101h (to be used with Modbus functions 3 and 4)
Description
Settings
03, 04, 06, 16
03, 04, 06, 16
03, 04, 06, 16
03, 04, 06, 1603, 04, 06, 16
Word Address Format Unit Range
1E04h (7684dec) 16S 0.1V 10 to 12.0 V 10.5 V16S 1 %
1E06h (7686dec) 16S 1: Enabled0: Disabled
0: Disabled
16S hour
16S 1
12 h
DescriptionDescription
Réserve d’énergie
Période de test de la batterieBattery test period
Sélection des seuils Vca : Vac threshold selection:
activée / désactivée
Seuil de décharge critiqueSerious discharge threshold
Energy backup threshold5 % of the batterynominal capacity
Energy backup enabled / disabled
Seuil de réserve d’énergie
Default value Function code
03, 04, 06, 1616S 0.1 Ah 24 Ah Battery nominal capacity Capacité nominale de la batterie
0: Off = 52 Vac, Low = 129 Vac1: Off = 69 Vac, Low = 172 Vac
0 : Arrêté = 52 Vca, Bas = 129 Vca1 : Arrêté = 69 Vca, Bas = 172 Vca
0: < 180 VacAC power supply
1: > 180 Vac
1E05h (7685dec)
1E07h (7687dec)
1E09h (7689dec)
1E08h (7688dec)
Bit Address Format Unit Range Default value
Function code
Description
0F00h (3840dec) Bit 01, 02, 03, 04, 05, 06, 15, 16 05, 06
24V/48V restart 0F0Fh (3855dec) Module check
CommandsDescription
Redémarrage 24/48 VVérification moduleBit
Modbus Register Table / Tableaux des registres Modbus (to be continued / suite)
S1B1233100-05 6/8
fr
10 Technical data / Caractéristiques
en Power supply
Technical characteristics
PS100-48 VcPS100-24 VcInput a voltage
Output c voltage VoltageCurrent
48 Vc ±10%
Output 12 Vc radio Voltage 12 Vc -10%, +25%
Auxiliary contact 2 dry contacts ‘‘Battery OK’’ and ‘‘AC supply ON’’
IEC 60 255-5 Insulation (50 Hz/1 min): 10 kV Surge (1.2/50 µs): 20 kVClimatic -40°C +70°C Operating.-40°C +85°C StorageWeight 2.8 kg
Relay type-breaking capacity 2 A 24 Vc, 1 A 48 Vc, 5 A 220 Va
Current 1.5 A rated 8 A 20 s Power 18 W / 100 W 20 sProtection By electronic against overloads and short circuits. Automatic restart after external fault.Limits A limitation, dedicated for radio units, is set up to avoid the battery discharge:
3 A in emitting mode for 3 mn.
2 A rated8 A for 15 s, 17 A peak for 50 ms
4 A rated16 A for 15 s, 25 A peak for 50 ms
Power 90 W rated with/without battery300 W (1 mn) with battery only
90 W rated with/without battery300 W (1 mn) with battery only
Protection By electronic against overloads and short circuits. Automatic restart after external fault.
24 Vc ±10%
Rated
LimitsProtection By electronic against reversal polarity and over voltage. Automatic restart after fault.
380 Vac
110 to 240 Va, +10%, -15%, 50Hz/60Hz (+/-5%)110 Vc , +20%, -20%
Limits Without battery total ouputs are limited to 90 W.Redundancy 2 units may be connected in parallel to increase availability.
Alimentation
Caractéristiques techniques
PS100-24 Vc PS100-48 VcTension a d’entrée
Tension c de sortie TensionCourant
24 Vc ±10%
Sortie 12 V c radio Tension 12 Vc -10%, +25%
Contacts auxiliaires 2 contacts secs Batterie OK et présence secteur
IEC 60 255-5 Isolement (50 Hz/1 min) : 10 kV Onde de choc (1,2/50 µs) : 20 kVClimatique Fonctionnement : -40°C à +70°C / Stockage : -40°C à +85°CPoids 2,8 kg
Pouvoir de coupure 2 A 24 Vc, 1 A 48 Vc, 5 A 220 Va
Courant 1,5 A nominal 8 A 20 s Puissance 18 W / 100 W 20 sProtection Electronique contre les surcharges et les court-circuits.
Redémarrage automatique après défaut externe. Limites Une limite dédiée aux unités radio est fixée pour éviter la décharge complète de la
batterie : 3 A pendant 3 mn.
2 A nominal8 A pendant 15 s, 17 A pic, 50 ms
4 A nominal16 A pendant 15 s, 25 A pic, 50 ms
Puissance 90 W nominal avec ou sans batterie300 W (1 mn) avec batterie uniquement
90 W nominal avec ou sans batterie300 W (1 mn) avec batterie uniquement
Protection Electronique contre les surcharges et les court-circuits. Redémarrage automatique après défaut externe.
48 Vc ±10%
Nominale
LimitesProtection Electronique contre les inversions de polarité et les surtensions.
Redémarrage automatique après défaut.
380 Vac
110 à 240 Va, +10%, -15%, -15%, 50Hz/60Hz (+/-5%)110 Vc , +20%, -20%
Limites
Redondance Possibilite de connecter en parallèle 2 unités pour augmenter la disponibilité.Puissance totale de sortie sans batterie limitée à 90 W.
Battery deep dischargeWhen PS100 is not supplied and 12V and 24/48V outputs are off (backup threshold or serious discharge threshold reached), the battery module continues to deliver a residual current to power its electronic boards. In case of prolonged power supply failure, it is recommended to insert a contactor between the battery and PS100 in order to avoid deep discharge of the battery (see Auto power off circuit wiring).
Décharge profonde de la batterieLorsque PS100 n'est pas alimenté et que ses sorties 12V et 24/48V ont été coupées (atteinte seuil de réserve ou seuil de déchargement critique), la batterie continue à délivrer un courant résiduel au PS100 afin d'alimenter son électronique. En cas d'absence prolongée de l'alimentation de PS100, il est recommandé d'insérer un contacteur entre la batterie et PS100 afin d'éviter une décharge profonde de la batterie (voir cablage de déconnexion automatique de la batterie).
S1B1233100-05 7/8
11 Installation in enclosure / Installation en coffret
Natural convection in the enclosure: 0.5 m/s upwards without obstacle
Convection naturelle dans le coffret : 0,5 m/s de bas en haut sans obstacle
en
fr
> 10 mm > 10 mm
> 50 mm
> 50 mm
12 Auto power off circuit wiring / câblage de déconnexion automatique de la batterie
en
fr
This wiring is an additional protection against the risk of deep discharge of the battery module. It has to be used in case of prolonged absence of power supply voltage on PS100.
Ce schéma de raccordement est une protection complémentaire pour éviter la décharge profonde de la batterie. Il est recommandé d’utiliser un des ces schémas en cas d’absence prolongée de la tension d’alimentation de la PS100 après la fin d’autonomie de la batterie.
en Wiring without use of back-up threshold
fr câblage si le seuil de réserve n’est pas utilisé
1/L1
A1
A2
3/L2
5/L3
13/N
O21
/NC
+
2/T1
4/T2
6/T3 14 22
B4 mm²
A4 mm²
C4 mm²
1.5 mm²
LC1 D32BL
A = B + C <= 400 mm
0.5Afuse
en Wiring with use of the backup threshold
fr câblage avec utilisation du seuil de réserve
1/L1
A1
A2
3/L2
5/L3
13/N
O21
/NC
A1
A2
+
2/T1
4/T2
6/T3 14 22
B4 mm²
A4 mm²C
4 mm²
1.5 mm²1.5 mm²
1.5 mm²
1.5 mm²
LC1 D32BL
A = B + C <= 400 mm
0.5Afuse
A1-
12
11
11
12 14
14
A2+
RM17UAS14
U
Tt
0,1Un
2 8
10s
4 6
H
5 20%6
8
1012 14
16
18
RM17UAS
U
15VDC
14
131211
10
9
<U>U
Mem Mem
No Mem
No Mem
S1B1233100-05 8/8
Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F - 92506 Rueil Malmaison Cedexwww.schneider-electric.com
Ce produit doit être installé, raccordé et utilisé en respectant les normes et/ou les règlements d'installation en vigueur.En raison de l'évolution des normes et du matériel, les caractéristiques et cotes d'encombrement données ne nous engagent qu'après confirmation par nos services.This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.As standards, specifications and designs change from time to time, always ask for confirmation of the informationgiven in this publication.
© 06-2016 Schneider Electric - All rights reserved.