DCL-CONS-34007212 2009-10-15
Technical Data sheets MGE Galaxy 300-AC
MGE Galaxy 300 MGE Galaxy 300 10kVA
MGE Galaxy 300 15kVA MGE Galaxy 300 20kVA MGE Galaxy 300 30kVA
MGE Galaxy 300 40kVA
Technical data sheets: manufacturers declaration according to IEC 62040-3
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09
2
MGE Galaxy 300
10, 15, 20, 30, 40kVA / IEC 62040-3 Technical data sheets - Manufacturer declaration
UPS tests
reference only
Characteristic of equipment Units and/or
informations
Manufacturer's declared
values
Minimum performance
requirements, methods and references
Construction
Model catalogue reference
(manufacturers reference)
MGE Galaxy 300
Three Phases In Three
Phases Out UPS
10/20/30/40kVA
&
MGE Galaxy 300
Three Phases In one Phase
Out UPS 10/20/30kVA
Model
Power, rated
VA ou W
Apparent -
Active
With Cos=0,8
10kVA 8kW
15kVA 12kW
20kVA 16kW
30kVA 24kW
40kVA 32kW
MGE Galaxy 300 UPS Unitary or Parallel 10kVA
MGE Galaxy 300 UPS Unitary or Parallel 15kVA
MGE Galaxy 300 UPS Unitary or Parallel 20kVA
MGE Galaxy 300 UPS Unitary or Parallel 30kVA
MGE Galaxy 300 UPS Unitary or Parallel 40kVA
5.1.1 UPS Configuration
Topology Double conversion with
Bypass
5.3.4 Classification of UPS by performance VFI SS 113
Mechanical
Dimensions (Height x Width x Depth) mm See separate declaration
(Paragraphe 1)
If details, to specify them in the separate declaration
Mass or Weight kg See separate declaration
(Paragraphe 1)
If details, to specify them in the separate declaration
Mass or Weight with batteries (if
integrated)
kg See separate declaration
(Paragraphe 1)
6.5.5
Acoustic noise at 1m
- Normal mode
- Stored energy mode
dBA
dBA
56dBA
56dBA
Measurements in accordance with standard
ISO 7779 (0,15m < d < 8m according to dimensions of
the source of noise, with ,preference 1m).
Safety
Access (operator access or restricted
access)
Restricted Access
IEC 62040-1 Degree of protection against hazards and
water ingress
IP IP 20 In accordance with IEC 60529
IP XX first X (/ foreign body) 2nd X (/ water)
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09
3
UPS tests
reference only
Characteristic of equipment Units and/or
informations
Manufacturer's declared
values
Minimum performance
requirements, methods and references
Electromagnetic Compatibility
Emission UPS Cat UPS category C3
See separate declaration
(paragraph 6)
CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-
2: 2005
- Immunity to electrostatic discharges
- Immunity to radiated IEC 62040-2
Immunity UPS Cat UPS category C3
See separate declaration
(paragraph 6)
- conducted a.c mains
- conducted a.c output
- Radiated - electric field
- Radiated - magnetic field
Environmental
4.2.1.1
Ambient storage temperature range C -10 C to +60 C
-15 C to +40 C
T specified, equipment without batteries
For Altitude < 1000m and moisture 20 to 95%
T specified, for Batteries
Ambient service temperature C 0 C to +35 C
0 C to + 25C
Continuous maximum ambient service temperature
at rated Current, Cos=0,8
Continuous maximum ambient service temperature
with Battery inside the Unit
4.2.1.2
Maximun service altitude m 1000m and
P = nP 10% all the 1000m
Until 1000m included
For 1500 to 5000m, coefficient of downgrading from
0,85 to 0,59
4.1.3
Relative humidity range % Storage : 0% to 90%
Operation : 05% to 90%
( without condensation )
Relative humidity without condensing at ambient
temperature
5.6 Communication circuits
4.2.1.1 (List communication / signalling circuits) See separate declaration
(paragraph 5)
Electrical characteristics - Input
5.2.1.a
Voltage (steady-state, r.m.s)
- rated
V 220V or 230V or 240V
380V or 400V or 415V
Nominal value of input voltage, and thresholds of
passage in stored energy mode by input voltage
exceeding the tolerance
To specify : if there is no a change of mode to
stored energy mode by U + 10% or if the thresholds
depend on the load use
Minimal value of input votage allowing the refill
battery during normal operation UPS
5.2.1.b - tolerance % 2%
5.2.1.c
Frequency
- rated
Hz 50Hz or 60Hz Nominal value of input frequency and thresholds of
a change of mode to stored energy mode of the
UPS, by input frequency exceeding the tolerance
If it there not a change of mode to stored energy
mode, to specify the minimum and maximum
frequency possible for the UPS
5.2.1.d - tolerance % 10% (45 to 65Hz)
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09
4
UPS tests
reference only
Characteristic of equipment Units and/or
informations
Manufacturer's declared
values
Minimum performance
requirements, methods and references
5.2.2.c
Current r.m.s.
rated (with the energy storage device
charged)
A 13A / (10kVA)
20A / (15kVA)
26A / (20kVA)
40A / (30kVA)
53A / (40kVA)
Input steady current with ,100% rated VA and W, on
linear and non linear load
5.2.2.f
maximum (with low input volt and energy
storage device charging)
A 16A / (10kVA)
23A / (15kVA)
29A / (20kVA)
42A / (30kVA)
56A / (40kVA)
5.2.2.h - total harmonic distortion (THD p.u.) % 50% rated VA and W on linear
load and non linear load
5.2.2.k AC power distribution system
-(TN, TT, IT) compatibility
TT, TN (S or C), IT
5.2.2.i - short-circuit power required Ssc See separate declaration
(paragraph 2)
5.2.2.a - phases required (1,2 or 3) Tree Phases 3P+N+G
5.2.2.b - neutral required (yes / no) Yes
5.2.3 Additional or unusual conditions NA
Output waveform
5.3.1.2
5.3.1.2
Waveform - Normal mode
Waveform - Stores energy mode
Sinusoidal
Sinusoidal
Sinusoidal or non sinusoidal
Sinusoidal or non sinusoidal
Transfer - Normal mode / Stored energy Break
No break
No Break
Complies with figure 1
Break time / Make time ( if applicable ) ms
On battery
mode
Without Break
Rated voltage 2% with a come
back to 1% in 100ms
Transfer transients and times measured at the time of
tranfer load from UPS to an alternative source and
return, by command or defect of switches of coupling
and bypass
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09
5
UPS tests
reference only
Characteristic of equipment Units and/or
informations
Manufacturer's declared
values
Minimum performance
requirements, methods and references
Electrical output characteristics - Static and Dyn amic characteristics - Normal mode
5.3.2 AC power distribution system
- compatibility (TN, TT, IT) TT, TN (S or C), IT
- phases available (1,2 or 3) One Phase 1P+N+G
Or Tree Phases 3P+N+G
- neutral available (yes / no) Yes
Voltage (steady state, r.m.s.)
Rated Output voltage V r.m.s 220V, 230V, 240V default value
for One phase
380V, 400V, 415V default value
for Tree phases
Operation at 415 VAC/60 Hz is not possible
Output voltage normal mode variation % Rated voltage 2% adjustable Output voltage measured at the two ends of the
range of rated power factor and with nominal rated
votage
Voltage variation = maximum and minimum
measured value
Stored energy mode variation % 2%
Rated output apparent power VA 10kVA
15kVA
20kVA
30kVA
40kVA
Rated output active power across a
linear load
W
8kW
12kW
16kW
24kW
32kW
Rated output active power across a
reference non linear load
W
Same as linear load
Total voltage distortion across a linear load %
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09
6
UPS tests
reference only
Characteristic of equipment Units and/or
informations
Manufacturer's declared
values
Minimum performance
requirements, methods and references
- linear %, s Complies curve 1 with IEC
62040-3
- Non-linear %, s Complies curve 3 with IEC
62040-3
6.4.2.11.1/2 - transfer normal mode / storage energy
mode
%, s Complies curve 1with IEC
62040-3
To note Fig 1, 2 or 3 and specified UPS
Performance with nominal power W a