  • DCL-CONS-34007212 2009-10-15

    Technical Data sheets MGE Galaxy 300-AC

    MGE Galaxy 300 MGE Galaxy 300 10kVA

    MGE Galaxy 300 15kVA MGE Galaxy 300 20kVA MGE Galaxy 300 30kVA

    MGE Galaxy 300 40kVA

    Technical data sheets: manufacturers declaration according to IEC 62040-3

  • APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09

    2

    MGE Galaxy 300

    10, 15, 20, 30, 40kVA / IEC 62040-3 Technical data sheets - Manufacturer declaration

    UPS tests

    reference only

    Characteristic of equipment Units and/or

    informations

    Manufacturer's declared

    values

    Minimum performance

    requirements, methods and references

    Construction

    Model catalogue reference

    (manufacturers reference)

    MGE Galaxy 300

    Three Phases In Three

    Phases Out UPS

    10/20/30/40kVA

    &

    MGE Galaxy 300

    Three Phases In one Phase

    Out UPS 10/20/30kVA

    Model

    Power, rated

    VA ou W

    Apparent -

    Active

    With Cos=0,8

    10kVA 8kW

    15kVA 12kW

    20kVA 16kW

    30kVA 24kW

    40kVA 32kW

    MGE Galaxy 300 UPS Unitary or Parallel 10kVA

    MGE Galaxy 300 UPS Unitary or Parallel 15kVA

    MGE Galaxy 300 UPS Unitary or Parallel 20kVA

    MGE Galaxy 300 UPS Unitary or Parallel 30kVA

    MGE Galaxy 300 UPS Unitary or Parallel 40kVA

    5.1.1 UPS Configuration

    Topology Double conversion with

    Bypass

    5.3.4 Classification of UPS by performance VFI SS 113

    Mechanical

    Dimensions (Height x Width x Depth) mm See separate declaration

    (Paragraphe 1)

    If details, to specify them in the separate declaration

    Mass or Weight kg See separate declaration

    (Paragraphe 1)

    If details, to specify them in the separate declaration

    Mass or Weight with batteries (if

    integrated)

    kg See separate declaration

    (Paragraphe 1)

    6.5.5

    Acoustic noise at 1m

    - Normal mode

    - Stored energy mode

    dBA

    dBA

    56dBA

    56dBA

    Measurements in accordance with standard

    ISO 7779 (0,15m < d < 8m according to dimensions of

    the source of noise, with ,preference 1m).

    Safety

    Access (operator access or restricted

    access)

    Restricted Access

    IEC 62040-1 Degree of protection against hazards and

    water ingress

    IP IP 20 In accordance with IEC 60529

    IP XX first X (/ foreign body) 2nd X (/ water)

  • APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09

    3

    UPS tests

    reference only

    Characteristic of equipment Units and/or

    informations

    Manufacturer's declared

    values

    Minimum performance

    requirements, methods and references

    Electromagnetic Compatibility

    Emission UPS Cat UPS category C3

    See separate declaration

    (paragraph 6)

    CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-

    2: 2005

    - Immunity to electrostatic discharges

    - Immunity to radiated IEC 62040-2

    Immunity UPS Cat UPS category C3

    See separate declaration

    (paragraph 6)

    - conducted a.c mains

    - conducted a.c output

    - Radiated - electric field

    - Radiated - magnetic field

    Environmental

    4.2.1.1

    Ambient storage temperature range C -10 C to +60 C

    -15 C to +40 C

    T specified, equipment without batteries

    For Altitude < 1000m and moisture 20 to 95%

    T specified, for Batteries

    Ambient service temperature C 0 C to +35 C

    0 C to + 25C

    Continuous maximum ambient service temperature

    at rated Current, Cos=0,8

    Continuous maximum ambient service temperature

    with Battery inside the Unit

    4.2.1.2

    Maximun service altitude m 1000m and

    P = nP 10% all the 1000m

    Until 1000m included

    For 1500 to 5000m, coefficient of downgrading from

    0,85 to 0,59

    4.1.3

    Relative humidity range % Storage : 0% to 90%

    Operation : 05% to 90%

    ( without condensation )

    Relative humidity without condensing at ambient

    temperature

    5.6 Communication circuits

    4.2.1.1 (List communication / signalling circuits) See separate declaration

    (paragraph 5)

    Electrical characteristics - Input

    5.2.1.a

    Voltage (steady-state, r.m.s)

    - rated

    V 220V or 230V or 240V

    380V or 400V or 415V

    Nominal value of input voltage, and thresholds of

    passage in stored energy mode by input voltage

    exceeding the tolerance

    To specify : if there is no a change of mode to

    stored energy mode by U + 10% or if the thresholds

    depend on the load use

    Minimal value of input votage allowing the refill

    battery during normal operation UPS

    5.2.1.b - tolerance % 2%

    5.2.1.c

    Frequency

    - rated

    Hz 50Hz or 60Hz Nominal value of input frequency and thresholds of

    a change of mode to stored energy mode of the

    UPS, by input frequency exceeding the tolerance

    If it there not a change of mode to stored energy

    mode, to specify the minimum and maximum

    frequency possible for the UPS

    5.2.1.d - tolerance % 10% (45 to 65Hz)

  • APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09

    4

    UPS tests

    reference only

    Characteristic of equipment Units and/or

    informations

    Manufacturer's declared

    values

    Minimum performance

    requirements, methods and references

    5.2.2.c

    Current r.m.s.

    rated (with the energy storage device

    charged)

    A 13A / (10kVA)

    20A / (15kVA)

    26A / (20kVA)

    40A / (30kVA)

    53A / (40kVA)

    Input steady current with ,100% rated VA and W, on

    linear and non linear load

    5.2.2.f

    maximum (with low input volt and energy

    storage device charging)

    A 16A / (10kVA)

    23A / (15kVA)

    29A / (20kVA)

    42A / (30kVA)

    56A / (40kVA)

    5.2.2.h - total harmonic distortion (THD p.u.) % 50% rated VA and W on linear

    load and non linear load

    5.2.2.k AC power distribution system

    -(TN, TT, IT) compatibility

    TT, TN (S or C), IT

    5.2.2.i - short-circuit power required Ssc See separate declaration

    (paragraph 2)

    5.2.2.a - phases required (1,2 or 3) Tree Phases 3P+N+G

    5.2.2.b - neutral required (yes / no) Yes

    5.2.3 Additional or unusual conditions NA

    Output waveform

    5.3.1.2

    5.3.1.2

    Waveform - Normal mode

    Waveform - Stores energy mode

    Sinusoidal

    Sinusoidal

    Sinusoidal or non sinusoidal

    Sinusoidal or non sinusoidal

    Transfer - Normal mode / Stored energy Break

    No break

    No Break

    Complies with figure 1

    Break time / Make time ( if applicable ) ms

    On battery

    mode

    Without Break

    Rated voltage 2% with a come

    back to 1% in 100ms

    Transfer transients and times measured at the time of

    tranfer load from UPS to an alternative source and

    return, by command or defect of switches of coupling

    and bypass

  • APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09

    5

    UPS tests

    reference only

    Characteristic of equipment Units and/or

    informations

    Manufacturer's declared

    values

    Minimum performance

    requirements, methods and references

    Electrical output characteristics - Static and Dyn amic characteristics - Normal mode

    5.3.2 AC power distribution system

    - compatibility (TN, TT, IT) TT, TN (S or C), IT

    - phases available (1,2 or 3) One Phase 1P+N+G

    Or Tree Phases 3P+N+G

    - neutral available (yes / no) Yes

    Voltage (steady state, r.m.s.)

    Rated Output voltage V r.m.s 220V, 230V, 240V default value

    for One phase

    380V, 400V, 415V default value

    for Tree phases

    Operation at 415 VAC/60 Hz is not possible

    Output voltage normal mode variation % Rated voltage 2% adjustable Output voltage measured at the two ends of the

    range of rated power factor and with nominal rated

    votage

    Voltage variation = maximum and minimum

    measured value

    Stored energy mode variation % 2%

    Rated output apparent power VA 10kVA

    15kVA

    20kVA

    30kVA

    40kVA

    Rated output active power across a

    linear load

    W

    8kW

    12kW

    16kW

    24kW

    32kW

    Rated output active power across a

    reference non linear load

    W

    Same as linear load

    Total voltage distortion across a linear load %

  • APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09

    6

    UPS tests

    reference only

    Characteristic of equipment Units and/or

    informations

    Manufacturer's declared

    values

    Minimum performance

    requirements, methods and references

    - linear %, s Complies curve 1 with IEC

    62040-3

    - Non-linear %, s Complies curve 3 with IEC

    62040-3

    6.4.2.11.1/2 - transfer normal mode / storage energy

    mode

    %, s Complies curve 1with IEC

    62040-3

    To note Fig 1, 2 or 3 and specified UPS

    Performance with nominal power W a