dropgate installation manual -...
TRANSCRIPT
OVERVIEW
Each drop gate consists of two sides – a master and a slave. They are to be installed as opposites of each
other. Part of the system flexibility is you can choose which side is which by simply installing the logic
control on the preferred side. We then refer to that side as the “master” and the opposite side as the
“slave”.
Each drop gate kit comes with the following components –
Two drop gate units complete. (Soon to be named master and slave)
Once manufactured to size cable.
One top cover pressing.
One logic control board in weather enclosure.
One connecting motor cable.
Optional components that may be included -
Safety cable cover.
Bolt down cable protector.
Safety photocells.
Access, egress and/or safety loop detectors.
Access control equipment.
Access control mounting bollards.
Traffic signal lights.
This manual covers the installation and layout of the standard Drop Gate components but does not cover
installation or layout of optional components. Most optional components are site specific and installations
of these are covered in detail in manuals supplied with those items. Design and layout we are happy to
assist with. Please contact your local Automatic Solutions branch or email -
IMPORTANT
It is important to plan and prewire any parts of the installation before installation including access control
and safety items, however we strongly advise that you install the Drop Gate as described in this manual
without connecting additional components such as access control and/or safety components.
Good installation practice is to install and program the Drop Gate to a point of completion before adding
other components. Then add each component one at a time testing the operation of each and it’s desired
affect before moving on to the next component.
This manual covers the installation and programming of the Drop Gate only but will offer general advice on
typical additional components.
PREWIRE
Both bases have conduit access holes in the centre of each base. This point is 275mm from the side edge of
your Drop Gate. The Drop Gate base is 344mm x 544mm. If you mark the opening width and then each
Drop Gate base the conduit entry point is 275mm from the side edge (Fig 1).
Fig 1
Before prewire you need to decide which side will be your master and which will be the slave. The master
is generally the side where your power will come in to the logic control board. This is normally also the side
that you will bring your access control cables and safety cables to terminate
Do not run mains powered cables in the same conduits as low voltage cables. As most of the system
however is low voltage it is permissible to run master to slave motor cables in the same conduit as safety
cables meaning only one conduit or cable run is required between the two Drop Gate units.
GENERAL LAYOUT
The Drop Gate needs to be securely anchored to a concrete hardstand at either end as the general
operation of the gate will exert significant pressure on each drop gate unit. There are a number of ways
this can be achieved with the two most common depicted below.
Fig 2 Example: Two concrete plinths are installed with conduits for power and master / slave function.
Fig 3 Existing hardstand (driveway). Use a combination of conduits and cable protector for wiring.
BOLT DOWN THE DROP GATE MASTER AND SLAVE
Remove the four top cover screws from each of the Drop Gate units and remove the top caps and external
sleeves from each unit. Place the caps and covers safely out of the way for now.
Position each unit to face each other in the approximate position on your hardstand area. Release each
Drop Gate cable lever by screwing the manual release bolt in until it comes to a stop. Now lift each lever to
about the half way point and attach one end of your cable using the provided shackle (Fig 4).
Fig 4
When your cable is attached at each end lower both cable levers until the lever comes to a hard stop on
the Drop Gate base (Fig 5) and lock the levers in place by turning the manual release bolts anti clockwise
until loose and the levers lock in.
Fig 5
Next complete positioning of each Drop Gate unit by manoeuvring the units so that the cable sits naturally
on the ground. Now check the layout to ensure that the drop gate units are aligned and in position where
you require them and that you’re cabling layout does not require further work (Fig 6).
Fig 6
Each Drop Gate unit has anchor holes pre drilled. Use these to mark your anchor points. Drill and use a
suitable anchor to secure each Drop gate unit to the hardstand.
INSTALL THE LOGIC CONTROL
Individual choice determines where you install the logic control but it must be either A) in the master unit
(Fig 7) or B) directly beside the master unit if housed separately. When using solar power it may be
preferable to install the logic control in a separate enclosure with the battery or a separate enclosure may
be desired if a large number of access control or safety cables are to be used.
Fig 7
Once the logic control is secured you can now connect each Drop Gate motor cable to the logic control
board at terminals 19, 20 and 21, 22. It does not matter which motor you connect to motor 1- terminal 19
and 20 or motor 2- terminals 21 and 22. What is important is that you maintain polarity. That is connecting
red to red and black to black at the motors. At the control board connect black to 19 and red to 20 from
one motor and black to 21 and red to 22 from the other motor.
Ensure that J1 is set to 12 volt. For the moment ensure that terminals 5&6 and 5&7 as well as terminals
11&12 all have loops (short lengths of wire) to close the safety inputs.
Connect the red and the black wires from the transformer to FS3 (Black Negative Wire) and FS4 (Red
Positive Wire). Connect mains power to the transformer.
PROGRAM THE LOGIC CONTROL
Basic programming is simply a matter of pressing the enter key (TS2) for one second whilst advanced
programming you need to hold enter for four seconds. Once inside any menu use the up (TS1) and down
(TS3) buttons to scroll options and the enter key to enter or accept an option.
You need to check a few settings before programming work times. Press and hold TS2 (Enter) for about 4
seconds until “Tn” appears. Release and press once and “T1” appear. Now use TS1 or TS2 to scroll until you
get to “DO” or “DC”. At either and eventually both we need to use TS2 to enter this parameter and if any
other value other than “00” is shown use the TS1 or TS3 to adjust the value to “00” and then TS2 to enter.
Once both “DO” and “DC” is set to zero you can use the TS1 or TS3 to scroll to “Eh” then use TS2 to exit.
Before programing work times ensure the cable is on the ground and both levers are resting at the bottom.
Also make sure manual override is completely disengaged. Finally gently turn TR2 the obstruction trimmer
fully clockwise. Locate programming button TS1 (UP). Press and hold until “Au” appears – release. The
Drop Gate will perform several tests and then it will learn working times. When it is finished the LED light
will go out.
WHAT’S NEXT?
When programming work times the unit adds a few seconds to the run time so when you run the drop gate
you might feel that the overrun is excessive. You can adjust these in advanced programming by going to
“T1” and “T2” and reducing the entry by a couple of seconds, exit, test and adjust further if necessary.
To complete the installation of the Drop Gate you would now slide each cover sleeve in place and secure
the tops with the caps but the reality is that you are now ready to add one by one your access control and
safety devices.
On the following pages you will find hints and notes on everything from solar power to input connections
as well as the full manual.
USING SOLAR POWER
The Drop Gate and ID200 will both easily adapt to solar power. Configuration should be solar panel to
regulator – regulator to battery – battery to logic control board (Do not go from regulator to the control
board). Negative to FS3 and Positive to FS4.
AUTOMATIC CLOSE
Most Drop Gate installations will want to use automatic closing. This needs to be enables in programming
along with setting the pause time to wait before closing. Press and release TS2 (Enter) and “oL” should
appear. This is where you set the operating logic. Press and release TS2 again and you will see “St”. Use TS3
(Down) to cycle through the choices but normally you will want “cd”. When you reach “cd” press and
release TS2 to enter your choice. Next use TS3 once and you should see “EH” (Exit). Press and release TS2
to exit and you should find yourself back at “oL”.
PAUSE TIME
Press TS3 a few times until you get to “SP” – press and release TS2 to enter and you should see “10” (or
any previously entered time). The 10 represents ten seconds pause time. Use the UP and DOWN (TS1 and
TS3) to arrive at the desired pause time (0 to 99 seconds) then press and release TS2 to enter. Press TS3
once to “EH” and press and release TS2 to exit.
EXIT PROGRAMMING
Use TS3 until you reach “EH” and then TS2 to exit.
ACCESS CONTROL INPUTS
Access control inputs must be dry contact and normally open connected to terminals 3&5 on the logic
control board. They should be a momentary close to activate.
SAFETY INPUTS
Safety devices like photocells and vehicle loops need to be normally closed dry contacts connected to
terminals 7&5 on the logic control board. Jumper J2 must be removed when using this input.
Technical characteristics
Power Supply 12-20Vac/100-200VA
Max current out (14-15) 250mA
Embedded battery charger 12-24V, 100mA
Max. motor current 8A (200VA transformer)
Max. flashing light current 1A
Electric-Lock current 2A
Operating temperature range -5 +60°C
Backup battery (2x) 12V 4,5Ah
1 Antenna
2 Antenna’s shield
3 Start input (NO) It completely opens the gate
4 Pedestrian start in. (NO)
It opens just motor 2
5 Common
6 Photocell input (NC)
During pause: Reloads pause
During closing: Reverses motors direction
7 Photostop input (NC)
During pause: Reloads pause
During closing: Reverses motors direction
During opening: stops the motors and waits till contact returns close.
8 Analog opening edge input (8K2 ohm)
Waiting an opening command: inhibits opening
During opening: reverses motor direction for 1 second.
If not used left unconnected.
9 Analog closing edge input (8K2 ohm)
Waiting a closing command: inhibits closing
During closing: reverses motor direction for 1 second
If not used left unconnected.
10 Common
11 Stop input (NC)
It always stops motors and blocks control unit activity.
12 Common
13-14 Poter supply output
12Vdc 250mA
15-16 Electric lock output
17-18 Flashing light output
12/24V 1A
19-20 Output motor 1 - 8A
21-22 Output motor 2 - 8A
TR1 Slowing down speed trimmer
TR2 Obstacle detection sensibility trimmer
TS1-TS3 Buttons up/down
TS2 Enter button
DSP Display
FS3 – FS4 Transformer input 12-20Vac / 100-200VA
F2 Battery fuse 10A Fast
FS1 – FS2 Backup battery input 12/24Vdc
JP1 Backup battery voltage selector 12/24V
J1 Photocell exclusion jumper
J2 Photostop exclusion jumper
J3 Stop exclusion jumper
DSP Display
CN7 Power supply input 230Vac
F1 230Vac outputs fuse, 5A Fast
F2 Electric-lock/logic fuse, 2A Fast
INPUT STATUS
When the control unit is waiting for an opening or closing cycle, or when it's in pause, status of inputs is displayed as following diagram.
In 3-5 Start / Pedestrian
In 6 Photocells
In 7 Photostop
In 9 closing edge
In 8 Opening edge
In 12 STOP
programming
TRIMMER REGULATIONS
TR1 The slow down speed trimmer regulates the slow down speed. Do not set speed to low (less than 10cm/sec on
the wing edge) to avoid that gate stops in too cold conditions.
TR2 The obstacle sensibility trimmer fine tunes the obstacle detection level learned by the control unit during
working times programming. This fine regulation must be do after working times learning. Normally the trimmer goes in the center, in this position should be possible to respect rules in most of installations.
If it's need to resolve problems related to norms or to environmental situations (ex. strong wind) is it possible to
regulate this trimmer increasing or decreasing sensibility.
Less speedy
More speedy
TR1 Slow down speed
Less pushing
More pushing
TR2 Obstacle sensibility
QUICK INSTALLATION
To program quickly the working times, open both wings , then keep pushed up till you read AU on the display.
The control unit will do several tests an than it'll learn working times. When the procedure is finish the blinker goes
off.
TRANSMITTERS AUTO LEARNING: It's possible to learn transmitters quickly without using the base menu. To insert a new transmitter transmit 3 times
with the new remote, making at least 1 second pause between each transmission. Than transmitt 3 times with a
transmitter already in memory and then once with the new. When programmation is done, the blinker flash once.
Attention: function must be enabled, refer to “advanced menu” - auto learning transmitters. The new code
takes the same channel as the one used to insert it.
BOARD PROGRAMMING
BASE MENU
Push enter 1 for at least 1 sec. to enter base menu.
oL is on the display, with up/down it's possible to select other functions
of this menu.
To exit this menu select exit (EX) or push up and down together.
After 2 minutes without actions, the control unit exits itself from this
menu.
UP ENTER DOWN
SCHEMA MENU DI BASE BAS MENU MAP
1 SEC.
oL Operating logic
5T Step by step logic.
At Automatic closing with stop
funcion.
CD Automatic closing for condominium function.
EX EXIT or push together
LC Learns radio codes
C1 Learn a transmitter on channel 1
C2 Learn a transmitter on channel 2
rt Delete a code with transmitter*
EX EXIT or push together
LC Learning / removing transmitters code:
Select learning code function LC and push enter, than select one of following functions with up/down.
C1: learn a transmitter on channel 1
C2: learn a transmitter on channel 2
Rt: Delete all transmitters in memory.
See tab operating logics for further informations.
Once selected the channel transmitt the code, on the display is show “OK” for a while if operation is done.
- To replace the channel of a code, just select desired channel and transmitt once the same code.
- To delete just one code, select RT and transmitt the code to be removed, on the display is show “OK” for
a while if operation is done.
- To delete all codes, select RT and push enter, then confirm with YS.
To exit this menu select EX or push up/down together.
LT Learn working times
AU Automatic learning procedure.
MN Manual learning procedure.
EX EXIT or push together
LT learn working time:
Attention: before to start leaning procedure, the gate must be open to do automatic procedure,
otherwise must be closed to do the manual procedure. Use “dead man” function to put the gate in the right
position.
Is it possible to program working time automatically, please refer to “Quick installation”.
Select LT in the base menu and push enter, after select the learning mode with up/down.
AU: Automatic learning procedure.
MN: Manual learning procedure.
To exit this menu select EX or push up/down together.
AU Automatic procedure for working time learning:
Attention: in this procedure all safety inputs are disabled.
The wings close themselves, in the meanwhile all the working times and values for obstacle detection sensor
are learned. If just motor 2 is connected, the control unit sets itself for “single wing working. If analogue
edges are connected, they are automatically enabled. MN Manual procedure for working time learning:
Attention: to do this procedure prepare at least a transmitter into memory. In this procedure all safety
inputs are disabled.
Both wings start opening, in this phase it's possible to set the slowing down speed with the trimmer. Once
both wings are open, push once enter or transmit with remote. The control unit makes some test of motor
consumption to set the threshold for the obstacle detection sensor.
Once the test is finish, you can see M1 on the display.
In the phase which follows, enter button or a memorized code control following sequence: start motor 1,
start motor 2, slow down motor 1, slow down motor 2, stop motor 1, stop motor 2.
If just motor 2 is connected (single wing mode), program times just for this motor.
5P Set pause time
0 – 99
EX push together
5P Set pause time:
Use up/down to set the pause time between 0 and 99 seconds. Push enter to confirm. To exit without
modifications push together up and down.
Attention, setting a pause time doesn't enables automatic closing, please refer to chapter “OL operating
logic” to enable this function.
DM Dead man mode
O1 Open motor 1
C1 Close motor 1
O2 Open motor 2
C2 Close motor 2
EX EXIT or push together
DM Dead man mode:
Selecting this menu it's possible to control each motor in dead man mode. Push up and down to select one of
following item:
O1 Open motor 1
C1 Close motor 1
O2 Open motor 2
C2 Close motor 2
EX Exit - Keep pushed enter to start the selected motor in dead man mode.
EX Exit
BOARD PROGRAMMING ADVANCED MENU
Push enter button till on the display is shown TM. With up/down it's possible to select all items in this menu.
To exit this menu select EX or push up/down together. After 2 minutes without actions, control unit exits itself from
this menu.
ADVANCED MENU MAP
4 SEC.
TM Working times menu
T1 Working time motor 1
0 –
99
51 Start time slowdown
motor 1
T2 Working time motor 2
52 Start time slowdown
motor 2
DO Motors delay opening
DC Motors delay closing
TC Courtesy light time
x10sec.
TL Electric lock activation
time
EX EXIT or push together
5G Single gate mode
YS Single wing YES
NT Single wing NOT
EX EXIT or push together
5G Single wing mode: In this menu it's possible to verify or set if gate works in single wing mode (motor2)
D2 Loads factory defaults
YS sets the control unit at factory
defaults.
NT Maintain settled parameters
EX EXIT or push together
RC Release end travel
torque
YS Enable release end travel torque
NT Disable release end travel torque
EX EXIT or push together
RC Release torque at work end: Enabling this function, the motors reverse direction for a while to release the torque at end of work.
Eo Analogue edge in
opening
YS Enable
NT Disable
EX EXIT or push together
Eo Enabling this function it's enabled the edge active in opening period
Ec Analogue edge in
closing
YS Enable
NT Disable
EX EXIT or push together
Ec Enabling this function it's enabled the edge active in opening period
Ar Transmitters auto
learning
YS Enable
NT Disable
EX EXIT or push together
Ar Enable automatic transmitters leaning:
Enabling this function it's possible to insert new transmitters without accessing base menu. Refer to
“Automatic transmitters learning”.
LP Low power mode
YS Enable
NT Disable
EX EXIT or push together
LP Enable low power mode:
In this menu you can enable the low power mode.
Attention: when this function is enabled, the display is not longer showing input status (Display off in
stand-by).
C5 Kickback stroke
YS Enable
NT Disable
EX EXIT or push together
C5 Enable kickback stroke:
In this menu you can enable the stroke at start to unlock electric lock and the final stroke to lock it.
EX Exit
QUICK TABLE BASE MENU
DISPLAY DESCRIZIONE DESCRIPTION
DATI DATA
DESCRIZIONE2 DESCRIPTION
DATI DATA
Descr
oL Operating logic
St Step by step
At Automatic closing with stop
funcion.
cd Automatic closing
uninterruptible CONDOMINIUM
EH EXIT
-
Lc Learning / removing
transmitters code
c1 Learn a transmitter on channel
1
c2 Learn a transmitter on channel
2
rt Erase codes YS Erase all
codes
EH Uscita
-
Lt
Learn working time
Au Automatic learning procedure
Mn Mutomatic learning procedure
EH EXIT
-
SP Set pause time ' '' '' '' '
0 -99 -
dM Dead man mode
o1 Open motor 1
c1 Close motor 1
o2 Open motor 2
c2 Close motor 2
EH EXIT
-
EH EXIT
QUICK TABLE ADVANCED MENU
DISPLAY DESCRIPTION DATA DESCRIPTION
tM Working times menu
t1 Working time motor1
0' '' '' '' '
-99
S1 Start time slowdown motor1
t2 Working time motor2
S2 Start time slowdown motor2
do Motors delay opening
dc Motors delay closing
tL Electric lock activation time
EH EXIT
-
SG Single wing mode
yS Yes
nt No
EH Exit
-
d2 Default settings
yS Yes
nt No
EH EXIT
-
rc Release torque at work end
yS Yes
nt No
EH EXIT
-
Eo Analogue edge in opening
yS Yes
nt No
EH EXIT
-
Ec Analogue edge in closing
yS Yes
nt No
EH EXIT
-
Ar Transmitters auto learning
yS Yes
nt No
EH EXIT
LP Low power mode
yS Yes
nt No
EH EXIT
-
C5 Kickback stroke yS Yes
nt No
EH EXIT
-
EH EXIT
5T STEP BY STEP MODE
PHASE COMMAND
START PEDESTRIAN PHOTOCELL FOTOSTOP EDGE
OPENING
EDGE
CLOSING
STOP
CLOSED Opens Opens Ignored Stops Stops Ignored Stop
OPENING Stops Stops Ignored Stops
and wait
release
Reverses
1sec.
Ignored
OPEN Closes Closes Ignored Stops Ignored Stops
CLOSING Stops Stops Reverses Reverses Ignored Reverses
1sec.
STOP Ignored Ignored Ignored Ignored Ignored Ignored -
AT AUTOMATIC CLOSING MODE
PHASE COMMAND
START PEDESTRIAN PHOTOCELL FOTOSTOP EDGE
OPENING
EDGE
CLOSING
STOP
CLOSED Opens Opens Ignored Stops Stops Ignored Stop
OPENING Stops Stops Ignored Stops
and waits
release
Reverses
1sec.
Ignored
OPEN Closes Closes Ignored Stops Ignored Stops
DURING
PAUSE
Exits
pause
Exits pause Reloads time Reloads
time
Ignored Reloads
time
CLOSING Stops Stops Reverses Reverses Ignored Reverses
STOP Ignored Ignored Ignored Ignored Ignored Ignored -
cd CONDOMINIUM MODE
PHASE COMMAND
START PEDESTRIAN PHOTOCELL FOTOSTOP EDGE
OPENING
EDGE
CLOSING
STOP
CLOSED Opens Opens Ignored Stops Stops Ignored Stop
OPENING Ignored Ignored Ignored Stops and
wait release
Reverses
1sec.
Ignored
OPEN Ignored Ignored Ignored Stops Ignored Stops
DURING
PAUSE
Reloads
time
Reloads
time
Reloads
time
Reloads
time
Ignored Reloads
time
CLOSING Ignored Ignored Reverses Reverses Ignored Reverses 1sec.
STOP Ignored Ignored Ignored Ignored Ignored Ignored -
Default settings
Here it follows list of default settings, the same set after a D2 command of advanced menu
Item Default
Ol Operating logic 5t Step by step
5p Pause time 10 10 seconds
T1 -t2 Working time motor 1 and 2 30 30 seconds
51- 52 Slowing down time motor 1 20 20 seconds
Do Wings delay opening 02 2 seconds
Dc Wings delay closing 05 5 seconds
Tc Courtesy light time 12 120 seconds
Tl Electric-lock time 02 2 seconds
5g Single gate mode Nt Not
Eo Analogue edge in opening Nt Not
Ec Analogue edge in closing Nt Not
Lp Low power mode Nt Not
C5 Kickback stroke Nt Not
Diagnostic and troubleshooting The control unit has a self diagnostic software able to find problems. Once a problem occurs, a code is shown on the
display in alternance with command status.
Here it follows a troubleshooting table.
Error code Problem and eventual solution
E1 Mains power fails, system is running with backup battery.
Verify mains switch and life switch. Verify fuse on transformer (fuse holder)
E2 Obstacle detected in the previous cycle.
Verify that gate is free and there's no obstacles in the range.
Verify gate wings aren't blocked.
E3
Photocells or photostop obstructed for longer than 2 minutes. The gate can't start moving
and the blinker could be fixed on.
Verify that photocells and photostop aren't obstructed, and if there's no bugs inside them.
Verify wiring to this devices.
E4 One of the analog edge is engaged for longer than 2 minutes. Verify edges aren't engaged, verify wiring to this devices. If no edge installed, disable them
in the advanced menu
E5 Stop is engaged for longer than 2 minutes.
Verify wiring to emergency device. If there isn't an emergency device installed, shunt this input with the common.
E6 Problem on motor 1.
Verify connections to the motor, verify motor can work in dead man mode
E7 Problem on motor 2. Verify connections to the motor, verify motor can work in dead man mode.