![Page 1: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/1.jpg)
Duration Addition to electricitY Storage (DAYS)
Scott Litzelman, Ph.D.
Program DirectorAdvanced Research Projects Agency – Energy (ARPA-E)
The why and how of long-duration energy storage
![Page 2: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/2.jpg)
What’s needed to enable LDES
‣Technology proven to be cheap and reliable
‣Applications (duty cycles)
‣Niche / entry markets
‣Policy drivers
1
![Page 3: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/3.jpg)
Objectives of this meeting
‣ Introduce the DAYS projects
‣Learn what’s happening from external stakeholders
‣Discuss potential early applications and requirements
‣Start building a LDES community
2
![Page 4: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/4.jpg)
Who’s here: DAYS, IONICS awardees
3
IONICS
![Page 5: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/5.jpg)
Who’s here: external stakeholders
4
![Page 6: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/6.jpg)
Outline
‣A brief overview of DAYS
‣Potential early applications
5
![Page 7: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/7.jpg)
Grid-Scale Storage Applications Today
6
Joe Eto, LBL
Frequency regulation Energy shifting
CODA Energy
Demand charge management
Distribution upgrade deferral
Flexible ramping
Reserves Power qualityExamples of other applications:
![Page 8: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/8.jpg)
7
To make the availability of this:
Dispatching variable (and uncertain) renewables
Look more like this:
Vox.com IEA
What will it take…
![Page 9: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/9.jpg)
Example: variability of wind in Texas
8
2016 wind output in Texas (GW)
Hour of the year
1-hour time blocks
![Page 10: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/10.jpg)
9
2016 wind output in Texas (GW)
Hour of the year
8-hour time blocks
Example: variability of wind in Texas
![Page 11: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/11.jpg)
10
2016 wind output in Texas (GW)
Hour of the year
72-hour time blocks
Example: variability of wind in Texas
![Page 12: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/12.jpg)
11
2016 wind output in Texas (GW)
Hour of the year
168-hour time blocks
Example: variability of wind in Texas
![Page 13: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/13.jpg)
Another viewpoint: integrating renewables with the grid
‣Wood Mackenzie report on 2019 polar vortex
‣ Examined grid conditions if capacity was 50% solar and 50% wind
‣ For solar to provide relief for low wind: 18-40 hours of storage
12Related presentations: Tim Grejtak (Lux Research) and Lon Huber (Navigant)
https://pv-magazine-usa.com/2019/02/12/wood-mackenzie-looks-at-the-polar-vortex-and-100-renewable-energy/
![Page 14: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/14.jpg)
Digging deeper: levelized cost of storage (LCOS)
13
!"#$ $ & '(ℎ*+ & ,-,./*+ = 12345
− 1 789:;+
4 <8(>)1 + A : +9
:;+
4 #&C(>)1 + A : +
"52D
+ "EF ∗ 9:;+
4 <8 >1 + A :
*+
Primarily technology-dependent parameters• ηRTE – round-trip efficiency of storage (AC basis)
• ηD – discharge efficiency of storage (AC basis)
• O&M – fixed and variable operations and maintenance cost (including component replacements)
• CE – installed marginal capital cost of energy in $/kWh
• CP – installed marginal capital cost of power in $/kW
Primarily application-dependent parameters• PC – input electricity price in $/kWh
• d – duration of storage at rated power in hours
• nC – number of equivalent full cycles
![Page 15: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/15.jpg)
Impact of capex for power and for energy
14
![Page 16: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/16.jpg)
The DAYS cost target
15
Input (charge) 1 kWh at 2.5 ¢ / kWh
Levelized cost per-cycle of efficiency loss
Sell (discharge) 1 kWh at 7.5 ¢ / kWh
LCOS: Levelized Cost of Storage per cycle
Levelized cost per-cycle of O&M
Installed cost per-cycle of storage system capital
Target: 5 ¢ / kWh-cycle for durations of 10 to ~100 h
Capital discounted at 10% over project life (20 years).
Charge/discharge prices are rough estimates; not market projections
![Page 17: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/17.jpg)
DAYS cost-duration target
16
![Page 18: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/18.jpg)
The DAYS innovations
‣ Fluidized bed heat exchanger
‣ Thermochemical Mg-Mn-O bed
‣ Reversible turbomachine
‣ Full loop controls system
‣ Supercritical CO2 cycle
17
‣ Elastic strain in underground rocks
‣ Aqueous sulfur
‣ Zr-Br2 membrane-less, single tank
‣ Reversible fuel cell for H2O2
‣ Sulfur-manganese flow battery
‣ High efficiency, stable over time
Thermal
Geomechanical
Electrochemical
Thermophotovoltaic
![Page 19: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/19.jpg)
Outline
‣A brief overview of DAYS
‣Potential early applications
18
![Page 20: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/20.jpg)
Islands and remote areas
‣ No contiguous grid
‣ Rural electricity: $0.60-$1.20/kWh
‣ Lots of renewable resources, including RoR hydro and pumped hydro
‣ Large seasonal variations
‣ Consisting diesel genset alternatives
19Related presentation: Vladimir Shvets (Hawaiian Electric Co.)
http://acep.uaf.edu/media/158027/Microgrids-6-26-15.pdf
![Page 21: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/21.jpg)
Transmission and distribution projects
‣ Utilities pursuing “non-wires” deferral projects
‣ Current RFP for Orange & Rockland Utilities– System reliability and load relief– 17 MW of load relief for 24 hours– Traditional solution: upgrade to two 35 MVA
transformers
20Related presentations: Jason Burwen (Energy Storage Association), Matt Arnold (Enel Green Power)
Fish and Wildlife Service
“D”
“T”
https://www.utilitydive.com/news/brattle-electrification-could-drive-600b-in-transmission-spending-by-2050/550010/
![Page 22: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/22.jpg)
Data centers, critical infrastructure
‣ Data traffic is doubling every 2-3 years
‣ Data centers today consume 200 TWh
worldwide
‣ By 2030: 8% of global electricity demand
‣ 45% of data centers are in the U.S.
‣ Backup power now: uninterruptible power
supply, diesel generators
21https://www.pjm.com/-/media/about-pjm/exploring-tomorrows-grid/advanced-tech.ashx
Synergy Research, 2017
Could long-duration storage replace diesel gensets
at critical sites such as data centers?
![Page 23: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/23.jpg)
Thinking about duty cycles
‣ Univ. of WA study: 11% decrease in annual energy bill from peak shaving
‣ Additional revenue from frequency regulation
‣ Microsoft: worked with PJM and Eaton on frequency regulation with a data center
22
Y. Shi, et al., IEEE Trans. Power Sys. 33, 2882-2894 (2017)
What’s the duty cycle for a long-duration system?
![Page 24: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/24.jpg)
Long-duration storage is an enabling technology
23https://storage.googleapis.com/gweb-sustainability.appspot.com/pdf/24x7-carbon-free-energy-data-centers.pdf
![Page 25: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/25.jpg)
Summary
‣ The onus right now is on the technology community (us)
‣ There are entry markets
‣ Longer-term picture: unclear, but policy will follow technology
24
![Page 26: Duration Addition to electricitY Storage (DAYS) · Synergy Research, 2017 Could long-duration storage replace diesel gensets at critical sites such as data centers? ... Gokul Vishwanathan](https://reader036.vdocument.in/reader036/viewer/2022071219/60553dc0dc9ed159e56b561f/html5/thumbnails/26.jpg)
Acknowledgements
25
Meeting PlannerNancy Hicks
Programmatic SupportErin Gilley
Alex Menzies
Technical Support
Rusty Heffner
Vivien Lecoustre
Sean Vail
Gokul Vishwanathan
Paul Albertus
Joe Manser
Tech-to-MarketMax Tuttman
The Brains Behind DAYS