ECOSMART GISMedium Voltage Gas Insulated Switchgear for Secondary Distribution
-
A Company Attuned To Your Needs
ECOSMART GIS is a medium voltage gas insulated switchgear that offers a loss of service continuity type LSC2. Because service continuity, long life performance and safety are paramount, the ECOSMART GIS series is fully developed and type tested according to the IEC standards 62271-200.
The health and safety management system complies with the OHSAS 18001 standards and is certified by a third party. The internal test laboratory complies with UNI CEI EN ISO/IEC 17025 with tests certified by a third party.
Driven by environmental sustainability, the materials used for the production of the ECOSMART GIS series provide a low environmental impact during the product life cycle.
The ECOSMART GIS series is composed of gas insulated Ring Main Units (RMUs) developed and manufactured in accordance with the following standards:
• IEC 62271 - 200 High-voltage switchgear and control gear - Part 200: AC metal-enclosed switchgear and control gear for rated voltages above 1kV and up to 52kV
• IEC 62271 - 100 High-voltage switchgear and control gear - Part 100: Alternating-current circuit-breakers
• IEC 62271 - 102 High-voltage switchgear and control gear - Part 102: Alternating current disconnectors and earthing switches
• IEC 62271 - 103 High-voltage switchgear and control gear - Part 103: Switches for rated voltages above 1kV up to 52kV
• IEC 62271 - 105 High-voltage switchgear and control gear - Part 105: Alternating current switch-fuse combinations for rated voltages above 1kV up to 52kV
• IEC 60255 - Measuring relays and protection equipment - Part 1: Common requirements
• IEC 60529 - Degrees of protection provided by enclosures (IP Code)
The ECOSMART GIS production site and the environmental management system assumed by G&W Electric is in compliance with the standard quality rules of ISO 14001.
After over a century of engineering exceptionally long-lasting electrical distribution and transmission solutions, G&W Electric knows power. And more importantly, we know the power of listening. By taking time to understand your application and asking the right questions, we develop solutions tailored to your needs. The answer may be our time-tested switches that keep power running seamlessly in mission-critical applications or an advanced automation system for next-generation grids. Whatever your challenge, you’ll experience decades of high performance — and your needs will always be heard.
SUSTAINABILITY AND ENVIRONMENTAL CARE
GENERAL DESCRIPTION
-
2
The ECOSMART GIS is available in different combinations of functionality to satisfy the most common electrical configurations of typical substation and distribution circuits. The product can be configured for compact style as a single assembled tank, or modular for field assembly of individual cubicles for maximum flexibility in configuration and replacement. The series offers a versatile switchgear ready to cover a variety of installation requirements and market segments.
Applications for the ECOSMART GIS series include:• Public medium voltage secondary distribution• Power transformer protection
FLEXIBILITY
• Transformers substations• Data center protection
• Hospitals• Residential centers
ECOSMART GIS COMPACT
TYPOLOGIES DESCRIPTION
3S Compact switchgear with 3 switch-disconnectors
4S Compact switchgear with 4 switch-disconnectors
BS Compact switchgear with 1 busbar riser and 1 switch-disconnectors
BFS Compact switchgear with 1 busbar riser and 1 fuse switch-disconnectors
SFS Compact switchgear with 1 switch-disconnector and 1 fuse switch-disconnector
2SFS Compact switchgear with 2 switch-disconnector and 1 fuse switch-disconnector
3SFS Compact switchgear with 3 switch-disconnector and 1 fuse switch-disconnector
4SFS Compact switchgear with 4 switch-disconnector and 1 fuse switch-disconnector
2S2FS Compact switchgear with 2 switch-disconnector and 2 fuse switch-disconnectors
2S3FS Compact switchgear with 2 switch-disconnector and 3 fuse switch-disconnectors
3S2FS Compact switchgear with 3 switch-disconnector and 2 fuse switch-disconnectors
BCBS Compact switchgear with 1 busbar riser and 1 vacuum circuit breaker
SCBS Compact switchgear with 1 switch-disconnector and 1 vacuum circuit breaker
2SCBS Compact switchgear with 2 switch-disconnector and 1 vacuum circuit breaker
3SCBS Compact switchgear with 3 switch-disconnector and 1 vacuum circuit breaker
2S2CBS Compact switchgear with 2 switch-disconnector and 2 vacuum circuit breaker
MODULAR UNITS 12-24kV
B Modular extensible switchgear with busbar riser
S Modular extensible switchgear with switch-disconnector
FS Modular extensible switchgear with fuse switch-disconnector
CBS Modular extensible switchgear with vacuum circuit breaker
BCS Modular extensible switchgear busbar coupler with switch-disconnectors and busbar riser
BCCBS Modular extensible switchgear busbar coupler with circuit breaker and busbar riser
METERING UNITS 12-24KV
MDDAV Metering unit bottom incoming-outgoing cables
MDDV Metering unit bottom incoming-outgoing cables only for VTs
MLRAV Metering unit incoming-outgoing from sides
MLINK-V Metering unit arranged for VT with connecting points isolated
MLINK-AV Metering unit arranged for CT & VT with connecting points isolated
MLINK-AVB Metering unit arranged for CT & VT with busbar riser and connecting points isolated
Functional Units Available
-
3
Lifting Eyebolts
Stainless Steel Tank
Operating Mechanisms
Vacuum Circuit Breaker
Voltage Presence Indicators
Pressure Gauge
Support Frame
Cables Compartment
Cables Compartment Panel
Low Voltage Cabinet
Fuse Holders
Optional Key Locks
Cable Bushings
8
2
1
4
6
7
3
5
9
10
11
13
ECOSMART GIS COMPONENTS
Compact Series, Configuration 2SCBS
1 8
2 9
3 10
4 11
5 12
136
7
12
-
4
Features and Benefits
With over 100 years in manufacturing switchgear, the ECOSMART GIS secondary distribution switchgear line offers a comprehensive range of functions. The unit is gas insulated to provide a low-maintenance, compact, safe, and easy-to-install product to meet the most difficult applications.
Designed to be a maintenance-free solution, the active parts of the ECOSMART GIS switchgear are contained and sealed in a stainless steel tank filled with gas, making it more compact compared to other insulation mediums. The gas can be easily recovered at the end of the product life through the filling valve positioned on the switchgear tank. The switchgear has been designed as a sealed pressure system as defined by IEC 62271-1.
Safety/Reliability:
• Total insulation of the live components is ensured by the welded stainless steel tank filled with gas (sealed pressure system as defined by the IEC 62271-200)
• Complete grounding of the whole switchgear• A complete interlocking system allows safe
operating sequences• Anti-reflex function of the operating lever• Switch-disconnector positive position indicator• Earthing switch with making capacity• Pressure relief valves located under the switchgear for
overpressure venting in the event of an internal arc• Internal arc fault protection both for the gas tank
and cable compartment (IAC classification: AFLR up to 20 kA x 1 second as per IEC 62271-200)
• Long service life• Pressure monitoring by included pressure
gauge and, upon request, a pressure switch with auxiliary contacts
ECOSMART GIS
Versatility:
• Compact and modular versions available• Fuses and vacuum circuit breaker protection functions• Wide range of accessories available • Easy installation• Maintenance free• Reduced footprint
Easy Operation:
• Operations are carried out from the switchgear front side• Mimic diagram indicating the position of the switch-
disconnector, earth switch and vacuum circuit breaker• Front cable connection and accessibility• Complete set of interlocks
Easy Installation and Handling:
• The compact design provides advantages during the switchgear installation, allowing:- Reduced installation rooms (kiosks, mobile substations, etc.)- Reduced civil works cost - Easy transport and handling
Environmental Care:
• Manufacturing energy optimization due to the switch-disconnector and cubicle components material
• Reduced use of epoxy resin components• Reduced gas quantity • Made of recyclable materials for ease of recovery and reuse at
the end of the product's life cycle
-
5
PROTECTION DEGREES
ENVIRONMENT AND OPERATIONAL CONDITIONS
TECHNICAL FEATURES
The ECOSMART GIS protection classes comply with the standard IEC 60529. As a switchgear for indoor installation, it offers the following protection degrees:
SWITCHGEAR PROTECTION DEGREES ACCORDING TO IEC 60529
Main Circuits (Gas Enclosure) IP 67
Fuses Holders IP 3X
Operating Mechanism IP 3X
Cable Compartments IP 3X
OPERATING CONDITIONS ACCORDING TO IEC 62271-1
Rated Filling Pressure at 20°C kPa (abs) 140
Minimum Functional Pressure 20°C kPa (abs) 130
Service Temperature °C -5/+40
Temperature (for stocking) °C -40/+70
Average Temperature Over 24h °C 35
Maximum Altitude (above sea level) m ≤1000
ECOSMART GIS - Internal view
Extension Kits
Extension Kits
All units can be ordered in a modular version to allow installation of additional units on both the left and right hand side.
This is accomplished through the use of extension kits positioned on the top or sides of the unit. The modular RMU type must be specified before the units go into production.
Steel Tank
The live parts including switch-disconnectors, earth switches, vacuum circuit breakers and power busbars are housed inside a welded stainless steel tank and insulated with gas. To meet a wide variety of electrical configurations, it is possible to combine up to five functions inside a single tank.
All items are front accessible including the operating mechanisms, vacuum circuit breakers, fuse holders and medium voltage cables. Mechanical interlocks are provided between the 3-position switch-disconnector, the earth position, the vacuum circuit breaker and the cables compartment panels to permit operations only in safe conditions.
The line and earth contacts are driven by a 3-position operating mechanism with two different operating lever slots which are mechanically interlocked. On top of the vacuum circuit breaker function (CBS), a low voltage box can be installed to house the auxiliary circuits, measure instruments and to house the protection relays.
The bottom plates of the cables compartment are equipped with grommets to allow the medium voltage cables entry. Cable clamps are included to support and maintain the medium voltage cables. Floor fastening holes are included on the bottom of both sides of the switchgear as well as in each corner of the switchgear support frame.
-
6
Technical Characteristics
ECOSMART GIS
Rated voltage Ur (kV) 12 24Power Frequency Withstands Voltage
- Towards ground — between phases - Across insulating distance
Ud (kV)28 50
32 60
Rated Lightning Impulse Withstand Voltage- Towards ground — between phases - Across insulating distance
Up (kV)75 125
85 145Rated Frequency fr (Hz) 50 50Rated Current Ir (A) 630 630
Rated Short Time Withstand Current Ik (kA)
16 (tk=1s) 16 (tk=1s)20 (tk=1s) 20 (tk=1s)20 (tk=3s) 20 (tk=3s)
25 (tk=1s)(1)
Internal Arc Withstand Current (IAC AFLR) (kA) 20 x 1s 20 x 1sInternal Arc Withstand Current (inside the fuse holder) (kA) 16 16Service Continuity LSC2A as per IEC 62271-200SWITCH DISCONNECTOR
Mainly Active Load CurrentTDload2 (A) 630 630TDload1 (A) 31.5 31.5
Closed-Loop Distribution Circuit Current TDloop (A) 630 630
Cable-Charging CurrentTDcc2 (A) 16 16TDcc1 (A) 4 4
Line-Charging Current TDlc (A) 1.5 1.5Earth Fault Current TDef1 48 48Cable And Line Charging Current Under Earth Faults TDef2 28 28
Short-Circuit Making Current TDma (kA)40 4050 50
62.5 (2)
Number Of Making Operations n.5 (2)
5 (12kV - 62.5kA)Electrical Endurance Class E3 (2)
Mechanical Endurance Class M1 (1000)FUSE SWITCH-DISCONNECTORRated Current Ir (A) 250 250
Short-Circuit Making Current TDma (kA)40 4050 50
Number Of Making Operations n.5 55 5
EARTHING SWITCH
Short-Circuit Making Current TDma (kA)40 4050 50
Number Of Making Operations n.5 55 5
EARTHING SWITCH DOWNSTREAM THE FUSESRated Short Time Withstand Current For Tk=1s Ik (kA) 2.1 2.1Short-Circuit Making Current TDma (kA) 5.4 5.4Number Of Making Operations n. 5 5VACUUM CIRCUIT BREAKERPower Frequency Withstands Voltage 50 Hz 1 Min. Ud (kV) 28 50Rated Lighting Impulse Withstand Voltage Up (kV) 75 125Rated Current Ir (A) 630 630Rated Short-Circuit Breaking Current Isc (kA) 16-20 16-20Rated Short Time Withstand Current (Tk=1s) Ik (kA) 16-20 16-20Operation Sequence O - 0,3sec - CO - 3min - CO
Single Phase and Double-Earth Fault Tests -20 kA at 13,8 kV 20 kA at 13,8 kV17,3 kA at 24 kV 17,3 kA at 24 kV
Mechanical Endurance Class M1 (2000) (3)
NOTE: (1) 25kA rating available with switch-disconnector only (2) For 12kV, 62.5kA Short-Circuit Making Current operations only, performed 2 times and with Electrical Endurance Class E1 (3) M2 (10000) available upon request
-
© 2020 G&W Electric GW22ENG-2020 02/2021gwelectric.com
Contact us today+1.708.388.5010 or [email protected]
Since 1905, G&W Electric has been a leading provider of innovative power grid solutions, including the latest in load and fault interrupting switches, reclosers, system protection equipment, power grid automation and transmission and distribution cable terminations, joints and other cable accessories. G&W Electric is headquartered in Bolingbrook, Illinois, U.S.A., with manufacturing facilities and sales support in more than 100 countries, including Canada, Italy, China, Mexico, Brazil, India, UAE and Singapore. We help our customers meet their challenges and gain a competitive edge through a suite of advanced products and technical services.