edoc commissioning circuit breakers

Upload: cadtil

Post on 05-Apr-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    1/77

    7/4/2011 Module Three 1

    SUBSTATIONCOMMISSIONING COURSE

    MODULE FOUR

    CIRCUIT BREAKERSTESTING PROCEDURES

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    2/77

    7/4/2011 Module Three 2

    INTRODUCTION

    The electrical commissioning andacceptance testing of electric powersystems is essential for theenergization of any electrical systemfor the first time

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    3/77

    7/4/2011 Module Three 3

    INTRODUCTION

    Module Four

    Discuss theory and ratings Safety issues Test equipment operation &

    hands on testing

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    4/77

    7/4/2011 Module Three 4

    INTRODUCTION

    Skills learned in MODULE FOUR:

    Acceptance testing for CircuitBreakers

    Operate Breaker analyzer Apply safe work practices

    Analyze test values Complete test forms

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    5/77

    7/4/2011 Module Three 5

    CIRCUIT BREAKERS

    North American Standards

    US Standards NEMA ANSI/IEEE IEEE standards are

    harmonized with IEC IEC are harmonized with IEEE

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    6/77

    7/4/2011 Module Three 6

    CIRCUIT BREAKERS

    Most Significant Standards

    C37.04 Rating Structure for AC High Voltage CircuitBreakers

    C37.06 AC High Voltage Circuit Breakers Rated on aSymmetrical Current Basis PreferredRatings and Related Required Capabilities

    C37.09 Standard Test Procedures for AC HighVoltage Circuit Breakers Rated on a

    Symmetrical Current Basis C37.010 Application Guide for AC High Voltage CircuitBreakers Rated on a Symmetrical CurrentBasis

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    7/77

    7/4/2011 Module Three 7

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    8/77

    7/4/2011 Module Three 8

    CIRCUIT BREAKERS

    Maximum Voltage Voltage range factor

    Continuous current Short circuit

    Symmetrical current Asymmetrical current

    % DC component Interrupting time Maximum tripping delay

    TRV Transient recoveryvoltage

    Withstand voltage Power frequency Lightning impulse

    Closing and latching

    current

    Rated Characteristics

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    9/77

    7/4/2011 Module Three 9

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    10/77

    7/4/2011 Module Three 10

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    11/77

    7/4/2011 Module Three 11

    CIRCUIT BREAKERS

    Application Considerations

    Circuit Beaker definition (IEEE C37.100)

    A circuit breaker is a mechanical device capable ofmaking, carrying and breaking currents under normalcircuit conditions and also making, carrying for aspecific time and breaking currents under specified

    abnormal conditions such as those of short circuit

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    12/77

    7/4/2011 Module Three 12

    CIRCUIT BREAKERS

    The upper limit of the system voltage for continuousoperation

    Rated maximum voltage: 4.76 kV 8.25 kV

    15 & 15.5 kV 25.8 kV 38 kV

    Maximum Voltage

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    13/77

    7/4/2011 Module Three 13

    CIRCUIT BREAKERS

    All North American Beakers are rated at 60Hz

    Manufacturers to be consulted for operation at otherfrequencies

    Frequency

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    14/77

    7/4/2011 Module Three 14

    CIRCUIT BREAKERS

    Operating within temperature rise specification Continuous current rating for normal operating

    conditions Ambient temperature between -30 C to 40 C Installed above sea level and below 1000 m Free of extreme environmental contamination

    Not affected by solar radiation Short time over current permissible for Motor starting, cold load pick-up, emergency

    conditions

    Continuous Current

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    15/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    16/77

    7/4/2011 Module Three 16

    CIRCUIT BREAKERS

    Rated constant symmetrical current rating in KA rms Synonymous with SF6 and vacuum breakers

    Older breakers rated in constant MVA (oil, air-magnetic)

    Isym = (Rated Isc) x (Rated Vmax / Vop) or Isym = MVA / (Vop x 3)

    Short Circuit Current - Symmetrical

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    17/77

    7/4/2011 Module Three 17

    CIRCUIT BREAKERS

    Multiplier factor for symmetrical current rating Modern / future breakers will be rated at K = 1

    Factor K to be eliminated in future standards Breakers to be rated on a constant symmetrical

    current rating K Factor to address older breaker rated in constant

    MVA

    Voltage Range Factor K

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    18/77

    7/4/2011 Module Three 18

    CIRCUIT BREAKERS

    Asymmetrical current rating Symmetrical rating multiplied by S

    Based on % DC rating for modern breakers %DC using standard decay curve for X/R = 17

    Short Circuit Current - Asymmetrical

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    19/77

    7/4/2011 Module Three 19

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    20/77

    7/4/2011 Module Three 20

    CIRCUIT BREAKERS

    % DC rating related to the speed of the breaker Fast breakers interrupt more DC current

    Peak currents can be 2X symmetrical peak value Symmetrical current rides on decaying DC current DC current decay based on X/R of system

    Slow breakers interrupt less DC current

    Current falls towards symmetrical value

    % DC

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    21/77

    7/4/2011 Module Three 21

    CIRCUIT BREAKERS

    The standard DC decay time constant can becalculated by:

    = (X/R) / (2 f)

    for X/R ratio of 17, = 45 msec

    Short Circuit Current - Asymmetrical

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    22/77

    7/4/2011 Module Three 22

    CIRCUIT BREAKERS

    The asymmetrical interrupting rating is calculated by:Iassym = Isym x S

    S = [ 1 + 2 (%dc/100)2 ]

    Iassym = Isym x [ 1 + 2 (%dc/100)2 ]

    Short Circuit Current - Asymmetrical

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    23/77

    7/4/2011 Module Three 23

    CIRCUIT BREAKERS

    Maximum allowable time between Energization of trip coil and arc extinction time

    Rating based on: Rated control voltage Maximum opening mechanical pressure Arc extinction in all 3 poles

    Interrupting time

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    24/77

    7/4/2011 Module Three 24

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    25/77

    7/4/2011 Module Three 25

    CIRCUIT BREAKERS

    Why Delay tripping ? Breaker contacts works less, less wear and tear

    Trade-off between increased interrupter / contactheating and speed

    Contact heating a function of I2t

    Permissible Tripping Delay T

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    26/77

    7/4/2011 Module Three 26

    CIRCUIT BREAKERS

    Asymmetrical current rating for closing unto a fault

    Enables downstream protection to operate Can be man made faults leaving grounds on

    Closing and Latching Current

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    27/77

    7/4/2011 Module Three 27

    CIRCUIT BREAKERS

    Power Frequency (60 Hz) dielectric test 1 minute time duration

    Part of total lightning impulse tests

    Trivia: Rate of rise at 2%/sec of the 75% level Test voltage reached between 60-70 sec, 90 sec

    OK

    Dielectric Withstand

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    28/77

    7/4/2011 Module Three 28

    CIRCUIT BREAKERS

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    29/77

    7/4/2011 Module Three 29

    CIRCUIT BREAKERS

    Series of factory dielectric tests Power frequency test; dry (1 minute), wet (10 sec)

    Full-wave lightning impulse Chopped wave lightning impulse Switching impulse

    Tests the insulation system Phase to ground Across open contacts

    LightningImpulse Withstand Voltage

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    30/77

    7/4/2011 Module Three 30

    CIRCUIT BREAKERS

    Voltage generated across open contact after currentinterruption

    Fast rise time and can peak at 2X ac crest value Dielectric must not flash-over after contact have

    stopped and parted Contact separation is greater than required for

    current interruption Rated in dV/dT or kV peak / time to peak

    TRV Transient Recovery Voltage

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    31/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    32/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    33/77

    7/4/2011 Module Three 33

    CIRCUIT BREAKERS

    Norm. operating pressure Min. operating pressure

    Volume of oil per tank Weight Instruction book number Part list number Capacitance current

    switching Out of phase current

    switching

    Nameplate Data

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    34/77

    7/4/2011 Module Three 34

    CIRCUIT BREAKERS

    Close coil volt. range Trip coil volt. range

    Closing / closing current Motor current / voltage Low pressure alarm / lock

    out pressure operatingpoints

    Wiring diagram number Instruction book number Parts list number

    Mechanism Nameplate Data

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    35/77

    7/4/2011 Module Three 35

    CIRCUIT BREAKERS

    Shall includeidentification and

    pertinent operatingcharacteristics

    Accessories Nameplate Data

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    36/77

    7/4/2011 Module Three 36

    CIRCUIT BREAKERS

    Essential markingsshould be provided

    Operating devices andpositions

    Instructions foroperation

    Special precautions Environmental

    warnings

    Instructions and WarningSigns

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    37/77

    7/4/2011 Module Three 37

    CIRCUIT BREAKERS

    Types ofcircuit Breakers

    Air magnetic Oil Air blast SF6 Vacuum

    Air Magnetic

    Obsolete technology forMV class

    Uses air as the dielectric In use until 1975

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    38/77

    7/4/2011 Module Three 38

    CIRCUIT BREAKERS

    Types ofcircuit Breakers

    Air magnetic Oil Air blast SF6 Vacuum

    Oil (tank / minimum / bulk)

    Obsolete technologyexcept for low voltageapplications

    Cease production is the1990s

    Uses oil as the dielectric Up to 230 kV

    Minimum oil was areplacement for air-magnetic in MV class

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    39/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    40/77

    7/4/2011 Module Three 40

    CIRCUIT BREAKERS

    Types ofcircuit Breakers

    Air magnetic Oil Air blast SF6 Vacuum

    SF6

    Todays technology Use SF6 as the dielectric Use in MV and HV class

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    41/77

    7/4/2011 Module Three 41

    CIRCUIT BREAKERS

    Types ofcircuit Breakers

    Air magnetic Oil Air blast SF6 Vacuum

    Vacuum

    Todays technology Use vacuum as the

    dielectric Limited to MV

    applications

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    42/77

    7/4/2011 Module Three 42

    CIRCUIT BREAKERS

    Functions ofCircuit

    Breakers

    Switching Fault Interruption

    Interrupters Current interruption

    Switching

    Control the flow of electricalenergy by opening orclosing its main contacts

    Breaker can be controlledlocally or remotely viaSCADA

    Operations accomplished by

    energizing the tripping orclosing coils

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    43/77

    7/4/2011 Module Three 43

    CIRCUIT BREAKERS

    Functions ofCircuit

    Breakers

    Switching Fault Interruption

    Interrupters Current interruption

    Fault Interruption

    The primary equipment usedfor interrupting short circuitcurrents

    A circuit breaker used forthree-phase is called a threepole breaker.

    One interrupter per pole for

    MV circuit breakers Series interrupters per polefor HV circuit breakers

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    44/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    45/77

    7/4/2011 Module Three 45

    CIRCUIT BREAKERS

    Functions ofCircuit

    Breakers

    Switching Fault Interruption

    Interrupters Current interruption

    Current interruption

    Arcing contact separates Arc energy used to built

    dielectric pressure Dielectric moves between

    contacts at current zerocrossing

    Maintained dielectric

    equates to currentinterruption

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    46/77

    7/4/2011 Module Three 46

    SAFETY CONSIDERATION

    High Voltage Safety

    Electrical safety using high voltage test equipment Testing performed by qualified personnel Familiarization with test set operations Know the hazards for the specific test

    Safe working practice and guidelines

    Safety practice regulations IEEE standard 510-1983; Recommended Practicefor Safety in High Voltage Testing and High PowerTesting

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    47/77

    7/4/2011 Module Three 47

    SAFETY CONSIDERATION

    X-Ray Radiation

    High voltage across vacuum gap can produce x-rayradiation

    Vacuum bottle integrity test voltage not to exceedmanufacturers recommended levels or 75% of thefactory dielectric test

    Indoor breaker optimally tested in the test /

    disconnected position for shielding Outdoor breakers tested at 1 metre distance withcovers in place as per indoor breakers outside itscubicle

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    48/77

    7/4/2011 Module Three 48

    SAFETY CONSIDERATION

    StaticHigh Voltage

    Electrostatic charge may be retained after highvoltage potential is removed

    Ground the primary bushing and mid-band ring for atleast 60 seconds

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    49/77

    7/4/2011 Module Three 49

    SAFETY CONSIDERATION

    Stored Energy

    Mechanical adjustments and checks should only beattempted after: Stored energy have been discharge / isolated Operating mechanism have been blocked

    Circuit breaker operation rely on the release /application of energy for closing and tripping

    operations Charged spring / pneumatic pressure / hydraulicpressure

    Energizing large operating coils

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    50/77

    7/4/2011 Module Three 50

    CIRCUIT BREAKER TESTING

    Mechanical Testing Inspection Manual tripping and

    closing

    Mechanical interlocks Contact timing

    Electrical Testing Insulation resistance Dielectric withstand Vacuum bottle integrity

    Contact resistance Operations PF (maintenance test

    as required)

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    51/77

    7/4/2011 Module Three 51

    CIRCUIT BREAKER TESTING

    Mechanical Testing Inspection Manual tripping and

    closing

    Mechanical interlocks Contact timing

    Inspection

    Verify the ratingsmatches the designspecifications

    Verify installed correctly Determine of any physical

    damage duringinstallation or transport

    Check all auxiliaryequipment are supplied

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    52/77

    7/4/2011 Module Three 52

    CIRCUIT BREAKER TESTING

    Mechanical Testing Inspection Manual tripping and

    closing

    Mechanical interlocks Contact timing

    Manual tripping / closing

    Energy storage devices Trip / latch mechanism Manual charging system

    Operations counter

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    53/77

    7/4/2011 Module Three 53

    CIRCUIT BREAKER TESTING

    Mechanical Testing Inspection Manual tripping and

    closing

    Mechanical interlocks Contact timing

    Mechanical Interlocks

    Positive interlock Spring discharge interlock Rating interference plate

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    54/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    55/77

    7/4/2011 Module Three 55

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    56/77

    7/4/2011 Module Three 56

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    57/77

    7/4/2011 Module Three 57

    CIRCUIT BREAKER TESTING

    Electrical Testing Insulation resistance Dielectric withstand Vacuum bottle integrity

    Contact resistance Operations PF (maintenance test

    as required)

    Insulation Resistance

    DC voltage test 100% of the Rated AC

    phase-ground crest value

    Crest value = 1.414 xVAC rms

    Preliminary to thedielectric withstand test

    Note: Value > NETArecommended test value

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    58/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    59/77

    7/4/2011 Module Three 59

    CIRCUIT BREAKER TESTING

    Electrical Testing Insulation resistance Dielectricwithstand Vacuum bottle integrity

    Contact resistance Operations PF (maintenance test

    as required)

    Dielectric Withstand

    AC 60 Hz test at 75% ofthe factory test value

    Voltage applied across

    open contacts Voltage applied across

    phase to ground withcontacts closed

    Untested terminalgrounded

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    60/77

    7/4/2011 Module Three 60

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    61/77

    7/4/2011 Module Three 61

    CIRCUIT BREAKER TESTING

    Electrical Testing Insulation resistance Dielectric withstand Vacuum bottle integrity

    Contact resistance Operations PF (maintenance test

    as required)

    Vacuum bottle integrity AC 60 Hz test at 75% of

    the factory test value Voltage applied across

    open contacts Test time can be limited

    to 10 sec for somebreaker type

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    62/77

    7/4/2011 Module Three 62

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    63/77

    7/4/2011 Module Three 63

    CIRCUIT BREAKER TESTING

    Electrical Testing Insulation resistance Dielectric withstand Vacuum bottle integrity

    Contact resistance Operations PF (maintenance test

    as required)

    Contact Resistance

    100 Adc Resistance from bushing

    terminal to bushing

    terminal Using 4-wire resistance

    measurement test set

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    64/77

    7/4/2011 Module Three 64

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    65/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    66/77

    7/4/2011 Module Three 66

    CIRCUIT BREAKER TESTING

    Electrical Testing PFTest (Classified as a

    maintenance test

    Insulation test Bushing test

    Power Factor Test

    Establish initial baselinereading for comparisonand trending

    Similar to the capacitanceand power dissipationtest

    Test voltage below

    operating phase-to-ground value

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    67/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    68/77

    7/4/2011 Module Three 68

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    69/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    70/77

    7/4/2011 Module Three 70

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    71/77

    7/4/2011 Module Three 71

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    72/77

    7/4/2011 Module Three 72

    CIRCUIT BREAKER TESTING

    Electrical Testing PF (maintenance test

    as required) Insulation test

    Bushing test

    Bushing Test

    Hot collar test Non condenser

    bushing

    GST Collar material

    Conducting Uniform dimension

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    73/77

    7/4/2011 Module Three 73

    CIRCUIT BREAKER TESTING

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    74/77

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    75/77

    7/4/2011 Module Three 75

    TEST SET MANUAL

    Module 4:Breaker Timing Test setPower Factor Test Set

    Module 2 & 3CT Tester15 KV Insulation Resistance Test setAC High Potential Test set

    DC High Potential Test setDigital Low Resistance Test set

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    76/77

    7/4/2011 Module Three 76

  • 7/31/2019 Edoc Commissioning Circuit Breakers

    77/77

    7/4/2011 Module Three 77