ABSTRACT:
One of the tests performed in transformer is the open-
circuit test. This test is necessary in the determination
of the core loss of the transformer........
INTRODUCTION:
When one side of a transformer is left open-circuited
and the other side is connected to an AC source
whose voltage is the rated value, the current will be
extremely low, about 2 to 10% of the rated loadcurrent. This no-load current or the exciting current
Io has two components, one producing the normal
mutual flux, and the other taking care of the
hysteresis and eddy-current losses in the core. Sincethe current is very low, the copper loss will be
negligible. For all practical purposes, therefore, the
power measured by the instrument under condition of
the open circuit will register the core loss.
OBJECTIVES:
To determine the amount of power lost in hysteresis
and eddy-current in the iron core of the single-phase
transformer.
MATERIALS AND EQUIPMENT USED:Transformer, Digital Power Meter, Variac, Multi-
Tester, Connecting Wires
METHODOLOGYConnect the circuit as shown in Figure1. Connect the
220 volt AC source to the variable autotransformer so
as to vary the input voltage in the circuit. Starting
from zero, gradually increase the input voltage step-
by-step up to ten per cent above the rated voltage ofthe transformer which is in this case equal to 220-
volts. For each of the voltage variation, record the
input current, input power and voltage.:
:
The circuit diagram is reconnected for a 220/440
volts configuration. As before, the input voltage...:
:
DATA and RESULTS
Table1: Tabulated results on the OCT of
Transformer with 220:220 configuration
Voltage
Input
Vin
Current
Input
IO
Power
Input
PC
Wattful
Current
Ih+e
Wattless
Current
Im
Table2: Tabulated results on the OCT of
Transformer with 220:440 configuration
Voltage
Input
Vin
Current
Input
IO
Power
Input
PC
Wattful
Current
Ih+e
Wattless
Current
Im
:
:
:
University of San Carlos
Department of Electrical and Electronics EngineeringEE421NL-EE Machines 1 Lab
7:30-10:30, Monday, 2nd Semester AY2015-16
Open Circuit Test of Transformer
Rafael D. Seva, Jr .
CIRCUIT DIAGRAM:
7/24/2019 EE421NL Lab Report Format
http://slidepdf.com/reader/full/ee421nl-lab-report-format 2/2
2
SAMPLE CALCULATIONS:
[1] Ih+e = Pc/Vin
[2] Im = √Io2 − Ih+e2
::
:
ANSWERS to QUESTIONS:
1.
Plot, with applied voltage as abscissa, the values
of the input watts, and total current Io. Taking the
magnetizing current Im versus the input voltage.
2. Draw a typical vector diagram of the transformer
on open-circuit test showing the phase
relationship between flux, primary voltage, no-
load current, and the wattful and wattless
components of the current Io.3. Explain the primary and secondary winding
connection.
GRAPHS
It can be seen from Figure1 that when the inputvoltage is varied, the input current varies
exponentially. It could be deduced that when thevoltage is increased beyond its rated value, the
increase in the input current is very dramatic. This isan indication that a transformer should not be
operated beyond its rated voltage because by doing
so the ........
[There should be an analysis of every graphs
presented ]
:
:
:
:
CONCLUSION:
[Must be based upon (1) Objective, (2) Graphs]
REFERENCES:
[ Books, Articles, PDF files, internet web-site, etc]
REFLECTION:
[ How the experiment/lab activity affected you
personally in preparation for your career, etc....
Maximum of 5 sentences only .]
CERTIFICATION:I hereby certify that this report is ........
________________________
Rafael D. Seva, Jr.[ Signature above name ]
Figure1: Graph of Vin and Iin