EIFS: StoThermRainscreen II 8.XX Series Details Index Description Detail# Wood Frame Construction 8.00 Reveals/Aesthetic Grooves 8.03 Aesthetic Band/Projection or Build-Out 8.04 Grade Condition with Waterproof Foundation 8.10 Pan Flashing at Window Sill 8.20 Pan Flashing at Window Sill (Window with No Nailing Flange) 8.20A Flashing at Window Sill with EIFS Trim (Window with Nailing Flange) 8.20B Flashing at Window Head (Window with Nailing Flange) 8.21 Flashing at Window Head with EIFS Trim (Window with Nailing Flange) 8.21B Flashing at Window Head with EIFS Trim and Drip Edge (Window with Nailing Flange) 8.21C Window Jamb (Window with Nailing Flange) 8.22 Window Jamb with EIFS Trim (Window with Nailing Flange) 8.22B Expansion Joint at Floorline 8.30 Expansion Joint at Floorline with EIFS Accent Board 8.31 Wood Deck Connection 8.32 Eave and Flashing at Roof/Wall Intersection 8.62 Surface Mount Fixture Penetration through the System 8.71 Downspout Attachment 8.72

Upload: others

Post on 11-Apr-2020

17 views

Category:

Documents


0 download

TRANSCRIPT

EIFS: StoTherm™ Rainscreen II 8.XX Series

Details Index

Description Detail#

Wood Frame Construction 8.00

Reveals/Aesthetic Grooves 8.03

Aesthetic Band/Projection or Build-Out 8.04

Grade Condition with Waterproof Foundation 8.10

Pan Flashing at Window Sill 8.20

Pan Flashing at Window Sill (Window with No Nailing Flange) 8.20A

Flashing at Window Sill with EIFS Trim (Window with Nailing Flange) 8.20B

Flashing at Window Head (Window with Nailing Flange) 8.21

Flashing at Window Head with EIFS Trim (Window with Nailing

Flange) 8.21B

Flashing at Window Head with EIFS Trim and Drip Edge (Window with

Nailing Flange) 8.21C

Window Jamb (Window with Nailing Flange) 8.22

Window Jamb with EIFS Trim (Window with Nailing Flange) 8.22B

Expansion Joint at Floorline 8.30

Expansion Joint at Floorline with EIFS Accent Board 8.31

Wood Deck Connection 8.32

Eave and Flashing at Roof/Wall Intersection 8.62

Surface Mount Fixture Penetration through the System 8.71

Downspout Attachment 8.72

Date: October 2007

Detail No.: 8.00StoTherm™ Rainscreen IIWood Frame Construction

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Secondary weatherresistive barrier

Structuralframing

Sheathing

StoInsulationBoard

Sto BaseCoat

Sto DetailMesh

Sto FinishCoat

Sto Adhesive

Starter trackwith weep holes

Drainagemat

Date: October 2007

Detail No.: 8.03StoTherm™ Rainscreen II Reveals/Aesthetic Grooves

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Do not locate reveals at stress areas such as corners of windows, doors, etc.

2. Horizontal reveals must be sloped to shed water. Minimum required slope is 1:2 (27 degrees), steeper for northern climates.

3. Offset reveals minimum 3" (76 mm) from insulation board joints.

4. Use Sto Detail Mesh to reinforce reveals and overlap with Sto Detail Mesh minimum 2-1/2" (64 mm).

5. Use proper tools to avoid build-up of material in reveals and to ensure consistent thickness.

6. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Structural frame

Sto Finish Coat

Secondary weather barrier

Sto Detail Mesh embedded in Sto Base Coat

Sheathing Minimum 2-1/2" (64 mm) Mesh Overlap

Sto Detail Mesh embedded in Sto Base Coat

Drainage mat

Reveal

Reveal/ Groove

3" (76 mm) minimum offset from insulation board joint

Minimum 1/2" (13 mm) gap for sealant joint

12" (305 mm)

2-1/2" (64 mm)

Sto Detail Mesh (back- wrapped)

Diagonal Reinforce- ment with Sto Detail Mesh

9" (229 mm)

Detail at Groove Required Shapes

”V” Groove

Beveled Groove

”U” Groove

3/4” (19 mm) minimum Minimum 2-1/2”

(64 mm) Mesh Overlap

Sto Adhesive

Sto Insulation Board

Date: October 2007

Detail No.: 8.04StoTherm™ Rainscreen IIAesthetic Band/Projection or Build-Out

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Sto Flexyl requires primer prior to application of finish coat. with Sto Detail Mesh required for projections greater than 2 inches (51 mm).

2. Minimum required slope is 1:2 (27 degrees) and maximum width is 12 inches (300 mm). Increase slope for northern climates to prevent accumulation of ice/snow and water on surface. Periodic inspections and increased maintenance of coating may be required.

3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Structuralframe

Secondary weatherresisitive barrier

Sheathing

Sto InsulationBoard

Sto Detail Meshembedded inSto Base Coat

Sto Finish Coat

Minimum 2-1/2"(64 mm) meshoverlap

Minimum 2-1/2"(64 mm) meshoverlap

Sto Detail Meshembedded in Sto Base Coat

Sto Adhesive

Sto Flexyl withSto Detail Meshembedded(See note 1)

Drainage mat

Date: October 2007

Detail No.: 8.10StoTherm™ Rainscreen IIGrade Condition with Waterproof Foundation

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Not recommended to extend finish coat below grade. Terminate finish coat minimum 8" (203 mm) above grade, higher for snow regions.

2. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Secondary weather resistive barrier

Sto Adhesive

Sto Insulation Board

Sto Detail Mesh embedded in Sto Base Coat

Drainage mat

Sto Detail Mesh embedded in Sto Flexyl Base Coat (Primed with Sto Primer)

Drainage mat

Perforated drainage tubing

Sto Armor Mat embedded in Sto Base Coat

Drainage material

Backfill

Sto Flexyl

Sto Finish Coat

Starter track with weep holes

Sheathing

Note: Protect against rising damp at sill plate as required

Date: October 2007

Detail No.: 8.20StoTherm™ Rainscreen IIPan Flashing at Window Sill

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Install flexible membrane flashing minimum 4" (102 mm) up jambs of rough opening to create end dams.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

EIFS

backwrapSto Adhesive

Sto Insulation Board

Sto Detail Meshembedded inSto Base Coat

Sto Finish Coat

Structuralframe

Window sill

Sealant andbacker rod

Secondary weatherresistive barrier

Drainage matSheathing

Flexiblewallflashing

Air seal(Completewindow perimeter)

Date: October 2007

Detail No.: 8.20AStoTherm™ Rainscreen IIPan Flashing at Window Sill(Window with No Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

2. Weep holes to be provided every 2 feet (610 mm) through the backer rod and sealant and at window corners and mullions.

EIFS

backwrap

Sto InsulationBoard

Sto Detail Meshembedded inSto Base Coat

Sto Finish Coat

Structuralframe

Window sill

Secondaryweather resistive barrier

Sheathing

Windowpan flashing withend dam

Sealant

Air Seal(Completewindowperimeter)

Backer rod and sealant (See Note 2)

Drainage mat

Sto Adhesive

Date: October 2007

Detail No.: 8.20BStoTherm™ Rainscreen IIFlashing at Window Sill with EIFS Trim(Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Install flexible membrane flashing minimum 4" (102 mm) up jambs of rough opening to create end dams.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

5. EIFS sill slope minimum1:2 (27 degrees).

6. EIFS sill trim pre-wrapped with base coat and reinforcing mesh on top and bottom. Leave face exposed for mechanical attachment. Attach every 8 inches (209 mm) on center and no more than 4 inches (102 mm) from ends with appropriate fastener. Then adhesively attach final trim piece.

EIFS

backwrap

Sto Adhesive

Drainage mat

Sto Insulation Board

Sto Detail Meshembedded inSto Base Coat

Sto Finish Coat

Structuralframe

Window sill

Sealant and backer rod

Sheathing

Flexiblemembraneflashing

Secondaryweatherresistivebarrier

Metal or plasticwindow flashing

Air Seal(Completewindowbarrier)

Date: October 2007

Detail No.: 8.21StoTherm™ Rainscreen IIFlashing at Window Head(Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Weep holes to be provided every 2 feet (610 mm) through the sealant joint above the flashing.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

EIFS

backwrap

Airseal(Completewindow perimeter)

Sto Adhesive

Sto Insulation Board

Sto Detail Meshembedded inSto Base Coat

Sto Finish Coat

Drainage mat

Structuralframe

Sealant and backer rod(See Note 3)

Window headflashing (per windowmanufacturer’srecommendations)

Sheathing

Secondaryweatherresisitivebarrier

Sealant bead

Date: October 2007

Detail No.: 8.21BStoTherm™ Rainscreen IIFlashing at Window Head with EIFS Trim(Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Weep holes to be provided every 2 feet (610 mm) through the sealant joint above the flashing.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

5. EIFS trim slope minimum 1:2 (27 degrees).

Sto Insulation Board

Sto Detail Mesh embedded in Sto Coat

Sto Finish Coat

Structural frame

Nailing flange

Window head flashing (per window manufacturer’s requirements)

Sheathing

Secondary weather resistive barrier

Sealant bead

Sealant and backer rod (See Note 3)

Air seal (complete window perimeter)

Drainage mat

Sto Adhesive

Date: October 2007

Detail No.: 8.21CStoTherm™ Rainscreen IIFlashing at Window Head with EIFS Trim and Drip Edge (Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, water- proof building paper or equivalent).

4. EIFS trim slope minimum 1:2 (27 degrees).

5. Embed starter track attachment flange in sealant before securing to substrate.

Starter track

Sheathing

Structuralframe

Nailingflange

Secondary weather resistivebarrier

Airseal(completewindowperimeter)

Drainage mat

Sto Adhesive

Sto Insulation Board

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

Window headflashing (per windowmanufacturer’srequirements)

Sealant bead

Date: October 2007

Detail No.: 8.22StoTherm™ Rainscreen IIWindow Jamb (Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, water- proof building paper or equivalent).

Drainage mat

Structural frame

EIFS backwrap

Air seal (completewindow perimeter)

Window jamb

Sill below

Sealant and backer rod

Secondary weatherresistive barrier

Sto Adhesive

Sto Insulation Board

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

Date: October 2007

Detail No.: 8.22BStoTherm™ Rainscreen IIWindow Jamb with EIFS Trim(Window with Nailing Flange)

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.

2. Provide minimum 1/2" (13 mm) sealant joint width.

3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Sto Insulation Board

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

Secondary weather resistive barrier

Sealant and backer rod

Window jamb

Sill below

Air seal (Complete window perimeter)

Sto Adhesive

Structural frame

Drainage mat

EIFS backwrap

Date: October 2007

Detail No.: 8.30StoTherm™ Rainscreen IIExpansion Joint at Floorline

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Similar joint required at attic floor line along gable end walls.

2. Gap wood sheathing edge and end joints in accordance with APA (American Plywood Association) recommendations. Gap at expansion joint the same dimension as the joint.

3. Locate expansion joint no lower than centerline of end joist.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

5. Secondary weather resistive barrier continuous at expansion joint.

Sto Adhesive

Sto Insulation Board

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

SheathingStructural frame

Sealant and backer rod

3/4" (19 mm) minimum

(See Note 3)

Drainage mat

Secondary weather resistive barrier

Flexible membrane flashing

EIFS backwrap

Date: October 2007

Detail No.: 8.31StoTherm™ Rainscreen IIExpansion Joint at Floorline with EIFS Accent Board

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 3/4" (19 mm) sealant joint width.

2. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

3. StoTherm trim slope minimum 1:2 (27 degrees).

Sheathing

Structural frame

Sto Adhesive

Sto Adhesive

Secondary weather resistive barrier

EIFS backwrap

Flexible membrane flashing

Sto Insulation Board

Sto Adhesive to attach EIFS accent

Sealant and backer rod

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

Date: October 2007

Detail No.: 8.32StoTherm™ Rainscreen IIWood Deck Connection

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Gap wood sheathing edge and end joints in accordance with APA (American Plywood Association) recommendations.

2. Seal penetrations through flashing where attached to framing.

3. Distance of EIFS to deck varies with climate. Allow sufficient distance to prevent snow/ice and puddling water against system.

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

5. Pressure treated wood (space from flashing or route backside to provide drainage).

Starter track

Secondary weather resistive barrier

Sto Insulation Board

Sheathing

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

4" (100 mm) minimum

2" (50 mm) minimum

SealantSecondary weather resistive barrier

(See Note 5)

Drainage mat

EIFS backwrap

Sto Adhesive

Structural frame

Drainage mat

Continuous leakproof flashing with end dams (as required by code)

Date: October 2007

Detail No.: 8.62StoTherm™ Rainscreen IIEave and Flashing at Roof/Wall Intersection

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide leakproof flashing (as required by code) to prevent water from draining into wall.

2. Drill several, evenly spaced weep holes in the base of the starter track within 1” (25 mm) of the termination at the diverter flashing to allow for completedrainage.

2” (50 mm) typical

2” (50 mm) minimum

Step Flashing (See Note 3)

Sealant and backer rod (minimum 1/2” (13 mm) sealant joint width)

Secondary weather resistive barrier as required by local code

Sto Detail Mesh embedded in Sto Base Coat

Sto Finish Coat

Sto Insulation Board

Sto Adhesive

Secondary weather resistive barrier as required by local code

Diverter flashing (See Note 1)

Drainage mat

Drainage mat

Starter track with weep holes minimum 2” (50 mm) above roof line (See Note 2)

Date: October 2007

Detail No.: 8.71StoTherm™ Rainscreen II Surface Mount FixturePenetration through the System

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Provide minimum 1/2" (13 mm) sealant joint width.

2. Flexible membrane flashing to be installed around electrical conduit.

3. Pressure treated wood (space from flashing or route back side to provide drainage).

4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).

Drainage mat

Sto Insulation Board

Sto Adhesive

Sheathing

(See Note 3)

Wood blocking

Electrical conduit

Secondary weather resistive barrier

Flexible membrane flashing

EIFS Backwrap

Washer embedded in sealant

Light fixture

Sealant and backer rod

Sto Finish Coat

Sto Detail Mesh embedded in Sto Base Coat

Date: October 2007

Detail No.: 8.72StoTherm™ Rainscreen IIDownspout Attachment

www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

Notes:

1. Distance to grade varies with climate. Allow sufficient distance to prevent snow/ice and puddling water against system.

Sto Adhesive

Sto Insulation Board

Sto Detail Meshembedded inSto Base Coat

Sto Finish

Sheathing

Structuralframe

Backwrap

Sealant andbacker rod

Gutter strap

Plastic sleeve

Sealant

Washer bedded in sealant

Sto Armor Matembedded in Sto Base Coat

8" (200 mm)typical(See Note 1)

Sto Flexyl towaterproof foundation(Sto Mesh optional)