EIFS: StoTherm™ Rainscreen II 8.XX Series
Details Index
Description Detail#
Wood Frame Construction 8.00
Reveals/Aesthetic Grooves 8.03
Aesthetic Band/Projection or Build-Out 8.04
Grade Condition with Waterproof Foundation 8.10
Pan Flashing at Window Sill 8.20
Pan Flashing at Window Sill (Window with No Nailing Flange) 8.20A
Flashing at Window Sill with EIFS Trim (Window with Nailing Flange) 8.20B
Flashing at Window Head (Window with Nailing Flange) 8.21
Flashing at Window Head with EIFS Trim (Window with Nailing
Flange) 8.21B
Flashing at Window Head with EIFS Trim and Drip Edge (Window with
Nailing Flange) 8.21C
Window Jamb (Window with Nailing Flange) 8.22
Window Jamb with EIFS Trim (Window with Nailing Flange) 8.22B
Expansion Joint at Floorline 8.30
Expansion Joint at Floorline with EIFS Accent Board 8.31
Wood Deck Connection 8.32
Eave and Flashing at Roof/Wall Intersection 8.62
Surface Mount Fixture Penetration through the System 8.71
Downspout Attachment 8.72
Date: October 2007
Detail No.: 8.00StoTherm™ Rainscreen IIWood Frame Construction
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Secondary weatherresistive barrier
Structuralframing
Sheathing
StoInsulationBoard
Sto BaseCoat
Sto DetailMesh
Sto FinishCoat
Sto Adhesive
Starter trackwith weep holes
Drainagemat
Date: October 2007
Detail No.: 8.03StoTherm™ Rainscreen II Reveals/Aesthetic Grooves
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Do not locate reveals at stress areas such as corners of windows, doors, etc.
2. Horizontal reveals must be sloped to shed water. Minimum required slope is 1:2 (27 degrees), steeper for northern climates.
3. Offset reveals minimum 3" (76 mm) from insulation board joints.
4. Use Sto Detail Mesh to reinforce reveals and overlap with Sto Detail Mesh minimum 2-1/2" (64 mm).
5. Use proper tools to avoid build-up of material in reveals and to ensure consistent thickness.
6. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Structural frame
Sto Finish Coat
Secondary weather barrier
Sto Detail Mesh embedded in Sto Base Coat
Sheathing Minimum 2-1/2" (64 mm) Mesh Overlap
Sto Detail Mesh embedded in Sto Base Coat
Drainage mat
Reveal
Reveal/ Groove
3" (76 mm) minimum offset from insulation board joint
Minimum 1/2" (13 mm) gap for sealant joint
12" (305 mm)
2-1/2" (64 mm)
Sto Detail Mesh (back- wrapped)
Diagonal Reinforce- ment with Sto Detail Mesh
9" (229 mm)
Detail at Groove Required Shapes
”V” Groove
Beveled Groove
”U” Groove
3/4” (19 mm) minimum Minimum 2-1/2”
(64 mm) Mesh Overlap
Sto Adhesive
Sto Insulation Board
Date: October 2007
Detail No.: 8.04StoTherm™ Rainscreen IIAesthetic Band/Projection or Build-Out
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Sto Flexyl requires primer prior to application of finish coat. with Sto Detail Mesh required for projections greater than 2 inches (51 mm).
2. Minimum required slope is 1:2 (27 degrees) and maximum width is 12 inches (300 mm). Increase slope for northern climates to prevent accumulation of ice/snow and water on surface. Periodic inspections and increased maintenance of coating may be required.
3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Structuralframe
Secondary weatherresisitive barrier
Sheathing
Sto InsulationBoard
Sto Detail Meshembedded inSto Base Coat
Sto Finish Coat
Minimum 2-1/2"(64 mm) meshoverlap
Minimum 2-1/2"(64 mm) meshoverlap
Sto Detail Meshembedded in Sto Base Coat
Sto Adhesive
Sto Flexyl withSto Detail Meshembedded(See note 1)
Drainage mat
Date: October 2007
Detail No.: 8.10StoTherm™ Rainscreen IIGrade Condition with Waterproof Foundation
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Not recommended to extend finish coat below grade. Terminate finish coat minimum 8" (203 mm) above grade, higher for snow regions.
2. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Secondary weather resistive barrier
Sto Adhesive
Sto Insulation Board
Sto Detail Mesh embedded in Sto Base Coat
Drainage mat
Sto Detail Mesh embedded in Sto Flexyl Base Coat (Primed with Sto Primer)
Drainage mat
Perforated drainage tubing
Sto Armor Mat embedded in Sto Base Coat
Drainage material
Backfill
Sto Flexyl
Sto Finish Coat
Starter track with weep holes
Sheathing
Note: Protect against rising damp at sill plate as required
Date: October 2007
Detail No.: 8.20StoTherm™ Rainscreen IIPan Flashing at Window Sill
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Install flexible membrane flashing minimum 4" (102 mm) up jambs of rough opening to create end dams.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
EIFS
backwrapSto Adhesive
Sto Insulation Board
Sto Detail Meshembedded inSto Base Coat
Sto Finish Coat
Structuralframe
Window sill
Sealant andbacker rod
Secondary weatherresistive barrier
Drainage matSheathing
Flexiblewallflashing
Air seal(Completewindow perimeter)
Date: October 2007
Detail No.: 8.20AStoTherm™ Rainscreen IIPan Flashing at Window Sill(Window with No Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
2. Weep holes to be provided every 2 feet (610 mm) through the backer rod and sealant and at window corners and mullions.
EIFS
backwrap
Sto InsulationBoard
Sto Detail Meshembedded inSto Base Coat
Sto Finish Coat
Structuralframe
Window sill
Secondaryweather resistive barrier
Sheathing
Windowpan flashing withend dam
Sealant
Air Seal(Completewindowperimeter)
Backer rod and sealant (See Note 2)
Drainage mat
Sto Adhesive
Date: October 2007
Detail No.: 8.20BStoTherm™ Rainscreen IIFlashing at Window Sill with EIFS Trim(Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Install flexible membrane flashing minimum 4" (102 mm) up jambs of rough opening to create end dams.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
5. EIFS sill slope minimum1:2 (27 degrees).
6. EIFS sill trim pre-wrapped with base coat and reinforcing mesh on top and bottom. Leave face exposed for mechanical attachment. Attach every 8 inches (209 mm) on center and no more than 4 inches (102 mm) from ends with appropriate fastener. Then adhesively attach final trim piece.
EIFS
backwrap
Sto Adhesive
Drainage mat
Sto Insulation Board
Sto Detail Meshembedded inSto Base Coat
Sto Finish Coat
Structuralframe
Window sill
Sealant and backer rod
Sheathing
Flexiblemembraneflashing
Secondaryweatherresistivebarrier
Metal or plasticwindow flashing
Air Seal(Completewindowbarrier)
Date: October 2007
Detail No.: 8.21StoTherm™ Rainscreen IIFlashing at Window Head(Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Weep holes to be provided every 2 feet (610 mm) through the sealant joint above the flashing.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
EIFS
backwrap
Airseal(Completewindow perimeter)
Sto Adhesive
Sto Insulation Board
Sto Detail Meshembedded inSto Base Coat
Sto Finish Coat
Drainage mat
Structuralframe
Sealant and backer rod(See Note 3)
Window headflashing (per windowmanufacturer’srecommendations)
Sheathing
Secondaryweatherresisitivebarrier
Sealant bead
Date: October 2007
Detail No.: 8.21BStoTherm™ Rainscreen IIFlashing at Window Head with EIFS Trim(Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Weep holes to be provided every 2 feet (610 mm) through the sealant joint above the flashing.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
5. EIFS trim slope minimum 1:2 (27 degrees).
Sto Insulation Board
Sto Detail Mesh embedded in Sto Coat
Sto Finish Coat
Structural frame
Nailing flange
Window head flashing (per window manufacturer’s requirements)
Sheathing
Secondary weather resistive barrier
Sealant bead
Sealant and backer rod (See Note 3)
Air seal (complete window perimeter)
Drainage mat
Sto Adhesive
Date: October 2007
Detail No.: 8.21CStoTherm™ Rainscreen IIFlashing at Window Head with EIFS Trim and Drip Edge (Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, water- proof building paper or equivalent).
4. EIFS trim slope minimum 1:2 (27 degrees).
5. Embed starter track attachment flange in sealant before securing to substrate.
Starter track
Sheathing
Structuralframe
Nailingflange
Secondary weather resistivebarrier
Airseal(completewindowperimeter)
Drainage mat
Sto Adhesive
Sto Insulation Board
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
Window headflashing (per windowmanufacturer’srequirements)
Sealant bead
Date: October 2007
Detail No.: 8.22StoTherm™ Rainscreen IIWindow Jamb (Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, water- proof building paper or equivalent).
Drainage mat
Structural frame
EIFS backwrap
Air seal (completewindow perimeter)
Window jamb
Sill below
Sealant and backer rod
Secondary weatherresistive barrier
Sto Adhesive
Sto Insulation Board
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
Date: October 2007
Detail No.: 8.22BStoTherm™ Rainscreen IIWindow Jamb with EIFS Trim(Window with Nailing Flange)
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) depth from back of insulation board to face of window frame for sufficient depth to install sealant.
2. Provide minimum 1/2" (13 mm) sealant joint width.
3. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Sto Insulation Board
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
Secondary weather resistive barrier
Sealant and backer rod
Window jamb
Sill below
Air seal (Complete window perimeter)
Sto Adhesive
Structural frame
Drainage mat
EIFS backwrap
Date: October 2007
Detail No.: 8.30StoTherm™ Rainscreen IIExpansion Joint at Floorline
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Similar joint required at attic floor line along gable end walls.
2. Gap wood sheathing edge and end joints in accordance with APA (American Plywood Association) recommendations. Gap at expansion joint the same dimension as the joint.
3. Locate expansion joint no lower than centerline of end joist.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
5. Secondary weather resistive barrier continuous at expansion joint.
Sto Adhesive
Sto Insulation Board
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
SheathingStructural frame
Sealant and backer rod
3/4" (19 mm) minimum
(See Note 3)
Drainage mat
Secondary weather resistive barrier
Flexible membrane flashing
EIFS backwrap
Date: October 2007
Detail No.: 8.31StoTherm™ Rainscreen IIExpansion Joint at Floorline with EIFS Accent Board
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 3/4" (19 mm) sealant joint width.
2. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
3. StoTherm trim slope minimum 1:2 (27 degrees).
Sheathing
Structural frame
Sto Adhesive
Sto Adhesive
Secondary weather resistive barrier
EIFS backwrap
Flexible membrane flashing
Sto Insulation Board
Sto Adhesive to attach EIFS accent
Sealant and backer rod
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
Date: October 2007
Detail No.: 8.32StoTherm™ Rainscreen IIWood Deck Connection
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Gap wood sheathing edge and end joints in accordance with APA (American Plywood Association) recommendations.
2. Seal penetrations through flashing where attached to framing.
3. Distance of EIFS to deck varies with climate. Allow sufficient distance to prevent snow/ice and puddling water against system.
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
5. Pressure treated wood (space from flashing or route backside to provide drainage).
Starter track
Secondary weather resistive barrier
Sto Insulation Board
Sheathing
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
4" (100 mm) minimum
2" (50 mm) minimum
SealantSecondary weather resistive barrier
(See Note 5)
Drainage mat
EIFS backwrap
Sto Adhesive
Structural frame
Drainage mat
Continuous leakproof flashing with end dams (as required by code)
Date: October 2007
Detail No.: 8.62StoTherm™ Rainscreen IIEave and Flashing at Roof/Wall Intersection
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide leakproof flashing (as required by code) to prevent water from draining into wall.
2. Drill several, evenly spaced weep holes in the base of the starter track within 1” (25 mm) of the termination at the diverter flashing to allow for completedrainage.
2” (50 mm) typical
2” (50 mm) minimum
Step Flashing (See Note 3)
Sealant and backer rod (minimum 1/2” (13 mm) sealant joint width)
Secondary weather resistive barrier as required by local code
Sto Detail Mesh embedded in Sto Base Coat
Sto Finish Coat
Sto Insulation Board
Sto Adhesive
Secondary weather resistive barrier as required by local code
Diverter flashing (See Note 1)
Drainage mat
Drainage mat
Starter track with weep holes minimum 2” (50 mm) above roof line (See Note 2)
Date: October 2007
Detail No.: 8.71StoTherm™ Rainscreen II Surface Mount FixturePenetration through the System
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Provide minimum 1/2" (13 mm) sealant joint width.
2. Flexible membrane flashing to be installed around electrical conduit.
3. Pressure treated wood (space from flashing or route back side to provide drainage).
4. Secondary weather resistive barrier as required by local code, (e.g., Southern Building Code, minimum one layer Type 15 felt, waterproof building paper or equivalent).
Drainage mat
Sto Insulation Board
Sto Adhesive
Sheathing
(See Note 3)
Wood blocking
Electrical conduit
Secondary weather resistive barrier
Flexible membrane flashing
EIFS Backwrap
Washer embedded in sealant
Light fixture
Sealant and backer rod
Sto Finish Coat
Sto Detail Mesh embedded in Sto Base Coat
Date: October 2007
Detail No.: 8.72StoTherm™ Rainscreen IIDownspout Attachment
www.stocorp.comATTENTIONSto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESS OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Notes:
1. Distance to grade varies with climate. Allow sufficient distance to prevent snow/ice and puddling water against system.
Sto Adhesive
Sto Insulation Board
Sto Detail Meshembedded inSto Base Coat
Sto Finish
Sheathing
Structuralframe
Backwrap
Sealant andbacker rod
Gutter strap
Plastic sleeve
Sealant
Washer bedded in sealant
Sto Armor Matembedded in Sto Base Coat
8" (200 mm)typical(See Note 1)
Sto Flexyl towaterproof foundation(Sto Mesh optional)