Stairs Closed tread construction with 2000mm min head clearance measured in accordance with Part K R= 216*mm G= 260 2R+ G = 662 * subject to final measure on site Handrail between 900mm and 1100mm high measured from the pitch line of the stairs. Roof Warm roof construction (no ventilation required) Metal web joists (Posi Joists or similar), design and calculations to be supplied by manufacturer allowing for snow loading and option of PV . supported on mild steel joist hanger manufactured to BS EN 10327 : 2004 . Fix firings to joists to fall to centre valley gutter min 1:80 with 18mm plyboard deck, fixed to every joist with 5mm dia. x 50mm long screws @ 500 crs (250 crs at both ends). Install vapour barrier (VCL) and protective layer as specified by Kingspan over deck before installing approximately 70mm* Kingspan OPTIM-R vacuum insulation with 25mm Kingspan Thermaroof TR27 over and finish with Classic Bond EPDM fully adhered with adhesive. All in accordance with manufacturers instructions. * Final specification of insulation by Kingspan to confirm minimum 0.12W/m2K Ceiling 3mm skim plastered 12.5mm pl/bd. Parapet Dales Weatherstruck Meridian (or eqiv.)Polyester Powder coated to BS 12206-1:2004, by Syntha Pulvin Approved and BS EN IOS 9002 registered applicators: Polyester Powder coating must be A2 s1, d0 limited combustibility (EN 13501-1: 2018 Classification of reaction to fire), colour to match render or door frames (tbc) and fitted in accordance with manufacturers instructions to BS 5642. DESCRIPTION DRAWING NO. DRAWN CHECKED DATE SCALE A. Davis -------- Building Regulations Sheet 2 REV DATE TITLE 22/05/2021 1/50 @A1 CF20 BAF 02 PSK CHELTENHAM LIMITED, Unit B4, Staverton Connection Gloucester Road, Cheltenham, GL51 0TF Tel: 01452 714 596 www.psk-architect.co.uk ELEC. GAS Flue : Rear entry factory made proprietary single walled metal flue certified to comply with relevant sections of BS 4543-1:1990 (1996), BS 4543-2:1990 (1996) and BS 4543-3:1990 (1996) (Part 1 withdrawn April 2000; partially superseded by BS EN 1859:2000) and installed on accordance with the relevant recommendations in BS 7566-1:1992(1998), BS 7566-2:1992(1998), BS 7566-31992(1998) and BS 7566-4:1992(1998). Insert inspection and cleaning openings a s required to terminate a minimum of 1000mm above weather surface. Alternatively install Isokern Pumice or equivalent proprietary modular chimney system in accordance with manufacturers instruction and current building regulations. Hearth: Provide hearth (minimum 12mm thick ) which has been independently certified that it cannot cause the temperature of the hearth to exceed 100 deg. or provide solid hearth, such as concrete or masonry, at least 125mm thick including the thickness of the non -combustible floor and or decorative surface, sample to be approved by client. All in accordance with Building Regulation Part J and appliance suppliers specification projecting a minimum of 150mm from the sides and 225mm at the front of the appliance although we would recommend a larger projection from the front to protect the floor from any material which might fall out of the appliance during loading or cleaning out. Air Supply: Provide air supply for stove via a 100mm dia insulated duct fed directly from the outside through a Cavibrick by Cavity Trays in outer wall of chimney with free airflow of 7500mm/sq per brick with conversion piece (rectangular to round fitting, with cavity tray over). Provide air directly via fresh air box to stove in accordance with manufacturers specifications (closed combustion system). This drawing is copyright and should not be reproduced without permission. Do not scale from drawing for dimensions. If in doubt contact main contractor before proceeding. The contractor is responsible for checking all information before any orders are placed or construction commences. All drawings to be read in conjunction with structural engineers report, structural engineers report to take precedence over all other specifications. Main contractor responsible for site safety. 1: 50 at A1 0m 5 m 1 2 3 4 side elevations FRONT FRONT

Upload: others

Post on 03-Jun-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELEC. GAS - psk-architect.co.uk

Stairs Closed tread construction with 2000mm min head clearance measured in accordance with Part K

R= 216*mmG= 2602R+ G = 662

* subject to final measure on site

Handrail between 900mm and 1100mm high measured from the pitch line of the stairs.

Roof Warm roof construction (no ventilation required) Metal web joists (Posi Joists or similar), designand calculations to be supplied by manufacturer allowing for snow loading and option of PV .supported on mild steel joist hanger manufactured to BS EN 10327 : 2004 . Fix firings to joiststo fall to centre valley gutter min 1:80 with 18mm plyboard deck, fixed to every joist with 5mmdia. x 50mm long screws @ 500 crs (250 crs at both ends). Install vapour barrier (VCL) andprotective layer as specified by Kingspan over deck before installing approximately 70mm*Kingspan OPTIM-R vacuum insulation with 25mm Kingspan Thermaroof TR27 over and finishwith Classic Bond EPDM fully adhered with adhesive. All in accordance with manufacturersinstructions.

* Final specification of insulation by Kingspan to confirm minimum 0.12W/m2K

Ceiling 3mm skim plastered 12.5mm pl/bd.

Parapet Dales Weatherstruck Meridian (or eqiv.)Polyester Powder coated to BS 12206-1:2004, bySyntha Pulvin Approved and BS EN IOS 9002 registered applicators: Polyester Powder coatingmust be A2 s1, d0 limited combustibility (EN 13501-1: 2018 Classification of reaction to fire),colour to match render or door frames (tbc) and fitted in accordance with manufacturersinstructions to BS 5642.

DESCRIPTION

DRAWING NO.

DRAWN CHECKED

DATE SCALE

A. Davis --------

Building RegulationsSheet 2

REV DATE

TITLE

22/05/2021 1/50 @A1

CF20 BAF 02

PSK CHELTENHAM LIMITED, Unit B4, Staverton ConnectionGloucester Road, Cheltenham, GL51 0TF

Tel: 01452 714 596 www.psk-architect.co.uk

ELEC. GAS

Flue : Rear entry factory made proprietary single walled metal flue certified to comply with relevantsections of BS 4543-1:1990 (1996), BS 4543-2:1990 (1996) and BS 4543-3:1990 (1996)(Part 1 withdrawn April 2000; partially superseded by BS EN 1859:2000) and installed on accordance with the relevant recommendations in BS 7566-1:1992(1998),BS 7566-2:1992(1998), BS 7566-31992(1998) and BS 7566-4:1992(1998). Insert inspection and cleaning openings as required to terminate a minimum of 1000mm aboveweather surface.

Alternatively install Isokern Pumice or equivalent proprietary modular chimney system inaccordance with manufacturers instruction and current building regulations.

Hearth: Provide hearth (minimum 12mm thick ) which has been independently certified that it cannotcause the temperature of the hearth to exceed 100 deg. or provide solid hearth, such asconcrete or masonry, at least 125mm thick including the thickness of the non -combustiblefloor and or decorative surface, sample to be approved by client. All in accordance withBuilding Regulation Part J and appliance suppliers specification projecting a minimum of150mm from the sides and 225mm at the front of the appliance although we would recommend a larger projection from the front to protect the floor from any material whichmight fall out of the appliance during loading or cleaning out.

Air Supply: Provide air supply for stove via a 100mm dia insulated duct fed directly from the outsidethrough a Cavibrick by Cavity Trays in outer wall of chimney with free airflow of 7500mm/sqper brick with conversion piece (rectangular to round fitting, with cavity tray over). Provide air directly via fresh air box to stove in accordance with manufacturers specifications(closed combustion system).

This drawing is copyright and should not be reproduced without permission.Do not scale from drawing for dimensions. If in doubt contact main contractor beforeproceeding.The contractor is responsible for checking all information before any orders areplaced or construction commences.All drawings to be read in conjunction with structural engineers report, structuralengineers report to take precedence over all other specifications.Main contractor responsible for site safety.

1:50 at A1

0m 5m1 2 3 4

side elevations

FRONT

FRONT

AutoCAD SHX Text
600min,1050max
AutoCAD SHX Text
frost resistant F2 brick finished 1 course above DPC. DPC 150mm min above adjacent ground level at highest point
AutoCAD SHX Text
Expansion joint formed with stainless steel lateral restraint slip ties and compressible materials as specified by structural engineers (concealed behind down pipes
AutoCAD SHX Text
full height PAS 24 composite door with powder coated or wood veneered finish and level threshold.
AutoCAD SHX Text
Install ACO style slot drain infront of windows and lay internal floor level through with patio with a similar detail to the sliding doors ensuring DPC, DPM and weather seal are completed to the satisfaction of Building Control on site.
AutoCAD SHX Text
exterior tap
AutoCAD SHX Text
white self colour render
AutoCAD SHX Text
meter boxes with cavity trays over and weep holes
AutoCAD SHX Text
MHRV input end extract on different elevation to prevent cross contamination
AutoCAD SHX Text
Expamet mechanically fixed to WBP Plywood and rendered in accordance withrender manufacturers instructions.
AutoCAD SHX Text
powder coated aluminium flashing white or RAL 9006 to match door and window frames
AutoCAD SHX Text
white self colour render
AutoCAD SHX Text
Cavibricks by Cavity Trays, inserted into outer wall to cross s by Cavity Trays, inserted into outer wall to cross by Cavity Trays, inserted into outer wall to cross ventilate floor using Cavity Trays Type TAV telescopic adjustable ventilator (cranked cavisleeve) with cavity tray over installed in accordance with manufactures instructions to give a minimum of 1500mm2 ventilation per metre length of external wall.
AutoCAD SHX Text
Cavibricks by Cavity Trays, inserted into outer wall to cross s by Cavity Trays, inserted into outer wall to cross by Cavity Trays, inserted into outer wall to cross ventilate floor using Cavity Trays Type TAV telescopic adjustable ventilator (cranked cavisleeve) with cavity tray over installed in accordance with manufactures instructions to give a minimum of 1500mm2 ventilation per metre length of external wall.
AutoCAD SHX Text
Provide air supply for balanced flue stove via a 100mm duct fed directly from the outside through a Cavibrick by Cavity Trays. Provide air directly to stove via fresh air box in accordance with manufacturers specifications (closed combustion system).
AutoCAD SHX Text
Expamet mechanically fixed to WBP Plywood and rendered in accordance withrender manufacturers instructions.
AutoCAD SHX Text
100 x 75 ALUMASC Flushjoint rectangular powder coated aluminium downpipe white or RAL 9006 to match door and window frames
AutoCAD SHX Text
100 x 75 ALUMASC Flushjoint rectangular powder coated aluminium downpipe white or RAL 9006 to match door and window frames
AutoCAD SHX Text
glass screen minimum of 1100mm high able to resist 0,74kN/m2 minimum, complying with Diagram 3.1 of K2 of the Building Regulations
AutoCAD SHX Text
Aluminium or white upvc angle edging with fixings in top only approved by EPDM supplier.
AutoCAD SHX Text
Aluminium or white upvc angle edging with fixings in top only approved by EPDM supplier.
AutoCAD SHX Text
white self colour render
AutoCAD SHX Text
white self colour render
AutoCAD SHX Text
white self colour render