    RVS COLLEGE OF ENGINEERING &TECHNOLOGY

    (Approved by AICTE and affiliated to Anna University- Chennai)

    Kumaran Kottam., Sulur, Coimbatore - 641402.

    DEPARTMENT OF

    ELECTRICAL AND ELECTRONICS ENGINEERING

    ELECTRICAL MACHINES

    LABORATORY LAB MANUAL

    R2013

    STUDENT NAME : ..

    REGISTER NUMBER : ..

    DEPARTMENT: ..

  • 7/25/2019 electrical machines lab manual for petrochemaical

    2/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    1

    EI6411 ELECTRICAL MACHINES LABORATORY L T P C

    0 0 3 2

    OBJECTIVE:

    To impart hands on experience in verification of circuit laws and theorems, measurement of

    circuit parameters, study of circuit characteristics and simulation of time response. To expose

    the students to the basic operation of electrical machines and help them to develop experimental

    skills.

    LIST OF EXPERIMENTS.

    1. Open circuit characteristics of D.C. shunt generator.

    2. Load characteristics of D.C. shunt generator.

    3.

    Load test on D.C. Shunt Motor.

    4. Load test on D.C. Series Motor.

    5. Swinburnes test

    6.

    Speed control of D.C. Shunt Motor.

    7. Load test on Single Phase Transformer

    8. Open circuit and Short circuit tests on Single Phase Transformer (Determination of

    equivalent circuit parameters).

    9.

    Load test on Single Phase Induction Motor.

    10.No load and blocked rotor tests on Three Phase Induction Motor (Determination of

    equivalent circuit parameters)

    11.Load test on Three Phase Induction Motor.

    12.Study of Starters

    TOTAL: 45 PERIODS

    OUTCOME:

    Ability to understand and analyze Instrumentation systems and their applications to

    various industries.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    3/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    2

    CYCLE I

    CYCLE II

  • 7/25/2019 electrical machines lab manual for petrochemaical

    4/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    3

    SUMMARY OF EXPERIMENTS

    (Fill in the order by which done)

    Ex.No. Date Experiment Name Page No. Mark Staff Signature

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    Average

  • 7/25/2019 electrical machines lab manual for petrochemaical

    5/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    4

    CIRCUIT DIAGRAM FOR OPEN CIRCUIT ON SEPERATELY EXCITED DC GENERATOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    6/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    5

    OPEN CIRCUIT TEST CHARACTERISTIC OF SEPARATELY

    EXCITED DC GENERATOR

    AIM:

    To conduct the open circuit test on a given separately excited dc generator and

    draw the characteristic curves.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1. Voltmeter MC (0-300)V 1

    2. Ammeter MC (0-2) A 1

    3. Rheostat Wire Wound 400 / 1.1 A 1

    4. Rheostat Double element 350 / 2A 1

    5. Tachometer Digital - 1

    6. Connecting Wires - - As Req.

    FUSE RATING:

    110-125% of rated current (full load current).

    PRECAUTION:

    The motor field rheostat should be kept at minimum resistance position.

    The generator field rheostat should be kept at maximum resistance position.

    FORMULAE USED:

    1.

    Generated voltage Eg = VL + IaRain Volts.

    Where, VLLoad voltage in Volts.

    Ia - Armature current in Amps.

    Ra - Armature resistance in Ohms.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    7/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    6

    CIRCUIT DIAGRAM FOR ARMATURE RESISTANCE

    TABLE 1: OPEN CIRCUIT TEST

    S. No

    Field current

    (If)

    Amps

    Open Circuit Voltage

    (Eo)

    Volts

  • 7/25/2019 electrical machines lab manual for petrochemaical

    8/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    7

    PROCEDURE:

    OPEN CIRCUIT TEST:

    1.

    Note down the nameplate details of motor.

    2. Connections are made as per the circuit diagram shown in diagram.

    3.

    Initially SPST Switch is kept open.

    4. Supply is given by closing the DPST Switch in the motor side.

    5. Using the DC three point starter, start the motor.

    6.

    The field rheostat of motor is adjusted to run the motor at rated speed.

    7. Emf generated due to residual magnetism in the generator is noted along with the zero

    value field current.

    8. Then, the SPST Switch is closed. Increase the field current in steps of 0.1 Amps by

    varying the resistance of the generator field and note down the corresponding open

    circuit voltages in Table (1).

    TO FIND ARMATURE RESISTANCE:

    1. Connections are made as per the circuit diagram shown in diagram.

    2.

    Supply is given by closing the DPST Switch and increase the load step by step.3. Enter the corresponding ammeter and voltmeter readings in Table (2).

  • 7/25/2019 electrical machines lab manual for petrochemaical

    9/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    8

    TABLE 2: TO FIND ARMATURE RESISTANCE

    S. No. Current Ia (Amps) Voltage V (Volts) Ra=V/Ia ( )

    Average value of R a=

    MODEL GRAPH:

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    10/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    9

    RESULT:

    VIVA QUESTIONS:

    1. What is the function of carbon brush used in D.C generator?

    2. What is meant by self-excited and separately excited dc generator?

    3. What is the basic difference between dc generator and dc motor

    4.

    Write down the emf equation of dc generator. Give the meaning of each symbol.5. What is critical resistance of a DC shunt generator?

    6. What are the conditions to be fulfilled for a shunt generator to build up Voltage?

    7. What do you mean by residual flux in DC generator?

  • 7/25/2019 electrical machines lab manual for petrochemaical

    11/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    10

    CIRCUIT DIAGRAM FOR LOAD TEST ON SELF EXCITED DC SHUNT GENERATOR

    FUSE RATING125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    12/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    11

    LOAD TEST ON SELF EXCITED DC SHUNT GENERATOR

    AIM:

    To conduct the load test on a given self-excited dc shunt generator and draw the

    characteristic curves.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1. Voltmeter MC (0-300)V 1

    2. Ammeter MC(0-10) A

    (0-2) A

    1

    1

    3. Rheostat Wire Wound400 / 1.1 A

    360 / 2 AEach 1

    4. Tachometer Digital - 1

    5. Connecting Wires - - As Req.

    6 Loading Rheostat Wire Wound - 1

    FUSE RATING: 110-125% of rated current (full load current).

    PRECAUTIONS:

    1. All connections should be perfectly tight and no loose wire should lie on the work

    table.

    2. Before switching ON the dc supply, ensure that the starters moving arm is at its

    maximum resistance position.

    3.

    There should be no load on the motor at the time of starting.4. At the time of starting, the field circuit rheostat is in minimum resistance position.

    5. Hold the tachometer with both hands steady and in line with the motor shaft so that it

    reads correctly.

    FORMULAE USED:

    1. Generated voltage (Eg) = VL + Ia Rain Volts.

    Where,

    VL- Load voltage in Volts.Ia- Armature current in Amps & Ra- Armature resistance in Ohms.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    13/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    12

    CIRCUIT DIAGRAM FOR ARMATURE RESISTANCE

    TABLE 1: LOAD TEST

    S

    .No

    IL

    Amps

    If

    Amps

    Ia= IL- If

    Amps

    Terminal

    Voltage

    (VL)

    Volts

    IaRa

    Volts

    E g=VL+ IaRa

    Volts

  • 7/25/2019 electrical machines lab manual for petrochemaical

    14/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    13

    PROCEDURE:

    LOAD TEST:

    1.

    Note down the nameplate details of motor.

    2. Connections are made as per the circuit diagram shown diagram.

    3.

    Supply is given by closing the DPST Switch in the motor side.

    4. Using the DC three point starter, start the motor.

    5. The field rheostat of motor is adjusted to run the motor at rated speed.

    6.

    The generator field rheostat is adjusted for the rated voltage.

    7. The DPST switch in the generator side is closed. Increase the resistive load in steps of

    2 Amps and note down the corresponding load current and terminal voltage values in

    Table (1).

    8. Then the resistive load is gradually decreased and the DPST Switch on the generator

    side is open. Then the supply is switched off.

    9. The generated voltage Egis calculated by using the formulae as mentioned above and

    enter the values in the Table (1).

    TO FIND ARMATURE RESISTANCE:

    1. Connections are made as per the circuit diagram shown in diagram.

    2. Supply is given by closing the DPST switch and increases the load step by step.

    3.

    Enter the corresponding ammeter and voltmeter readings in Table (2).

  • 7/25/2019 electrical machines lab manual for petrochemaical

    15/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    14

    TABLE 2: TO FIND ARMATURE RESISTANCE.

    S. No.

    Current

    Ia

    (Amps)

    Voltage

    V

    (Volts)

    Ra=V/Ia

    ( )

    Average value of R a=

    MODEL GRAPH:

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    16/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    15

    RESULT:

    VIVA QUESTIONS:

    1. State the various types of DC generators.

    2. List the main parts of DC machine.

    3.

    State the applications of various types of DC generators.

    4. What is residual voltage?

    5.

    Difference between self-excited and separately excited of DC generator.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    17/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    16

    CIRCUIT DIAGRAM FOR LOAD TEST ON D.C SHUNT MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    18/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    17

    LOAD TEST ON DC SHUNT MOTOR

    AIM:

    To conduct the load test on DC shunt motor and draw the characteristic curves.

    APPARATUS REQUIRED:

    S. No APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MC (0-20) A 1

    2 Voltmeter MC (0-300) V 1

    3 Tachometer Digital - 1

    4 Rheostat Wire Wound 400 / 1.1 A 1

    5 Connecting Wires - - As Req.

    FUSE RATING:

    110-125% of rated current (full load current).

    PRECAUTIONS:

    1. All connections should be perfectly tight and no loose wire should lie on the work

    table.

    2.

    Before switching ON the dc supply, ensure that the starters moving arm is at its

    maximum resistance position.

    3. There should be no load on the motor at the time of starting.

    4.

    At the time of starting, the field circuit rheostat is in minimum resistance position.

    5. Hold the tachometer with both hands steady and in line with the motor shaft so that it

    reads correctly.

    FORMULAE USED:

    1. Torque T = (S1~S2) (R) 9.81 in N-m.

    Where,

    R- Radius of the Brake drum in m.

    t- Thickness of the Belt in m.

    S1, S2- Spring balance reading in Kg.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    19/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    18

    TABULATION:

    Radius of the brake drum:

    S. No

    Load

    Current

    (IL)

    Amps

    Load

    Voltage

    ( VL)

    Volts

    Input

    Power

    ( Pi)

    Watts

    Speed

    ( N )

    rpm

    Spring Balance Reading

    (Kg)

    Torque

    (T)

    N-m

    Input

    Power

    (Pin)

    Watts

    Output

    Power

    (PO)

    Watts

    Efficiency

    ( )%

    S1 S2 S1~S2

  • 7/25/2019 electrical machines lab manual for petrochemaical

    20/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    19

    2. Input power = VL ILin Watts.

    Where,

    VL - Load Voltage in Volts.

    IL -Load current in Amps.

    3. Output power = 2NT/60 in Watts.

    Where,

    N- Speed of the armature in rpm.

    T- Torque in N-m.

    4. Percentage of Efficiency = (Output power/Input power) 100.

    PROCEDURE:

    1.

    Connections are given as per the circuit diagram.

    2. Using the three-point starter the motor is started to run at the rated speed by adjusting

    the field rheostat if necessary.

    3.

    The meter readings are noted at no load condition.

    4. By using the Brake drum with spring balance arrangement the motor is loaded and the

    corresponding readings are noted up to the rated current.

    5.

    After the observation of all the readings the load is released gradually.

    6. Load is gradually decreased and field rheostat is brought to the minimum resistance

    position and the supply is switched off.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    21/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    20

    MODEL GRAPH:

    Electrical Characteristics Mechanical Characteristics

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    22/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    21

    RESULT:

    VIVA QUESTION:

    1. How do you load the motor in this experiment?

    2.

    What was the assumption made in calculations?

    3. What is the condition for maximum torque of a D.C. shunt motor?

    4. Why is the starter necessary?

    5.

    What is the power factor of the load used?

  • 7/25/2019 electrical machines lab manual for petrochemaical

    23/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    22

    CIRCUIT DIAGRAM FOR LOAD TEST ON D.C. SERIES MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    24/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    23

    LOAD TEST ON D.C. SERIES MOTOR

    AIM:

    To conduct load test on DC series motor and determine the load characteristics.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1. Voltmeter MC (0-300V) 1

    2. Ammeter MC (0-20A) 1

    3. Tachometer Digital - 1

    4. Connecting wires - - As Req.

    PRECAUTIONS:

    The series motor should be started with some minimum load.

    Water should be poured in the hollow portion of brake drum.

    Motor should be stopped with some minimum load.

    After shut down, the load should be fully released, so as to make the drum free of cool.

    FORMULAE USED:

    1 . Torque applied on the motor, T = (S1~S2) x r x 9.81 Nm.

    2. Input Power (Pi) = VL x ILWatts.

    Output, P0 = (2NT)/60 Watts.

    3. % Efficiency, = (Po/Pi) x 100.

    Where,

    Circumference of the brake drum, 2 r = ---------- m2

    Radius of the brake drum, r = ---------- m

    S1&S2spring balance readings in kg.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    25/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    24

    TABULATION:

    Sl. No

    Line

    voltage

    VL Volts

    Line

    current

    IL

    Amps

    Speed

    N

    (rpm)

    Spring balance

    reading

    Torque

    T (N.m)

    OutputPower

    P0

    Watts

    InputPower

    Pi

    Watts

    % Efficiency

    S1

    Kg

    S2

    Kg

    1

    2

    3

    4

    5

  • 7/25/2019 electrical machines lab manual for petrochemaical

    26/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    25

    PROCEDURE:

    1. Connections are made as per the circuit diagram.

    2. Supply is given by closing DPSTS.

    3.

    Start the motor using the starter.4. Note down the readings for varying load conditions and plot the graph.

    MODEL CALCULATION:

    RESULT:

    VIVA QUESTIONS:

    1.

    Why the series motor is started with some minimum load?

    2. What are the applications of D.C. series motor?

    3. Why series motors are used for traction purpose?

    4. While running, if series field winding is opened what happens?

  • 7/25/2019 electrical machines lab manual for petrochemaical

    27/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    26

    CIRCUIT DIAGRAM FOR SWINBURNS TEST

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    28/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    27

    SWINBURNES TEST

    AIM:

    To predetermine the efficiency of a given dc shunt machine when working as a motor

    as well as generator by Swinburnes test and also draw the characteristic curves.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1. Voltmeter MC( 0-300 ) V

    ( 0-50 ) V

    1

    1

    2. Ammeter MC

    (0-5) A

    (0-2) A

    1

    1

    3. RheostatWire

    Wound

    400 / 1.1 A 1

    4 Loading RheostatWire

    Wound50 / 5 A 1

    5. Tachometer Digital - 1

    6. Connecting Wires - - As Req

    FUSE RATING:

    110-125% of rated current (full load current).

    PRECAUTIONS:

    1.

    All connections should be perfectly tight and no loose wire should lie on the work

    table.

    2. Before switching ON the dc supply, ensure that the starters moving arm is at its

    maximum resistance position.

    3. There should be no load on the motor at the time of starting.

    4.

    At the time of starting, the field circuit rheostat is in minimum resistance position.

    5. Hold the tachometer with both hands steady and in line with the motor shaft so that it

    reads correctly.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    29/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    28

    CIRCUIT DIAGRAM FOR ARMATURE RESISTANCE

    TABLE 1: TO FIND CONSTANT LOSSES

    TABLE 2: TO FIND ARMATURE RESISTANCE Ra

    S.NO INPUT

    SUPPLY

    VOLTAGE

    (Volts)

    NO LOAD

    CURRENT

    I 0(Amps)

    FIELD

    CURRENT

    I f(Amps)

    ARMATURE

    CURRENT

    Iao=I 0- I f(Amps)

    CONSTANT

    LOSSES

    Wo

    = VI0I ao2Ra(Watts)

    S.NO CURRENT

    Ia( Amps )

    VOLTAGE

    V

    ( Volts )

    ARMATURE RESISTANCE

    Rdc= V / Ia

    (Ohms)

    1.

    2.

    3.

    4.

    5.

    Average value of Ra =

  • 7/25/2019 electrical machines lab manual for petrochemaical

    30/76

  • 7/25/2019 electrical machines lab manual for petrochemaical

    31/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    30

    TABLE (3): CALCULATION OF EFFICIENCY AS A MOTOR:

    Constant Loss: Calculated value from Table (1)

    TABLE (4): CALCULATION OF EFFICIENCY AS A GENERATOR:

    S.

    No Load Current

    I

    (Amps)

    Armature

    Current

    Ia=I - I f(Amps)

    Armature

    Copper loss

    = I a2R a(Watts)

    Total Losses

    = Wo+I a2Ra

    (Watts)

    Input

    V I

    (Watts)

    Output =

    Inputlosses

    (Watts)

    Efficiency

    =(output/

    input)x100

    (Percentage)

    1. thofrated value

    2. th

    ofrated value

    3. thofrated value

    4. Rated value

    S.

    No

    Load

    Current

    I

    (Amps)

    Armature

    Current

    Ia=I + I f(Amps)

    Armature

    Copper loss

    = I a2R a(Watts)

    Total Losses= Wo+I a2Ra

    (Watts)

    Output

    V I(Watts)

    Input =Output +Losses

    (Watts)

    Efficiency

    =(output/

    Input)x100

    (Percentage)

    1. thof

    rated value

    2. thofrated value

    3. t of

    rated value

    4. Rated value

  • 7/25/2019 electrical machines lab manual for petrochemaical

    32/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    31

    MODEL GRAPH:

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    33/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    32

  • 7/25/2019 electrical machines lab manual for petrochemaical

    34/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    33

    RESULT:

    VIVA QUESTION:

    1. What is the function of no-volt release coil in 3point starters?

    2. How to change the direction of rotation of d.c motor?

    3. Swinburnestest is also called?4. List the various losses in d.c machine.

    5.

    Name the various methods of testing the d.c machine.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    35/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    34

    CIRCUIT DIAGRAM FOR SPEED CONTROL OF DC SHUNT MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    36/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    35

    SPEED CONTROL OF DC SHUNT MOTOR

    AIM:

    To control the speed of the given DC shunt motor by field and armature control methods

    and also to draw their characteristics curves.

    APPARATUS REQUIRED:

    S. No APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MC (0-2) A 1

    2 Voltmeter MC (0-300) V 13 Tachometer Digital - 1

    4 Rheostat Wire Wound 400 / 1.1 A 1

    5 Rheostat Wire wound 50 / 5 A 1

    6 Connecting Wires - -- As Req

    FUSE RATING:

    110-125% of rated current (full load current).

    PRECAUTIONS:

    All connections should be perfectly tight and no loose wire should lie on the work table.

    There should be no load on the motor at the time of starting.

    At the time of starting, the field circuit rheostat is in minimum resistance position and

    armature rheostat is in maximum position.

    Hold the tachometer with both hands steady and in line with the motor shaft so that it

    reads correctly.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    37/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    36

    TABLE 1: FIELD CONTROL METHOD.

    Rated Speed:

    TABLE 2: ARMATURE CONTROL METHOD

    Rated Speed:

    S.NO.

    Armature Voltage (Va)=

    Speed (N)

    (Rpm)

    Field Current (If)

    (Amps)

    S.NO

    Field Current(If)=

    Speed (N)

    (Rpm)

    Armature Voltage

    (Va)

    (Volts)

  • 7/25/2019 electrical machines lab manual for petrochemaical

    38/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    37

    PROCEDURE:

    Field current (or) flux control method:

    1.

    Note down the name plate details of the motor.

    2. Connections are made as per circuit diagram.

    3.

    The motor run at rated speed by adjusting the armature and field rheostat.

    4. Keep the armature voltage constant at rated value.

    5. Increase the speed in steps of 50 rpm above the rated speed using field rheostat and note

    down the corresponding field current values in Table (1).

    Armature (or) voltage control method:1. Note down the name plate details of the motor.

    2. Connections are made as per circuit diagram.

    3.

    The motor run at rated speed by adjusting the armature and field rheostat.

    4. Keep the field current constant at rated speed.

    5. Decrease the speed in steps of 50 rpm below the rated speed using armature rheostat

    and note down the corresponding field current values in Table (2).

  • 7/25/2019 electrical machines lab manual for petrochemaical

    39/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    38

    MODEL GRAPH:

    Armature Control Method Field Control Method

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    40/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    39

    RESULT:

    VIVA QUESTION:

    1.

    What are the limitations of armature voltage control and field current control methods?

    2. Why both rheostats are kept at minimum resistance position in the starting condition?

    3. What is starter? Why is it required?

    4.

    What are the applications of dc shunt motor?

    5. Why brushes are made from carbon?

    6. Why is thin conductor used for field winding? & thick conductor for armature winding?

  • 7/25/2019 electrical machines lab manual for petrochemaical

    41/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    40

    CIRCUIT DIAGRAM FOR LOAD TEST ON SINGLE PHASE TRANSFORMER

    FUSE RATING125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    42/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    41

    LOAD TEST ON SINGLE PHASE TRANSFORMER

    AIM:

    To conduct the load test on a given single phase transformer and draw its performance

    curves.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MI

    (0-5)A 1

    (0-10)A 1

    2 Voltmeter MI(0-300)V 1

    (0-150)V 1

    3 Wattmeter UPF 300V,5A 1

    4 1 auto transformer 230/(0-270)V 1

    5 1 stepdown transformer 230/110V,1KVA 1

    6 Loading Rheostat Wire Wound 1

    7 Tachometer Digital 1

    8 Connecting wires - - As required

    9 DPST - - 1

    FUSE RATING:

    Primary Current = KVA Rating of the Transformer / Primary Voltage.

    Secondary Current = KVA Rating of the Transformer / Secondary Voltage.

    110-125% of Primary current (fuse rating for primary side).

    110-125% of Secondary current (fuse rating for secondary side).

    PRECAUTIONS:

    At the time of starting, the DPST switch on secondary side should be kept in open

    condition.

    At the time of starting, there should be no load on the loading rheostat.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    43/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    42

    Table: Load Test on Single Phase Transformer.

    Multiplication Factor =

  • 7/25/2019 electrical machines lab manual for petrochemaical

    44/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    43

    FORMULAE:

    1.

    Output power = Vsx Isx Cosin Watts.

    Where,

    VsSecondary voltage in volts.Issecondary current in amps.

    Cos - power factor.

    2. Input Power = Wattmeter reading in Watts.

    3.

    Efficiency = (output power/Input power) X100 %

    4. Voltage Regulation = [(V no load- V load) / (V load)] X100 %

    Where,

    V no loadno load voltage in volts.

    V loadload voltage in volts.

    PROCEDURE:

    1. Connections are given as per the circuit diagram.

    2. The SPST Switch on the Primary side is closed and the DPST Switch on the Secondary

    side is opened.

    3.

    The Autotransformer is adjusted to energize the transformer with rated PrimaryVoltage.

    4.

    The Volt meters and Ammeters Readings are noted and tabulated at No load condition.

    5. The DPST switch on the secondary side is closed.

    6. The transformer is loaded up to 130% of the Rated Load, corresponding Ammeters,

    Voltmeters and Wattmeter readings are noted and tabulated.

    7. After the observation of all the readings the load is released gradually to its initial

    position.

    8. The Autotransformer is brought to its initial position.

    9. The Supply is switched off.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    45/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    44

    MODEL GRAPH:

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    46/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    45

    RESULT:

    VIVA QUESTIONS:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    47/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    46

    CIRCUIT DIAGRAM FOR OPEN CIRCUIT TEST ON SINGLE PHASE TRANSFORMER

    Tabulation for OC test on Single phase transformer

    Multiplication Factor =

  • 7/25/2019 electrical machines lab manual for petrochemaical

    48/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    47

    OPEN CIRCUIT TEST AND SHORT CIRCUIT TEST

    ON SINGLE PHASE TRANSFORMER

    AIM:

    To Predetermine the Efficiency and Regulation on a given single phase

    transformer by conducting the Open Circuit test and Short Circuit test and also draw its

    Equivalent circuit.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MI(0-1)A, (0-5A)

    (0-10A)

    Each 1

    2 Voltmeter MI(0-300)V 1

    (0-150)V 1

    3 Wattmeter LPF

    UPF

    150V,1A

    150V,5A

    Each 1

    4 1 auto transformer 230/(0-270)V 1

    4 1 Tapingtransformer 230/110V,1KVA 1

    5 Tachometer Digital - 1

    6 Connecting wires - - As required

    FUSE RATING:

    Primary Current = KVA Rating of the Transformer / Primary Voltage.

    Secondary Current = KVA Rating of the Transformer / Secondary Voltage.

    110-125% of Primary current (fuse rating for primary side).

    110-125% of Secondary current (fuse rating for secondary side).

    PRECAUTIONS:

    At the time of starting, the auto transformer should be in the minimum voltage

    position.

    For O.C test, the HV side of the transformer is in open circuit condition.

    For S.C test, the LV side of the transformer is short circuited.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    49/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    48

    CIRCUIT DIAGRAM FOR SHORT CIRCUIT TEST ON SINGLE PHASE TRANSFORMER

    Tabulation for SC test on Single phase transformerMultiplication Factor =

  • 7/25/2019 electrical machines lab manual for petrochemaical

    50/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    49

    FORMULAE USED:

    O.C Test:

    1. No load Power factor, Cos o = [ Woc / ( Vocx I oc ) ]

    Where, WocNo load losses.

    VocNo load voltage.

    I ocNo load current.

    2.

    Magnetizing component, Im= Ioc x Sin o

    3. Working component, Iw = Ioc x Cos o

    4. No load resistance, R 0= Voc / Iwin ohms

    5. No load reactance, X 0= Voc / Imin ohms

    S.C Test.

    1. Primary winding resistance, R1 = Wsc / Isc2in ohms

    Where, Wsc- Short circuit power in Watts

    Isc- Short circuit current in Amps

    2. Primary winding impedance, Z1= Vsc/ Iscin ohms

    where, V sc = Short circuit voltage in Volts

    3. Primary winding reactance, X1 = Z12- R1

    2 in ohms

    4.

    Secondary winding resistance, R 2 = W sc / I sc2in ohms

    5. Secondary winding impedance , Z 2= V sc / Isc in ohms

    6. Secondary winding reactance , X2= Z 22R22 in ohms

    7. Transformation ratio ( K ) = V 2/ V1

    8. Equivalent secondary resistance referred to primary side,

    R2 = R2 / K 2 in ohms.

    9. Equivalent secondary reactance referred to primary side,

    X2 = X2/ K 2 in ohms.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    51/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    50

    TO CALCULATE THE EFFICIENCY:

    Iron loss (Wi): Calculated from Table (1)

    Short Circuit loss (Wsc): Calculated from Table (2)

    S.NO LOAD

    FRACTION

    X

    IRON

    LOSS

    Wi

    (Watts)

    COPPER

    LOSS

    X2WSC

    (Watts)

    TOTAL

    LOSS

    W

    (Watts)

    OUTPUT

    POWER

    PO

    (Watts)

    INPUT

    POWER

    Pi

    (Watts)

    EFFICIENCY

    (%)

    UPF PF=0.8 UPF PF=0.8 UPF PF=0.8

    1 0.25

    2 0.5

    3 0.75

    4 1.00

    5 1.25

  • 7/25/2019 electrical machines lab manual for petrochemaical

    52/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    51

    EFFICIENCY:

    1. Iron loss, wi= wocin Watts.

    Where, Woc- No load loss.

    2.

    Copper loss, Wc- x2

    WSCin Watts.

    Where, x - Fraction of load.

    WSC- Short circuit losses.

    3.

    Total loss, W = Wi + Wcin Watts.

    4. Output power, Po = x XkVA XCos

    5. Where,

    Cos power factor.

    Cos = 1 for UPF.Cos = 0.8 for LPF.

    6. Input power, Pi = Po+ W in Watts.

    7. Efficiency, = (Po/ Pi) X 100 %

    REGULATION:

    1. Percentage Regulation

    = [x Isc / VOC( R01Cos X01Sin ) ] x 100 %

    + Lagging Leading

    2. Total resistance as referred to primary side, R01= R1 + R2 in ohms.

    3.

    Total reactance as referred to primary side, X01 = X1+ X2 in ohms.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    53/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    52

    Resultant Tabulation to find out the Efficiency:Core (Or) Iron Loss = A Rating of Transformer =

    Rated Short Circuit Current (ISC) = Short Circuit Power (WSC) =

    Resultant Tabulation to find out the Regulation:

    POWERFACTOR

    COS

    125% LOAD, X = 1.25 100% LOAD, X = 1 75% LOAD, X = 0.75

    LAG LEAD LAG LEAD LAG LEAD

    0.2

    0.4

    0.6

    0.8

    1

  • 7/25/2019 electrical machines lab manual for petrochemaical

    54/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    53

    PROCEDURE:

    OPEN CIRCUIT TEST:

    1. Connections are given as per the circuit diagram.

    2.

    The SPST Switch on the Primary side is closed.

    3. The Autotransformer is adjusted to Energize the transformer with rated Primary

    Voltage on the LV side

    4.

    The Volt meter, Watt meter and Ammeter Readings are noted at No load condition

    5. The Autotransformer is brought to its initial position

    6. The Supply is switched off.

    SHORT CIRCUIT TEST:

    1.

    Connections are given as per the circuit diagram.

    2. The SPST Switch on the Primary side is closed

    3. The Autotransformer is adjusted to energize the transformer with rated Primary Current

    on the HV side.

    4. The Voltmeter, Wattmeter and Ammeter Readings are noted down at short circuit

    condition.

    5. The Autotransformer is brought to its initial position

    6.

    The Supply is switched off.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    55/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    54

    EQUIVALENT CIRCUIT FOR SINGLE PHASE TRANSFORMER

    MODEL GRAPH:

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    56/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    55

    RESULT:

    VIVA QUESTIONS:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    57/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    56

    CIRCUIT DIAGRAM FOR LOAD TEST ON SINGLE PHASE INDUCTION MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    58/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    57

    LOAD TEST ON SINGLE PHASE INDUCTION MOTOR

    AIM:

    To determine the performance characteristic of a given single phase capacitor start

    induction motor by conducting load test.

    APPARATUS REQUIRED:

    FUSE RATING:

    Fuse rating = 125% of rated current.

    PRECAUTION:

    Before switching on the supply the single phase auto transformer is kept in minimum

    position.

    Initially these should be on no load while starting the motor.

    FORMULA USED:

    1. Torque, T = (S1~S2)*9.81*R N.m.

    2. Output power = 2 NT/60*W

    3. Effecting (%) = 0/P Power/I/p Power*100

    4.

    Slip (%S) = NSN/NS*1005. Power factor = Cos =W/VI

    PROCEDURE:

    1.

    Connections are given as per the circuit diagram.

    2. Switch on the supply at no load condition.

    3. Apply the rated voltage to the motor using the single phase auto transformer and note

    down the readings at ammeter and wattmeter.

    4.

    Vary the load in suitable steps and note down all the meter readings till full loadcondition.

    SL. NO APPARATUS RANGE TYPE QUANTITY1 Voltmeter (0-300) V MI 1

    2 Ammeter (0-20) A MI 1

    3 Wattmeter 300 V, 20 A UPF 1

    4 Tachometer - Digital 1

    5 1 auto transformer 230V/0-270V 16 Connecting wires - As Req.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    59/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    58

    TABLULATION: M.F =

    MODEL CALCULATION:

    Sl.No.

    VL

    (V)

    IL

    (A)

    Speed(N

    (Rpm)

    S1

    (Kg)

    S2

    (Kg)

    S1~ S2

    (Kg)

    Torque

    (N-m)

    Wattmeter Reading Output

    Power

    (W)Efficiency

    %

    PF=cos

    %

    SlipObs.

    (W)

    Actual

    (W)

  • 7/25/2019 electrical machines lab manual for petrochemaical

    60/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    59

  • 7/25/2019 electrical machines lab manual for petrochemaical

    61/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    60

    MODEL GRAPH:

    ELECTRICAL CHARACTERISTICS:

    MECHANICAL CHARACTERISTICS:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    62/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    61

    RESULT:

    VIVA QUESTIONS:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    63/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    62

    CIRCUIT DIAGRAM FOR NO LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    64/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    63

    EQUIVALENT CIRCUIT OF THREE PHASE SQUIRREL

    CAGE INDUCTION MOTORAIM:

    To conduct a No Load test and Blocked Rotor test on three phase squirrel cage induction

    motor and to draw the equivalent circuit.

    APPARATUS REQUIRED:

    S.NO APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MI (0-5A),

    (0-10A)

    Each 1

    2 Voltmeter MI (0-600)V 13 Wattmeter UPF,LPF 600V,5A

    150V,10A

    Each 1

    4 3 auto transformer 415/(0-470)V 1

    5 Tachometer Digital - 1

    6 Connecting wires - - As required

    FUSE RATING:

    No Load: 10 % of rated current (Full load current).

    Load: 110-125 % of rated current (Full load current).

    PRECAUTION:

    The autotransformer should be kept at minimum voltage position.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    65/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    64

    CIRCUIT DIAGRAM FOR BLOCKED ROTOR TEST ON THREE PHASE SQUIRREL CAGE

    INDUCTION MOTOR (Equivalent circuit)

  • 7/25/2019 electrical machines lab manual for petrochemaical

    66/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    65

    FORMULAE USED:

    OC TEST:

    1. No load power factor (Cos 0) = P0/V0I0

    V0- No load voltage per phase in volts.

    I0- No load current per phase in amps.

    P0- No load power per phase in watts.

    2. Working component current (Iw) = I0 (ph) X Cos 0

    3. Magnetizing current (Im) = I0 (ph) X Sin 0

    4. No load resistance (R0) =V0/I0(ph) Cos 0in W.

    5.No load reactance (X0) = V0/I0(ph) Sin 0in W.

    SC TEST:

    1. Motor equivalent Impedance referred to stator (Zsc(ph)) = Vsc(ph) / Isc(ph) in .

    2. Motor equivalent Resistance referred to stator (Rsc(ph)) = Psc(ph) / I2sc(ph) in .

    3.

    Motor equivalent Reactance referred to stator (Xsc(ph)) = (Z sc(ph)2- Rsc(ph)2) in .

    4.

    Rotor Resistance referred to stator (R2(ph)) = Rsc(ph) R1in .

    5. Rotor Reactance referred to stator (X2(ph)) = Xsc(ph) / 2 = X1in .

    Where, R1- stator resistance per phase.

    X1stator reactance per chapter.

    R1= R(ac) =1.6 x R(dc).

    6. Equivalent load resistance (RL) = R2 (1/s 1) in .

    Where, Slip (S) = (Ns-Nr) / Ns.

    NsSynchronous speed in rpm.

    NrRotor speed in rpm.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    67/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    66

    TABULATION FOR NO LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTORSpeed of the Induction motor:

    Type of the Stator connection:Multiplication Factor:

    TABULATION FOR BLOCKED ROTOR TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTORType of the Stator connection:

    Multiplication Factor:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    68/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    67

    PROCEDURE:

    1.

    Connections are given as per the circuit diagram.

    2. For No-Load or open circuit test by adjusting autotransformer, apply rated voltage and

    Note down the voltmeter, ammeter and wattmeter readings. In this test rotor is free torotate.

    3. For short circuit or blocked rotor test by adjusting autotransformer, apply rated current

    and note down the voltmeter ,ammeter and wattmeter readings. In this test rotor is

    blocked.

    4. After that make the connection to measure the stator resistance as per the circuit

    diagram.

    5. By adding the load through the loading rheostat note down the ammeter, voltmeter

    reading for various values of load.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    69/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    68

    EQUIVALENT CIRCUIT FOR THREE PHASE SQUIRREL CAGE

    INDUCTION MOTOR

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    70/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    69

    RESULT:

    VIVAQUESTION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    71/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    70

    CIRCUIT DIAGRAM FOR LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR

    FUSE RATING

    125% of rated current.

    NAME PLATE DETAILS

  • 7/25/2019 electrical machines lab manual for petrochemaical

    72/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    71

    LOAD TEST ON THREE PHASE SQUIRREL CAGE

    INDUCTION MOTOR

    AIM:

    To conduct a load test on a three phase squirrel cage induction motor and to draw the

    performance characteristic curves.

    APPARATUS REQUIRED:

    FUSE RATING:

    110-125% of rated current (Full load current).

    PRECAUTIONS:

    There should be no load on the motor at the time of starting.

    FORMULAE USED:

    1.

    Torque = (S1-S2) (R+t/2) x 9.81 N-m

    Where, S1, S2spring balance readings in Kg.

    R - Radius of brake drum in m.

    t - Thickness of belt in m.

    Output Power = 2 PNT/60 watts.

    N- Rotor speed in rpm.

    T- Torque in N-m.

    2. Input Power = (W1+W2) Watts.

    W1, W2Wattmeter readings in Watts.

    3.

    Percentage of Efficiency = (Output Power/ Input Power) x 100%.

    S.NO APPARATUS TYPE RANGE QUANTITY

    1 Ammeter MI (0-5/10)A 1

    2 Voltmeter MI (0-600)V 1

    3 Wattmeter UPF 600V,5/10A 2

    4 Tachometer Digital 1

    5 Connecting wires - - As required

  • 7/25/2019 electrical machines lab manual for petrochemaical

    73/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    72

    TABULATION FOR LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR.

    Multiplication Factor:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    74/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    73

    4. Percentage of Slip = (NS-Nr)/Ns x 100%

    Ns-Synchronous speed in rpm.

    Nr-Rotor speed in rpm.

    5. Power factor = (W1+W2)/ 3VLIL.

    PROCEDURE:

    1.

    Connections are given as per the circuit diagram.

    2. The TPSTS is closed and the motor is started using On Line starter to run at rated speed.

    3. At no load the speed, current, voltage and power are noted down.

    4.

    By applying the load for various values of current the above-mentioned readings are

    noted.

    5.

    The load is later released and the motor is switched off and the graph is drawn.

  • 7/25/2019 electrical machines lab manual for petrochemaical

    75/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    74

    MODEL GRAPHS:

    Mechanical Characteristics Electrical Characteristics

    MODEL CALCULATION:

  • 7/25/2019 electrical machines lab manual for petrochemaical

    76/76

    Lab Manual: Electrical Machines Laboratory (EI6411) Regulation 2013

    RESULT:

    VIVA QUESTION: