ENERGY STAR Qualified Homes

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

Page 2: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

TABLE OF CONTENTS

Section 1. Water-Managed Site and Foundation

Section 2. Water-Managed Wall Assembly

Section 3. Water-Managed Roof Assembly

Section 4. Water-managed Building Materials

Page 3: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.1. Patio slabs, porch slabs, walks, and driveways sloped ≥ 0.25 in. per ft. away from home to edge of surface or 10 ft., whichever is less 4

1.2. Back-fill has been tamped and final grade sloped ≥ 0.5 in. per ft. away from home for ≥ 10 ft. See footnote for alternatives 4

Page 4: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.3. Capillary break beneath all slabs (e.g., slab on grade, basement slab) except crawlspace slabs using either: ≥ 6 mil polyethylene sheeting, lapped 6-12 in., or ≥ 1” extruded polystyrene insulation with taped joints. 5

Page 5: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.4 Capillary break at all crawlspace floors using > 6 mil polyethylene sheeting, lapped 6-12 in., and installed using one of the following three options: 5

1.4.1 Placed beneath a concrete slab; OR,

1.4.2 Lapped up each wall or pier and fastened with furring strips or equivalent; OR,

1.4.3 Secured in the ground at the perimeter using stakes.

Page 6: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.5 Exterior surface of below-grade walls finished as follows:• For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proofing coating• For wood framed walls, finish with polyethylene and adhesive or other equivalent waterproofing

1.6 Class 1 vapor retarders not installed on the interior side of air permeable insulation in exterior below-grade walls 6

Page 7: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.7 Sump pump covers mechanically attached with full gasket seal or equivalent

1.8 Drain tile surrounded with clean gravel and fabric filter 7

Page 8: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.1. Patio slabs, porch slabs, walks, and driveways sloped ≥ 0.25 in. per ft. away from home to edge of surface or 10 ft., whichever is less 4

1.2. Back-fill has been tamped and final grade sloped ≥ 0.5 in. per ft. away from home for ≥ 10 ft. See footnote for alternatives 4

Page 9: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 10: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

Water Management System Builder Checklist

Driveway is not sloped away from the house.

Driveway is installed to slope water away from the house.

1.1- 2Patio slabs, porch slabs, walks, and driveways sloped ≥ 0.25 in. per ft. away from home to edge of surface or 10 ft., whichever is less 4

A / B

Page 11: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.1- 2

Click icon to add picture

The final grade does not slope away from the house.

Back-fill has been tamped and final grade sloped ≥ 0.5 in. per ft. away from home for ≥ 10 ft. See footnote for alternatives 4

The final grade slopes away from the house.

E

Page 12: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

BAD PIC OF IMPROPERLY INSTALLED OR NO SWALE

GOOD PIC OF PROPERLY INSTALLED SWALE

1.1- 2Back-fill has been tamped and final grade sloped ≥ 0.5 in. per ft. away from home for ≥ 10 ft. See footnote for alternatives 4

C/G

Page 13: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

Drain pipe has been cut and foundation penetration has not been properly sealed.

The drain slopes away from the foundation and terminates at the proper distance.

1.1- 2Patio slabs, porch slabs, walks, and driveways sloped ≥ 0.25 in. per ft. away from home to edge of surface or 10 ft., whichever is less 4

D/H

Page 14: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.3. Capillary break beneath all slabs (e.g., slab on grade, basement slab) except crawlspace slabs using either: ≥ 6 mil polyethylene sheeting, lapped 6-12 in., or ≥ 1” extruded polystyrene insulation with taped joints. 5

Page 15: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 16: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.3

There is no polyethylene sheeting installed between the ground and the slab.

Capillary break beneath all slabs (e.g., slab on grade, basement slab) except crawlspace slabs using either: ≥ 6 mil polyethylene sheeting, lapped 6-12 in., or ≥ 1” extruded polystyrene insulation with taped joints. 5

There is polyethylene sheeting installed to provide a capillary break between the ground and slab.

B

Page 17: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.3

Click icon to add picture

The seams of the rigid insulation are not taped and it will not provide a complete capillary break.

Capillary break beneath all slabs (e.g., slab on grade, basement slab) except crawlspace slabs using either: ≥ 6 mil polyethylene sheeting, lapped 6-12 in., or ≥ 1” extruded polystyrene insulation with taped joints. 5

GOOD PIC OF PROPERLY INSTALLED RIGID INSULATION

C

Page 18: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.4 Capillary break at all crawlspace floors using > 6 mil polyethylene sheeting, lapped 6-12 in., and installed using one of the following three options: 5

1.4.1 Placed beneath a concrete slab; OR,

1.4.2 Lapped up each wall or pier and fastened with furring strips or equivalent; OR,

1.4.3 Secured in the ground at the perimeter using stakes.

Page 19: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 20: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.4.1

There is no polyethylene sheeting installed in the crawlspace.

Placed beneath a concrete slab.

There is 6 mil polyethylene sheeting installed and sealed in the crawlspace.

A

Page 21: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.4.1

Click icon to add picture

There is no polyethylene sheeting installed in the crawlspace.

Placed beneath a concrete slab.

GOOD PIC OF POLY INSTALLED IN THE CRAWLSPACE OVERLAPPED 6-12”

B

Page 22: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 23: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.4.2

There is no polyethylene sheeting installed in the crawlspace.

Lapped up each wall or pier and fastened with furring strips or equivalent.

There is polyethylene sheeting installed and sealed in the crawlspace.

B

Page 24: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.4.2

Click icon to add picture

The polyethylene sheeting is not staked or attached to furring strips for mechanical support.

Lapped up each wall or pier and fastened with furring strips or equivalent.

GOOD PIC OF PROPERLY INSTALLED FURRING STRIPS

C

Page 25: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.5 Exterior surface of below-grade walls finished as follows:• For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proofing coating

Page 26: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 27: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.5

The below-grade concrete does not have the correct mixture to be impermeable to moisture.

Exterior surface of below-grade walls finished as follows: For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proof coating

Below-grade concrete has been properly sealed against moisture and is now having insulation installed.

A

Page 28: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

1.5

Click icon to add picture

BAD PIC OF CMU WALL WITHOUT PARGING

Exterior surface of below-grade walls finished as follows: For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proof coating

GOOD PIC OF CMU WALL WITH PARGING

B

Page 29: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.5

The below-grade concrete walls do not have any damp-proof coating.

Exterior surface of below-grade walls finished as follows: For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proof coating

The below-grade concrete walls have damp-proof coating.

C

Page 30: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.5

The insulated concrete forms at the foundation do not have a damp-proof coating.

Exterior surface of below-grade walls finished as follows: For poured concrete, concrete masonry, and insulated concrete forms, finish with damp-proof coating

The insulated concrete forms that are below grade have a damp-proof coating to prevent moisture seeping into the foundation.

D

Page 31: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.5 Exterior surface of below-grade walls finished as follows:• For wood framed walls, finish with polyethylene and

adhesive or other equivalent waterproofing

Page 32: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 33: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.5

Click icon to add picture

Untreated lumber has been used on a below-grade wall against masonry.

Exterior surface of below-grade finished as follows: For wood framed walls, finish with polyethylene and adhesive or other equivalent waterproofing

GOOD PIC OF TREATED WOOD / MATERIALS ON BELOW GRADE WALL

a

Page 34: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

1.5

Click icon to add picture

BAD PIC OF FOUNDATION WITHOUT POLY

Exterior surface of below-grade finished as follows: For wood framed walls, finish with polyethylene and adhesive or other equivalent waterproofing

GOOD PIC OF FOUNDATION WITH POLY

b

Page 35: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.6 Class 1 vapor retarders not installed on the interior side of air permeable insulation in exterior below-grade walls 6

Page 36: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 37: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.7 Sump pump covers mechanically attached with full gasket seal or equivalent

Page 38: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 39: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.7

The sump pump does not have a cover.

Sump pump covers mechanically attached with full gasket seal or equivalent

The sump pump has a sealed cover that is mechanically attached.

A

Page 40: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.7

The sump pump does not have a cover.

Sump pump covers mechanically attached with full gasket seal or equivalent

The sump pump has a sealed cover that is mechanically attached.

A

Page 41: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 1. WATER-MANAGED SITE AND FOUNDATION

1.8 Drain tile surrounded with clean gravel and fabric filter 7

Page 42: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 43: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.8

The drain tile is not wrapped in fabric and could become clogged with debris.

Drain tile surrounded with clean gravel and fabric filter 7

The drain tile is wrapped in fabric which will prevent it clogging with debris.

A

Page 44: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.8

The drain tile is cut and now does not extend around the entire foundation footing.

Drain tile surrounded with clean gravel and fabric filter 7

The drain tile is installed along the bottom of the entire foundation footing.

B

Page 45: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.8

The drain tile is not installed to terminate properly and will not transport water to the exterior.

Drain tile surrounded with clean gravel and fabric filter 7

The drain tile connects to a sump pump which will pump water away from the foundation.

C

Page 46: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

1.8

Click icon to add picture

The gravel surrounding the drain tile is too large and will let too much debris through.

Drain tile surrounded with clean gravel and fabric filter 7

GOOD PIC OF DRAIN TILE SURROUNDED WITH GRAVEL

D

Page 47: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 2. WATER-MANAGED WALL ASSEMBLY

2.1 Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

2.2 Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

2.3 Window and door openings fully flashed 9

Page 48: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 2. WATER-MANAGED WALL ASSEMBLY

2.1 Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

Page 49: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 50: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

There is no flashing installed at the bottom of the exterior walls to create a drainage system.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

There is flashing installed at the bottom of the wall to create a satisfactory drainage system.

A

Page 51: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

Click icon to add picture

There is no flashing installed at the bottom of the exterior walls to create a drainage system.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

GOOD PIC OF FLASHING INSTALLED FINISHED

A

Page 52: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 53: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

The weep holes were not properly cleaned before the weeps were installed.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

The weep holes are properly cleaned out and the weeps properly installed.

A

Page 54: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

There are no weep holes installed at the bottom of the exterior wall.

.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

There is both flashing and weep holes installed at the bottom of the exterior wall.

B

Page 55: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

The weep holes are spaced too far apart.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

The weep holes are spaced at the correct distance to provide a complete drainage system.

B

Page 56: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 57: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

There is not a weep screed installed at the bottom of the stucco wall.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

There is a weep screed installed at the bottom of the wall.

A

Page 58: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

2.1

BAD PIC OF FLASHING OVER WATER BARRIER

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

There is a water-resistant barrier installed underneath the stucco and lathe.

B

Page 59: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.1

The water-resistant barrier, weep screed, and stucco lathe are not properly layered.

Flashing at bottom of exterior walls with weep holes included for masonry veneer and weep screed for stucco cladding systems, or equivalent drainage system

The water-resistant barrier, weep screed, and stucco lathe are properly layered and will create a complete drainage system.

C

Page 60: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 2. WATER-MANAGED WALL ASSEMBLY

2.2 Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

Page 61: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 62: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.2

The water-resistant barrier is not complete and the holes and gaps could cause moisture problems.

Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

The water-resistant barrier covers the entire house and the seams are taped to provide a complete drainage system.

A

Page 63: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.2

The rigid sheathing seams are not taped and the gaps could cause moisture problems.

Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

The rigid insulation covers all of the exterior walls and all of the seams are taped to provide a complete drainage system.

B

Page 64: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.2

The building felt is not installed on the entire house.

Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

The building felt is installed on all exterior walls and provides a complete drainage system.

C

Page 65: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.2

Click icon to add picture

There is not a water-resistant barrier installed underneath the exterior finish of the walls.

Fully sealed continuous drainage plane behind exterior cladding that laps over flashing in Section 2.1. Additional bond-break drainage plane layer provided behind all stucco and non-structural masonry cladding wall assemblies 8

GOOD PIC OF A DIFFERENT TYPE OF WATER RESISTANT BARRIER

D

Page 66: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 2. WATER-MANAGED WALL ASSEMBLY

2.3 Window and door openings fully flashed 9

Page 67: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 68: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.3

The corners are not properly flashed, leaving a vulnerable area in the drainage system.

Window and door openings fully flashed 9

The flashing is properly installed to create a complete drainage system.

A

Page 69: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.3

There is no flashing installed along the sides of the window.

Window and door openings fully flashed 9

Side flashing extends over the pan flashing.

B

Page 70: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

2.3

There is no flashing installed at the top of the window.

Window and door openings fully flashed 9

There is flashing installed along the top of the window and the water-resistant barrier is layered over to create a complete drainage system.

C

Page 71: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.1 Step and kick-out flashing at all roof-wall intersections, extending ≥ 4” on wall surface above roof deck and integrated with drainage plane above 10

3.2 For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system ≥ 10 ft. from foundation.11

Page 72: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.3 Self-sealing bituminous membrane or equivalent at all valleys & roof deck penetrations 12

3.4 In 2009 IECC Climate Zones 5 and higher, self-sealing bituminous membrane or equivalent over sheathing at eaves from the edge of the roof line to > 2 ft. up roof deck from the interior plane of the exterior wall.12

Page 73: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.1 Step and kick-out flashing at all roof-wall intersections, extending ≥ 4” on wall surface above roof deck and integrated with drainage plane above 10

Page 74: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 75: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

3.1

Click icon to add picture

BAD PIC OF ROOF FELT INSTALLATION

Step and kick-out flashing at all roof-wall intersections, extending ≥ 4” on wall surface above roof deck and integrated with drainage plane above 10

GOOD PIC OF PROPERLY LAYERED ROOFING

A

Page 76: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.1

The step flashing is not the required height above the roof deck.

Step and kick-out flashing at all roof-wall intersections, extending ≥ 4” on wall surface above roof deck and integrated with drainage plane above 10

The step flashing is the correct height above the roof deck.

B

Page 77: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.1

The water-resistant barrier is layered underneath the step flashing and could create a water damage.

Step and kick-out flashing at all roof-wall intersections, extending ≥ 4” on wall surface above roof deck and integrated with drainage plane above 10

The water-resistant barrier is layered over the step flashing to provide a complete drainage system.

C

Page 78: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.2 For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system > 10 ft. from foundation.11

Page 79: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 80: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.2

The downspout terminates too close to the foundation of the house.

For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system ≥ 10 ft. from foundation.11

The downspout pipes far enough away from the foundation to prevent moisture problems.

A

Page 81: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.2

The downspout terminates too close to the foundation of the house.

For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system ≥ 10 ft. from foundation.11

The downspout terminates into a catchment system that moves water away from the foundation of the house.

B

Page 82: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.2

There are no gutters installed and there is not a proper gravel bed located at the foundation.

For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system ≥ 10 ft. from foundation.11

House without gutters has waterproof liner, drain tile and gravel bed extending more than 5 feet from foundation.

C

Page 83: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.2

Rain barrel installed without an overflow spout that terminates away from foundation.

For homes that don’t have a slab-on-grade foundation and do have expansive or collapsible soils, gutters & downspouts provided that empty to lateral piping that deposits water on sloping final grade ≥ 5 ft. from foundation or to underground catchment system ≥ 10 ft. from foundation.11

Rain barrel installed with an overflow spout terminating at least 5 feet from foundation.

D

Click icon to add picture

Page 84: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.3 Self-sealing bituminous membrane or equivalent at all valleys & roof deck penetrations 12

Page 85: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 86: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

3.3

There is not a self-sealing bituminous membrane installed at the valley of the roof.

Self-sealing bituminous membrane or equivalent at all valleys & roof deck penetrations 12

There is a self-sealing bituminous membrane installed at the valley of the roof prior to the roof felt.

A

Page 87: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

3.3

BAD PIC OF ROOF WITHOUT MEMBRANE INSTALLED

Self-sealing bituminous membrane or equivalent at all valleys & roof deck penetrations 12

There is a properly installed and layered self-sealing bituminous membrane installed at the roof penetration.

A

Page 88: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 3. WATER-MANAGED ROOF ASSEMBLY

3.4 In 2009 IECC Climate Zones 5 and higher, self-sealing bituminous membrane or equivalent over sheathing at eaves from the edge of the roof line to > 2 ft. up roof deck from the interior plane of the exterior wall.12

Page 89: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 90: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

3.4

Click icon to add picture

BAD PIC OF NO MEMBRANE AT EAVES

In 2009 IECC Climate Zones 5 and higher, self-sealing bituminous membrane or equivalent over sheathing at eaves from the edge of the roof line to > 2 ft. up roof deck from the interior plane of the exterior wall.12

GOOD PIC OF PROPERLY INSTALLED MEMBRANE AT EAVES

A

Page 91: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

3.4

Click icon to add picture

BAD PIC OF NO MEMBRANE AT EAVES

In 2009 IECC Climate Zones 5 and higher, self-sealing bituminous membrane or equivalent over sheathing at eaves from the edge of the roof line to > 2 ft. up roof deck from the interior plane of the exterior wall.12

GOOD PIC OF PROPERLY INSTALLED MEMBRANE AT EAVES

A

Page 92: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.1 Wall-to-wall carpet not installed within 2.5 feet of toilets, tubs, and showers

4.2 Cement board or equivalent moisture-resistant backing material installed on all walls behind tub and shower enclosures composed of tile or panel assemblies with caulked joints. Paper-faced backerboard shall not be used 13

Page 93: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.3 In Warm-Humid climates, Class 1 vapor retarders not installed on the interior side of air permeable insulation in above-grade walls, except at shower and tub walls 6

4.4 Building materials with visible signs of water damage or mold not installed 14

4.5 Interior walls not enclosed (e.g., with drywall) if either the framing members or insulation products have high moisture content 15

Page 94: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.1 Wall-to-wall carpet not installed within 2.5 feet of toilets, tubs, and showers

Page 95: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 96: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.1

There is carpet installed too close to the plumbing fixtures in the bathroom.

Wall-to-wall carpet not installed within 2.5 feet of toilets, tubs, and showers

There is no carpet installed in the bathroom.

A

Page 97: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.1

There is carpet installed too close to the plumbing fixtures in the bathroom.

Wall-to-wall carpet not installed within 2.5 feet of toilets, tubs, and showers

There is no carpet installed in the bathroom.

A

Page 98: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.2 Cement board or equivalent moisture-resistant backing material installed on all walls behind tub and shower enclosures composed of tile or panel assemblies with caulked joints. Paper-faced backerboard shall not be used 13

Page 99: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 100: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.2

No backing installed behind shower enclosure.

Cement board or equivalent moisture-resistant backing material installed on all walls behind tub and shower enclosures composed of tile or panel assemblies with caulked joints. Paper-faced backerboard shall not be used 13

Foam board taped at seams installed behind shower enclosure.

A

Page 101: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

4.2

BAD PIC OF NON MOISTURE RESISTANT MATERIAL BEHIND TUB/SHOWER

Cement board or equivalent moisture-resistant backing material installed on all walls behind tub and shower enclosures composed of tile or panel assemblies with caulked joints. Paper-faced backerboard shall not be used 13

Moisture resistant backing material has been used above the tub enclosure.

B

Page 102: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.3 In Warm-Humid climates, Class 1 vapor retarders not installed on the interior side of air permeable insulation in above-grade walls, except at shower and tub walls 6

Page 103: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 104: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

SECTION 4. WATER-MANAGED BUILDING MATERIALS

4.4 Building materials with visible signs of water damage or mold not installed 14

4.5 Interior walls not enclosed (e.g., with drywall) if either the framing members or insulation products have high moisture content 15

Page 105: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3
Page 106: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.4-5

Building materials are being stored outdoors with no protection from weather.

Building materials with visible signs of water damage or mold not installed 14

Shingles kept wrapped and on pallets to prevent from getting wet.

A

Page 107: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.4-5

Building materials with visible signs of mold have been used.

Building materials with visible signs of water damage or mold not installed 14

Building materials were kept dry and free of mold.

B

Page 108: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJ

4.4-5

Building materials have signs of water damage and high moisture content.

Interior walls not enclosed (e.g., with drywall) if either the framing members or insulation products have high moisture content 15

A moisture meter verifies that the moisture content of the framing is below the recommended 18%.

C

Page 109: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

LD CJClick icon to add picture

4.4-5

Click icon to add picture

BAD PIC OF WET BLOWN INSULATION PRODUCT

Interior walls not enclosed (e.g., with drywall) if either the framing members or insulation products have high moisture content 15

GOOD PIC OF WET BLOWN INSULATION PRODUCT

D

Page 110: ENERGY STAR Qualified Homes WATER MANAGEMENT SYSTEM BUILDER CHECKLIST 1, 2, 3

ENERGY STAR® QUALIFIED HOMES

WATER MANAGEMENT SYSTEM BUILDER CHECKLIST

EPA Disclaimer

Any mention of trade names, commercial products and organizations in this document does not imply endorsement by the U.S. Environmental Protection Agency ("EPA") or the U.S. Government.  The EPA and its collaborators make no warranties, whether expressed or implied, nor assume any legal liability or responsibility for the accuracy, completeness or usefulness of the contents of this publication, or any portion thereof, nor represent that its use would not infringe privately owned rights.  Further, the EPA cannot be held liable for construction defects or deficiencies resulting from the proper or improper application of the content of this guidebook.