engine drives

Upload: camelod555

Post on 01-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 Engine Drives

    1/19

    ENGINE DRIVEN ELECTRICAL POWER GENERATION

    Generator Type power sources convert mechanical energy or mechanical power that is obtained from an inter-

    nal combustion engine into electrical power suitable for arc welding and/or auxiliary electrical power. For

    welding, two basic types of rotating power sources are used, the generator and the alternator. Both designs

    have a rotating member, called a rotor. A system of magnetic field excitation is needed for both types.

    There are three essentials for electrical power generation:

    1. Magnetic Lines of Force (Magnetic Field)2. Electrical Current Carrying Conductor

    3. Relative Motion Between the Magnetic Field and the Electrical Current Carrying Conductor.

    In electrical power generation, there must be relative motion between a magnetic field and a current carrying

    conductor. Whenever a wire moves through the lines of force of a magnetic field or whenever lines of force of

    a magnetic field are moved through a wire, a voltage is induced in the wire. This induced voltage causes elec-

    tric current to flow when the circuit is complete. Thus, the principle of any rotating power source is that elec-

    trical current is produced in electrical conductors (coil of wire) when they are moved through a magnetic field.

    Physically, it makes no difference whether the magnetic field moves or the conductor moves, just so that the

    coil experiences a changing magnetic field intensity.

    Page 1

  • 8/9/2019 Engine Drives

    2/19Page 2

    The amount of voltage generated depends upon the number lines of force cut per second. Three ways ofincreasing the voltage from a generator are (1) by increasing the motion (speed/velocity)of the magnetic field

    (or the coil), (2) by using a stronger magnet (or magnetic field), and (3) by increasing the number of turns of

    wire in the coil.

    A direct current generator consists of a rotor and a stator. The stator or the stationary portion of the generator,

    within which the rotor assembly turns, holds the electromagnetic field coils which conduct a small amount of

    direct current to maintain the necessary continuous electromagnetic field excitation required for power genera-

    tion. Direct current is used to create the electromagnetic field. The direct current for the field windings of the

    generator is called the exciting current, and the generator that supplies the direct current is called the exciter.

    This direct current amperage is normally no more than 10 to 15 ampere and very often is less. Electromagnets

    provide stronger magnetic fields and control the amount of induced current. This control is important, for

    when the amount of current flowing through the electromagnets is changed, the strength of the magnetic field

    is changed.

    The rotor assembly consists of (1) a through shaft, (2) two end bearings to support the rotor and shaft load, (3)

    an armature which includes the laminated armature iron core and the current-carrying armature coils. It is in

    the armature coils that the electrical welding power is generated. And (4) a commutator brush arrangement for

    mechanically rectifying or changing alternating current to direct current welding power.

    In actual practice, the armature turns within the stator and its electromagnetic field system, and welding cur-

    rent is generated. The AC voltage produced by the armature coils moving through the magnetic field of the

    stator is carried to the copper commutator bars through electrical conductors from the armature coils. The

    commutator is located at one end of the armature. The commutator is a system of copper bars mounted on the

    rotor shaft. The conductors are soft-soldered to individual commutator bars. The latter may be considered as

    terminals, or "collector bars," for the alternating current generated from the armature. It is a group of conduct-

    ing bars arranged parallel to the rotating shaft to make switching contact with a set of stationary carbon brush-

    es (contact points). These bars are connected to the armature conductors. The whole arrangement is construct-

    ed in proper synchronization with the magnetic field. As the armature rotates, the commutator performs the

    function of mechanical rectification.

    Each copper bar has a machined and polished top surface. Carbon contact brushes ride on that top surface to

    pick up each half-cycle of the generated alternating current. The carbon contact brushes pick up each half-

  • 8/9/2019 Engine Drives

    3/19

    cycle of generated alternating current and direct it into a conductor as direct current. The purpose of the com

    mutator is to carry both half-cycles of the generated AC sine wave, but on separate copper commutator bars.

    Each of the copper commutator bars is insulated from all the other copper bars.

    Page 3

    INDUCED

    VOLTAGE

    TIME N SAC

    HERE

    COMMUTATOR

    DC HERE

    ()

    (+)

    VOLTAGE AT BRUSHES

    The magnetic field is contained in the stator assembly of a generator. It is in the armature coilsthat welding power is generated. The commutator-brush rectifies ac to dc welding power.

    2 POLEGENERATOR

    DC Generator

    Normally, the direct current generator is a three-phase electrical device. Three-phase welding systems normal-

    ly provide the smoothest welding power of any of the electromechanical welding power sources.

    1. END VIEW OF THE ARMATURE ANDFIELD COILS OF GENERATOR

    2. END VIEW OF FOUR POLE ROTORAND STATOR OF ALTERNATOR

  • 8/9/2019 Engine Drives

    4/19

    MILLER ALTERNATOR DESIGN VS. GENERATOR DESIGN

    The entire line, of Miller Electric's engine driven power sources, uses a design concept called the "revolving

    (electromagnetic) field design." This concept is commonly called an alternator design (often called an alternat-

    ing current generator). This design in welding power sources is in direct contrast to how DC generator rotating

    power sources are designed. There are distinct differences and advantages to using alternator design over the

    DC generator design. It is very similar, except the alternator rotor assembly contains the electromagnetic field

    coils instead of the stator coils as found in generators. The heavy current-carrying conductor windings are

    wound into the stator. These machines are also called revolving or rotating field machines.

    Slip rings are used to conduct low DC power into the rotating member to produce a rotating electromagnetic

    field. An alternator usually has brushes and slip rings to provide the low direct current power to the field coils.

    It is not usual practice in alternators to feed back part of the welding current to the field circuit. Rather the

    alternator usually uses the brushes and slip rings to provide the low DC power to the field coils. The voltage

    induced in the armature coil passes through a set of slip rings connected to the ends of the armature coil and

    through a set of brushes making contact with the slip rings, to an external circuit. This configuration precludes

    the necessity of the commutator and the brushes used with DC output generators.

    The welding output is alternating current, which requires external rectification for direct current applications.

    Rectification is usually done with a bridge rectifier using silicon diodes. Both single and three-phase alterna-

    tors are available to supply AC to the necessary rectifier system. The DC welding characteristics are similar to

    those of single and three-phase transformer-rectifier units.

    Page 4

  • 8/9/2019 Engine Drives

    5/19

    The alternator design presents several fundamental advantages. Some important facts are:

    Page 5

    Miller Alternator Design

    1. Higher duty cycle - 100%- Design permits 100% duty cycle rating.

    2. Operates cooler

    - Most heat is generated in the weld windings.located on the outside of the unit.

    - Easy to cool.- Minimum cold to hot drift.

    3. Low currents in moving parts- Rotating field coils carry less than 10 amps.

    4. No brush-commutator assembly- Slip rings and brush carry less than 10 amps.

    - Minimum brush wear.- No chance of polarity changing.

    5. Rotor is lighter- Quicker to accelerate to speed.- Rotates easier, engine easily handles 300 amppower source.

    - Less fuel consumption for same amperageoutput.

    6. No "kits" required for paralleling- Hook any number of units together for increased

    output.- No current feedback can occur since diodesblock feedback.

    Generator Design

    Lower duty cycle - 60%- To obtain higher duty cycle requires heavier

    windings in the armature.- Small units are usually 30-50% duty cycle rated.

    Harder to cool

    - Heat is generated in the armature. Must be cooledby air movement and conduction to the outside ofthe unit.

    - More heat build up, greater cold to hot drift. Outputwill drop off when unit heats up.

    High current in moving parts- Armature carries full welding current. Heat builds

    up internally.

    Brush assembly and commutator bars- Brushes must carry full welding current.

    - Arcing occurs.- Brushes wear, lowering efficiency, maintenancerequired.

    - Welding polarity may change during welding whenbrushes lift off the commutator.

    - Commutator will require maintenance.

    Armature is a large mass of iron- Slower to respond.- Engine can only handle a 200 amp power source.- More torque required to rotate. Harder on bearings,

    etc.- During heavy usage such as arc gouging, stress

    relieving, etc. heat buildup will cause solder to bethrown from commutator area.

    Special kits required to parallel- Adapter kits required to connect units together.

    Current feedback from one unit to another causesone to "drive" the other as a motor.

    ROTATING MAGNETICFIELD COIL DESIGN

    ROTATING ARMATURE

    OF AN ALTERNATOR100% DUTY CYCLE

    DESIGN OF AGENERATOR

    60% DUTY CYCLE

    ROTOR COMPARISONS

  • 8/9/2019 Engine Drives

    6/19

    The blocking nature of the rectifiers makes direct current alternator units easy to operate in parallel for obtain-

    ing increased welding current output by connecting two or more welding alternators (generators) in parallel.

    Care should be taken to ensure that connections are the same polarity. All units paralleled must be set to deliv-

    er equal welding (amperage & polarity) outputs. Parallel connection is not advised unless the manufacturer's

    specific instructions are followed. Such a precaution is necessary because successful paralleling depends upon

    matching the output-voltage, output amperage setting, and polarity of each machine.

    In the case of self-excited generators, the problem may be further complicated by the necessity to equalize the

    excitation between the generators.

    Both the generator and alternator type power sources generally provide welding current adjustment in broad

    steps called ranges. A rheostat or other control is usually placed in the electromagnetic field circuit to adjust

    the internal magnetic field strength for fine adjustment of power output. The fine adjustment of welding power

    output regulates the strength of the magnetic field, and will also change the open circuit voltage. When the

    rheostat is adjusted near the bottom of the range with a low rheostat setting, the open circuit voltage will nor-

    mally be substantially lower than at the high end of the range.

    Page 6

    Typical Engine Drive Amperage Control

    With many alternator power supplies, broad ranges are obtained from taps on a reactor in the AC portion of

    the circuit. As such, the basic machine does not often have the dynamic response required for shielded metal

    arc welding. Thus, a suitable inductor is generally inserted in series connection in one leg of the DC output

    from the rectifier. Welding generators do not normally require an inductor.

    There is a limited range of overlap normally associated with rotating equipment where the desired welding

    current can be obtained over a range of open circuit voltages. If welding is done in this area, welders have the

    capability to fine tune or adjust the arc to the job. With a lower open circuit voltage, the slope of the voltam-

    pere curve is less. This allows the welder to regulate the welding current to some degree by varying the arc

    length. This can assist in weld-pool control, particularly for out-of-position welding.

    A generator or an alternator unit produces a maximum or a finite amount of power that is measured in kilo-

    watts. As the voltage increases the amperage will decrease proportionately. Conversely as the voltage decreas-

    es the amperage will increase proportionately. In other words, if there is a relatively high open circuit voltage

    at some particular setting on a power source, there must be a relatively limited amount of maximum short cir-

    cuit current at the same time.

  • 8/9/2019 Engine Drives

    7/19

    Volt-Amp Curves

    Welding power sources are available that produce both constant current and constant voltage. These units are

    used for field applications where both are needed at the job site when primary, utility power is not available.

    Also, many new designs use electronic solid-state circuitry to obtain a variety of volt-ampere characteristics.

    Saturable reactors and moving-core reactors may be used for output control of these machines. The normal

    method is to provide a tapped reactor for broad control of current ranges, in combination with control of the

    alternator magnetic field to produce fine control within these ranges.

    ENGINE DRIVE AUXILIARY POWERMILLER welding generators are combination welding and power generators specifically designed for the

    welding application. An auxiliary power winding is included in the generator to provide convenience power

    incidental to the welding operation for accessory equipment. Most auxiliary power generators are singlephase

    and may be either two-wire or three-wire design depending upon the model. There is no significant advantage

    of the two-wire system versus the three-wire except that the three-wire design is capable of supplying two dif-

    ferent voltages simultaneously (120/240 VAC).

    These machines are designed to provide nominal 120 or 240 volts, 60 Hertz power, which are the common

    small load voltages in the United States. Different voltages and frequencies are found in various parts of the

    world and optional auxiliary power generator designs are available for these requirements. These generators

    can be used to power portable tools, lights, heaters, compressors, pumps, etc., within the capabilities of the

    unit. They are not designed to power voltage and/or frequency sensitive electronic equipment which may be

    damaged by voltage or frequency changes normal to the operation.

    An alternator or generator may be either self-excited or separately-excited, depending on the source of the

    field power. Either unit may use a small auxiliary alternator or generator, with the rotor on the same shaft as

    the main rotor, to provide exciting power. On many engine-driven units, a portion of exciter field power is

    available to operate tools or lights necessary to the welding operation. In the case of a generator, this auxiliary

    power is usually 115 volts of direct current. With alternator-type power source, 120 or 120/240 volts of alter-

    nating current is usually available. Alternating Current Voltage frequency (hertz) depends upon the engine

    Page 7

    The volt-ampere curves show theminimum and maximum voltageand amperage output capabilities ofthe welding generator. Curves of allother settings fall between thecurves shown.

    0

    20

    40

    60

    80

    100

    0 100 200 300 400 500 600 700 800 900

    DC AMPERES

    DC

    VOLTS

    Ranges

    300Max185425

    125320 85190

    5590

  • 8/9/2019 Engine Drives

    8/19

    speed. The frequency of the output welding current is controlled by the rotation of the rotor assembly and by

    the number of poles in the alternator design. A two-pole alternator must operate at 3600 rpm to produce

    60 Hz alternating current, whereas a four-pole alternator design must operate at 1800 rpm to produce 60 Hz

    alternating current.

    Page 8

    N S

    AC HERE

    DCHERE

    2 Pole Alternator With Tapped

    FINE AMPERAGEADJUSTMENT

    TAPPEDREACTOR

    STABILIZER(INDUCTOR)Reactor For Coarse Current

    Control And Adjustable MagneticField Amperage For Fine CurrentOutput Control

    Design:

    1. Two Pole Alternator

    2. Four Pole Alternator

  • 8/9/2019 Engine Drives

    9/19

    Considerations:

    1. Generator Sizing

    2. Load Analysis

    Rated Output

    Found on machine nameplate

    E.G. Trailblazer 301: 9,500 Watts

    120 Volts - 84 Amps

    240 Volts - 42 Amps

    kVA while welding is dependent on welding output

    Page 9

    Two Pole Alternator

    Four Pole Alternator

  • 8/9/2019 Engine Drives

    10/19

    1. Generator Sizing: How Much Power Can Generator Supply?

    Page 10

    Limits of a Generator

    MILLER welding generators are designed to operate at maximum load, but doing so allows very little reserve

    engine horsepower to follow changes in load requirements. This makes itself known by noticeable voltage and

    frequency changes (light bulbs flicker, etc.) Much improved voltage and frequency regulation can be realized

    by not loading the generator to 100% of its capacity. For best performance and load handling, only use approx-imately 90% of the available output. The 10% margin allows for more satisfactory engine governor response

    to changing load situations. The rule becomes simple: Always know the total load requirements and the gener-

    ator's capability. Select a generator to adequately meet load requirements, or limit load requirements to the

    capabilities of the existing generator.

    2. Load Analysis: How Much Power Does Equipment Require?

  • 8/9/2019 Engine Drives

    11/19

    Load analysis and generator sizing are essential for satisfactory generator and equipment operation. The avail-

    able auxiliary power is limited by engine horsepower and is a small, finite power system as compared to the

    large, seemingly-infinite electric utility system. Any single load may represent usage of a large portion of the

    total power available. It is necessary to carefully determine the total load that will be applied by adding up all

    the individual loads. Some tools are rated in watts, others in amperes. Lights and heaters are rated in watts.

    Most equipment will specify on its nameplate what its specific requirements will be.

    For example, a drill requires 4.5 amperes at 115 volts. Watts equals volts times amperes. Therefore, this drill

    requires approximately 520 watts. Add three 200 watt flood lamps, and requirements increase by 600 watts for

    a total of 1120 watts. Continue in this fashion until all loads have been added. Be sure to add all motor run-

    ning requirements to the total (motor starting requirements will be discussed later). Consider also that a load is

    not always constant. To be sure, lights and resistance heaters are constant, but portable power tools are not.

    One rarely grinds or drills with a constant, even pressure. Thus, the load requirements change greater than

    anticipated. Induction motors normally power loads that require variable amounts of power from the generator

    and will be discussed later.

    Page 11

    VOLTS x AMPERES = WATTS

    This equation provides an actual power requirement for resistive loads, or an approximate running requirement for non-resistive loads.

    EXAMPLE 1:If a drill requires 4.5 amperes at 115 volts, calculate its running power requirement in watts.

    115 V x 4.5 A = 520 W

    Therefore, the individual load applied by the drill is 520 watts.

    EXAMPLE 2:If a flood lamp is rated at 200 watts, the individual load applied by the lamp is 200 watts. If three 200 watt floodlamps are used with the drill from Example 1, add the individual loads to calculate total load.

    Therefore, the total load applied by the three flood lamps and drill is 1120 watts.

    (200 W + 200 W + 200 W) + 520 W = 1120 W

    Calculating Power Required To Run Equipment

  • 8/9/2019 Engine Drives

    12/19Page 12

    S-0624

    1 Motor Start Code

    2 Running Amperage

    3 Motor HP

    4 Motor Voltage

    To find starting amperage:

    Step 1:Find code and use table tofind kVA/HP. If code is not listed,multiply running amperage by six tofind starting amperage.

    Step 2: Find Motor HP and Volts.

    Step 3:Determine starting amper-age (see example).

    Welding generator amperage out-put must be at least twice themotors running amperage.

    VOLTS AMPS

    HP

    230 2.5

    1/4

    Hz

    PHASE

    CODE 60

    1

    M

    AC MOTOR1

    2

    3

    4

    Single-Phase Induction Motor Starting Requirements

    Motor StartCode G H J K L M N P

    KVA/HP 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0

    EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4HP motor with a motor start code of M.

    Starting the motor requires 12.2 amperes.11.2 x 1/4 x 1000

    230= 12.2 A

    kVA/HP x HP x 1000

    VOLTS= STARTING AMPERAGE

    Volts = 230 HP = 1/4 Using Table, Code M results in kVA/HP = 11.2

    Starting Motors

    Different types of loads require different types of output from the generator. When a nonmotor load is applied,

    generator output goes to the ampere requirement of the equipment, but voltage remains near rated. The non-

    motor load does not cause the voltage to drop significantly below its nominal rating. When a motor load is

    applied, the generator will attempt to supply motor starting current causing output voltage to drop to nearly

    zero volts because the starting current is many times the running current. For this reason, it is necessary to

    determine the starting amperage required by the motor and verify the the generator can supply that amount of

    amperage. This can be done using the formula shown below, or by using the charts shown on the followingpages.

    Caculating Motor Starting Requirements

  • 8/9/2019 Engine Drives

    13/19Page 13

    Industrial Motors Rating Starting Watts Running Watts

    Split Phase 1/8 HP 800 300

    1/6 HP 1225 500

    1/4 HP 1600 600

    1/3 HP 2100 700

    1/2 HP 3175 875

    Capacitor Start-Induction Run 1/3 HP 2020 720

    1/2 HP 3075 9753/4 HP 4500 1400

    1 HP 6100 1600

    1-1/2 HP 8200 2200

    2 HP 10550 2850

    3 HP 15900 3900

    5 HP 23300 6800

    Capacitor Start-Capacitor Run 1-1/2 HP 8100 2000

    5 HP 23300 6000

    7-1/2 HP 35000 8000

    10 HP 46700 10700

    Fan Duty 1/8 HP 1000 400

    1/6 HP 1400 550

    1/4 HP 1850 6501/3 HP 2400 800

    1/2 HP 3500 1100

    Farm/Home Equipment Rating Starting Watts Running Watts

    Stock Tank De-Icer 1000 1000

    Grain Cleaner 1/4 HP 1650 650

    Portable Conveyor 1/2 HP 3400 1000

    Grain Elevator 3/4 HP 4400 1400

    Milk Cooler 2900 1100

    Milker (Vacuum Pump) 2 HP 10500 2800

    FARM DUTY MOTORS 1/3 HP 1720 720Std. (e.g. Conveyors, 1/2 HP 2575 975

    Feed Augers, Air 3/4 HP 4500 1400

    Compressors) 1 HP 6100 1600

    1-1/2 HP 8200 2200

    2 HP 10550 2850

    3 HP 15900 3900

    5 HP 23300 6800

    High Torque (e.g. Barn 1-1/2 HP 8100 2000

    Cleaners, Silo Unloaders, 5 HP 23300 6000

    Silo Hoists, Bunk Feeders) 7-1/2 HP 35000 8000

    10 HP 46700 10700

    3-1/2 cu. ft. Mixer 1/2 HP 3300 1000

    High Pressure 1.8 Gal/Min 500 PSI 3150 950

    Washer 2 gal/min 550 PSI 4500 1400

    2 gal/min 700 PSI 6100 1600

    Refrigerator or Freezer 3100 800

    Shallow Well Pump 1/3 HP 2150 750

    1/2 HP 3100 1000

    Sump Pump 1/3 HP 2100 800

    1/2 HP 3200 1050

    Approximate Power Requirements for Industrail Motors

    Approximate Power Requirements for Farm/Home Equipment

  • 8/9/2019 Engine Drives

    14/19Page 14

    Contractor Rating Starting Watts Running Watts

    Hand Drill 1/4 in 350 350

    3/8 in 400 400

    1/2 in 600 600

    Circular Saw 6-1/2 in 500 500

    7-1/4 in 900 900

    8-1/4 in 1400 1400

    Table Saw 9 in 4500 150010 in 6300 1800

    Band Saw 14 in 2500 1100

    Bench Grinder 6 in 1720 720

    8 in 3900 1400

    10 in 5200 1600

    Air Compressor 1/2 HP 3000 1000

    1 HP 6000 1500

    1-1/2 HP 8200 2200

    2 HP 10500 2800

    Electric Chain Saw 1-1/2 HP, 12 in 1100 1100

    2 HP, 14 in 1100 1100

    Electric Trimmer Standard 9 in 350 350

    Heavy Duty 12 in 500 500Electric Cultivator 1/3 HP 2100 700

    Elec. Hedge Trimmer 18 in 400 400

    Flood Lights HID 125 100

    Metal Halide 313 250

    Mercury 1000

    Sodium 1400

    Vapor 1250 1000

    Submersible Pump 400 gph 600 200

    Centrifugal Pump 900 gph 900 500

    Floor Polisher 3/4 HP, 16 in 4500 1400

    1 HP, 20 in 6100 1600

    High Pressure Washer 1/2 HP 3150 950

    3/4 HP 4500 1400

    1 HP 6100 1600

    55 gal Drum Mixer 1/4 HP 1900 700

    Wet & Dry Vac 1.7 HP 900 900

    2-1/2 HP 1300 1300

    Approximate Power Requirements for Contractor equipment

  • 8/9/2019 Engine Drives

    15/19

    Auxiliary Power While Welding

    Page 15

    Weld Current Total Power 120 V Receptacle 240 V Receptaclein Amperes in Watts Amperes Amperes

    0 10,000 84* 42*

    90 8000 66* 33125 5200 43* 21

    180 3500 29* 14

    250 2200 18 9

    Weld CurrentIn Amperes

    300

    250

    200

    150

    100

    0

    Total Powerin Watts

    1000

    3500

    5200

    6700

    8000

    10000

    120 V

    ReceptacleAmperes

    10

    31

    46

    60

    70

    84

    240 V

    ReceptacleAmperes

    5

    15

    23

    30

    35

    42

    Bobcat 250 Power While Welding

    Trailblazer 301 Power While Welding

    Typical Connections To Supply Standby Power

    Generators may be used to provide emergency power to systems normally supplied by other sources of elec-

    tricity, but extreme caution must be exercised to properly install the generator. The specific rules for installa-

    tion and use of auxiliary generators are established by the National Electrical Code, state, local, and in some

    cases OSHA codes. These codes were developed to assure personnel safety - vitally important for any user. Itis the responsibility of the installer to be familiar with and meet all installation requirements. Major require-

    ments of the National Electrical Code (1990 edition) for auxiliary power plant installations are (1) overcurrent

    protection as required for the generator, (2) proper grounding of the generator, and (3) isolation of the genera-

    tor from other sources of power. Additional requirements may be established by state and local codes.

    Overcurrent protection is required if a generator is supplying a permanent installation. Fuses or circuit break-

    ers are adequate for small auxiliary power plants. Overcurrent protection is generally not required for genera-

    tors supplying portable, cord-connected equipment through receptacles mounted on the generator.

  • 8/9/2019 Engine Drives

    16/19

    Customer-supplied equipment is required if generator is to supply standby power during emergencies or power

    outages. Locate the power company service meter (Item 1), and main and branch overcurrent protection (Item

    2), and install equipment as shown below.

    Page 16

    Have only qualified personsperform these connectionsaccording to all applicablecodes and safety practices.

    1 Power Company ServiceMeter

    2 Main and Branch OvercurrentProtection

    3 Double-Pole, Double-ThrowTransfer Switch

    Obtain and install correct switch.Switch rating must be same as orgreater than the branch overcurrentprotection.

    4 Circuit Breakers or FusedDisconnect Switch

    Obtain and install correct switch.

    5 Extension Cord

    Select as shown in Section 13-11.

    6 Generator Connections

    Connect terminals or plug of ade-quate amperage capacity to cord.Follow all applicable codes andsafety practices.

    Turn off or unplug all equipmentconnected to generator beforestarting or stopping engine. Whenstarting or stopping, the engine haslow speed which causes low volt-age and frequency.

    7 Load Connections

    Customer-supplied equipment is required ifgenerator is to supply standby power duringemergencies or power outages.

    120/240 Volt60 Hz

    Three-WireService

    240 V

    120 V

    120 V

    Neutral

    240 V

    120 V

    120 V120/240 VoltSingle-PhaseThree-Wire

    Generator Output

    Connection Ground

    F1

    or

    CB

    240 V

    120 V

    120 VLoad

    1

    2 3

    6

    74

    5

    Item 4 is not necessary if circuitprotection is already present inwelding generator auxiliarypower output circuit.

    Standby Power Equipment And Connections

  • 8/9/2019 Engine Drives

    17/19

    Selecting Extension Cords

    Use the tables below to select extension cords. Use shortest cords possible because long cords may reduce out-

    put or cause unit overload.

    Page 17

    Cord Lengths for 120 Volt Loads

    If unit does not have GFCI receptacles, use GFCI-protected extension cord.

    Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

    Current(Amperes)

    Load (Watts) 4 6 8 10 12 14

    5 600 350 (106) 225 (68) 137 (42) 100 (30)

    7 840 400 (122) 250 (76) 150 (46) 100 (30) 62 (19)

    10 1200 400 (122) 275 (84) 175 (53) 112 (34) 62 (19) 50 (15)

    15 1800 300 (91) 175 (53) 112 (34) 75 (23) 37 (11) 30 (9)

    20 2400 225 (68) 137 (42) 87 (26) 50 (15) 30 (9)

    25 3000 175 (53) 112 (34) 62 (19) 37 (11)

    30 3600 150 (46) 87 (26) 50 (15) 37 (11)

    35 4200 125 (38) 75 (23) 50 (15)

    40 4800 112 (34) 62 (19) 37 (11)

    45 5400 100 (30) 62 (19)

    50 6000 87 (26) 50 (15)

    *Conductor size is based on maximum 2% voltage drop

    Cord Lengths for 240 Volt Loads

    If unit does not have GFCI receptacles, use GFCI-protected extension cord.

    Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

    Current(Amperes)

    Load (Watts) 4 6 8 10 12 14

    5 1200 700 (213) 450 (137) 225 (84) 200 (61)

    7 1680 800 (244) 500 (152) 300 (91) 200 (61) 125 (38)

    10 2400 800 (244) 550 (168) 350 (107) 225 (69) 125 (38) 100 (31)

    15 3600 600 (183) 350 (107) 225 (69) 150 (46) 75 (23) 60 (18)

    20 4800 450 (137) 275 (84) 175 (53) 100 (31) 60 (18)

    25 6000 350 (107) 225 (69) 125 (38) 75 (23)

    30 7000 300 (91) 175 (53) 100 (31) 75 (23)

    35 8400 250 (76) 150 (46) 100 (31)

    40 9600 225 (69) 125 (38) 75 (23)

    45 10,800 200 (61) 125 (38)

    50 12,000 175 (53) 100 (31)

    *Conductor size is based on maximum 2% voltage drop

  • 8/9/2019 Engine Drives

    18/19

    Engine and Fuel Choices

    Rotating type power supplies are used for field erection and fabrication work when no electric power is avail-

    able. For this use, a wide variety of internal combustion engines are available. Both liquid-cooled and air-

    cooled engines are used. Gasoline is the most popular fuel because of price and availability. Diesel fuel is pop-

    ular because of its high flash point. Also, some regulations will permit only diesel fuel for engines used in spe-

    cific applications. A good example is the use of diesel engines for welding power sources on offshore drilling

    rigs and marine applications. Propane and natural gas are used in some applications because it is cleaner burn-

    ing than gasoline. However, they require a special carburetion system. An example of the need for these clean-er burning fuels is "in plant" maintenance welding.

    Engine driven power sources are often equipped with idling devices to save fuel. These devices are automatic

    in that the engine will run at a set idle speed until the electrode is touched to the work or a load is sensed on

    the auxiliary power outlet. Under idling conditions, the open circuit voltage of the alternator/generator is low.

    Touching the electrode to the work energizes a sensing circuit that automatically accelerates the engine to the

    operating speed. When the arc is broken, the engine will return to its idle speed after a set time.

    Page 18

    The curve shows typical fuel useunder weld or power loads.

    193 093

    1800 RPM

    IDLE

    Fuel Consumption

    Engine driven power sources are available with many auxiliary features. Units may be equipped with a remote

    output control attachment. It may be either fingertip, hand, or foot control operated so that the operator may

    take the power source adjustment (contactor, voltage and/or amperage) to the work area while welding.

    Other auxiliary features that can be obtained on the engine driven welding machines are: polarity switches (to

    easily change from DCEN to DCEP), running hour meters, fuel gauges, battery chargers, high-frequency arc

    starters, and volt/ampere meters. Some larger units are equipped with an air compressor for carbon arc air cut-

    ting and gouging, plasma arc cutting and gouging, and operating pneumatic hand tools.

  • 8/9/2019 Engine Drives

    19/19

    Why Buy A Diesel Engine Powered Welder?

    - It uses approximately half as much fuel as a similar sized gasoline engine.

    - It has no points, plugs, condenser or carburetor, which means no downtime from costly tune-ups and

    adjustments.

    - It doesn't have carburetor icing problems in severe cold climates or fuel and vapor lock problems in severe

    warm climates.

    - It is less apt to be pilfered for personal use than gasoline due to lack of diesel fueled automobiles, and it's a

    more common fuel for the large construction machinery.- It will be running long after a gasoline engine has had to be overhauled.

    - It is safer fuel to use than gasoline, which is very important on construction job sites, on offshore rigs and in

    the oil fields.