457 g Multilin Multi-point energy demand data logging Revenue certifiable metering Meets ANSI C12.1 & C12.16 accuracy Wall mountable easy-to-install enclosures Local LCD viewing Communication over existing AC Power Lines (PLC) or Modbus RTU Ideal for commercial, residential and industrial sub-metering applications requiring multi-point energy data logging. This includes multi-point high rise, garden style apartment, condos, or office suites. FEATURES EPM 4000 SUB-METERING SYSTEM Multi-tenant digital electric meter with power line communications FEATURES APPLICATIONS KEY BENEFITS Monitoring and Metering Real-time per-phase viewing of voltage, current, power factor, phase angle, watts, VARs, VA, and frequency Event reporting with time and date stamps regarding power consumption, demand resets, power-ups/power downs, and is available via LCD for viewing Communications PLC Communication (Power Line Communications) Modbus RS 485 (optional) Up to 48 pulse inputs (optional) IEC optical front panel interface for programming

Upload: others

Post on 01-Jun-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EPM 4000 - 01 · 2007. 1. 24. · EPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed

457g Multilin

• Multi-point energy demand data logging• Revenue certifiable metering• Meets ANSI C12.1 & C12.16 accuracy

• Wall mountable easy-to-install enclosures• Local LCD viewing• Communication over existing AC Power Lines (PLC)

or Modbus RTU

• Ideal for commercial, residential and industrial sub-metering applications requiring multi-point energy data logging. This includes multi-point high rise, garden style apartment, condos, or office suites.

FEATURES

EPM 4000SUB-METERING SYSTEM

Multi-tenant digital electric meter with power line communications

FEATURES

APPLICATIONS

KEY BENEFITS

Monitoring and Metering• Real-time per-phase viewing of voltage, current, power

factor, phase angle, watts, VARs, VA, and frequency• Event reporting with time and date stamps regarding power

consumption, demand resets, power-ups/power downs, and is available via LCD for viewing

Communications• PLC Communication (Power Line Communications) • Modbus RS 485 (optional)• Up to 48 pulse inputs (optional)• IEC optical front panel interface for programming

Page 2: EPM 4000 - 01 · 2007. 1. 24. · EPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed

www.GEMultilin.com

EPM 4000 Sub-metering System

458

Standard FeaturesGE Multilin’s EPM 4000 is an easy-to-use multi-tenant energy/demand data logging meter suitable for new construction or retrofit application. The integral LCD display provides access to electrical parameters in real-time or historical format. The EPM 4000 is available in residential packages (kWh) in 120/208V or 120/240V services, it is also available in commercial and industrial packages in 120/208V, 277/480V or 347/600V. Other optional packages include delta configuration for 480V or 600V configurations. CTs are available in solid or split core applications. The EPM 4000 can be ordered in specific circuit sizes depending on application and electrical service requirements.

Mounting VersatilityEPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed for fast installation.

MeteringEPM 4000 meter provides local real-time viewing, per-phase of voltage, current, power factor, phase angle, watts, kVARs, kVA, and frequency. Event reporting with time and date stamps regarding consumption, demand resets, power ups/downs, and time changes is available through LCD Display. Non-volatile flash memory retains daily and interval metering data during power outages. Backup battery is also provided to maintain time during power outages.

• Ia Ib Ic

• Va Vb Vc Vab Vbc Vca

• PF

• W var VA

• Wh

• F

PLC CommunicationThe EPM 4000 provides standard communication over patented 2-way PLC (Power Line Communication) where the AC lines act as the communication medium - perfect for retrofit applications where placing new communication lines can be difficult and expensive. Data can be retrieved in a GE or a third-party software through use of a transponder.

GE’s PLC technology is an extremely reliable and cost-effective solution.

PLC TransponderThe Transponder is the central data collector for the Power Line Communication (PLC) system. It is installed on the secondary of the utility transformer and will communicate with all meters installed on the load side of the transformer. The Transponder is typically installed in the main electric room close to the service entrance of the utility transformer secondary. In properties with multiple utility services, a Transponder is required for each transformer/ service and can handle as many as 240 metering points.

The Transponder network is accessed utilizing a telephone modem or local RS-232 connection to an on-site PC for data transfers.

Each Transponder has a database or “cross reference” of installed meters (by serial number) on its particular electrical service. The Transponder collects data for each of these meters and stores it in internal non-volatile flash memory for up to 40 days for typical billing requirements. This design provides data redundancy for the data stored in the meter.

Using the transponder the signal can communicate through distribution transformers. With the Transponder installed at the main (120/208, 277/480 or 347/600) distribution panel, the Transponder will communicate through any existing step-down transformer with any meter fed from that particular distribution panel.

GE PLC complies with IEC Signaling Standard (10-90Khz), and less than 4W is transmitted. It does not interfere with any existing equipment. The system produces a round signal with no harmonics. The signal is sensed only by other GE devices.

Modbus Communication:Optional RS-485 Modbus Open Protocol Communication is available for networking to GE and third party systems. A transponder data collector is not required when the Modbus option of the EPM4000 is selected.

Local Viewing DisplaySimple pushbutton access allows instant viewing of real-time and historical data on easy-to-read front LCD.

• Push button scroll

• 32 digit liquid crystal display (16 digit x 2 rows)

• 6 whole digit consumption register

• Data digit height: 0.31”

• Programmable display scroll & decimal place display

Comprehensive PackageEPM 4000 is available with solid or split core current transformer options. A comprehensive packaged selection of CT sizes, amperes and dimensions, is available for new construction (solid core/lower cost options) or split core (for retrofit/existing) applications.

EPM 4000 PackagePackage includes wall mountable metal enclosure with built-in LCD, IEC optical port, fuse block and CT shorting assembly.

Accuracy RequirementsEPM 1000 meets ANSI C12.1 and C12.16 revenue certifiable accuracy specifications, and the stringent requirements of Measurement Canada (AE-1148)

OptionsThere are a variety of options available to the user, allowing a range of custom configurations:

Pulse InputsPulse Inputs: Up to 48 Form A Pulse Inputs are available for additional energy information inputs derived from water, gas, steam, and similar meters that utilize Form A outputs. Information can then be read on LCD display.

E n e r g y D e m a n d L o g g i n g : k W i s programmable in 15 minutes time interval block demand. This feature also allows local reset of peak demand register.

EnerVista SoftwareEnerVista LaunchpadEnerVista Launchpad is a powerful software package that provides users a platform to access all of the setup and support tools needed for configuring and maintaining GE Multilin Products.

Included in Launchpad is a document archiving and management system that ensures critical documentation is up-to-date and available when needed by automatically checking for and downloading new versions of manuals, applications nates, specifications, and service bulletins.

EnerVista Viewpoint MonitoringViewpoint monitoring is a simple-to-use, full-featured monitoring and data recording software package for small systems. Viewpoint Monitoring provides a

Page 3: EPM 4000 - 01 · 2007. 1. 24. · EPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed

www.GEMultilin.com 459

EPM 4000 Sub-metering System

709701A3.CDR

ØA ØB ØCIA IB ICNA NB NC N

120/208V277/480V347/600V

FerriteBeadsPower Header

MC -5

C T 3C T 1

C T 4C T 2

MCI INTERFACE

TE

NA

NT

BR

EA

KE

RP

AN

EL

TE

NA

NT

BR

EA

KE

RP

AN

EL

Tenant Breaker Panel

Con

duit

RECOMMENDED: Service Disconnect Switch15A Fast Acting Only

NeutralPhase A (ØA)

Phase B (ØB)Phase C (ØC) BL

RDBK

WH

BK

RD

BL

WH

BK

RD

BL

WH

BK

RD

BL

WH

To CT1 To CT3

To CT2 To CT4

CT Header CT Header

CT Header CT Header

WH

RDBL

BK

BK RD BL WH

WH

WH

WH

BL

BK

RD

ØA

ØB

ØC

Shor

ting

Link

s

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

WHBK

WHRD

WHBL

Diagram 2. Shorting Links. See Installation Notes for details.

Met

er#1

Met

er#2

Met

er#3

Met

er#4

Met

er#1

Met

er#8

Met

er#7

Met

er#6

Met

er#5

Power Source

Connect CT Header to meterhead

A

BC

N

Load

Load

Load

Diagram 3. CT Phasing. Dot or H1 should point towards the line or source.

Reference Voltage

CRITICAL - Current Transformers (CT) must be installed correctly. See Diagram 1 for CT installation for each meter point. See Diagram 3 for CT polarity and Table 1 for Phase Association relationships.

Diagram 1. Current Transformers installed inside tenant breaker panel.

LINE SOURCE

BK/RD/BL

WHITEDot

H1

RDBK

Met

er#2

ØB

ØA

WH

WHBLØC BL

WH

RD

BK

WH

Typical High-rise Commercial Applicationcomplete HMI package that instantly puts critical real-time device data on your PC through pre-configured graphical screens with the following functionality.

• Plug-&-Play Device Monitoring

• System Single-Line Monitoring & Control

• Annunciator Alarm Screens

• Trending Reports

• Automatic Event Retrieval

• Automatic Waveform Retrieval

EnerVista IntegratorEnerVista Integrator is a toolkit that allows seamless integration of GE Multilin devices into new or existing automation systems by sending GE device data to HMI, DCS, and SCADA systems. Included in EnerVista Integrator is:

• OPC/DDE Server

• GE Multilin Drivers

• Automatic Event Retrieval

• Automatic Waveform Retrieval

Typical Wiring

Scan Transponder (Data Collection)

Page 4: EPM 4000 - 01 · 2007. 1. 24. · EPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed

www.GEMultilin.com

EPM 4000 Sub-metering System

460

METER ACCURACY 0.5 class accuracy + 0.5% @ unity and 50% power factor; 1-100% of full-scale Meets revenue certifiable ANSI C12.1 & C12.16 accuracy standards

LIQUID CRYSTAL DISPLAY (LCD) 32 digit liquid crystal display (16 digit x 2 rows) Data digit height: .31”6 whole digit consumption registerScrollable display Push button scroll

METERING

MEASURED VALUES REAL TIME DATA PARAMETER PER PHASE LOGGING Voltage x Current x kW x kVAR x kVA x kWh x Power factor x Frequency x kW demand x Phase Angle x

EPM 4000 Dimensions

EPM 4000 ENCLOSURE DIMENSIONS19.900"

13.5"

EPM 4000 EPM 4000 INTERFACE

2.500"

8.700"

2.500" 29.5"

EPM 4000

EPM 4000 INTERFACE

2.500"

4.500"

13.5"

ENVIRONMENTALHumidity: 0 to 95% Relative Humidity (non-condensing) Temperature: -20°C to + 60°CMeter Dimensions: 13.65”H x 8.5”W x 4.5”DEnclosure: NEMA 1 ratedCT Dimensions: Variable sizes please see drawings

PACKAGINGShipping Weight: 1 meter assembly 34lbs (total weight)Shipping Dimensions 2 enclosures each 13.5”H x 8.5”W x 4.5”D Field mounting options: top to bottom or side to side

EPM 4000 Technical SpecificationsMONITORING

DEMAND MONITORING

Consumption & Demand: kW & kWhInterval Data & Peak DemandCommercial: 15-min block demand interval & peak demand with date & time stampResidential: 1-hour block demand intervalData Logging: 120 days with kW & kWhBattery Backup: During power outage long time lithium battery maintains time, logs, incoming pulses and stores the current time and interval data. Demand Reset: Allows local reset of peak demand register

APPROVALSANSI: C12.1 & C12.16 accuracyUL & CUL: Listed under E204142Industry Canada: MC# AE-1148

TYPE TESTSTransient/Surge Suppression: ANSI C37.90.1-1989Voltage: Rated Voltage (90% to 110%)

COMMUNICATIONSPower Line Communications (PLC)RS-485 ModbusIEC Front Optical Point of Access (POA) port Built-in Internal Modem (19.2K)

POWER SUPPLYCONTROL POWERInput: 120V Phase A to Neutral 277V phase A to Neutral 480V phase to phase (Internally powered thru metered voltage no external source is required) Frequency: 50-60HzOperating Power: 2 Watts for 120V 5 Watts for 277V & 480V

INPUTSAC CURRENT INPUTSCT input: 50 amp to 800 amp primary availableSecondary inputs: 0.1 A or 5A AC VOLTAGE INPUTSMetered voltage: 120/208V Wye, 277/480V Wye, 480 or 600V Delta 50-60HzRated voltage: 90% to 110%

PULSE INPUTSInputs: Up to 48 Form A Pulse Inputs logged in programmable intervals also count during power outageMin. wire gauge: 20 AWGMax. wire length: 300 feetMax rate: 5 transitions/secMin pulse width: 100 ms.

Page 5: EPM 4000 - 01 · 2007. 1. 24. · EPM 4000 is wall mountable, tamper resistant and can be located away from the electrical circuit to be monitored. Its rugged metal enclosure is designed

www.GEMultilin.com 461

EPM 4000 Sub-metering System

PL 4000 * * * * DescriptionApplication Type R Residential - 120/208 or 120/240 Volts single phaseNo. of Metering Points for 120/208 Volts System 03 3 Single Phase Metering Points - 120/208 V 06 6 Single Phase Metering Points - 120/208 V 09 9 Single Phase Metering Points - 120/208 V 12 12 Single Phase Metering Points - 120/208 Vfor 120/240 Volts System 12 12 Single Phase Metering Points - 120/240 V 18 18 Single Phase Metering Points - 120/240 V 24 24 Single Phase Metering Points - 120/240 V CTs L 0.1 amps CT Secondary input H 5 amps CT Secondary input Voltage 120 120/208 Volts Connection Single Phase Only 240 240 Volts - Single phase Only

Ordering

PL 4000 * * * * Description Application Type C Commercial - 120/208, 277/480 or 347/600 Volts three phase No. of Metering Points 06 6, Three Phase Metering Points 08 8, Three Phase Metering Points CTs L 0.1 amps CT Secondary input H 5 amps CT Secondary input Voltage 120 120/208 Volts Connection 3 Phase Only 277 277/480 Volts - 3 Phase Only 347 347/600 Volts - 3 Phase OnlyModifications:PL4000MOD Modbus CommunicationsThis modification must be selected at time of order to factory convert the meter from PLC to Modbus communication.

OPTIONSPL4000C12L480DEL EPM 4000, 480V Delta 3-phase 4-wire 12 meters - 0.1A CT

secondaryPL4000C12H600DEL EPM 4000, 600V Delta 3-phase 3-wire 12 meters - 5A CT

secondary

CTS SOLID CORE(0.1 A Secondary)PLSUBCTSL050 50/0.1A PLSUBCTSL101 100/0.1A PLSUBCTSL201 200/0.1A PLSUBCTSL401 400/0.1A PLSUBCTSL201CDN 2/5DARL(Canadian)

CTS SPLIT CORE(0.1 A Secondary)PLSUBCTSP050 50/0.1APLSUBCTSP101 100/0.1APLSUBCTSP201 200/0.1APLSUBCTSP401 400/0.1APLSUBCTSP801 800/0.1A

CTS SOLID CORE PLSUBCTSL201CDN 200/5A (Canadian)

TRANSPONDER Transponder required for standard PLC Communication version of EPM 1000 and EPM 4000. Transponder not required when using Modbus version of EPM 1000 and EPM 4000 MODELS Voltage OptionsPLMODXPONDER120V 120/208* ModemPL485XPONDER120V 120/208 RS-485PLMODXPONDER277V 277/480 ModemPL485XPONDER277V 277/480 RS-485PLMODXPONDER347V 347/600 ModemPL485XPONDER347V 347/600 RS-485

Pulse Inputs (for more information contact your local sales office)PL4000PULSINAPL4000PULSINBPL4000PULSINCPL4000PULSIND

EPM 4000 Residential (R)Single-phase 120/208 or 120/240 Volts connectionsResidential use measures kWh only (no demand measurement)

EPM 4000 Commercial (C)Three-phase 120/208, 277/480, or 347/600 Volts connections. Delta optional. Commercial use measures kWh and kW Demand

* same model works for 120/240

0124v0.0

The EPM4000 meter comes standard with Power Line Carrier (PLC) communications protocol. A Transponder is required when using PLC communication. When the Modbus communication modification is selected, no Transponder is required.